Bab 9 Controler
Bab 9 Controler
PENGENDALI OTOMATIS
DI INDUSTRI
v Pendahuluan
v Pengendali On-Off
v Pengendali Proporsional
v Pengendali Integral
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-1
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
v PENDAHULUAN
Pengendali Otomatik
Masukan Detektor galat
referensi + Keluaran
Penguat Aktuator Plant
(set point) -
sinyal galat aktuasi
Sensor
u Mode Pengendali:
- Diskontinyu / Digital: - On / Off (2 posisi)
- 3 posisi
- Programmable (PLC)
- Microcomputer
- Kontinyu / Analog : - Proporsional
- Integral
- Proporsional + Integral
- Proporsional + Derivatif
- Proporsional + Integral + Derivatif
u Implementasi : - Mekanik
- Hidraulik
- Pneumatik
- Elektronik : Analog / Digital
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-2
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
v PENGENDALI ON-OFF
• Aplikasi :
Sistem skala besar dengan laju proses lambat
(sistem pendingin/pemanas ruangan).
• Contoh implementasi:
Katup yang digerakkan oleh solenoid.
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-3
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
v PENGENDALI PROPORSIONAL
+ E(s) U(s)
KP
-
u(t) = Kp.e(t),
atau:
U(s) = Kp.E(s)
dengan Kp : gain proporsional
• Aplikasi :
- Sistem dengan manual reset dapat dilakukan,
- Sistem yang tak mengalami perubahan beban besar.
• Contoh Implementasi:
Amplifier dengan penguatan yang dapat diatur.
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-4
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
v PENGENDALI INTEGRAL
+ E(s) Ki U(s)
- s
du (t )
= K i . e ( t ),
dt
atau
t
u(t ) = K i ∫ e (t )dt
0
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-5
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
aksi kendali
u(t) PI
e(t)
2
+ E(s) K p (1 + Ti s) U(s)
Kp
- Ti s 1
Kp
hanya proporsional
0
t Ti t
a b c
masukan fungsi keluaran
undak satuan pengendali
t
Kp
u ( t ) = K p e( t ) +
Ti ∫ e(t )dt
0
• Aplikasi :
Sistem dengan perubahan beban besar yang tak terlalu
Cepat (perlu waktu integrasi).
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-6
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
• Pengendali PI :
1 K p 1 + Ti s
G c ( s) = K p 1 + =
Ti s Ti s
• Kompensator Lag:
Ts + 1
G c ( s) = K c β ; β >1
βTs + 1
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-7
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
aksi kendali
u(t) PD
e(t) Td
+ E(s) U(s)
K p (1 + Td s)
-
hanya
proporsional
0
t t
de(t )
u(t ) = K p e(t ) + K p Td
dt
• Fungsi alih Pengendali:
U ( s)
= K p (1 + Td s)
E ( s)
Kp : konstanta proporsional (adjustable)
Td: waktu derivatif (adjustable)
Pengendali PD:
Gc ( s) = K p (1 + Td s)
Kompensator Lead:
Ts + 1
G c ( s) = K c α ( 0 < α < 1)
αTs + 1
• Pengendali PD = versi sederhana dari kompensator lead.
• Kp ditentukan dari spesifikasi steady state
t
Kp de( t )
u( t ) = K p e ( t ) +
Ti ∫ e(t )dt +K p Td
0
dt
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-10
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
1 1
s + s +
T1 T2
G c ( s) = K c ; γ > 1; β > 1
γ 1
s + s +
T1 βT2
⇓ ⇓
lead lag
• Bode Plot Pengendali PID untuk
(0,1s + 1)( s + 1)
G c ( s) = 2
s
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-11
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
+
K p(1+ 1 s+ Tds) plant
- Ti
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-12
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
0
L T t
c(t)
Pcr
0 t
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-14
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
Contoh 9-1:
Suatu sistem kendali umpanbalik satuan:
( s + 2)(s + 3)
G ( s) =
s( s + 1)( s + 5)
Persamaan karakteristik:
s(s + 1)(s + 5) + K p (s + 2)(s + 3) = 0
s3 + (6 + K p )s 2 + (5 + 5K p )s + 6K p = 0
1
30 + 29K p + 5K 2p
s 0
6 + Kp
s0 6K p
Sistem stabil untuk semua nilai Kp positif. Jadi sistem tidak berosilasi :
nilai penguatan kritis Kcr tidak ada. Dengan demikian metoda kedua tidak
dapat diterapkan.
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-15
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
Contoh 9-2:
Suatu sistem dengan pengendali PID sbb:
R(s) + 1 C(s)
Gc( s)
- s(s+1)(s+5)
pengendali
PID
1
G c (s) = K p (1 + + Td s)
Ti s
Solusi:
Karena plant mengandung integrator, gunakan metoda kedua (Ti = ∞ dan
Td = 0):
C(s) Kp
=
R (s) s(s + 1)(s + 5) + K p
Menentukan nilai Kcr :
Persamaan karakteristik sistem: s3 + 6s2 + 5s + K p = 0
Deret R-H nya:
s3 1 5
s2 6 Kp
30 - K p
s1
6
0
s Kp
Osilasi akan terjadi jika Kp = 30. Jadi penguatan kritis Kcr = 30
Persamaan karakteristik nya:
s3 + 6s2 + 5s + 30 = 0
Frekuensi osilasinya:
( jω ) 3 + 6( jω ) 2 + 5 jω + 30 = 0
6(5 − ω 2 ) + jω (5 − ω 2 ) = 0
Frekuensi keadaan berosilasi menjadi ω = 5 → ω = 5 rad/s.
2
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-16
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
2π 2 π
Perioda osilasi adalah: Pcr = = = 2,8099 detik
ω 5
Gunakan Tabel pada Metoda II, diperoleh:
K p = 0,6K cr = 0,6x30 = 18
Ti = 0,5Pcr = 0,5x2,8099 = 1,405
Td = 0,125Pcr = 0,125x2,8099 = 0,35124
Fungsi alih PID adalah :
1
G c (s) = K p (1 + + Td s)
Ti s
1 6,3223(s + 1,4235) 2
= 18(1 + + 0,35124s) =
1,405s s
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-17
Bab 9: Pengendali Otomatis di Industri EL303:Sistem Kendali
Bila Kp = 39,42:
1 (s + 0,65) 2
G c (s) = 39,42(1 + + 0,7692s) = 30,322
3,077s s
__________________________________________________________________________________
Teknik Elektro ITB [EYS-1998] hal 9-18