SAUDI ARAMCO INSPECTION CHECKLIST
FBE Reinforcing Steel, Embedded Items, and Form Closure
SAIC-Q-1013 18-May-05 CIVIL-
Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

A Reinforcing Steel Inspection

Forms shall be inspected and checked before the reinforcing steel is


SAES-Q-001
A1 placed to the dimensions and locations on the structural plans.
Sec. 8.0
(ACI 347, Sec. 3.2.4.1)

Form coatings shall be applied before reinforcing steel is placed;


SAES-Q-001
A2 reinforcing steel, embedments or joints shall not be contaminated with
Sec. 8.0
form coating. (ACI 347, Sec. 3.2.5.2)

The minimum concrete cover shall be measured from the outer most
rebar (tie bar), that shall be provided for reinforcement of cast-in-place
concrete structures as follows:

Table 2-Minimum Concrete Cover


Concrete Structure Minimum Cover (mm)
Concrete cast against and permanently
exposed to earth (including foundations
over a sub-slab) 75
Formed concrete exposed to earth or weather SAES-Q-001
A3
Supporting Process Equipment 75 Sec. 5.8
Buildings, walkway platforms, stairs, AC pads 50
Concrete not exposed to weather nor in contact with
ground (which can be inspected from all sides):
Beams, Columns 50
Slabs, Walls, Joists 25
Concrete exposed to sea water, raw water or sewage 75
Between reinforcement and anchor flange/pipe within
pipeline anchor blocks 100
Concrete slab over 50 mm sub-slab 50

No sign of damage or cracking of epoxy coating shall exist; All field cut SAES-Q-001
A4
ends of rebar be re-touched with approved Epoxy Coating Material. Sec. 5.6

Damaged coated steel reinforcing bars should be shall be repaired with SAES-Q-001
A5
the approved patching material. (ASTM A775, Appendix X1.3.11) Sec. 5.6

Maximum amount of repaired damaged rebar coating shall not exceed


SAES-Q-001
A6 1% of the total surface area in each 0.3 m (1-ft) of the bar; This limit shall
Sec. 3.2
not include sheared or cut ends. (ASTM A775, Sec. 11.1)

Reinforcing steel rebar shall be correct in quantity, layout, spacing,


A7 IFC Drawings
position, etc. per the IFC Drawings.

Reinforcing Steel lap splice lengths for each bar size shall be as detailed
A8 IFC Drawings
for each size as shown on the IFC Drawings.

All wire bar supports, spacers, and tying wire shall be coated with
SAES-Q-001
A9 dielectric material, for example, an epoxy-coated or plastic coated
Sec. 5.6
material. (ASTM A775, Appendix X1.3.13)

Page 1 of 5
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 1 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
FBE Reinforcing Steel, Embedded Items, and Form Closure
SAIC-Q-1013 18-May-05 Civil
Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Reinforcing steel bars, anchor bolts or other steel embedments shall not SAES-Q-001
A10
be used as a means for electrical grounding. Sec. 6.4

The diameter of reinforcing bar bends, other than stirrups or ties, in sizes
SAES-Q-001
A11 from No. 10 through No. 25 shall be 6 bar diameters.
Sec. 5.6
(ACI 318, Sec. 7.2.3, Table 7.2)

The diameter of reinforcing bar bends, other than stirrups or ties, for
SAES-Q-001
A12 sizes No. 29 through No. 36 shall be 8 bar diameters.
Sec. 5.6
(ACI 318, Sec. 7.2.3, Table 7.2)

The diameter of reinforcing bar bends, other than stirrups or ties, for
SAES-Q-001
A13 sizes No. 43 through No. 57 shall be 10 bar diameters.
Sec. 5.6
(ACI 318, Sec. 7.2.3, Table 7.2)

The inside diameter of bends for stirrups and ties shall be no less than 4
SAES-Q-001
A14 bar diameter for sizes 5 and smaller, all other sizes shall be bent in
Sec. 5.6
accordance with items 11, 12 and 13 above. (ACI 318-04, Se. 7.2.2)

Welded wire fabric shall be located as shown on IFC Drawings. SAES-Q-001


A15
(ACI 318, Sec. 7.5.3) Sec. 5.6

Welding of reinforcement shall not be allowed unless authorized by


SAES-Q-001
A16 Saudi Aramco or called for specifically on the IFC Drawings.
Sec. 5.6
(ACI 318, Sec. 7.5.4)

Reinforcing, including tendons and post-tensioning ducts shall be


SAES-Q-001
A17 accurately placed and adequately supported before concrete is placed.
Sec. 5.6
(ACI 318, Sec. 7.5.1)

B Anchor Bolts & Embedded Items Inspection

Anchor bolts shall be in compliance with Standard Drawing AA-036322 SAES-Q-005


B1
Sht. 001 (rev 7 or later). Sec. 4.8.6

Minimum clear distance from anchor bolts or sleeves to edge of concrete SAES-Q-005
B2
shall be 100mm. Sec. 4.8.6

SAES-Q-005
B3 Anchor bolt metallic sleeves are not allowed.
Sec. 4.8.6

SAES-Q-005
B4 Anchor bolts shall not be in contact with reinforcing steel.
Sec. 4.8.6

The minimum anchor bolt diameter shall be 20mm unless specified by


the vendor for small equipment or for the anchorage of small SAES-Q-005
B5
miscellaneous items e.g. ladder supports, small piping supports, handrail Sec. 4.8.4
anchorage, stair stringers, small platforms etc.

Anchor bolts and embedded items shall be set accurately, using SAES-Q-005
B6
templates. Sec. 4.8.2

Variation in dimension between the centers of adjacent anchor bolt within SAES-Q-005
B7
and anchor bolt group shall be equal to or less than 3mm. (AISC 7.5.1a) Sec. 4.8.2

Variation in dimension between the centers of adjacent bolt groups shall SAES-Q-005
B8
be equal to or less than 6mm. (AISC 7.5.1b) Sec. 4.8.2

Variation in elevation of the tops of anchor bolts shall be equal to or less SAES-Q-005
B9
than ±13mm. (AISC 7.5.1c) Sec. 4.8.2

Page 2 of 5
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 1 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
FBE Reinforcing Steel, Embedded Items, and Form Closure
SAIC-Q-1013 18-May-05 Civil
Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Anchor bolt projection above the top of concrete is computed as follows:


Single Nuts
Thickness of grout + thickness of base plate (or height of anchor bolt
SABP Q-001
B10 chair above the top of grout) + 1.5 x diameter of anchor bolt
Sec. 6.2.4
Double Nuts
Thickness of grout + thickness of base plate (or height of anchor bolt
chair above the top of grout) + 2.5 x diameter of anchor bolt

The thread length required at the top of the anchor bolt must be sufficient
to accommodate two nuts and about ½ of the anchor bolt diameter
SABP Q-001
B11 projecting above the top nut. Normally a thread length of about 3 bolt
Sec. 6.2.5
diameters of will be sufficient to provide some tolerance for errors in the
elevation of the anchor bolt placement in the field.
The accumulated variation in dimension between centers of anchor bolt
groups along the established column line through multiple anchor bolt SAES-Q-005
B12
groups shall be equal to or less than 2mm per 10,000 mm, but not to Sec. 4.8.2
exceed a total of 25 mm. (AISC 7.5.1d)
Variation in dimension from the center of any Anchor-rod group to the
SAES-Q-005
B13 established column line through that group shall be equal to or less than
Sec. 4.8.2
6mm. (AISC 7.5.1e)
Welded wire fabric shall be located as shown on IFC Drawings. SAES-Q-001
B14
(ACI 318, Sec. 7.5.3) Sec. 5.6

All sleeves, inserts, anchor bolts, waterstops and other embedded items
SAES-Q-001
B15 shall be installed in accordance with the design drawings and supported
Sec 6.1
against displacement.

Waterstops shall be provided in joints where watertight construction is SAES-Q-001


B16
required. Waterstop type shall be specified on the IFC Drawings. Sec 14.3

Projecting steel items which are attached to the formwork and cast at the
SAES-Q-001
B17 concrete surface shall be either hot dip galvanized or coated with a zinc
Sec 6.3
rich epoxy primer.

Conduits, pipes and other items made from aluminum shall not be
SAES-Q-001
B18 embedded in structural concrete unless effectively coated to prevent
Sec. 6.5
aluminum-concrete reaction.

A plasticized sheet vapor barrier, minimum 0.15mm (6mils) in thickness,


SAES-Q-001
B19 shall be placed beneath slabs on grade. Outdoor sidewalks are exempt
Sec. 11.1
from this requirement.

A plasticized sheet vapor barrier, minimum 0.15mm (6mils) in thickness


SAES-Q-001
B20 or a 50mm sub-slab (lean concrete) shall be placed beneath concrete
Sec. 11.2
foundations.

A plasticized sheet vapor barrier shall be placed below and around the
SAES-Q-001
B21 sides of concrete that is placed directly into excavation without the use of
Sec. 11.3
formwork, where coal tar or bitumen coating cannot be applied.

Page 3 of 5
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 1 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
FBE Reinforcing Steel, Embedded Items, and Form Closure
SAIC-Q-1013 18-May-05 Civil
Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Fabrication and Installation Tolerances on Embedded Items shall be:


Lateral Alignment for weakened plane embedments in slabs- 19mm
Level Alignment on grooves and items exposed to view- 12.7mm
Relative alignment on Grooves 50mm or less- 3mm
Lateral Alignment of other embedded items:
Reglets for glazing gaskets 3mm
SAES-Q-001
B22 Bolts 6mm
Sec. 5.7
Flashing reglets 6mm
Flashing reglets at panel edges 3mm
Electrical outlets and pipe sleeves 12.7mm
Weld plates 25mm
Inserts 12.7mm
(ACI 117, Sec. 3.2 & 3.3)

C Form Closure Inspection

Telltale devices shall be installed on the formwork shores to detect SAES-Q-001


C1
formwork movements during concreting. (ACI 318, Sec. 3.6.1.1) Sec. 3.2

Wedges used for final alignment before concrete placement shall be SAES-Q-001
C2
secured before placing concrete. (ACI 347, Sec. 3.6.1.2) Sec. 3.2

Formwork shall be anchored to shoring to prevent any movement of any SAES-Q-001


C3
part of the formwork during concreting. (ACI 347, Sec. 3.6.1.3) Sec. 3.2

Closure of form joints, settlement of blinding slabs, shrinkage of lumber,


SAES-Q-001
C4 elastic shortening and deflections of form members shall all be
Sec. 3.2
countered prior to concrete placement. (ACI 347, Sec. 3.6.1.4)

Access holes shall be sealed up after the areas of the forms they were
SAES-Q-001
C5 made for have been cleaned or lower areas filled with concrete.
Sec. 3.2
(ACI 347, Sec. 3.2.1.7)

Bulkheads for joints shall be made by splitting along the lines of


SAES-Q-001
C6 reinforcement so that each can be removed without applying undue
Sec. 3.2
pressure upon the reinforcing steel. (ACI 347, Sec. 3.2.2.2)

The top of concrete foundation shall be a minimum of 150 mm above


finished grade. SAES-Q-005
C7
(Note: Not applicable to instrument stand pipe or pedestals inside Sec. 4.3.2 (a)
buildings not subjected to washdown water. )

REMARKS:

REFERENCE DOCUMENTS:
1- SAES-Q-001 -- Criteria for Design and Construction of Concrete Structures, 29 October 2003
2- SAES-Q-005 -- Concrete Foundations, 29 January 2003

Page 4 of 5
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 1 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
FBE Reinforcing Steel, Embedded Items, and Form Closure
SAIC-Q-1013 18-May-05 Civil
Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 5 of 5