Anda di halaman 1dari 46

60

3. PREACTION (SPECIAL) SYSTEMS


3.1 General Description
A preaction system employs closed sprinklers and is used to provide fire protection primarily in water
sensitive environments where serious water damage would otherwise occur, as a result of a broken
sprinkler or broken sprinkler piping. Preaction systems, during normal conditions, contain no water in
the sprinkler piping. However, they may contain air at atmospheric pressure (i.e., unsupervised
systems), or a slightly compressed gas (air or dry nitrogen) for the purpose of supervising the leak
tightness of a sprinkler system. Usually, supervising of sprinkler piping is done at a pressure of 1 to 2
psi (0,1 bar); however, some types of preaction systems require supervising at pressure levels between
15 and 50 psi (1,0 and 3,5 bar). For example, when using RELIABLE Model G3 dry sprinklers, which
require nearly 7 psi (0,5 bar) of opening pressure, system supervising should employ a pneumatic
pressure of approximately 15 psi (1,0 bar). Also, a pneumatic preaction system using a Model A Dry
Pilot Actuator releasing device may require up to 50 psi (3,5 bar) of supervising pressure.
Preaction systems differ from dry pipe systems in that the primary control valve for preaction is
activated by a fire detection device, and not by exclusive operation of a sprinkler head in the system
piping, as is the case when a dry pipe valve is the primary control valve.
When a fire is detected by a preaction system, the primary control valve is opened to allow water flow
into the sprinkler piping in readiness for possible subsequent opening of one or more sprinklers, i n the
event the fire cannot be extinguished by hand-held means. With the flow of water into the sprinkler
system piping, alarm devices are activated. This type of system is often referred to as a
SINGLE-INTERLOCK PREACTION SYSTEM, and it is used to provide fire protection in computer
rooms, libraries, museums, and telephone equipment rooms. When local codes permit and Factory
Mutual Approval is not required, it may be desirable to arrange electrical detectors in a cross-zoned
array. This arrangement (see Section 1.4.1.2) will prevent a false activation of one detector from
causing water to flow into the sprinkler piping prematurely since two detectors must operate before
water will flow.
Certain design conditions may exist which require that a system be arranged as a
DOUBLE-INTERLOCK PREACTION SYSTEM. A large refrigerated storage area, where temperatures
are below freezing, is an example. Double-interlock systems can also be used in museums and
electronic equipment rooms. In contrast to single-interlocking, double interlocking prevents flow of
water into a sprinkler system, until both a detecting device and a sprinkler head are operated
simultaneously. Operation of either a detector or a sprinkler will produce an alarm, but is insufficient to
produce water flow into the system. When freezing refrigerated systems are protected by a preaction
system, double-interlocking assures that once water flows into the system, it will continue to flow
through one or more open sprinklers. This minimizes the possibility of ice blockage which could occur
with a single-interlock system that holds the water statically until a sprinkler operates.

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
61

The Fire Protection Handbook, published by the National Fire Protection Association (NFPA), contains a
comprehensive description of preaction systems.
The water supply to each preaction system is controlled by a primary control valve which is usually a
deluge valve. Deluge valves manufactured by RELIABLE are described in Section 1.1.1 and 1.1.2. On
occasion, a dry pipe valve (see Section 1.1.3) may be used as the primary control valve for a
NON-INTERLOCK PREACTION SYSTEM. With this arrangement, a detector operating first will cause
water to flow into the sprinkler piping in readiness for the operation of a sprinkler (just like a
single-interlock system). However, whenever a sprinkler head operates first, this system will respond as
a dry pipe system with water flow from the sprinkler within 60 seconds. More information on this type of
combined dry pipe preaction system is provided in Section 3.3.1.
3.2 Hydraulic (Wet Pilot) Activation
3.2.1 Single-Interlock Type
Wet pilot line operation is the simplest and least costly method for arranging a preaction system. The
closed, quick response sprinklers in the pilot line serve as heat detectors over the area to be protected.
The pilot line contains water at the same pressure as the water in the top chamber or push rod chamber
of RELIABLE Deluge Valves (see Figures 1 or 2). Pilot line sprinklers function as both thermal detectors
and releasing devices, and when one or more operate, the resulting water discharge and pressure loss
in the chamber of the deluge valve causes it to open and allow water flow into the sprinkler system
piping. The sprinkler system is now in readiness for conditions that cause a sprinkler head to open and
immediately discharge water on the fire. Note that water discharge from a pilot line sprinkler
contributes little toward fire control. When quick response sprinkler heads are used, quick response
pilot heads should have a lower temperature rating.
Manual emergency pull stations (see Section 1.2.4.1) can provide a remote hydraulic method of
causing water flow into the sprinkler piping when visual indications of fire precede thermal indications.
A wet pilot line installation is subject to the following restrictions:

a) It is not to be installed in an area subject to freezing.

b) It is not to be installed in an area where temperatures in excess of 150°F (66°C) are


anticipated.

c) NFPA Pamphlet No. 13, or the Authority Having Jurisdiction, should be consulted
for pilot sprinkler spacing requirements.

d) It is to be installed in accordance with the following table. See the Appendix Section 4.1
for the combination of height and distance limitations

01/01

The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
62

The trimmings for Model A, B, and BX Deluge Valves are arranged for rapid, compact attachment, and
serve as connection points to alarm and other devices.

Average Supply Maximum Height of Wet Pilot Line Above Deluge Valve
Pressure At Valve Feet (Meters)

psi bar 2½″ (65mm) 4″ (100mm) 6″ (150mm)


20 1,4 7.7 (2.3) 7.7 (2.3) 10.8 (3.3)

40 2,8 12.3 (3.8) 18.4 (5.6) 21.5 (6.6)


60 4,2 21.6 (6.6) 27.8 (8.5) 32.3 (9.8)
80 5,6 30.8 (9.4) 37.0 (11.3) 43.1 (13.1)
100 7,0 43.1 (13.1) 44.6 (13.6) 50.8 (15.5)

120 8,4 53.9 (16.4) 52.4 (15.9) 58.5 (17.8)


140 9,8 67.8 (20.7) 66.2 (20.2) 75.5 (23.0)
160 11,3 80.1 (24.4) 78.5 (23.9) 81.6 (24.9)

175 12,1 92.4 (28.2) 84.6 (25.8) 84.7 (25.8)

All RELIABLE Deluge Valves are listed and approved by Underwriters Laboratories, Inc., and Factory
Mutual Research Corp. when used with the above trim sets.
Supervision of a hydraulic preaction system may not be required. However, when supervision is
required, a riser check valve must be installed on the system side of the deluge valve to prevent the
supervising pressurized gas (air or dry nitrogen) from escaping through the alarm line of the deluge
valve. A riser check valve is not required, when supervision of the system is not necessary. Supervising
pressure provided by a RELIABLE Model B or C Compressor Panel (see Section 1.4.2.2.1) or a Model
C Pressure Maintenance Device (see Section 1.4.2.2.2) requires the check valve to be capable of
leak-tight sealing for a pressure of 2.0 psi (30 to 40 oz/in2 (0,15 bar)).

This system is not shown in detail because of its limited use. To order this system, use the
wet deluge system. If supervised, you must add a check valve and supervisory air
equipment.

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
63

(Future)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
64

3.3 Pneumatic (Dry Pilot) Activation


3.3.1 Non-Interlock Type
Dry pilot line operation of this type is the
least costly pneumatic preaction system.
This non-interlock system will respond as
a true preaction system whenever a pilot
line quick response sprinkler (heat
detector) operates before a system
sprinkler. However, if a system sprinkler
should operate first, then the system will
respond exactly like a dry pipe system.
When a sprinkler head operates, as the
result of being damaged, the inherent
safeguarding provided by a preaction
system against accidental water
discharge does not exist with this system.
When water damage, due to accidental
discharge would be a negligible factor,
this preaction system can be quite cost
effective.

Figure 1 Model A Dry Pipe Valve - Model A Trimmings

Pilot line pressure is maintained at a level somewhere between 20 and 50 psi (1,4 and 3,5 bar), and is
simultaneously the pressure in the sprinkler system piping. A Model A Compressor (see Bulletin 275
for proper sizing) and Model B-1 Pressure Maintenance Device should be used to provide this level of
pressure. If a compressed air system is constantly available on the site, than a Model A-2 Pressure
Maintenance Device (see Section 1.4.2.1.2 for maintenance device information) should be used to
simultaneously supply the pilot line and sprinkler piping.

Maintaining pneumatic pressure, according to Table 1, will hold a RELIABLE Dry Pipe Valve (primary
control valve) closed (see Section 1.1.3). This same level of pressure will also hold a Model A Dry Pilot
Actuator releasing device (see Section 1.2.2) closed, preventing system pressure from entering the
intermediate chamber of the dry pipe valve. When one or more pilot heads open, due to fire conditi ons,
the loss of pilot line pressure allows the dry pilot actuator to open. This sufficiently pressurizes the
intermediate chamber of the dry pipe valve causing it to release and flow water into the sprinkler
system. Subsequent opening of one or more sprinkler heads will soon result in water flow on the fire.

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
65

Figure 2 Model D Dry Pipe Valve - Model D Basic Trimming

Model A Manual Emergency Pull Stations (see Section 1.2.4.1) can be incorporated into the dry pilot
line, and they should be piped so that discharging pneumatic pressure is directed away from the
person that operated the station. Pneumatic supervision of sprinkler piping leak tightness in a
non-interlock preaction system is accomplished by employing a low pressure switch to activate a
trouble annunciating device when pilot line pressure falls below a predetermined level. Ignoring this
warning can result in a significant loss of pneumatic pressure which will open the primary control (dry
pipe) valve to flow water into the system.
Models A and D Dry Pipe Valves require a basic trim set for convenient and compact connection
points to alarm and other devices. Basic Trim Sets (Figures 1 & 2) provide a main drain connection,
alarm devices connection, alarm test connection, and gauges for water supply and pneumatic
pressures.

Water Pressure Pneumatic Pressure to be Pumped Into System, psi (bar)


In Supply Line, psi (bar)
Maximum Not Less Than Not More Than

20 (1,7) 10 (0,7) 20 (1,4)


50 (3,5) 15 (1,0) 25 (1,7)
75 (5,1) 20 (1,4) 30 (2,1)
100 (7,0) 25 (1,7) 35 (2,4)

125 (8,6) 30 (2,1) 40 (2,8)


150 (10,3) 35 (2,4) 45 (3,1)
175 (12,1) 40 (2,8) 50 (3,5)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
66

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
67

Preaction System Design Specifications


Pneumatic (Dry Pilot) Activation &
Ordering Information
Non-Interlock Type
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
1 Isolating Valve OS&Y or Butterfly Type
7 Water Flow Pressure Switch G Model EPS 10-1 (SPDT)
(Optional) Model EPS 10-2 (DPDT)
8 Mechanical Alarm (Optional) D Mod. C (Bulletin 612 & 613)

15 Sprinklers D Closed Type


(Bulletin 110, 117, 131, 136, etc.)
16 Manual Emergency Station D Mod. A
(Optional) Hydraulic (Pilot Line) Type
18 Air Compressor I Mod. A, 1 3, 3 4, 11 2 hp (Bulletin 275)
19 Pressure Maintenance Device D Mod. B-1, Use with Item No. 18
(Bulletin 251)
Mod. A-2, Use with N2 or Owner’s Air Supply
(Bulletin 251)
21 Dry Pipe Valve D Mod. A, 2½″ THD x THD or GRV x GRV
Mod. D, 4″ or 6″ FLNG x FLNG or FLNG x GRV
22 Basic Trim Set D Mod. A, (Bulletin 353)
(Dry Pipe Valve) Mod. D, (Bulletin 350)
25 Low Pressure Switch G Model EPS 40-1(SPDT)
(10-100 psi)
26 Air Pressure Gauge D Mod. UA 0-250 psi (Bulletin 206)
28 Dry Pilot Actuator D Mod. A (Bulletin 504)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
68

3.3.2 Single-Interlock Type


Dry pilot single-interlock preaction systems contain several components that differ from those in
non-interlock systems. These add to the cost of a preaction system; however, they do provide
desirable features described below.

The primary control valve is a deluge valve


instead of a dry pipe valve, as employed in
the non-interlock system (see Section
3.3.1). The operating characteristics of
RELIABLE Deluge Valves are discussed in
Section 1.1.1 (2 ½″ Model A) and Section
1.1.2 (4″ & 6″ Model B & BX).
Sprinkler piping in single-interlock systems
can be effectively supervised by using the
same air supply required for pressurization
of the dry pilot actuator (See Section
1.4.2.1). Loss of the supervising pneumatic
pressure, due to a damaged sprinkler or pipe
line, will not cause water flow through a deluge
valve and into the system piping. It will,
however, produce a trouble condition
annunciation.

Figure 1 Model A Deluge Valve with


Single-Interlock Preaction, Dry Pilot Line Trim

A dry pilot line of closed sprinklers (thermal


detectors) is located over an area to be
protected, and is pressurized with
compressed gas, such as air or dry
nitrogen. This pressurized pilot line is
connected to a Model A Dry Pilot Actuator
releasing device (see Section 1.2.2), which
functions like a small dry pipe valve. While
the pilot line is pressurized adequately, the
actuator remains closed keeping sufficient
water pressure in the top chamber or push
rod chamber of a RELIABLE Deluge Valve
(see Figure 1 or 2) to keep it closed.
When a pilot line sprinkler operates, the
pneumatic pressure is reduced until the
actuator is no longer able to hold water
pressure in the top chamber or push rod
chamber. The deluge valve is then
released to open and flow water into the
sprinkler system. A dry pilot line is only for Figure 2 Model BX Deluge Valve with
thermal detection purposes. Single-Interlock Preaction,
Dry Pilot Line Trim

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
69

It will not discharge water from any of its opened sprinklers. Model A Manual Emergency Pull Stati ons
(see Section 1.2.4.1) can be incorporated into the dry pilot line, and they should be piped so that
discharging pneumatic pressure is directed away from the person operating the station. It is very
important that suitable automatic pressure maintenance equipment (see Section 1.4.2.1) be used to
safeguard against accidental deluge valve operation due to possible pressure leakage in the dry pil ot
line. The dry pilot line trim set, required when pneumatically activating a RELIABLE Model A, B, or BX
Deluge Valve, includes a Model A Dry Pilot Actuator releasing device and a low pressure switch for
supervision purposes. This switch is factory set to activate a warning annunciator whenever pressure
falls below 25 psi (1,7 bar). The switch can be adjusted to other pressure levels, if required.
Appropriate pneumatic pressures for dry pilot lines used with RELIABLE Deluge Valves are given by
the following table:

Water Pressure, psi (bar) Pneumatic Pressure to be Pumped into Dry Pilot Line, psi (bar)

Maximum Not Less Than Not More Than


20 (1,7) 10 (0,7) 20 (1,4)
50 (3,5) 15 (1,0) 25 (1,7)

75 (5,1) 20 (1,4) 30 (2,1)


100 (7,0) 25 (1,7) 35 (2,4)
125 (8,6) 30 (2,1) 40 (2,8)
150 (10,3) 35 (2,4) 45 (3,1)

175 (12,1) 40 (2,8) 50 (3,5)

When Model G3 or G3FR Dry Sprinklers are used, a minimum of 15 psi (1.0 bar) pneumatic pressure
should be used.

01/01

The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
70

Model B/BX 4″ & 6″

Model A - 2½″

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
71

Preaction System Design Specifications


Pneumatic (Dry Pilot) Activation &
Ordering Information
Single - Interlock Type
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
1 Isolating Valve OS&Y or Butterfly Type
2 Deluge Valve D Mod. A, 2½″ THD x THD or GRV x GRV
Mod. B, 4″ or 6″ FLNG x FLNG or FLNG x GRV
Mod. BX, 4″ or 6″ FLNG x FLNG or FLNG x
GRV
4 Preaction Trim D Mod. A
Single-Interlock Dry Pilot Mod. B & BX
6 Drain Manifold (Optional) D 2½″ Preaction or 4″/ 6″ Preaction
7 Water Flow Pressure Switch G Mod. EPS 10-1 (SPDT)
(Optional) Mod. EPS 10-2 (DPDT)
8 Mechanical Alarm (Optional) D Mod. C (Bulletin 612 & 613)
15 Sprinklers D Closed Type
(Bulletin 110, 117, 131, 136, etc.)
16 Manual Emergency Station D Mod. A
(Optional) Hydraulic (Pilot Line) Type
18 Air Compressor D Mod. A, 13, ¾, 1½ hp (Bulletin 275)
1
D Mod. A, 6 hp (Bulletin 707, Section 1.4.2)
19 Pressure Maintenance D Mod. B-1, Use with Item No. 18
Device (Bulletin 251)
Mod. A-2, Use with N2 or Owner’s Air Supply
(Bulletin 251)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
72
3.4 Electric Activation (Supertrol System)
Electric activation of a primary control valve requires heat, smoke, or flame detectors (see Sections
1.3.2, 1.3.3, and 1.3.4), which communicate electrically with an electrical releasing control panel (see
Section 1.4.1). Electrically activated preaction systems are generally more costly than hydraulic and
pneumatic systems. However, electrical systems offer the greatest number of features, design
flexibility, speed of operation, and ability to interface with other building services systems.
When the detection section of an electrical preaction system senses the presence of fire, an electrical
signal to the releasing control panel immediately activates an alarm bell circuit and energizes open a
normally closed solenoid releasing valve (see Section 1.2.3). The releasing control panel will
electrically latch a solenoid releasing valve in the open position, and resetting it closed can onl y be
accomplished by operating a resetting switch in the panel, after all detectors and electrical manual
emergency pull stations have been reset.
Manual emergency pull stations (see Section 1.2.4.2) are incorporated electrically into detector
circuits. The single pole, Model BNG-1 is normally used; however, when a releasing control panel is
arranged with the briefly delaying characteristic of cross-zoned operation (see Section1.4.1.2), then
the two-pole, Model BNG-1F station is required. The two-pole station enables activation of both
detector circuits simultaneously; circumventing the delaying characteristic by causing immediate
water flow into the system when fire is visually observed.
A releasing panel must have the capacity to supervise constantly the power supply, detector, alarm
bell, and solenoid releasing valve electrical circuits; and to provide visual and audible trouble
annunciation whenever electrical faults occur in these circuits.
Releasing control panels accept both Class A and Class B detector circuit wiring. Class A wiring,
required by Factory Mutual, uses two (2) wires to each detector, and two (2) wires returning to the
panel. With Class A wiring, a control panel will sound and display trouble signals, and simultaneously
operate an alarm bell and solenoid releasing valve while single and some multiple unrepaired wiring
faults exist.
Class B detector circuit wiring uses two (2) wires to each detector and an end-of-line resistor. With
Class B wiring, the control panel will sound and display trouble signals, but may not operate an al arm
bell and solenoid releasing valve while an unrepaired wiring fault exists.
See page 53 for illustrations of Class A and Class B Wiring.

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
73

In the event of a primary (120/230VAC) power failure, a control panel will automatically switch to battery
power. Batteries are available to supply adequate power to operate the detection, signaling and
releasing components, as required, for a minimum of 60 hours UL and 90 hours FM. Control panels
include a charging circuit which constantly maintains gel cell batteries at full charge.
3.4.1 Non-Interlock Type
This non-interlock system will respond as a true preaction system whenever an electrical detector
operates before a system sprinkler head does. However, if a system sprinkler should operate first, then
the system will respond exactly like a dry pipe system. When a sprinkler head operates, as the result of
being damaged, the inherent safeguarding associated with the preaction systems against accidental
water discharge does not exist with this system. When accidental discharge of water from a sprinkler
head would be a negligible factor, this type of preaction system is the most cost effective of the various
electrical systems.
Maintaining pneumatic pressure, according to the Table below, will hold a RELIABLE Dry Pipe Valve
(Primary Control Valve) closed (see Section 1.1.3).
A Model A Compressor (see Bulletin 275 for proper sizing) and Model B-1 Pressure Maintenance
Device should be used to provide a proper level of pressure. If a compressed air system is constantly
available on the site, then a Model A-2 Pressure Maintenance Device (see Section 1.4.2.1.2 for
maintenance device information) should be used to supply the sprinkler piping.

Water Pressure Pneumatic Pressure to be Pumped Into System, psi (bar)


In Supply Line, psi (bar)
Maximum Not Less Than Not More Than
20 (1,7) 10 (0,7) 20 (1,4)
50 (3,5) 15 (1,0) 25 (1,7)

75 (5,1) 20 (1,4) 30 (2,1)


100 (7,0) 25 (1,7) 35 (2,4)
125 (8,6) 30 (2,1) 40 (2,8)

150 (10,3) 35 (2,4) 45 (3,1)


175 (12,1) 40 (2,8) 50 (3,5)

When Model G3 or G3FR Dry Sprinklers are used, a minimum of 15 psi (1,0 bar) pneumatic
pressure should be used.

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
74
When one (1) electrical detector senses the
presence of fire, the electrical releasing control
panel latches the solenoid releasing valve in the
open position. (Note that arranging detectors in
a cross-zoned pattern will require operation of
two (2) detectors before the solenoid valve can
open.) This pneumatically pressurizes the
intermediate chamber of the dry pipe valve
causing it to release and flow water into the
sprinkler system. Subsequent opening of one
(1) or more sprinkler heads will soon result in
water flow on the fire.
A Model A Manual Emergency Pull Station (see
Section 1.2.4.1) can be incorporated into the
line supplying air pressure to the solenoid valve.
This pull station should be piped so that
discharging pneumatic pressure is directed
away from the person that operated the station.
Figure 1 Model A Dry Pipe Valve - Model A Trimmings

Model BNG Electrical Manual Emergency


Stations (see Section 1.2.4.2) are incorporated into the detector circuit(s).
Pneumatic supervision of sprinkler piping leak tightness in a non-interlock preaction system is
accomplished by employing a low pressure switch to activate a trouble annunciating device, when system
pressure falls below a predetermined level that is considerably higher than the normal dry pipe valve
releasing (tripping) pressure. Ignoring this annunciating device can result in further pneumatic pressure
decrease leading to unintentional releasing (opening) of the dry pipe valve. Models A and D Dry Pipe
Valves require a basic trim set for convenient and compact connection points to alarm and other devices.
Basic trim sets (Figures 1 & 2) provide a main drain connection, alarm devices connection, alarm test
connection, and gauges for water supply and pneumatic pressures.

Figure 2 Model D Dry Pipe Valve - Model D Basic Trimmings


01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
75

(Future)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
76

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
77

Preaction System Design Specifications


Electrical Activation &
Ordering Information
Non-Interlock Type
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
1 Isolating Valve OS&Y or Butterfly Type
7 Water Flow Pressure Switch G Mod. EPS 10-1 (SPDT)
(Optional) Mod. EPS 10-2 (DPDT)
8 Mechanical Alarm (Optional) D Mod. C (Bulletin 612 & 613)
Solenoid Releasing Valve C Mod. 73218BN4UNLVNOC111C2 24VDC
9
(Normally Closed)
10 Releasing Control Panel A Mod. RP-1001
(Optional)
Batteries (2 Required) A Mod. PS 12120 (90 Hrs. Back-up) (FM)
Mod. PS 1270 (60 Hrs. Back-up)
Optional Accessories A Mod. 4XTM Transmitter Module
Mod. 4XLM Annun. Driv. Module
Mod. RZA-4X Remote Annun.
Mod. 4XZM Zone Relay Module
11 Alarm Annunciator (Optional) G Mod. SSM-24-8-24VDC / Polarized Bell
Mod. SSM-24-10-24VDC / Polarized Bell
Mod. H 12/24-24VDC / Polarized Horn
Mod. P2415-24VDC / Polarized Horn Strobe
12 Trouble Annunciator G Mod. SSM-24-6-24VDC / Polarized Bell
Mod. H 12/24-24VDC / Polarized Horn
13 Manual Emergency Station A Mod. BNG-1 (SPDT)
(Optional) 1 & 2 Area Detection
Mod. BNG-1F (DPDT) Cross Zone Detection

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
78

(Future)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
79

Preaction System Design Specifications


Electrical Activation &
Ordering Information
Non-Interlock Type
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
14 Detectors (Optional)
Thermal H Mod. 302 Pendent / Interior, 135°F, 200°F
Thermal Mod. 302H Horizontal / Interior, 135°F, 200°F
Thermal Mod. 302AW Pendent / All Weather, 135°F, 200°F
Adapter Mod. AP-P Adapter Plate (Mod. 302 Only)
Smoke B Mod. PSD7155 Photoelectric
Smoke Mod. CPD7051 Ionization
Base (Required with PSD & B Mod. 70-201000-001
CPD Detectors) Base (2-Wire)
16 Manual Emergency Station D Mod. A
(Optional) Hydraulic (Pilot Line) Type
1
18 Air Compressor D Mod. A, 3 , 3 4, 1 1 2 hp (Bulletin 275)
1
D Mod. A, 6 hp (Bulletin 707, Section 1.4.2)
19 Pressure Maintenance D Mod. B-1, Use with Item No. 18
Device (Bulletin 251)
Mod. A-2, Use with N2 or Owner’s Air Supply
(Bulletin 251)
21 Dry Pipe Valve D Mod. A, 2½ ″ THD x THD or GRV x GRV
Mod. D 4″ or 6″ FLNG x FLNG or FLNG x GRV
22 Basic Trim Set D Mod. A (Bulletin 353)
(Dry Pipe Valve) Mod. D (Bulletin 350)
23 Accelerator (Optional) D Mod. B1 (Bulletin 320 & 322)
Low Pressure Switch Mod. EPS 40-1 (SPDT)
25 G
(10-100 psi)
26 Air Pressure Gauge D Mod. UA 0-250 psi (Bulletin 206)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
80

(Future)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
81
3.4.2 Single-Interlock Type Supertrol Systems
Electric single-interlock preaction systems contain several components that differ from those in
non-interlock systems. These add to the cost of a preaction system; however, they do provide desirable
features described below.

The primary control valve is a deluge valve instead of a dry pipe valve, as employed in the non-int erlock
system (see Section 3.4.1). The operating characteristics of RELIABLE Deluge Valves are discussed
in Section 1.1.1 (2½″ (65mm) Model A) and Section 1.1.2 (4″ & 6″ (100mm and 150mm) Model B &
BX).

Sprinkler piping in single-interlock systems can be effectively supervised by means of a Model B or C


Air Compressor Panel or a Model C Pressure Maintenance Device (see Section 1.4.2.2). Loss of the
2.0 psi (0,14 bar) supervising pneumatic pressure, due to a damaged sprinkler or pipe line, will not
cause water flow through a deluge valve and into the system piping. A significant loss of pneumati c
pressure will activate a trouble annunciating device when system pressure falls below 7 psi (0,5 bar).

Figure 1 Model BX Deluge Valve with Electrical Actuation Preaction Trim


When one (1) electrical detector senses the presence of fire, the electrical releasing control panel
activates fire alarm devices and latches the solenoid releasing valve in the open position. (Note that
arranging detectors in a cross-zoned pattern will require operation of two (2) detectors before the
solenoid valve can open.) The solenoid releasing valve (Figures 1 & 2), when closed, is preserving
sufficient water pressure in the top chamber or push rod chamber of a RELIABLE Deluge Valve to hold
it closed. Opening the solenoid release valve relieves that water pressure, and thereby opens the
deluge valve to allow water flow in the sprinkler system.
To fully operate a cross-zoned , single-interlock system, two (2) electrical detectors must activat e, and
a sprinkler head must open. The operating sequence of a cross-zoned system follows. During the
initial stages of a fire, smoke or heat activates the first detector which causes the panel to produce a
local alarm and an alarm at the main fire alarm panel. Electrical relays inside the releasing cont rol panel
can be used to shut down air moving equipment and computer systems or activate security doors and
other electrical devices, when the panel goes into this “first alarm” condition. Subsequent activation of
a second, nearby (adjacent) detector will cause the panel to energize the solenoid valve open and
release pressure in the top or push rod chamber of the deluge valve which causes the clapper to
unlatch. This immediately sends water into the sprinkler piping.

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
82

Water flowing into the sprinkler piping will


simultaneously produce water pressure in the
alarm trim piping of the deluge valve, a
condition that causes the transfer of dry
contacts in one or more pressure switches
mounted in this alarm line. Each pressure
switch can electrically control the shutdown or
start-up of equipment, such as, computers or
other “second alarm” devices, respectively.
The flow of water into the sprinkler piping
effectively converts the heretofore dry system
into a wet pipe system. In the event the fire
subsequently produces sufficient heat to
operate a sprinkler head, water will flow from
that sprinkler on the fire.
The major benefits of a single-interlock
preaction system, when compared with
a wet-pipe system, are as follows:

Figure 2 Model A Deluge Valve with


Electrical Actuation Preaction Trim

A. A fire alarm sounds prior to the operation of a sprinkler which may enable
extinguishing the fire by hand-held means before the operation of any sprinkler head
occurs.

B. A trouble annunciator signals whenever the integrity of piping or sprinklers is


accidentally or intentionally disturbed; however, no water flow or water damage will
result at this time.

C. Speedy detection and an early fire alarm is provided by fire detectors, without the
delay of water delivery time, in the event of a fire. Note that with a wet-pipe system,
the fire alarm is produced only after water has begun flowing from an operated
sprinkler head.

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
83

Model B/ BX 4″ & 6″

Model A 2½″

* When Model G3 or G3FR Dry Sprin klers are used (Ref. Sec tion 3.1) or when su per vi sory
pressures above 15 psi are preferred, substitute the Model A-2 Pres sure Main te nance De vice
(Item 19) and the Low Pres sure Switch (Item 25) for Item 17.

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
84

Preaction System Design Specifications


Electrical Activation &
Ordering Information
Single - Interlock Type
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls, Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
1 Isolating Valve OS&Y or Butterfly Type
2 Deluge Valve D Mod. A, 2½″ THD x THD or GRV x GRV
Mod. B, 4″ or 6″ FLNG x FLNG or FLNG x GRV
Mod. BX, 4″ or 6″ FLNG x FLNG or FLNG x GRV
Preaction Trim D Mod. A (Bulletin 715)
4
Single-Interlock - Electric Mod. B&BX (Bulletin 716)
6 Drain Manifold (Optional) D 2½″ Preaction or 4″/6″ Preaction
7 Water Flow Pressure Switch G Mod. EPS 10-1 (SPDT)
(Optional) Mod. EPS 10-2 (DPDT)
8 Mechanical Alarm (Optional) D Mod. C (Bulletin 612 & 613)

10 Releasing Control Panel A Mod. RP-1001


(Optional)
Batteries (2 Required) A Mod. PS 12120 (90 Hrs. Back-up) (FM)
Mod. PS 1270 (60 Hrs Back-up)
Optional Accessories A Mod. 4XTM Transmitter Module
Mod. 4XLM Annun. Driv. Module
Mod. RZA-4X Remote Annun.
Mod. 4XZM Zone Module
11 Alarm Annunciator (Optional) G Mod. SSM-24-8-24VDC / Polarized Bell
Mod. SSM-24-10-24VDC / Polarized Bell
Mod. H 12/24-24VDC / Polarized Horn
Mod. P2415-24VDC / Polarized Horn/Strobe

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
85
Preaction System Design Specifications
Electrical Activation &
Ordering Information
Single - Interlock Type
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls, Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
Trouble Annunciator Mod. SSM-24-6-24VDC / Polarized Bell
12 G
(Optional)
Mod. P2415-24VDC / Polarized Sounder
13 Manual Emergency Station A Mod. BNG-1 (SPDT)
(Optional) 1 & 2 Area Detection
Mod. BNG-1F (DPDT) Cross Zone Detection
14 Detectors (Optional)
Thermal H Mod. 302 Pendent / Interior, 135°F, 200°F
Thermal Mod. 302H Horizontal / Interior, 135°F, 200°F
Thermal Mod. 302AW Pendent / All Weather, 135°F, 200°F
Adapter Mod. AP-P Adapter Plate (Mod. 302 Only)
Smoke B Mod. PSD7155 Photoelectric
Smoke Mod. CPD7051 Ionization
Base (Required with PSD & B Mod. 70-201000-001
CPD Detectors) Base (2-Wire)
15 Sprinklers D Closed Type (Bulletins 110, 117, 131, 136, etc.)
17 Supervisory Pressure D Mod. B Air Compressor Panel 120 VAC / 60HZ
Supply (Optional)
Mod. C Air Compressor Panel 220 VAC / 50HZ
Mod. C Pressure maintenance Device requires 40
to 100 psi Supply
Pressure Maintenance D Mod. B-1 (Bulletin 251)
19
Device (Optional)
1
20 Air Compressor with I Mod. 1 HAB-11T-M100X, 6 hp 2 Gal. Tank
Tank
25 Low Pressure Switch G Mod. EPS 40-1 (SPDT)
(10-100psi) (Optional)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
86

1½″ Preaction System Design Specifications


Electrical Activation &
Ordering Information
Single-Interlock Type
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls, Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.
ITEM
No. COMPONENT PART (1) DESCRIPTION
2 Deluge Riser Assembly D/C Model H 1½″ Thd x Thd (Bulletin 507)
Preaction Trim Model H (Bulletin 719)
4 D
Single-Interlock-Electric
10 Releasing Control Panel A Model RP-1001
(Optional)
Batteries (2 Required) A Model PS 12120 (90 Hrs. Back-up) (FM)
Model PS 1270 (60 Hrs. Back-up)
Optional Accessories A Model 4XTM Transmitter Module
Model 4XLM Annunciator Driv. Module
Model RZA-4X Remote Annunciator
Model 4XZM Zone Module
11 Alarm Annunciator (Optional) G Model SSM-24-8-24VDC/Polarized Bell
Model SSM-24-10-24VDC/Polarized Bell

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
87

1½″ Preaction System Design Specifications


Electrical Activation &
Ordering Information
Single - Interlock Type
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
12 Trouble Annunciator G Mod. SSM-24-6-24VDC / Polarized Bell
(Optional)
Mod. H 12/24-24VDC / Polarized Horn
13 Manual Emergency Station A Mod. BNG-1 (SPDT)
(Optional) 1 & 2 Area Detection
Mod. BNG-1F (DPDT) Cross Zone Detection
14 Detectors (Optional)
Thermal H Mod. 302 Pendent / Interior, 135°F, 200°F
Thermal Mod. 302H Horizontal / Interior, 135°F, 200°F
Thermal Mod. 302AW Pendent / All Weather, 135°F, 200°F
Adapter Mod. AP-P Adapter Plate (Mod. 302 Only)
Smoke B Mod. PSD7155 Photoelectric
Smoke Mod. CPD7051 Ionization
Base (Required with PSD & B Mod. 70-201000-001
CPD Detectors) Base (2-Wire)
15 Sprinklers D Closed Type (Bulletins 110, 117, 131, 136, etc.)
17 Supervisory Pressure D Mod. B Air Compressor Panel 120 VAC / 60HZ
Supply (Optional)
Mod. C Air Compressor Panel 220 VAC / 50HZ
Mod. C Pressure Maintenance Device requires 40
to 100 psi Supply
Air Compressor with Tank Mod. 1 HAB-11T-M100X, 1 6 hp 2 Gal. Tank
20 I
(Optional) (Use with Mod. C Pressure Maintenance Device)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
88
3.4.2.1 PrePaK Systems
The Reliable PrePaK Preaction Systems are completely self-contained supervised preaction systems
for UL Applications that can be readily installed within a floor space of 4 or 7.5 square feet (0.37 or
2
0.7m ). Installation for the PrePaK (not including exterior devices, i.e., detectors and alarm bells)
requires just three piping connections: a supply line, a system line, and a drain line. Locations of these
piping connections are shown in Reliable Bulletins 723, 724, and 725 Figure 1. Also two 120 VAC
electrical supply connections are required for the Potter Panel and the air compressor.
Each Reliable PrePaK Preaction System contains the following components within their gauge 12 steel
enclosure:
• One of the following Reliable Deluge Valves:
– Model H 1½″ (40mm) Deluge Riser Assembly (see Bulletin 507).
– Model A 2½″ (65mm) Deluge valve (see Bulletin 503).
– Model BX 4″ (100mm) or 6″ (150mm) deluge valve (see Bulletin 501).
• One Reliable Model A-2 Pressure Maintenance Device (see Reliable Bulletin 251)
• One Model G Right-Check Valve, sizes 2½″ - 6″ (see Bulletin 806)
• One Gast Tank-Mounted Air Compressor
– Model 1 HAB-11T-M100X 1 6 hp with 2 Gal. (7.6 liters) Tank (1½″ and 2½″ PrePaK)
– Model 5HCD-108 M550X ¾ hp with 10 gal. (37.9 liters) Tank (4″ and 6″* PrePaK)
* For 6″ systems, a 1 ½ hp compressor is available as an option.
• One Potter Model PFC-4410 Fire Alarm/Releasing Panel (see Potter Manual #5403527)
• All required piping, fittings, gauges, electrical connectors, and electrical devices to utilize the
system in single interlock, single-interlock cross-zoned, double-interlock and double-interlock
cross-zoned applications.
The Reliable PrePaK Preaction Systems utilize the Potter Model PFC-4410 Fire Alarm Releasing Panel.
This fully programmable, microprocessor-based releasing panel is Underwriters Laboratories, Inc.
Listed and is in compliance with NFPA 13 and NFPA 72.
Because the PFC-4410 is totally zone and output programmable, the Reliable PrePaK can be utilized i n
four different preaction applications without having to rewire any of the factory installed devices. Once
the previously described connections are completed, the 24 VDC detectors, output devices, and relay
contacts may be connected to achieve the desired system implementation.
The PrePaK Preaction System can be used in both single and double-interlock applications. Reliable
Single and Double-Interlock Preaction Systems are designed for water sensitive areas which require
protection from inadvertent water flow into the sprinkler system piping.
The major benefits of Single or Double-Interlock PrePaK Preaction Systems are described in Bulletins
723, 724, 725 and in Section 3.1 of this manual.
Approvals
The Reliable PrePaK Preaction Systems are Underwriters Laboratories Inc. (UL) Listed, and UL
Certified for Canada*, as an assembled unit, in the “Special System Water Control Valves-Assembled
Units” category (VKYL). The system components within the PrePaK enclosure are Factory Mutual
Approved as Supertrol Single-Interlock Preaction Systems and Supertrol Double-Interlock Type D
Refrigerated Area Preaction Systems for use in refrigerated rooms or buildings. (Refer to respective
PrePak Bulletins for New York City MEA approvals, guidelines and limitations.)
* Electrical devices and control panel must be specified to meet Canadian requirements. This option is
available.
Technical Data
The Reliable PrePaK Preaction Systems are rated for a minimum supply pressure of 20 psi (1,4 bar)
and a maximum supply pressure of 175 psi (12 bar).
01/01
The Reliable Automatic Sprinkler Co., Inc. 525 North MacQuesten Parkway, Mount Vernon New York 10552
89

Model H 1½″ PrePaK Shown

PrePaK Model Friction Loss (1) Enclosure Dimensions Shipping Weight


Model H 1½″ (40mm) 36 ft. (11m) (2) 64 ″ H x 24″ W x 24″ D 460 lbs (209kg)
PrePaK (1626mm H x 610mm W x 610mm D)
Model A 2½″ (65mm) 62 ft. (19m)(3) 64 ″ H x 24″ W x 24″ D 480 lbs (218kg)
PrePaK (1626mm H x 610mm W x 610mm D)
Model BX 4″ (100mm) 58 ft. (18m)(4) 72 ″ H x 36″ W x 30″ D 800 lbs (363kg)
PrePaK (1829mm H x 914mm W x 762mm D)
Model BX 6″ (150mm) 83 ft. (25m)(4) 72 ″ H x 36″ W x 30″ D 900 lbs (408kg)
PrePaK (1829mm H x 914mm W x 762mm D)
(1)
Friction Loss expressed in equivalent length of Schedule 40 pipe, based on the Hazen-Williams
(2)
formula with C=120 and a flowing velocity of 15 ft/s (4.6m/s).
Includes Total Riser Assembly.
(3)
Includes Deluge Valve, 90° Elbow, Tee, Model G Right-Check Valve, and Butterfly Control Valve.
(4)
Includes Deluge Valve, Model G Right-Check Valve, Tee, and Butterfly Control Valve.

System Design Considerations


The automatic sprinkler releasing devices, fire detection devices, manual pull stations, and signal ing
devices which are utilized with the Reliable PrePaK Preaction Systems must be UL and/or ULC Listed,
as applicable. The steel enclosure and all interconnecting piping must be a minimum temperature of
40°F (4°C).
NOTE: HEAT TRACING IS NOT PERMITTED
The solenoid valve is operated and supervised by the Potter electric releasing control panel. Details on
the electrical connections of this system to a Potter model PFC-4410 Releasing Control Panel can be
found in Potter Manual #5403527, Installation, Operation, and Instruction of PFC-4410 Fire
Alarm/Releasing Panel. This panel is programmable and may be adapted to several applications.

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
90
3.4.3 Double-Interlock Type Supertrol Systems
Electric double-interlock preaction systems can be accomplished with several different arrangements
of all the same components that comprise single-interlock preaction systems. A double-interlock
system is defined as a system which requires the operation of both a detector and a sprinkler before
water is able to flow through a primary control valve (deluge valve) into the sprinkler system pipi ng.
Double-interlock systems are treated as a dry pipe system and therefore are more costly to install than
the single-interlock types.

Recall that single-interlock systems require only the operation of one (1) or two (2) (cross-zoned)
detectors to cause water to flow into the sprinkler piping, making the system ready (wet) for when a
sprinkler subsequently operates. This brief time of waiting for a sprinkler operation could result in an
impairment to fire protection if ambient temperature surrounding the sprinkler system is below freezing.
Not only could ice forming inside the piping become an impairment, it could also cause extensive
damage to the sprinkler system and the area/materials being protected by the system.

Consequently, double-interlock arrangements were developed for fire protection that has as much
assurance as possible that water would continually flow through the deluge valve and open sprinklers
when subfreezing conditions existed. These are the systems of choice for refrigerated warehouses.

Electrical detector activation of the releasing control panel for electrical double-interlock systems is
accomplished in the same manner as activation of single-interlock systems, and the reader is referred
to Section 3.4.2 for a description of electrical activation.
3.4.3.1 Type A
Double-Interlock Supertrol System (Interlocked Dry Pilot Actuator & Solenoid Valve
Releasing Devices)
SUMMARY OF OPERATION

The Model A Compressor and the Model B-1 Air Maintenance Device combine to provide air pressure
in the sprinkler piping at an appropriate level between 20 and 50 psi (1,4 and 3,5 bar). The purpose of
this air is to maintain the Model A Dry Pilot Actuator releasing device in the closed position, thereby
preventing the possibility of water flowing from the push rod or top chamber of the deluge valve. The
dry pilot actuator functions as described in Section 1.2.2. However, a tank mounted air compressor,
supplying air pressure between 50 and 100 psi (3,5 and 6,9 bar) to the Model A-2 pressure
maintenance device, is recommended.

In series with and upstream of the dry pilot actuator is a second releasing device identified as the
solenoid valve. The solenoid valve is activated electrically when a manual electrical emergency station
or a thermal or smoke detector operates and signals the releasing control panel to open the solenoi d
valve.

For this system, the double-interlocking feature requires both the dry pilot actuator and the solenoid
valve to be open simultaneously before the deluge valve will open to permit water flow into the sprinkler
system. When only a sprinkler head operates (or is broken), air pressure will be lowered which opens
the dry pilot actuator and activates the low-pressure switch causing only an alarm annunciation. There
will be no waterflow into the sprinkler system, as long as the solenoid valve remains closed.

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
91
Conversely, if a smoke detector operates (or produces a false alarm), the signal to the control panel
will, in turn, open the solenoid valve. However, the dry pilot actuator will remain closed thereby
preventing the operation of the deluge valve. Again, only an alarm will sound, but there will be no
waterflow into the sprinkler piping.
In a fire scenario, operation of a sprinkler and at least one (1) detector will cause both releasing devices
to open, thereby opening the deluge valve permitting water to flow into the sprinkler piping and out the
open sprinkler head.
Note that the air pressure in the sprinkler piping has the secondary purpose of supervising the integrity
of the sprinkler piping. Any condition that would result in significant pressure reduction, such as a
damaged sprinkler or broken fitting, would cause an alarm device to annunciate until the damage has
been corrected. Also, supervision of various electrical circuits, such as the detector circuit, alarm bell
circuit, solenoid circuit, and power supply circuits are all annunciated by a common trouble bell and
individual circuit lights on the releasing control panel. See Section 1.4.1 for information on the Model
RP1001 Panel.
APPROVALS
The 4 and 6 inch Supertrol Type A Double-
Interlock Preaction Systems are Factory Mutual
Approved for use in refrigerated rooms or
buildings. Refrigerated area sprinkler systems
are FM Approved as complete systems. Only
the approved components for this system as
listed in this bulletin can be used in combination.
Systems are FM Approved for use with thermal
detectors and Class A detector circuit wiring
only.

The Reliable Type A Double-Interlock Preaction


System is Listed By Underwriters Laboratories in
the Special System Water Control Valves-
Double-Interlock Type (VLJH) Category.

The components of the Supertrol Double-


Interlock Preaction Systems are individually listed
by Underwriters’ Laboratories of Canada.

Type A Double-Interlock System

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
92
Type A Double-Interlock Systems must be used with Latching Deluge Valves such as 4″ (100mm) and
6″ (150mm) Models B & BX.
Non-latching deluge valves may close prematurely if air pressure is permitted to increase above the
Model A Dry Pilot Actuator.

Note: The Model A, 2½″Deluge Valve is not available for Type A Systems.

4″ & 6″ Model BX PREACTION SYSTEM Electric Activation Double-Interlock Type A

*Optional compressor equipment includes: 1 6 thru 2 hp tankless or tank-mounted types


(recommended). Item 19 must be a Model A-2 Pressure Maintenance Device when tank-mounted
compressors are used.

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
93

Preaction System Design Specifications


Electrical Activation &
Ordering Information
Double - Interlock Type A
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
1 Isolating Valve OS&Y or Butterfly Type
2 Deluge Valve D
Mod. B, 4″ or 6″ FLNG x FLNG or FLNG x GRV
Mod. BX, 4″ or 6″ FLNG x FLNG or FLNG x GRV
5 Preaction Trim D Mod. B&BX (Bulletin 710)
Double-Interlock Type A
6 Drain Manifold (Optional) D 4″/6″ Preaction
7 Water Flow Pressure Switch G Mod. EPS 10-1 (SPDT)
(Optional) Mod. EPS 10-2 (DPDT)
8 Mechanical Alarm (Optional) D Mod. C (Bulletin 612 & 613)
10 Releasing Control Panel A Mod. RP-1001
(Optional)
Batteries (2 Required) A Mod. PS 12120 (90 Hrs. Back-up) (FM)
Mod. PS 1270 (60 Hrs Back-up)
Optional Accessories A Mod. 4XTM Transmitter Module
Mod. 4XLM Annun. Driv. Module
Mod. RZA-4X Remote Annun.
Mod. 4XZM Zone Module
Alarm Annunciator G Mod. SSM-24-8-24VDC / Polarized Bell
11
(Optional)
Mod. SSM-24-10-24VDC / Polarized Bell
Mod. H 12/24-24VDC / Polarized Horn
Mod. P2415-24VDC / Polarized Horn/Strobe

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
94

(Future)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
95

Preaction System Design Specifications


Electrical Activation &
Ordering Information
Double - Interlock Type A
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
12 Trouble Annunciator (Optional) G Mod. SSM-24-6-24VDC / Polarized Bell
Mod. H 12/24-24VDC / Polarized Horn
13 Manual Emergency Station A Mod. BNG-1 (SPDT)
(Optional) 1 & 2 Area Detection
Mod. BNG-1F (DPDT) Cross Zone Detection
14 Detectors (Optional)
Thermal H Mod. 302 Pendent / Interior, 135°F, 200°F
Thermal Mod. 302H Horizontal / Interior, 135°F, 200°F
Thermal Mod. 302AW Pendent / All Weather,
135°F, 200°F
Adapter Mod. AP-P Adapter Plate (Mod. 302 Only)
15 Sprinklers D Closed Type (Bulletins 110, 117, 131, 136, etc.)
18 Air Compressor D Mod. A, 1 3, ¾, 1½ hp (Bulletin 275)
1
Mod. A, 6 hp (Bulletin 707, Section 1.4.2)
19 Pressure Maintenance Device D Mod. B-1, Use with Item No. 18
(Bulletin 251)
Mod. A-2, Use with N2 or Owner’s Air Supply
(Bulletin 251)
23 Accelerator (Optional) D Mod. B1 (Bulletin 320 & 322)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
96
3.4.3.2 Type D Double-Interlock Supertrol Systems
(Interlocked Detector & Supervisory Pressure Switch)

SUMMARY OF OPERATION

The Type D Double-Interlock Supertrol System contains a pressure switch which activates one detector
circuit in a cross-zoned panel whenever supervising dry nitrogen gas or air pressure in the sprinkl er
piping drops below 5 psi (0,4 bar). Normally, the Model A-2 Pressure Maintenance Device would
maintain the pressure at 7 to 10 psi (0,5 to 0,7 bar) for supervising the sprinkler system integrity. A
special regulator will be required on nitrogen tanks to reduce their 2000 psi (138 bar) pressure down to
approximately 175 psi (12 bar), which is the maximum level required for supplying the Model A-2
device. Refer to Section 3.4.3.3 and Bulletin 253 for information describing Reliable’s Nitrogen
Regulating Device.

When a sprinkler head operates (or is accidentally broken), the resulting reduction of pressure at the low
pressure switch will send a pneumatic signal to the RP1001 Releasing Control Panel causing the panel
to annunciate a “first” alarm. However, there will not be waterflow into the sprinkler piping. Replacing the
broken sprinkler, permitting the pressure to return to the normal 7 to 10 psi (0,5 to 0,7 bar), and pushing
the reset button in the RP-1001 Releasing Control Panel will restore the system to a fire-ready condition.

However, in a fire scenario, the combined operation of a sprinkler and at least one (1) detector on the
second detector circuit will cause the RP-1001 Releasing Control Panel to activate the solenoid valve,
thereby releasing the deluge valve and flowing water into the piping and out the open sprinkler head.
Simultaneously, the waterflow pressure switch mounted in the alarm line trim of the deluge valve will
operate, and it will be used to annunciate a “second” alarm (waterflow) condition. This switch (or
multiples thereof) can also be used to start or stop various items of electrical equipment.

It is likely that during a fire, a detector would operate before a sprinkler. Again, the RP-1001 Releasing
Control Panel would signal a “first” alarm without permitting waterflow into the system. After the fire had
developed sufficient heat to also operate a sprinkler, and subsequently the low pressure switch, only
then would water flow into the sprinkler system and out of the open sprinkler. Of course, the vari ous
“second” alarm actions would also occur.

The pneumatic system supervision feature has already been discussed. Supervision of various
electrical circuits, such as the detector, alarm bell, solenoid valve, and power supply circuits are
annunciated by a common trouble bell and individual circuit lights on the RP-1001 Releasing Control
Panel.

APPROVALS
The 2½″ (65mm), 4″ (100mm), and 6″ (150mm) Supertrol Type D Double-Interlock Preaction Systems
are Factory Mutual Approved for use in refrigerated rooms or buildings. Refrigerated area sprinkler
systems are FM Approved as complete systems. Only the approved components for this system as
listed in this bulletin can be used in combination. Systems are FM Approved for use with thermal
detectors and Class A detector circuit wiring only.

The components of the Supertrol Double-Interlock Preaction Systems are individually listed by
Underwriters’ Laboratories of Canada. The 2½″ (65mm), 4″ (100mm), and 6″ (150mm) Type D
Double-Interlock Preaction Systems are Underwriters Laboratories Listed in the Special System Water
Control Valves Double-Interlock Type (VLJH) Category.

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
97

(Future)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
98

Model BX 4″ & 6″

Note: A Con stant source of pres sure is re quired. A tank mounted air com pres sor is
rec om mended . Dry ni tro gen is an op tion for freezer ap pli ca tions.

Model A 2½″
01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
99

Preaction System Design Specifications


Electrical Activation &
Ordering Information
Double - Interlock Type D
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
1 Isolating Valve OS&Y or Butterfly Type
2 Deluge Valve D Model A, 2½″ THD x THD or GRV x GRV
Model B, 4″ or 6″ FLNG x FLNG or FLNG x GRV
Model BX, 4″ or 6″ FLNG x FLNG or FLNG x GRV
5 Preaction Trim D Model A (Bulletin 713)
Double-Interlock Type D Model B&BX (Bulletin 714)
6 Drain Manifold (Optional) D 2½″ Preaction, 4″/6″ Preaction
7 Water Flow Pressure Switch G Model EPS 10-1 (SPDT)
(Optional) Model EPS 10-2 (DPDT)
8 Mechanical Alarm (Optional) D Model C (Bulletin 612 & 613)

10 Releasing Control Panel A Model RP-1001


(Optional)
Batteries (2 Required) A Model PS 12120 (90 Hrs. Back-up) (FM)
Model PS 1270 (60 Hrs Back-up)
Optional Accessories A Model 4XTM Transmitter Module
Model 4XLM Annun. Driv. Module
Model RZA-4X Remote Annun.
Model 4XZM Zone Module
11 Alarm Annunciator (Optional) G Model SSM-24-8-24VDC / Polarized Bell
Model SSM-24-10-24VDC / Polarized Bell
Model H 12/24-24VDC Polarized Horn
Mod. P2415-24VDC / Polarized Horn/Strobe

*Priming water should not be used in systems maintained at temperatures below 32°F (0°C) .

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
100

(Future)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
101

Preaction System Design Specifications


Electrical Activation &
Ordering Information
Double - Interlock Type D
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
Trouble Annunciator Model SSM-24-6-24VDC / Polarized Bell
12 G
(Optional)
Model H 12/24-24VDC / Polarized Horn

13 Manual Emergency Station A Model BNG-1 (SPDT)


(Optional) 1 & 2 Area Detection

14 Detectors (Optional)
Thermal H Model 302 Pendent / Interior, 135°F, 200°F
Thermal Model 302H Horizontal / Interior, 135°F, 200°G
Thermal Mod. 302AW Pendent / All Weather, 135°F, 200°F
Adapter Model AP-P Adapter Plate (Model 302 Only)
Smoke B Model PSD7125 Photoelectric
Smoke Model CPD7021 Ionization
Base (Required with PSD & Model 70-201000-001
CPD Detectors) Base (2-wire)
15 Sprinklers D Closed Type (Bulletins 110, 117, 131, 136, etc.)
Pressure Maintenance Model A-2, Use with Item number 20
19 D
Device (Bulletin 251)
20 Air Compressor I Model 1HAB-11T-M100X 1 6″ & 2 Gal Tank
Model 5LCA-11T-M550X ¾″ & 20 Gal Tank

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
102

Preaction System Design Specifications


1½″ Electrical Activation &
Ordering Information
Double-Interlock Type D
(1)
System Equipment Manufacturers
(A) Notifier , Division of Pitway Corp. (E) United Electric Controls Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
2 Deluge Riser Assembly D/C Model H 1½ Thd x Thd (Bulletin 507)
5 Preaction Trim D Model H (Bulletin 720)
Double-Interlock-Type D
10 Releasing Control Panel A Model RP-1001
(Optional)
Batteries (2 Required) A Model PS 12120 (90 Hrs. Back-up) (FM)
Model PS 1270 (60 Hrs. Back-up)
Optional Accessories A Model 4XTM Transmitter Module
Model 4XLM Annunciator Driv. Module
Model RZA-4X Remote Annunciator

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
103

Preaction System Design Specifications


1½″ Electrical Activation &
Ordering Information
Double-Interlock Type D
(1)
System Equipment Manufacturers
(A) Notifier, Division of Pitway Corp. (E) United Electric Controls Co. (I) Gast Manufacturing, Inc.
(B) Fenwal Inc., Division of W. Kidde & Co., Inc. (F) Meggitt Avionics
(C) Skinner Valve Division, Parker Hannifin Corp. (G) System Sensor, Division of Pitway Corp.
(D) The Reliable Automatic Sprinkler Co., Inc. (H) Thermotech, Inc.

ITEM
No. COMPONENT PART (1) DESCRIPTION
Alarm Annunciator (Optional) G Model SSM-24-8-24VDC / Polarized Bell
11

Model SSM-24-10-24VDC / Polarized Bell


Model H 12/24-24VDC / Polarized Horn
Model P2415-24VDC Polarized Horn/Strobe
12 Trouble Annunciator G Model SSM-24-10-24VDC / Polarized Bell
(Optional)
Model H 12/24-24VDC / Polarized Horn
13 Manual Emergency Station A Model BNG-1 (SPDT)
(Optional) 1 & 2 Area Detection
14 Detectors (Optional)
Thermal H Model 302 Pendent / Interior, 135°F, 200°F
Thermal Model 302H Horizontal / Interior, 135°F, 200°F
Thermal Mod. 302AW Pend./All Weather, 135°F, 200°F
Adapter Model AP-P Adapter Plate (Model 302 Only)
Smoke B Model PSD7155 Photoelectric
Smoke Model CPD7051 Ionization
Base (Required with PSD & Model 70-201000-001
CPD Detectors) Base (2-Wire)
15 Sprinklers D Closed Type (Bulletins 110, 117, 131, 136, etc.)
Air Compressor Model 1LAA-11T-M100X, 16 hp Compressor and 2
20 I Gal. Tank (Bulletin 707, Section 1.4.2 & Bulletin
720)

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
104
3.4.3.3 Nitrogen Regulating Device

General Description
Re li able Ni tro gen Reg u lating De vices are used to pro vide ni tro gen pres sure in Re li able Supertrol Dou -
ble-Interlock Preaction Type D Systems or any other Reliable system using a Re li able Model A-2 or
Model C Pres sure Main te nance De vice. The ni tro gen sup ply is ob tained from a high pres sure nitrogen
cylinder.
In stalled at the su per vi sory pres sure port of the sys tem, the Ni tro gen Regu lat ing De vice in cludes a sin-
gle stage pres sure regu la tor equipped with high pres sure in let and low pres sure out let gages. As the
ni tro gen is gradu ally de pleted and the pres sure in side the cyl in der drops, the low pres sur e regu lated
output remains stable. Connected to the regulator is a coiled copper tubing with connector and
adapter for a flexi ble and di rect con nec tion to the above men tioned Re li able pres sure main tenance
devices.
If de sired, an op tional ad just able low pres sure switch kit is avail able. In stalled be tween the Nitrogen
Regu lat ing De vice out let and the Model A-2 or Model C Pres sure Main te nance De vice in let, i t sig nals a
control panel such as the Notifier RP1001 the approachingdepletion of the nitrogen supply.

Figure 1  Ni tro gen Regu lat ing De vice shown with op tional low pres sure switch kit
The Re li able Ni tro gen Regu lat ing De vice is avail able as sem bled, ready for con nec tion to the sys tem.

Item Part Qty.


No. Number Description Req’d
1 6999991570 Pressure Regulator 1

2 98085630 Connector, ¼″ Tubing x ¼″ NPT 2


3 98768004 Tubing ¼″ O.D. X 6 ft. - Copper 1

4 98048025 Reducer Bushing, ¾″ x ¼″ - Galv. 1

5 6501200100 Optional - Low Pressure Switch Kit 1

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
105
Nitrogen Regulating Device
P/N 6304030101 (Item 5 included)
P/N 6304030100 (Without Item 5)
Technical Data
The Reliable Nitrogen Regulating Device consists of components shown in Fig. 1.
The single-stage pressure regulator, made of brass, has a 200-4000 psi (13,8 - 275,8 bar) cylinder
pressure gauge and a 10- 200 psi (0,7 - 13,8 bar) out let pres sure gauge. A coiled ¼″ copper tubing al -
lows for flexibility in connecting the Device to the system air supply inlet.
The low pressure switch kit consisting of galvanized tee, outlet nipple, branch nipple, branch coupling
reducer and adjustable low pressure switch is optional. Mounted between the Nitrogen Regulating
Device and the supervisory pressure inlet, it sends a warning signal to replace a nitrogen cylinder that
is approaching a preset pressure depletion level.
The high pressure nitrogen cyl in der can typi cally be rented from a lo cal source, with rental fees varying
by supplier and cylinder sizes. Typical cylinders are:

Cylinder Size: “Q” “S” “K” “T”


Nitrogen Weight lbs.(kg): 5.50 (2.50) 10.28 (4.66) 16.51 (7.50) 22.01 (9.98)
Nitrogen Volume cu. ft. (m3): 76 (2.2) 142 (4.0) 228 (65) 304 (8.6)
Pressurized at psig (bar):* 2200 (151.7) 2200 (151.7) 2200 (151.7) 2640 (182.0)

* Note: Initial pressure and thus nitrogen weight and volume can vary slightly. Check with your local
supplier.
System Freezer Temperature °F (°C)
Capacity Approx.
Fill Time
(min.)**
Gal. (L) 20° (-6.7°) 0° (-18°) -20° (-29°) -40° (-40°) -60° (-51°)
250 (946.4) 4.49 (2.04) 4.69 (2.13) 4.90 (2.22) 5.13 5.39 (2.44) 1
500 (1892.7) 8.98 (4.07) 9.37 (4.25) 9.80 (4.45) 10.27 10.78 (4.90) 2
750 (2839.0) 13.47 (6.11) 14.06 (6.38) 14.70 (6.67) 15.40 16.17 (7.33) 3
1000 (3785.4) 17.97 (39.62) 18.75 (8.50) 19.60 (8.90) 20.54 21.56 (9.78) 4

When used in conjunction with the Reliable Dou ble-Interlock Type D Pre ac tion Sys tem in a refrigerated
area, the calculatednitrogen sup ply in lbs. (kg.) to pres sur ize var i ous sys tem ca paci ties to 10 psig (0,7
bar) at different freezer temperatures is as follows:
** Note: When used in conjunction with the Reliable Model A-2 Pressure Maintenance Device having
by-pass line open.
The nitrogen used in refrigerated area systems minimizes a possibility of ice buildup and blockage inside
the sys tem pip ing that could pre vent proper sys tem op er a tion. The dew-point of nitrogen compressed to a
maximum of 10 psig (0,7 bar) pressure in the Reliable Double-Interlock Type D Preaction System is -52°F
(-46.7°C).
The fol low ing list of bul le tins de scribes the sys tems and de vices which are used in con junc tion with this
Device:
Supertrol Double-Interlock Type D
Preaction System 4″ & 6″ (100mm &150mm) size 714
2½″ size (65mm) 713
1½″ size (40mm) 720
Control Panel 707/708
Model A-2 Pressure Maintenance Device 251
Model C Pressure Maintenance Device 252
Low Pneumatic Pressure Switch (System Sensor) D770-08-00

01/01
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552

Anda mungkin juga menyukai