Introduction
Climate change and environmental concerns are tremendously influencing and shaping the future of the
power industry. As a positive consequence, there has been a remarkable, rapid increase in the past
several years in the megawatts produced by renewable energy resources across the globe, and this trend
will continue for the next decades. These renewable energy resources, including wind generating units
and solar generation, are for the most part intermittent in nature. Smart Grid technologies will enable
power systems to operate with larger amounts of these energy resources since they enable both the
suppliers and consumers to compensate for such intermittency. New features addressing the intermittent
nature of these resources should be added into Energy Management Systems (EMS) and power system
planning, so that systems with Smart Grids can be operated safely.
Automatic Generation Control (AGC) is an important function in modern EMS systems. Since January
1998, new control performance standards (CPS) have been enforced in North America by the North
American Electric Reliability Corporation (NERC). NERC requires that control areas must be no less than
100% compliant with CPS1 and no less than 90% compliant with CPS2. CPS1 measures the correlation of
a control area’s area control error (ACE) and interconnection frequency error over a moving window of a
12-month duration. CPS2 measures how many times a control area manages to hold the magnitude of its
10-minute ACE average within a predetermined ACE limit over a calendar month duration. In addition to
the new CPS criteria, the new disturbance control standard (DCS) was proposed to ensure that the
balancing authority is able to utilize its contingency reserve to balance resources and demand and return
interconnection frequency within defined limits following a reportable disturbance. These control
performance criteria continue to evolve. Adjustments to these control performance criteria have been
made over time, for instance, with the inclusion of automatic time error correction. The increased number
of renewable energy resources connected into power grids definitely imposes great challenges on AGC.
Questions arise which need to be answered: Can the current AGC in EMS meet the NERC criteria? How
much power injection from renewable energy resources can be connected so that NERC criteria can still
be met? If a new wind farm is planned, can it be connected to power grids without violating NERC criteria
on AGC? PSS®E can answer these questions.
PSS®E provides the capability to simulate extended term dynamics in power systems. The simulation
may extend to an unlimited period and include the effects of slow acting controls and equipment, such as
AGC, switched shunts, load tap changing transformers, load changes, etc. The integration time step may
vary in the course of the simulation. Theoretically, there is no upper limit for the integration time step and
it can be very large (e.g., 0.2 seconds).
This article first describes extended term dynamic simulation in PSS®E. Then three user-written models
are developed for extended term dynamic simulation, namely an AGC model, a load model and a wind
generation model. Simulation is run on a small power system. Simulation results are presented and
explained. Conclusions are made. The simulation presented in this article can quantify AGC performance.
It can be used for validating AGC performance both in EMS for real-time operation and in power system
planning for future renewable energy resource connections.
Power Technology February 2011
GP
GI Σ
ACE PTDG
s
GD s
1 sTD
It should be pointed out that the state variables in the AGC PID controller are integrated differently than
other PSS®E state variables (e.g., the ones in generator models) during simulation. The AGC PID
integration time step is generally AGC cycle interval (e.g., 4 seconds or 2 seconds) while the integration
time step in PSS®E extended term simulation ranges from 0.00833 to 1 second. The PID integrator state
variable is initialized so that the integrator output is the initial total generation, that is, PTDG equals the total
Page 3
Power Technology February 2011
generation when ACE=0. During simulation, the integrator is reinitialized so that its output equals the
current total generation whenever ACE changes across zero (when ACE changes sign).
B. Determine the AGC unit's base points
The unit desired generation for each participating AGC unit is split into two components: the base point
and the regulation. The base point of each AGC participating unit is set at its Economic Dispatch (ED)
point:
Pbpi = PEdi
where PRegsys is the control area’s total regulation. The control area's total regulation is then allocated
among all regulating units. There are various kinds of regulation allocation schemes. A simple regulation
allocation scheme is proposed and used in the simulation:
where PRegi is the regulation obligation of unit i, RRi is the ramp rate of unit i, and PRegmaxi is the maximum
regulation for unit i. The unit's regulation is allocated based on unit's ramp rate share and subject to its
maximum regulation with the unit's base point set to Pbpi.
If any unit's desired regulation PRegi plus its base point hits its maximum regulating limit, then subtract the
regulation allocated to this unit from the area's total regulation, then allocate the remaining area's total
regulation among the remaining regulating units.
Page 4
Power Technology February 2011
δ(t)
Δfi(t)
1 1 K qfil f i (t ) Qil(t)
1
Pf il2
where Psystem(t) is system load forecast, δ(t) is the load disturbance, Dil is the load distribution factor at bus
i, Δfi(t) is the frequency deviation at bus i, Kpfil and Kqfil are the active and reactive load frequency
sensitivities respectively at bus i, Pfil is the load power factor at bus i. Pil(t) and Qil(t) are split into three
parts: constant MVA load, constant I load and constant Y load, which are used to calculate the current
injection at bus I according to the voltage at bus i.
Piwg(t) Piwg(t)
1
2
1 Qiwg(t)
Pf iwg
where Piwg(t) is the wind generation active power output, Pfiwg is the constant wind generation power factor
at bus i, Piwg(t) and Qiwg(t) are the actual MW and Mvar of the wind generation at bus i.
Page 5
Power Technology February 2011
This is a single area system. There are five regular generation units and a wind generation unit in the
system. Each of the five regular generation units has a generator model, exciter model, and governor
model. The wind generation unit is connected to bus 3018. It is dispatched at 100 MW with the given
power factor. Four of the five regular generation units are AGC controlled (regulating units). AGC control
cycle interval is 4 seconds. This system initially has about 3200 MW load. Some tentative data are used
for the load forecast and wind generation. The system load forecast is shown in Fig. 5. It is a sine wave
deviating from 3200 MW to 1600 MW with a cycle of 3600 seconds. The wind generation data is shown in
Fig. 6. Both are in pu of 100 MVA. The wind generation is also a sine wave with the magnitude of 50 MW
and a cycle of 180 seconds.
Page 6
Power Technology February 2011
Page 7
Power Technology February 2011
Simulation Results
The extended term simulation is run for a 3 hour period using PSS®E. The simulation results are shown in
Fig. 7 – Fig. 12.
Fig. 7 shows the frequency deviation. Due to AGC, the frequency is kept in a very narrow range not
exceeding 0.15%. Fig. 8 shows the ACE. It can be seen that the frequency deviation and ACE have
similar shape but in opposite sign due to the fact that the system simulated is a single area.
Fig. 9 shows the total desired generation. The spikes are caused by the re-initialization of AGC PID
controller. Fig. 10 shows the total generation. It can be seen that both the total desired generation and the
total generation respond well with the load change and wind generation change.
Fig. 11 shows CPS1 and Fig. 12 shows CPS2. Both are compliant with NERC standards (CPS1>100%,
CPS2>90%).
Page 8
Power Technology February 2011
Page 9
Power Technology February 2011
Page 10
Power Technology February 2011
Conclusions
With more and more renewable energy resources connected into power grids, their impacts on AGC must
be understood both at the planning stage and in real time operation. PSS®E provides customers with the
capability to simulate AGC dynamically under the condition of intermittent generation and varying load.
This simulation can help the power system planner to study and understand AGC behavior when a
renewable energy resource is planned. As long as the current operating plan and other necessary
information are available, system operators can use PSS®E’s AGC dynamic simulation capability to
determine if NERC AGC control criteria are met.
This article described an example of the simplified AGC PSS®E model applied to the single area sample
system using PSS®E. The results of the simulation showed how AGC can positively affect the frequency
of the system when the loads of the system follow the given forecast and there is an intermittent
component in generation.