Installation
& Servicing
Instructions
THESE INSTRUCTIONS
TO BE RETAINED
BY USER
Contents
Design principles and operating sequence Page Servicing instructions Page
1.1 principle components 2 6.1 general 18
1.2 mode of operation 2 6.2 routine annual servicing 18
1.3 safety devices 2 6.3 replacement of components 18
6.4 component removal procedure 18
6.5 pump head 18
Technical data Page 6.6 safety valve 18
6.7 automatic air release valve 18
2.1 performance 3
6.8 water pressure switch 19
2.2 gas pressure 3
6.9 pressure gauge 19
2.3 expansion vessel 3
6.10 NTC thermistors 19
2.4 dimensions 3
6.11 high limit thermostat 19
2.5 clearances 3
6.12 PCB 19
2.6 connections 3
6.13 gas valve 19
2.7 electrical 3
6.14 integral time switch 19
2.8 flue details 3
6.15 burner, injectors, and spark electrode 20
2.9 efficiency 3
6.16 flue fan 20
2.10 pump duty 4
6.17 heat exchanger 20
6.18 air pressure switch 21
6.19 expansion vessel 21
General requirements Page 6.19.1 expansion vessel (removal) 21
3.1 related documents 5
3.2 location of appliance 5
3.3 gas supply 5 Checks, adjustments, and fault finding Page
3.4 flue system 5 7.1 checking appliance operation 22
3.5 air supply 6 7.2 appliance mode of operation 22
3.6 water circulation 6 7.3 checking burner pressure 22
3.6.1 pipework 6 7.4 combustion analysis test 22
3.6.2 automatic bypass 6 7.5 checking the expansion vessel 22
3.6.3 drain cocks 6 7.6 external faults 23
3.6.4 air release points 6 7.6.1 installation faults 23
3.6.5 expansion vassel 6 7.7 electrical checks 23
3.6.6 filling point 6 7.7.2 short circuit check 23
3.6.7 low pressure sealed system 7 7.7.4 reversed polarity or supply fault 23
3.6.8 frequent filling 7 7.7.5 resistance to earth check 22
3.7 electrical supply 7
3.8 mounting on a combustible surface 7
3.9 timber framed building 7
The Vokera 10, 14, and 20e Mynutes are central heating These appliances are designed for use with sealed
boilers, which – by design – incorporate electronic systems only; consequently they are not intended for use
ignition, circulating pump, expansion vessel, safety valve, on open vented systems.
pressure gauge, and automatic by-pass.
The provision of stored hot water is possible by the
They are produced as room sealed, category II2H3+ addition of an indirect cylinder.
appliances, suitable for wall mounting applications only.
They are provided with a fan powered flue outlet with an A range rating facility is incorporated in the appliance.
annular co-axial combustion air intake that can be rotated
– horizontally – through 360 degrees for various horizontal
or vertical applications.
The Mynute range can also be used with the Vokera twin
flue system.
1
24
2
4 1 Flue outlet
2 Air intake
22 3 Pressure differential switch
4 Silicone tubes (pressure diff. switch)
5
5 Heat exchanger
6 6 NTC thermistor
21
7 High limit thermostat
7 8 Spark/sensing electrode
20 9 Gas valve
10 Clock aperture
8 11 Pressure gauge
12 Thermostat
19 13 Mode switch
14 Warning led
15 Water pressure switch
16 Safety valve
18 17 Pump
18 Automatic air vent
19 Burner
17 20 Expansion vessel
21 Combustion chamber
22 Fan
9 23 Air chamber
24 Flue gas analysis test point
16 15 12
13 11
10
14
Fig. 1
Mynute 1
SECTION 1: DESIGN PRINCIPLES AND OPERATING SEQUENCE
● Integral pump
● Fan
● Expansion vessel
● Pressure gauge
● Safety valve
2 Mynute
SECTION 2: TECHNICAL DATA
2.1 PERFORMANCE
10e 14e 20e
Heat input 12.75 kW 17.1 kW 24.2 kW
Heat output (max) 10.35 kW 14.2 kW 19.8 kW
Heat output (min) 5.06 kW 7.4 kW 14.0 kW
Minimum working pressure 0.5 bar 0.5 bar 0.5 bar
Maximum working pressure 3.0 bar 3.0 bar 3.0 bar
Minimum flow rate 350 l/hour 350 l/hour 350 l/hour
2.9 EFFICIENCY
10e 14e 20e
SEDBUK rating 77.0 % 79.2 % 78.05 %
Appliance type C12 - C22 - C32
Category IP20
Mynute 3
SECTION 2: TECHNICAL DATA
600
500
Water pressure (mbar)
400
300
200
100
0
1 2 3 4 5 6 7 8 9 10 11 12 13
Fig. 3 Litres Per Hour (x100)
4 Mynute
SECTION 3: GENERAL REQUIREMENTS
This appliance must be installed by a competent cupboard design including airing cupboard
person in accordance with the Gas Safety installations are given in BS 6798. This appliance
(Installation & Use) Regulations. is not suitable for external installation.
Mynute 5
SECTION 3: GENERAL REQUIREMENTS
3.6.1 PIPEWORK
It is recommended that copper tubing to BS 2871
Part 1 is used in conjunction with soldered capillary
joints.
6 Mynute
SECTION 3: GENERAL REQUIREMENTS
Mynute 7
SECTION 4: INSTALLATION
8 Mynute
SECTION 4: INSTALLATION
FITTING THE TELESCOPIC FLUE KIT (0225705 Insert the flue restrictor ring (supplied with
& 0225710) instruction pack) into the appliance flue gas outlet
Carefully measure the distance from the centre of if the total flue length is less than 1.0 metre.
the appliance flue outlet to the face of the outside
wall (dimension ‘X’ see fig. 8). Add 50mm to If the horizontal flue kit (2359029) requires to be
dimension ‘X’ to give the overall flue length cut to the correct size (dimension ‘Y’), you must
(dimension ‘Y’). Using the complete telescopic ensure that the inner (60mm) pipe stands proud of
flue assembly adjust the length to suit dimension the outer (100mm) pipe by 7.5mm (see fig. 8B).
‘Y’. Once the telescopic flue terminal has been Ensure any burrs are filed or removed and that
adjusted to the correct length, secure the flue any seals are located properly before assembly.
assembly with the screw supplied.
Connect the inner (60mm) pipe of the terminal
Insert the flue restrictor ring (supplied in the assembly to the push-fit end of the 90º bend
instruction pack) into the appliance flue gas outlet. (supplied) using a twisting action. Insert the
Slide the flue assembly into the previously drilled assembled flue into the previously drilled hole.
flue hole and locate the flue bend over the appliance Using the clips & screws supplied, connect the
flue outlet. Push the flue bend down over the flue assembly to the boiler, ensuring that the
appliance flue outlet and ensure the correct seal is terminal protrudes past the finished outside wall
made. Pull the flue assembly towards and over by the correct length (135mm).
the flue bend – using a twisting action – ensuring
the correct seal is made. Check that the terminal You must ensure that the entire flue system is
protrudes past the finished outside wall by the properly supported and connected.
correct length (115mm).
Fig. 8 a
NOTE
Dimension ‘Y’ is measured from the end of the
terminal to the end of the outer (100mm) pipe.
The internal trim should be fitted to the flue pipe Fig. 8 b
before connection of the 90º bend.
Mynute 9
SECTION 4: INSTALLATION
NOTE IMPORTANT
When cutting the horizontal flue terminal or an The vertical flue terminal is 1.0 metre in length
extension to the required length, you must ensure and cannot be cut; therefore it may be necessary
that the excess is cut from the plain end of the to adjust the height of the appliance to suit or use
terminal or extension, and that the inner (60mm) a suitable extension.
pipe is 7.5mm longer than outer (100mm) pipe
(see fig. 8A & 8B). Remove any burrs, and check Insert the flue restrictor ring into the appliance
that any seals are located properly. flue outlet (see fig. 1), if the total flue length –
including the allowance for any additional bends
You must ensure that the entire flue system is – does not exceed 1.0 metre.
properly supported and connected.
Connect the vertical flue assembly to the boiler
Seal the flue assembly to the wall using cement or flue spigot using the 60mm & 100mm clips,
a suitable alternative that will gaskets, & screws (supplied), ensuring the correct
provide satisfactory weatherproofing. The interior seal is made. The flue support bracket (supplied
and exterior trim can now be fitted. with the vertical flue kit) can now be fitted.
10 Mynute
SECTION 4: INSTALLATION
GUIDANCE NOTES ON TWIN FLUE INSTALLATION instruction pack) if the total flue length –
● The flue must have a fall back of 1º back to the including the allowance for any bends – is less
appliance to allow any condensate that may than 7.5 m (20e) and 5 m (14e & 10e).
form in the flue system to drain via the ● Insert the exhaust connection manifold onto the
small amount of condensate dripping from the adapter kit) over the rim of the exhaust
terminal. connection manifold.
● Ensure that the entire flue system is adequately ● Remove the blanking plate (located to the left
supported, use at least one bracket for each of the appliance flue outlet) and – using the
extension. same screws – install the air baffle.
● The entire flue system must be adequately
Fig. 11
Mynute 11
SECTION 4: INSTALLATION
4.5.3.2 INSTALLATION OF CONDENSATE DRAIN KIT The last twin flue pipes must be pushed 50mm
(fig. 11) onto the male sockets of the concentric to twin
The condensate drain kit must be fitted within 1 converter.
metre of the appliance flue outlet. It is
recommended that the condensate drain kit NOTE;
should be fitted in the vertical plane, however it You must ensure that the entire flue system is
can be fitted horizontally with care. properly supported and connected.
● Fit the first bend to the condensate drain kit or
exhaust connection manifold by firmly pushing Seal the flue terminal assembly to the wall using
in to position. cement or a suitable alternative that will provide
● Using the two holes in the exhaust connection satisfactory weatherproofing.
manifold as a guide, drill a 3mm hole in each
and secure using the screws provided. The interior and exterior trim can now be fitted.
● Connect the air inlet pipe to the air baffle as
(See fig. 12) the concentric terminal through the ceiling and/
The twin flue system must be converted to the or roof.
dedicated concentric flue kit for termination.
● The horizontal terminal is supplied with a built- Depending on site conditions it may be preferable
in converter box and cannot be shortened. to install the terminal assembly prior to fitting the
● A 130mm hole is required for the passage of twin flue pipes.
the concentric terminal through the wall.
Fit the appropriate flashing plate to the roof and
Depending on site conditions it may be preferable insert the vertical flue terminal through the
to install the terminal assembly prior to fitting the flashing plate from the outside, ensuring that the
twin flue pipes. collar on the flue terminal fits over the flashing.
Mark and drill a 130mm hole for the passage of Push-fit the twin flue pipes onto the concentric to
the horizontal flue terminal, ensuring that there twin converter ensuring that the exhaust pipe
is a 1º fall back to the boiler (17mm per 1000mm). connects to the exhaust connection on the
Insert the terminal assembly into the flue hole. concentric to twin converter.
If necessary cut the plain ends (male) of the twin
Push-fit the twin flue pipes onto the concentric to flue pipes to allow connection to the concentric
twin converter box ensuring that the exhaust pipe to twin converter.
connects to the exhaust connection on the
concentric to twin converter.
If necessary cut the plain ends (male) of the twin
flue pipes to allow connection to the concentric
to twin converter.
12 Mynute
SECTION 4: INSTALLATION
Fig. 12
Fig. 13
Mynute 13
SECTION 4: INSTALLATION
14 Mynute
SECTION 4: INSTALLATION
● 1
● 2
● 3
● 4
● 5
● 6
Protective cap
E N 2 4 6
L 1 3 5
Natural gas
14
14e 20e
14 E
12
10e
10 E
10
Burner pressure (mbar)
0
4 6 8 10 12 14 16 18 20
Output (kW) Fig. 17a
Mynute 15
SECTION 5: COMMISSIONING
16 Mynute
SECTION 5: COMMISSIONING
Although not necessary for the correct operation 5.13 INSTRUCTING THE USER
of the boiler, an inhibitor may be added at this Hand over all documentation supplied with this
point. Contact the inhibitor manufacturer for appliance – including these instructions – and
further information regarding application and explain the importance of keeping them in a safe
dosage. place.
5.9 SETTING THE BOILER OPERATING Explain to the user how to isolate the appliance
TEMPERATURE from the gas, water, and electricity supplies, and
The flow outlet temperature can be adjusted the locations of all drain points.
between 40°C - 80°C via the thermostat knob
(see fig.1). Show the user how to operate the appliance and
its associated controls correctly.
5.10 SETTING THE SYSTEM DESIGN PRESSURE
The design pressure should be a minimum of 1 Show the user the location of the filling valve and
BAR and a maximum of 1.5 BAR. how to top-up the system pressure correctly, and
show the location of all manual air release points.
The actual reading should ideally be 1BAR plus
the equivalent height in metres (0.1 BAR = 1 Explain to the user how to turn off the appliance
metre) to the highest point in the system above for both long and short periods and advise on the
the base of the appliance (up to the maximum of necessary precautions to prevent frost damage.
1.5 BAR total).
N.B. The safety valve is set to lift at 3 BAR/30 Explain to the user that for continued safe and
metres/45 psig. efficient operation, the appliance must be serviced
annually by a competent person.
To lower the system pressure to the required
value, pull lever on head of safety valve to release
water until the required figure registers on the
pressure gauge (see fig. 1).
FOR SOUNDNESS.
● RE-FIT APPLIANCE CASING.
Mynute 17
SECTION 6: SERVICING
18 Mynute
SECTION 6: SERVICING
burner pressure
adjusting screw
supply plug
Mynute 19
SECTION 6: SERVICING
fig. 22 fig. 23
fig. 22a
20 Mynute
SECTION 6 SERVICING
fig. 24
Mynute 21
SECTION 7 CHECKS, ADJUSTMENTS, & FAULT FINDING
7.1 CHECKING APPLIANCE OPERATION Light the boiler as described in 5.6 and compare
When carrying out any repairs or servicing to the the reading on the manometer with the value
appliance, the relevant commissioning procedure described in fig. 17a. If adjustment is required
must be undertaken to ensure the continued safe remove the compensator tube from the gas valve
operation of the appliance. Particular attention regulator.
should be made to ensure gas soundness, water
soundness, and the electrical integrity of the Locate and remove the protective screwed cap
appliance. that covers the burner pressure adjusting screw.
Adjust the screw clockwise to increase the
7.2 APPLIANCE MODE OF OPERATION pressure or anti-clockwise to reduce.
When there is a request for heat and/or hot water
via the programmer/time clock and/or any external Once the pressure has been adjusted, isolate the
control, the pump and fan are started. appliance from the electrical supply, replace the
protective screwed cap, refit the compensator
NOTE there must be sufficient system water tube, remove the manometer, and tighten the
pressure (min. 0.5 BAR) to ensure the water outlet test nipple.
pressure switch is activated. If there is insufficient
system pressure the pump and fan will be IMPORTANT, A GAS SOUNDNESS CHECK
prevented from operating. MUST BE CARRIED OUT.
When the fan runs, it proves the differential air 7.4 COMBUSTION ANALYSIS TEST
pressure switch which in-turn allows an ignition A combustion analysis check can easily be carried
sequence to begin. out on the appliance via the test points located on
the top of the appliance, however you must
NOTE the ignition sequence lasts approximately check that the burner pressure is set at maximum
5 seconds, during which the appliance will (see 7.3).
continue to spark even if the burner has already
lit.
If the spark/sensing electrode does not sense
ignition the appliance will then go to lockout. 10e 14e 20e
Ignition is sensed by the electronic circuitry to CO 80ppm 60ppm 160ppm
ensure flame stability at the burner. Once
successful ignition has been achieved, the CO2 4.8% 7.0% 6.0%
electronic circuitry allows full gas rate through the
appliance.
When the appliance reaches the desired 7.5 CHECKING THE EXPANSION VESSEL
temperature the burner will shut down and the Carry out the component removal procedure as
boiler will perform a three-minute anti-cycle (timer described in 6.4. You must ensure that the boiler
delay). is completely drained of water.
Using a suitable pressure gauge, remove dust
NOTE the timer delay can be de-activated by the cap on expansion vessel and check the charge
insertion of a ‘jumper’ on the PCB or by isolating pressure. The correct charge pressure should be
the appliance from the electrical supply from 30 0.8 BAR ± 0.1 BAR.
seconds. If the charge pressure is less, use a suitable
pump to increase the charge.
When the request for heat and/or hot water has
been satisfied the appliance pump will continue
to circulate for a period of 30 seconds to dissipate
any residual heat within the appliance.
22 Mynute
SECTION 7 CHECKS, ADJUSTMENTS, & FAULT FINDING
Appliance wont fire External wiring fault Disconnect external wiring and
fit link between 1 & 2
Insufficient system pressure Ensure pressure gauge is
above 0.5 BAR
Blown fuse Check and replace
Appliance stays fired after time External wiring fault Check wiring and or
clock/programmer has Faulty motorised valve disconnect external wiring
switched off
Appliance fires but no Service valves closed Open service valves!
circulation Defective motorised valve Check operation
Defective external wiring Check wiring
Air in system/boiler Check dust cap on AAV
Vent system & radiators
7.7 ELECTRICAL CHECKS Connect test leads between the Live & Earth
Any electrical checks must be carried out by a connections at the appliance terminal strip. (fig.16)
suitably qualified person. the meter should read approximately 230V ac. If
so proceed to next stage. If not, see 7.7.4.
7.7.1 EARTH CONTINUITY TEST Connect test leads between the Neutral & Earth
Isolate the appliance from the electrical supply, connections at the appliance terminal strip. (fig.16)
and using a suitable multi-meter carry out a the meter should read approximately 0 – 15Vac.
resistance test. Connect test leads between an If so polarity is correct. If not, see 7.7.4.
appliance earth point and the earth wire of the
appliance supply cable. The resistance should 7.7.4 REVERSED POLARITY OR SUPPLY FAULT
be less than 1 OHM. If the resistance is greater Repeat the above tests at the appliance isolator,
than 1 OHM check all earth wires and connectors if testing reveals correct polarity and/or supply at
for continuity and integrity. the isolator, re-check wiring and connections
between the isolator and the appliance.
7.7.2 SHORT CIRCUIT CHECK If tests on the isolator also reveal reversed polarity
Isolate the appliance from the electrical supply, or a supply fault, consult the local electricity
and using a suitable multi-meter, carry out a short supplier for advice.
circuit test between the Live & Neutral connections
at the appliance terminal strip (fig.16). 7.7.5 RESISTANCE TO EARTH CHECK
Repeat above test on the Live & Earth connections Isolate the appliance from the electrical supply,
at the appliance terminal strip. (Fig.16) and using a suitable multi-meter carry out a
NOTE resistance test. Connect test leads between the
Should it be found that the fuse has failed but no Live & Earth connections at the appliance terminal
fault is indicated, a detailed continuity. strip. (fig.9a) If the meter reads other than infinity
Check will be required to trace the fault. A visual there is a fault that must be isolated, carry out a
inspection of components may also assist in detailed continuity check to identify the location
locating the fault. of the fault.
Mynute 23
SECTION 7: CHECKS, ADJUSTMENTS, & FAULT FINDING
wiring
● Continuity through mode selector switch
● PCB
24 Mynute
SECTION 7: CHECKS, ADJUSTMENTS, & FAULT FINDING
Mynute 25
SECTION 8: WIRING DIAGRAMS
26 Mynute
SECTION 8: WIRING DIAGRAMS
Mynute 27
SECTION 8: WIRING DIAGRAMS
8.5 INSTALLATION OF VOKERA TIME CLOCK (24 8.6 INSTALLATION OF VOKERA TWIN CHANNEL
hour & 7 day versions). PROGRAMMER
● Isolate the appliance from the electrical supply ● Isolate the appliance from the electrical supply
and remove the casing as described in 4.7.1. and remove the casing as described in 4.7.1.
● Remove the circular blanking disc from the ● Remove the circular blanking disc from the
using the screws provided. and connect them as shown in fig. 25.
● Remove the factory fitted link between ● Mount the clock to the clock aperture plate
terminals 1 & 2 on the appliance terminal strip. using the screws provided.
● Connect the clock wires to the appliance ● Connect any external controls as detailed in
the clock installation has been completed. the programmer installation has been
completed.
fig. 24 fig. 25
NOTE NOTE
If the connection of a room thermostat is The appliance and integral programmer must be
also required, the spare terminals on the appliance connected as described in these instructions, to ensure
terminal strip can be used for this purpose. the safe and correct operation of this appliance.
28 Mynute
SECTION 8: WIRING DIAGRAMS
Mynute 29
SECTION 8: WIRING DIAGRAMS
30 Mynute
SECTION 9: EXPLODED DIAGRAMS
31
42 8
37
3
Tav. 2 7
9
6
1 4
34
32 39
41
5 42 40
12 42 10
33
22
35 21
11
42 36 36 13
19
18
36 36
17
38
14 28
27
36
20
16 26
37 15
25
30 24
43 23 29
Table 1 Mynute 10 & 14e 38
KEY DESCRIPTION Part no 10e Part no 14e
1 Side panel LH 10021247 10021247
2 Side panel RH 10021245 10021245
3 Top transverse panel (10e,14e) 10021250 10021250 KEY DESCRIPTION Part no 10e Part no 14e
4 Lower transverse panel 10020951 10020951 24 Plastic catch 1864 1864
5 Distribution panel 10021249 10021249 25 Blanking disc 1609 1609
6 Insert 2127 2127 26 Pressure gauge 2468 2468
7 Upper casing hook LH 1882 1882 27 Clock blanking plate 8654 8654
8 Upper casing hook RH 1881 1881 28 Vokera logo 1978 1978
9 White casing 10020973 10020973 29 Front flap 10020966 10020966
10 Wiring tray 10021233 10021233 30 Controls/fascia panel 10021260 10021287
11 Control panel strengthener RH 7787 7787 31 Wall mounting bracket 10021273 10021273
12 Control panel strengthener LH 7788 7788 32 Rivet (for earth terminal) 5037 5037
13 Lower control panel hook RH 10020967 10020967 33 Cable entry 5371 5371
14 Lower control panel hook LH 10020968 10020968 34 Ignition transformer 10021272 10021272
15 Selector switch extension shaft 10021263 10021263 35 Self threading screw 4.8mm x 25mm 5171 5171
16 Selector switch 9461 9461 36 Self threading screw 3.5mm x 12mm 5240 5240
17 Earthing strip 10021484 10021484 37 Rivet 3.2mm x 7mm 5093 5093
18 Thermostat extension shaft 2785 2785 38 Self threading screw 3.9mm x 13mm 5199 5199
19 PCB 10021984 10021984 39 Edge clip 5128 5128
20 LED lens 10021267 10021267 40 Casing clip 5588 5588
21 PCB cover 10021265 10021265 41 Locating stud 5589 5589
22 Terminal block cover 10021266 10021266 42 Self threading screw 3.9mm x 9.5 5079 5079
23 Thermostat/mode switch knob 10021264 10021264 43 Self threading screw 3.5mm x 12mm 5193 5193
Mynute 31
SECTION 9: EXPLODED DIAGRAMS
19
28 21 18
Table
Tav.11 20
22
23
17
22
26
16
22
27
15
35 14
31
2
29
29 11 9
32 29
31
7
10 8
32 Mynute
SECTION 9: EXPLODED DIAGRAMS
23 22
2
Tav. 1 23
Table 1 1 3-24
11
19
18
6
22 3-24 12
13
17
8
7 20 9
14 10
21
16
15
Mynute 33
SECTION 9: EXPLODED DIAGRAMS
32
31
1 2
Table33
Tav.
24 4
Table 4 Mynute 10 & 14e
3 KEY DESCRIPTION Part no 10e Part no 14e
1 Air baffle 10021702 10021702
1 2 Air pressure switch bracket 9233 9233
5 3 Air pressure switch 9232 9232
4 Combustion test nipple screw 8086 8086
5 Silicone tubes 1457 1457
6 Combustion test nipple 8085 8085
7 6 7 Flue tube 1141 1141
8 8 Air deflector 2928 2928
9 Seal 5917 5917
30 9 10 Flue clip 1140 1140
11 Venturi (negative) 7948 7948
11 29 12 Venturi (positive) 6985 6985
13 Fan to flue connector 7779 7779
12 14 Fan 5963 5963
10 15 Air baffle RH 2820 2820
16 Flue hood 5958 5958
13 17 Ari baffle LH 2821 2821
24 28 18 Combustion chamber 6026 6026
19 Rear insulation panel 5962 5962
20 Side insulation panel 5271 5271
21 Support bracket (insulation panel) 5279 5279
14 22 Front insulation panel 5961 5961
23 Combustion cover (front) 2819 2819
24
24 Self threading screw 3.9mm x 13mm 5079 5079
15 25 Rivet 3.2mm x 7mm 5093 5093
26 Self threading screw 3.9mm x 13mm 5080 5080
28 Venturi locknut 4807 4807
29 Self threading screw 3.9mm x 19mm 5081 5081
30 Rivet 3.9mm x 7mm 5094 5094
31 Self threading screw 3.9mm x 6.5mm 5077 5077
32 Screw 3,5X6 5145 5145
24
24
17 16
Tav. 33
Table
18
19
22
21
24 26
20
25
23
24
34 Mynute
SECTION 9: EXPLODED DIAGRAMS
31
8
37
9
6
1 4
34
32 39
41
5 3 40
12 3 10
33
22
35 21
11
3 36 36 13
19
18
36 36
17
38
14 28
27
36
20
16 26
37 15
25
Mynute 35
SECTION 9: EXPLODED DIAGRAMS
1
19
21 18
28 20
22
23
17
22
26
Tav.
Table1 1 16
22
27
15
35 14
31
2
29
29 11 9 Table 2 Mynute 20e
32 29 KEY DESCRIPTION Part no 20e
31 1 Expansion vessel 10020839
7
10 8 2 Expansion pipe 2164
3 Manifold plug 2261
4 Pump (complete) 2225
5 Screwed nipple 3/4 2217
30 6 Safety valve 1806
32 7 Water pressure switch 2044
29 32 31
31 8 Manifold extension 10021251
6 5 9 Flow Manifold 10020621
10 Automatic bypass 2047
4 11 Manifold plug 2216
12 Safety valve extension 2260
3 33 13 Flow/return service valve 1789
14 Flow pipe 10021259
32 31 15 Return pipe 10021258
5 16 Return pipe 10021289
17 Flow pipe 10021290
32 18 High limit thermostat 8367
19 NTC thermistor 8484
20 Heat exchanger 10021232
Tav. 1 1
Table 21 Aluminium washer 5041
22 3/4in fibre washer 5023
26 23 Self threading screw 2.9mm x 6.5mm 5077
12
26 24 22mm compression ring 1822
27 25 3/4in fibre washer 5070
36 25 26 3/4in locknut 4026
27 1/2in Fibre washer 5026
28 Self threading screw 3.9mm x 9.5mm 5079
25 29 Locking pin 2165
30 Self threading screw 3.9mm x 19mm 5081
34 24 31 ‘o’ ring 6898
13 32 Locking pin 2223
24
33 Locking pin 2222
34 Nut 1824
35 O-ring 7999
36 Pre-formed pipe 10021906
36 Mynute
SECTION 9: EXPLODED DIAGRAMS
23 22
2
Table
Tav. 1 1 23
1 3-24
11
19
18 6
22 3-24 12
13
17
8
7 20 9
14 10
21
16
15
Mynute 37
SECTION 9: EXPLODED DIAGRAMS
1
31
2
Table
Tav. 33
Table 4 Mynute 20e
KEY DESCRIPTION Part no 20e
1 Screw 3.5mm x 6mm 5145
24 4 2 Air pressure switch bracket 9233
3 Air pressure switch 9232
3 4 Combustion test nipple screw 8086
5 Silicone tubes 1457
32 5 6 Combustion test nipple 8085
7 Flue tube 2939
8 Air deflector 2928
9 Seal 5917
7 6 10 Flue clip 5916
8 11 Venturi (negative) 7948
12 Venturi (positive) 6985
30 9 13 Fan to flue connector 7816
14 Fan 5910
11 29 15 Air baffle RH 7814
16 Flue hood 2936
12 17 Ari baffle LH 7815
10
18 Combustion chamber 9264
19 Rear insulation panel 7818
13 20 Side insulation panel 5271
21 Support bracket (insulation panel) 5279
22 Front insulation panel 7817
24 23 Combustion cover (front) 7813
28 24 Self threading screw 3.9mm x 13mm 5079
25 Rivet 3.2mm x 7mm 5093
26 Self threading screw 3.9mm x 13mm 5080
14 27 Machine screw M4 x 10mm 5176
15 28 Venturi locknut 4807
24 29 Self threading screw 3.9mm x 19mm 5081
16 30 Rivet 3.9mm x 7mm 5094
31 Self threading screw 3.9mm x 6.5mm 5077
32 Air baffle 10021730
17
24
24
18 19
22
21
26
24 20
Tav.
Table33 25
21 23
24
25
38 Mynute
SECTION 10: LPG INSTRUCTIONS
For details of converting boilers to LPG please refer to the instructions supplied with the relevant conversion kit.
LPG
40
10e
10 E 14e 20e
14 E
35
30
Burner pressure (mbar)
25
20
15
10
0
4 6 8 10 12 14 16 18 20
Mynute 39
energizing home heating Cod. 10022254 - 19/01 - Ed. 1
Vokèra Ltd.
4th Floor, Catherine House, Boundary Way, Hemel Hempstead, Herts, HP2 7RP
Vokèra Ireland
West Court, Callan, Co Kilkenny
Tel: 056 55057 Fax: 056 55060
Vokèra Ltd. reserve the right to change the specifications without prior notice. Consumers’ statutory rights are not affected.
COLLECTIVE MARK
“Vokèra”
supports Benchmark