Anda di halaman 1dari 46

EE462

Electric Machines

PROJECT REPORT
VARIABLE SPEED DC MOTOR DRIVE

Done By:

ID# NAME SEC# E-mail Tel#


212417 Al-Hajjaj, Muhammad 02 s212417@kfupm.edu.sa 0500099661

Done for:

Dr. M. Abido

Due date
21 May 2006

1
TABLE OF CONTENTS

1.0 DC MOTOR THEORY 3


1.1 Torque 6
1.2 Generator Action in a Motor 7
1.3 DC Motor Theory Summary 8
1.4 TYPES OF DC MOTORS 8

2.0 DC DRIVE FUNDAMENTALS 17


2.1 DC MOTORS 17
2.2 TYPICAL ADJUSTMENTS 23
2.3 DC DRIVES - PRINCIPLES OF OPERATION 26
2.4 DC MOTOR CONTROL CHARACTERISTICS 27
2.5 TYPES OF VARIABLE SPEED DC DRIVES 28

3.0 RECOMMENDATIONS 42

4.0 CONCLUSIONS 44

5.0 REFERENCES 46

2
1.0 DC MOTOR THEORY:

Inducing a Force on a Conductor.

There are two conditions which are necessary to produce a force on a conductor:

i. The conductor must be carrying current.

ii. The conductor must be within a magnetic field.

When these two conditions exist, a force will be applied to the conductor, which
will attempt to move the conductor in a direction perpendicular to the magnetic
field. This is the basic theory by which all DC motors operate.

Theory of Operation (Figure 1), Left-Hand Rule for Current-Carrying Conductors


Every current-carrying conductor has a magnetic field around it. The direction
of this magnetic field may be found by using the left-hand rule for current-
carrying conductors. When the thumb points in the direction of current flow,
the fingers will point in the direction of the magnetic field produced, as
shown in Figure 1.

If a current-carrying conductor is placed in a magnetic field, the combined


fields will be similar to those shown in Figure 2. The direction of current flow
through the conductor is indicated with an "x" or a "•". The "x" indicates the
current flow is away from the reader, or into the page. The "•" indicates the
current flow is towards the reader, or out of the page.

Figure 1: Left-Hand Rule for Current-Carrying Conductors

3
Figure 2: Current-Carrying Conductor in a Magnetic Field

Above the conductor on the left, the field caused by the conductor is in the
opposite direction of the main field, and therefore, opposes the main field. Below
the conductor on the left, the field caused by the conductor is in the same direction
as the main field, and therefore, aids the main field. The net result is that above
the conductor the main field is weakened, or flux density is decreased; below the
conductor the field is strengthened, or flux density is increased. A force is
developed on the conductor that moves the conductor in the direction of the
weakened field (upward).

Above the conductor on the right, the field caused by the conductor is in the same
direction as the main field, and therefore, aids the main field. Below the
conductor on the right, the field caused by the conductor is in the opposite
direction of the main field, and therefore, opposes the main field. The net result is
that above the conductor the field is strengthened, or flux density is increased,
and below the conductor, the field is weakened, or flux density is
decreased. A force is developed on the conductor that moves the conductor in
the direction of the weakened field (downward).

In a DC motor, the conductor will be formed in a loop such that two parts of the
conductor are in the magnetic field at the same time, as shown in Figure 3. This
combines the effects of both conductors to distort the main magnetic field and
produce a force on each part of the conductor. When the conductor is placed on a
rotor, the force exerted on the conductors will cause the rotor to rotate clockwise,
as shown on Figure 3. You can think of these magnetic lines of force as rubber
bands that are always trying to shorten themselves. The lines of force above the

4
conductor exert a downward force due to the magnetic lines of force trying to
straighten themselves.

Figure 3: Motor Action

The above explanation of how a force is developed is convenient; however, it is


somewhat artificial. It is based on a fundamental principle of physics which
may be stated as follows: "A current-carrying conductor in a magnetic field tends
to move at right angles to that field." Another important way to show the
relationship between the current-carrying conductor, magnetic field, and
motion, is the right-hand rule for motors, as shown in Figure 4.

Figure 4: Right hand rule for motors

5
The right-hand rule for motors shows the direction in which a current-carrying
conductor moves in a magnetic field. When the forefinger is pointed in the
direction of the magnetic field lines, and the center finger is pointed in the
direction of current flow, the thumb will point in the direction of force
(motion).

1.1 Torque

Torque is defined as that force which tends to produce and maintain rotation. The
function of torque in a DC motor is to provide the mechanical output or drive the
piece of equipment that the DC motor is attached to.

When a voltage is applied to a motor, current will flow through the field
winding, establishing a magnetic field. Current will also flow through the
armature winding, from the negative brush to the positive brush as shown in
Figure 5. Since the armature is a current- carrying conductor in a magnetic
field, the conductor has a force exerted on it, tending to move it at right angles
to that field. Using the left-hand rule for current- carrying conductors,
you will see that the magnetic field on one side is strengthened at the
bottom, while it is weakened on the other side. Using the right-hand rule for
motors, we can see that there is a force exerted on the armature which tends to turn
the armature in the counter-clockwise direction. The sum of the forces, in
pounds, multiplied by the radius of the armature, in feet, is equal to the torque
developed by the motor in pound-feet (1b - ft). It is evident from Figure 5 that if
the armature current was reversed, but the field was the same, torque would be
developed in the opposite direction. Likewise, if the field polarities were reversed
and the armature remained the same, torque would also be developed in the
opposite direction. The force that is developed on a conductor of a motor armature
is due to the combined action of the magnetic fields. The force developed is
directly proportional to the strength of the main field flux and the strength of the
field around the armature conductor. As we know, the field strength around each
armature conductor depends on the amount of current flowing through the
armature conductor.

6
Figure 5: Armature Current in a Basic DC Motor

T = KFIa

Where T = torque, lb-ft, K = a constant depending on physical size of motor, F =


field flux, number of lines of force per pole Ia = armature current

1.2 Generator Action in a Motor

A generator action is developed in every (CEMF) motor. When a


conductor cuts lines of force, an EMF is induced in that conductor. Current to start
the armature turning will flow in the direction determined by the applied DC
power source. After rotation starts, the conductor cuts lines of force. By
applying the left-hand rule for generators, the EMF that is induced in the armature
will produce a current in the opposite direction. The induced EMF, as a result of
motor operation, is called counter electromotive force, or CEMF, as
illustrated in Figure 6.

7
Figure 6: Counter electromotive Force (CEMF)

1.3 DC Motor Theory Summary

½ There are two conditions necessary to produce a force on a conductor: -


i. The conductor must be carrying current.
ii. The conductor must be within a magnetic field.

½ The right-hand rule for motors states that when the forefinger is pointed in the
direction of the magnetic field lines, and the center finger is pointed in
the direction of current flow, the thumb will point in the direction of motion.
½ The function of torque in a DC motor is to provide the mechanical
output to drive the piece of equipment that the DC motor is attached to.
½ Torque is developed in a DC motor by the armature (current-carrying
conductor) being present in the motor field (magnetic field).
½ CEMF is developed in a DC motor by the armature (conductor) rotating
(relative motion) in the field of the motor (magnetic field).
½ The function of the voltage that is developed in a DC motor (CEMF) opposes
the applied voltage and results in the lowering of armature current.
½ The speed of a DC motor may be changed by using resistors to vary the field
current and, therefore, the field strength.

1.4 TYPES OF DC MOTORS

There are three basic types of dc motors: (1) Series motors. (2) Shunt motors, and
(3) compound motors. They differ largely in the method in which their field and
armature coils are connected.

8
Series DC Motor

In the series motor, the field windings, consisting of a relatively few turns of
heavy wire, are connected in series with the armature winding. The same current
flowing through the field winding also flows through the armature winding. Any
increase in current, therefore, strengthens the magnetism of both the field and the
armature.

Because of the low resistance in the windings, the series motor is able to draw a
large current in starting. This starting current, in passing through both the field and
armature windings, produces a high starting torque, which is the series motor's
principal advantage.

The speed of a series motor is dependent upon the load. Any change in load is
accompanied by a substantial change in speed. A series motor will run at high
speed when it has a light load and at low speed with a heavy load. If the load is
removed entirely, the motor may operate at such a high speed that the armature
will fly apart. If high starting torque is needed under heavy load conditions, series
motors have many applications. Series motors are often used in aircraft as engine
starters and for raising and lowering landing gears, cowl flaps, and wing flaps.

Shunt DC Motor

In the shunt motor the field winding is connected in parallel or in shunt with the
armature winding. The resistance in the field winding is high. Since the field
winding is connected directly across the power supply, the current through the
field is constant. The field current does not vary with motor speed, as in the series

9
motor and, therefore, the torque of the shunt motor will vary only with the current
through the armature. The torque developed at starting is less than that developed
by a series motor of equal size.

The speed of the shunt motor varies very little with changes in load. When all
loads are removed, it assumes a speed slightly higher than the loaded speed. This
motor is particularly suitable for use when constant speed is desired and when
high starting torque is not needed.

Compound DC Motor

The compound motor is a combination of the series and shunt motors. There are
two windings in the field: a shunt winding and a series winding. The shunt
winding is composed of many turns of fine wire and is connected in parallel with
the armature winding. The series winding consists of a few turns of large wire and
is connected in series with the armature winding. The starting torque is higher than
in the shunt motor but lower than in the series motor. Variation of speed with load
is less than in a series wound motor but greater than in a shunt motor. The
compound motor is used whenever the combined characteristics of the series and
shunt motors are desired.

Like the compound generator, the compound motor has both series and shunt field
windings. The series winding may either aid the shunt wind (cumulative
compound) or oppose the shunt winding (differential compound).

The starting and load characteristics of the cumulative compound motor are
somewhere between those of the series and those of the shunt motor.

10
Because of the series field, the cumulative compound motor has a higher starting
torque than a shunt motor. Cumulative compound motors are used in driving
machines which are subject to sudden changes in load. They are also used where a
high starting torque is desired, but a series motor cannot be used easily.

In the differential compound motor, an increase in load creates an increase in


current and a decrease in total flux in this type of motor. These two tend to offset
each other and the result is a practically constant speed. However, since an
increase in load tends to decrease the field strength, the speed characteristic
becomes unstable. Rarely is this type of motor used in aircraft systems.

Counter E.M.F.

The armature resistance of a small, 28 volt dc motor is extremely low, about 0.1
ohms. When the armature is connected across the 28 volt source, current through
the armature will apparently be

This high valve of current flow is not only impracticable but also unreasonable,
especially when the current drain, during normal operation of a motor, is found to
be about 4 amperes. This is because the current through a motor armature during
operation is determined by more factors than ohmic resistance.

When the armature in a motor rotates in a magnetic field, a voltage is induced in


its windings. This voltage is called the back or counter e.m.f. (electromotive force)
and is opposite in direction to the voltage applied to the motor from the external
source.

Counter e.m.f. opposes the current which causes the armature to rotate. The
current flowing through the armature, therefore, decreases as the counter e.m.f.
increases. The faster the armature rotates, the greater the counter e.m.f. For this
reason, a motor connected to a battery may draw a fairly high current on starting,
but as the armature speed increases, the current flowing through the armature
decreases. At rated speed, the counter e.m.f. may be only a few volts less than the
battery voltage. Then, if the load on the motor is increased, the motor will slow
down, less counter e.m.f. will be generated, and the current drawn from the
external source will increase. In a shunt motor, the counter e.m.f. affects only the
current in the armature, since the field is connected in parallel across the power
source. As the motor slows down and the counter e.m.f. decreases, more current
flows through the armature, but the magnetism in the field is unchanged. When the
series motor slows down, the counter e.m.f. decreases and more current flows

11
through the field and the armature, thereby strengthening their magnetic fields.
Because of these characteristics, it is more difficult to stall a series motor than a
shunt motor.

Types of Duty

Electric motors are called upon to operate under various conditions. Some motors
are used for intermittent operation; others operate continuously. Motors built for
intermittent duty can be operated for short periods only and, then, must be allowed
to cool before being operated again. If such a motor is operated for long periods
under full load, the motor will be overheated. Motors built for continuous duty
may be operated at rated power for long periods.

Reversing Motor Direction

By reversing the direction of current flow in either the armature or the field
windings, the direction of a motor's rotation may be reversed. This will reverse the
magnetism of either the armature or the magnetic field in which the armature
rotates. If the wires connecting the motor to an external source are interchanged,
the direction of rotation will not be reversed, since changing these wires reverses
the magnetism of both field and armature and leaves the torque in the same
direction as before.

One method for reversing direction of rotation employs two field windings wound
in opposite directions on the same pole. This type of motor is called a split field
motor. The single pole, double throw switch makes it possible to direct current
through either of the two windings. When the switch is placed in the lower
position, current flows through the lower field winding, creating a north pole at the
lower field winding and at the lower pole piece, and a south pole at the upper pole
piece. When the switch is placed in the upper position, current flows through the
upper field winding, the magnetism of the field is reversed, and the armature
rotates in the opposite direction. Some split field motors are built with two
separate field windings wound on alternate poles. The armature in such a motor, a
four pole reversible motor, rotates in one direction when current flows through the
windings of one set of opposite pole pieces, and in the opposite direction when
current flows through the other set of windings.

Another method of direction reversal, called the switch method, employs a double
pole, double throw switch which changes the direction of current flow in either the
armature or the field. In the illustration of the switch method. Current direction
may be reversed through the field but not through the armature. When the switch
is thrown to the "up" position, current flows through the field winding to establish

12
a north pole at the right side of the motor and a south pole at the left side of the
motor. When the switch is thrown to the "down" position, this polarity is reversed
and the armature rotates in the opposite direction.

Motor Speed

Motor speed can be controlled by varying the current in the field windings. When
the amount of current flowing through the field windings is increased, the field
strength increases, but the motor slows down since a greater amount of counter
e.m.f. is generated in the armature windings. When the field current is decreased,
the field strength decreases, and the motor speeds up because the counter e.m.f. is
reduced. A motor in which speed can be controlled is called a variable speed
motor. It may be either a shunt or series motor.

In the shunt motor, speed is controlled by a rheostat in series with the field
windings. The speed depends on the amount of current which flows through the
rheostat to the field windings. To increase the motor speed, the resistance in the
rheostat is increased, which decreases the field current. As a result, there is a
decrease in the strength of the magnetic field and in the counter e.m.f. This
momentarily increases the armature current and the torque. The motor will then
automatically speed up until the counter e.m.f. increases and causes the armature
current to decrease to its former value. When this occurs, the motor will operate at
a higher fixed speed than before.

To decrease the motor speed, the resistance of the rheostat is decreased. More
current flows through the field windings and increases the strength of the field;
then, the counter e.m.f. increases momentarily and decreases the armature current.
As a result, the torque decreases and the motor slow down until the counter e.m.f.
decreases to its former value; then the motor operates at a lower fixed speed than
before.

The rheostat speed control is connected either in parallel or in series with the
motor field, or in parallel with the armature. When the rheostat is set for maximum
resistance, the motor speed is increased in the parallel armature connection by a
decrease in current. When the rheostat resistance is maximum in the series
connection, motor speed is reduced by a reduction in voltage across the motor. For
above normal speed operation, the rheostat is in parallel with the series field. Part
of the series field current is bypassed and the motor speeds up.

Energy Losses in DC Motors

Losses occur when electrical energy is converted to mechanical energy (in the
motor), or mechanical energy is converted to electrical energy (in the generator).

13
For the machine to be efficient, these losses must be kept to a minimum. Some
losses are electrical, others are mechanical. Electrical losses are classified as
copper losses and iron losses; mechanical losses occur in overcoming the friction
of various parts of the machine.

Copper losses occur when electrons are forced through the copper windings of the
armature and the field. These losses are proportional to the square of the current.
They are sometimes called I²R losses, since they are due to the power dissipated in
the form of heat in the resistance of the field and armature windings.

Iron losses are subdivided in hysteresis and eddy current losses. Hysteresis losses
are caused by the armature revolving in an alternating magnetic field. It, therefore,
becomes magnetized first in one direction and then in the other. The residual
magnetism of the iron or steel of which the armature is made causes these losses.
Since the field magnets are always magnetized in one direction (DC field), they
have no hysteresis losses.

Eddy current losses occur because the iron core of the armature is a conductor
revolving in a magnetic field. This sets up an e.m.f. across portions of the core,
causing currents to flow within the core. These currents heat the core and, if they
become excessive, may damage the windings. As far as the output is concerned,
the power consumed by eddy currents is a loss. To reduce eddy currents to a
minimum, a laminated core usually is used. A laminated core is made of thin
sheets of iron electrically insulated from each other. The insulation between
laminations reduces eddy currents, because it is "transverse" to the direction in
which these currents tend to flow. However, it has no effect on the magnetic
circuit. The thinner the laminations, the more effectively this method reduces eddy
current losses.

Inspection and Maintenance of DC Motors

Use the following procedures to make inspection and maintenance checks:

1. Check the operation of the unit driven by the motor in accordance with the
instructions covering the specific installation.

2. Check all wiring, connections, terminals, fuses, and switches for general
condition and security.

3. Keep motors clean and mounting bolts tight.

14
4. Check brushes for condition, length, and spring tension. Minimum brush
lengths, correct spring tension, and procedures for replacing brushes are given
in the applicable manufacturer's instructions.

5. Inspect commutator for cleanness, pitting, scoring, roughness, corrosion or


burning. Check for high mica (if the copper wears down below the mica, the
mica will insulate the brushes from the commutator). Clean dirty commutators
with a cloth moistened with the recommended cleaning solvent. Polish rough
or corroded commutators with fine sandpaper (000 or finer) and blow out with
compressed air. Never use emery paper since it contains metallic particles
which may cause shorts. Replace the motor if the commutator is burned, badly
pitted, grooved, or worn to the extent that the mica insulation is flush with the
commutator surface.

6. Inspect all exposed wiring for evidence of overheating. Replace the motor if the
insulation on leads or windings is burned, cracked, or brittle.

7. Lubricate only if called for by the manufacturer's instructions covering the


motor. Most motors used in today's airplanes require no lubrication between
overhauls.

8. Adjust and lubricate the gearbox, or unit which the motor drives, in accordance
with the applicable manufacturer's instructions covering the unit.

When trouble develops in a dc motor system, check first to determine the source
of the trouble. Replace the motor only when the trouble is due to a defect in the
motor itself. In most cases, the failure of a motor to operate is caused by a defect
in the external electrical circuit, or by mechanical failure in the mechanism driven
by the motor.

Check the external electrical circuit for loose or dirty connections and for
improper connection of wiring. Look for open circuits, grounds, and shorts by
following the applicable manufacturer's circuit testing procedure. If the fuse is not
blown, failure of the motor to operate is usually due to an open circuit. A blown
fuse usually indicates an accidental ground or short circuit. The chattering of the
relay switch which controls the motor is usually caused by a low battery. When
the battery is low, the open circuit voltage of the battery is sufficient to close the
relay, but with the heavy current draw of the motor, the voltage drops below the
level required to hold the relay closed. When the relay opens, the voltage in the
battery increases enough to close the relay again. This cycle repeats and causes
chattering, which is very harmful to the relay switch, due to the heavy current
causing an arc which will burn the contacts.

15
Check the unit driven by the motor for failure of the unit or drive mechanism. If
the motor has failed as a result of a failure in the driven unit, the fault must be
corrected before installing a new motor.

If it has been determined that the fault is in the motor itself (by checking for
correct voltage at the motor terminals and for failure of the driven unit), inspect
the commutator and brushes. A dirty commutator or defective or binding brushes
may result in poor contact between brushes and commutator. Clean the
commutator, brushes, and brush holders with a cloth moistened with the
recommended cleaning solvent. If brushes are damaged or worn to the specified
minimum length, install new brushes in accordance with the applicable
manufacturer's instructions covering the motor. If the motor still fails to operate,
replace it with a serviceable motor.

16
2.0 DC DRIVE FUNDAMENTALS
UNDERSTANDING DC DRIVES
DC motors have been available for nearly 100 years. In fact the first electric
motors were designed and built for operation from direct current power.

AC motors are now and will of course remain the basic prime movers for the fixed
speed requirements of industry. Their basic simplicity, dependability and
ruggedness make AC motors the natural choice for the vast majority of industrial
drive applications.

Then where do DC drives fit into the industrial drive picture of the future?

In order to supply the answer, it is necessary to examine some of the basic


characteristics obtainable from DC motors and their associated solid state
controls.

1. Wide speed range.


2. Good speed regulation.
3. Compact size and light weight (relative to mechanical variable speed).
4. Ease of control.
5. Low maintenance.
6. Low cost.

In order to realize how a DC drive has the capability to provide the above
characteristics, the DC drive has to be analyzed as two elements that make up the
package. These two elements are of course the motor and the control. (The
"control" is more accurately called the "regulator").

2.1 DC MOTORS

Basic DC motors as used on nearly all packaged drives have a very simple
performance characteristic the shaft turns at a speed almost directly proportional to
the voltage applied to the armature. Figure 1 shows a typical voltage/speed curve
for a motor operating from a 115 volt control.

17
From the above curve you can see that with 9 volts applied to the armature, this
motor would be operating at Point 1 and turn at approximately 175 RPM.
Similarly with 45 volts applied, the motor would be operating at Point 2 on the
curve or 875 RPM. With 90 volts applied, the motor would reach its full speed of
1750 RPM at point 3.

From this example a general statement can be made that DC motors have "no
load" characteristics that are nearly a perfect match for the curve indicated in
Figure 1.

However, when operated at a fixed applied voltage but a gradually increasing


torque load, they exhibit a speed droop as indicated in Figure 2.

This speed droop is very similar to what would occur if an automobile accelerator
pedal was held in a fixed position with the car running on level ground. Upon
starting up an incline where more driving torque would be needed, the car would
slow down to a speed related to the steepness of the hill. In a real situation, the
driver would respond by depressing the accelerator pedal to compensate for the
speed loss to maintain a nearly constant speed up the incline.

18
In the DC drive a similar type of "compensation" is employed in the control to
assist in maintaining a nearly constant speed under varying load (torque)
conditions.

The measurement of this tendency to slow down is called Regulation and is


calculated with the following equation:

No Load Speed - Full Load Speed


% Regulation = X 100
No Load Speed

In DC drives the regulation is generally expressed as a percentage of motor base


speed.

If the control (regulator) did not have the capability of responding to and
compensating for changing motor loads, regulation of typical motors might be as
follows:

% MOTOR % MOTOR
HP HP
REGULATION REGULATION
1/4 13.6 1.5 8.0
1/3 12.9 2 7.2
1/2 13.3 3 4.2
3/4 10.8 5 2.9
1 6.7 7.5 2.3

One other very important characteristic of a DC motor should be noted. Armature


amperage is almost directly proportional to output torque regardless of speed. This
characteristic is shown by Figure 3. Point 1 indicates that a small fixed amount of
current is required to turn the motor even when there is no output torque. This is
due to the friction of the bearings, electrical losses in the motor materials and load
imposed by the air in the motor (wind age).

19
Beyond Point 1 through Point 2 and 3, the current increases in direct proportion to
the torque required by the load.

From this discussion and Figure 3 a general statement can be made that for PM
and Shunt Wound motors load torque determines armature amperage.

In summary, two general statements can be made relative to DC motor


performance.

1. Motor Speed is primarily determined by Applied Armature Voltage.


2. Motor Torque is controlled by Armature Current (amperes).

Understanding these two concepts of DC motors provides the key to


understanding total drive performance.

REGULATORS (CONTROLS)

The control provides two basic functions:

1. It rectifies AC power converting it to DC for the DC motor.


2. It controls the DC output voltage and amperage in response to various
control and feedback signals thereby regulating the motor's performance,
both in speed and torque.

RECTIFYING FUNCTION

The basic rectifying function of the control is accomplished by a combination of


power semiconductors (Silicon Controlled Rectifiers and Diodes) that make up the
"power bridge" assembly.

20
REGULATING FUNCTION

The regulating function is provided by a relatively simple electronic circuit that


monitors a number of inputs and sums these signals to produce a so called "error"
signal. This error signal is processed and transformed into precisely timed pulses
(bursts of electrical energy). These pulses are applied to the gates of the SCR's in
the power bridge thereby regulating the power output to the DC motor.

For most purposes it is not necessary to understand the electronic details of the
regulator, however, in order to appreciate the regulator function it is good to
understand some of the input signals that are required to give the regulator its
capabilities, these are shown diagrammatically in Figure 4.

The AC to DC power flow is a relatively simple straight through process with the
power being converted from AC to DC by the action of the solid state power
devices that form the power bridge assembly.

The input and feedback signals need to be studied in more detail.

SET POINT INPUT

In most packaged drives this signal is derived from a closely regulated fixed
voltage source applied to a potentiometer. 10 volts is a very common reference.

The potentiometer has the capability of accepting the fixed voltage and dividing it
down to any value of from, for example, 10 to zero volts, depending on where it is

21
set. A 10 volt input to the regulator from the speed adjustment control
(potentiometer) corresponds to maximum motor speed and zero volts correspond
to zero speed. Similarly any speed between zero and maximum can be obtained by
adjusting the speed control to the appropriate setting.

SPEED FEEDBACK INFORMATION

In order to "close the loop" and control motor speed accurately it is necessary to
provide the control with a feedback signal related to motor speed.

The standard method of doing this in a simple control is by monitoring the


armature voltage and feeding it back into the regulator for comparison with the
input "set point" signal.

When armature voltage becomes high, relative to the set point, established by the
speed potentiometer setting, an "error" is detected and the output voltage from the
power bridge is reduced to lower the motor's speed back to the "set point".
Similarly when the armature voltage drops an error of opposite polarity is sensed
and the control output voltage is automatically increased in an attempt to re-
establish the desired speed.

The "Armature Voltage Feedback System" which is standard in most packaged


drives is generally called a "Voltage Regulated Drive".

A second and more accurate method of obtaining the motor speed feedback
information is called "Tachometer Feedback". In this case the speed feedback
signal is obtained from a motor mounted tachometer. The output of this
tachometer is directly related to the speed of the motor. Using Tachometer
Feedback generally gives a drive improved regulation characteristics. When
"Tachometer Feedback" is used the drive is referred to as a "Speed Regulated
Drive". Most controls are capable of being modified to accept tachometer signals
for operation in the tachometer feedback mode.

In some newer high performance "digital drives" the feedback can come from a
motor mounted encoder that feeds back voltage pulses at a rate related to motor
speed. These (counts) are processed digitally being compared to the "set point"
and error signals are produced to regulate the armature voltage and speed.

CURRENT FEEDBACK

The second source of feedback information is obtained by monitoring the motor


armature current. As discussed previously, this is an accurate indication of the
torque required by the load.

22
The current feedback signal is used for two purposes:

1. As positive feedback to eliminate the speed droop that occurs with


increased torque load on the motor. It accomplishes this by making a slight
corrective increase in armature voltage as the armature current increases.
2. As negative feedback with a "threshold" type of control that limits the
current to a value that will protect the power semiconductors from damage.
By making this function adjustable it can be used to control the maximum
torque the motor can deliver to the load.

The current limiting action of most controls is adjustable and is usually called
"Current Limit" or "Torque Limit".

In summary, the Regulator accomplishes two basic functions:

1. It converts the alternating Current to Direct Current.


2. It regulates the armature voltage and current to control the speed and torque
of the DC Motor.

2.2 TYPICAL ADJUSTMENTS

In addition to the normal external adjustment such as the speed potentiometer.


There are a number of common internal adjustments that are used on simple small
analog type SCR Drives (Silicon Controlled Rectifier Drive). Some of these
adjustments are as follows:

• Minimum Speed
• Maximum Speed
• Current Limit (Torque Limit). IR Compensation
• Acceleration Time. Deceleration Time

The following is a description of the function that these individual adjustments


serve and their typical use.

MINIMUM SPEED

In most cases when the control is initially installed the speed potentiometer can be
turned down to its lowest point and the output voltage from the control will go to
zero causing the motor to stop. There are many situations where this is not
desirable. For example there are some machines that want to be kept running at a
minimum speed and accelerated up to operating speed as necessary. There is also a
possibility that an operator may use the speed potentiometer to stop the motor to
work on the machine. This can be a dangerous situation since the motor has only

23
been brought to a stop by zeroing the input signal voltage. A more desirable
situation is when the motor is stopped by opening the circuit to the motor or power
to the control using the on/off switch. By adjusting the minimum speed up to some
point where the motor continues to run even with the speed potentiometer set to its
lowest point, the operator must shut the control off to stop the motor. This adds a
little safety into the system. The typical minimum speed adjustment is from 0 to
30% of motor base speed.

MAXIMUM SPEED

The maximum speed adjustment sets the maximum speed attainable either by
raising the input signal to its maximum point or turning the potentiometer to the
maximum point. For example on a typical DC motor the rated speed of the motor
might 1750 RPM but the control might be capable of running it up to 1850 or 1900
RPM. In some cases it's desirable to limit the motor (and machine speed) to
something less than would be available at this maximum setting. The
maximum adjustment allows this to be done. By turning the internal potentiometer
to a lower point the maximum output voltage from the control is limited. This
limits the maximum speed available from the motor. In typical controls such as
our BC140 the range of adjustment on the maximum speed is from 50 to 110% of
motor base speed.

CURRENT LIMIT

One very nice feature of electronic speed controls is that the current going to the
motor is constantly monitored by the control. As mentioned previously, the current
drawn by the armature of the DC motor is related to the torque that is required by
the load. Since this monitoring and control is available an adjustment is provided
in the control that limits the output current to a maximum value.

This function can be used to set a threshold point that will cause the motor to stall
rather than putting out an excessive amount of torque. This capability gives the
motor/control combination the ability to prevent damage that might otherwise
occur if higher values of torque were available. This is handy on machines that
might become jammed or otherwise stalled. It can also be used where the control
is operating a device such as the center winder where the important thing becomes
torque rather than the speed. In this case the current limit is set and the speed goes
up or down to hold the tension 0 the material being wound. The current limit is
normally factory set at 150% of the motor's rated current. This allows the motor to
produce enough torque to start and accelerate the load and yet will not let the
current (and torque) exceed 150% of its rated value when running. The range of
adjustment is typically from 0 to 200% of the motor rated current.

24
IR COMPENSATION

IR compensation is a method used to adjust for the droop in a motor's speed due to
armature resistance. As mentioned previously, IR compensation is positive
feedback that causes the control output voltage to rise slightly with increasing
output current. This will help stabilize the motor's speed from a no load to full load
condition. If the motor happens to be driving a load where the torque is constant or
nearly so, then this adjustment is usually unnecessary. However, if the motor is
driving a load with a widely fluctuating torque requirement, and speed regulation
is critical, then IR compensation can be adjusted to stabilize the speed from the
light load to full load condition. One caution is that when IR compensation is
adjusted too high it results in an increasing speed characteristic. This means that as
the load is applied the motor is actually going to be forced to run faster. When
this happens it increases the voltage and current to the motor which in turn
increases the motor speed further. If this adjustment is set too high an unstable
"hunting" or oscillating condition occurs that is undesirable.

ACCELERATION TIME

The Acceleration Time adjustment performs the function that is indicated by its
name. It will extend or shorten the amount of time for the motor to go from zero
speed up to the set speed. It also regulates the time it takes to change speeds from
one setting (say 50%) to another setting (perhaps 100%). So this setting has the
ability to moderate the acceleration rate on the drive.

A couple notes are important: if an acceleration time that is too rapid is called for
"acceleration time" will be overridden by the current limit. Acceleration will only
occur at a rate that is allowed by the amount of current the control passes through
to the motor. Also important to note is that on most small controls the acceleration
time is not linear. What this means is that a change of 50 RPM may occur more
rapidly when the motor is at low speed than it does when the motor is approaching
the set point speed. This is important to know but usually not critical on simple
applications where these drives are used.

DECELERATION TIME

This is an adjustment that allows loads to be slowed over an extended period of


time. For example, if power is removed from the motor and the load stops in 3
seconds, then the decal time adjustment would allow you' to increase that time and
"power down" the load over a period of 4, 5, 6 or more seconds. Note: On a
conventional simple DC drive it will not allow for the shortening of the time
below the "coast to rest" time.

25
ADJUSTMENT SUMMARY

The ability to adjust these six adjustments gives great flexibility to the typical
inexpensive DC drive. In most cases the factory preset settings are adequate and
need not be changed, but on other applications it may be desirable to tailor the
characteristics of the control to the specific application.

Many of these adjustments are available in other types of controls, such as variable
frequency drives.

2.3 DC DRIVES - PRINCIPLES OF OPERATION

DC drives, because of their simplicity, ease


of application, reliability and favorable cost
have long been a backbone of industrial
applications. A typical adjustable speed drive
using a silicon controller rectifier (SCR)
power conversion' section, common for this
type unit, is shown in Figure 2. The SCR,
(also termed a thyristor) converts the fixed
voltage alternating current (AC) of the power
source to an adjustable voltage, controlled
direct current (DC) output which is applied to the armature of a DC
motor.

SCR's provide a controllable power output by "phase angle control",


so called because the firing angle (a point in time where the SCR is
triggered into conduction) is synchronized with the phase rotation of
the AC power source. If the device is triggered early in half cycle,
maximum power is delivered to the motor; late triggering in the half
cycle provides minimum power, as illustrated by Figure 3. The
effect is similar to a very high speed switch, capable of being turned
on and "conducted" off at an infinite number of points within each
half cycle. This occurs at a rate of 60 times a second on a 60 Hz line,
to deliver a precise amount of power to the motor. The efficiency of
this form of power control is extremely high since a very small
amount of triggering energy can enable the SCR (Silicon Controlled
Rectifier) to control a great deal of output power.

26
2.4 DC MOTOR CONTROL CHARACTERISTICS

A shunt-wound motor is a direct-current motor in which the field windings and the
armature may be connected in parallel across a constant-voltage supply. In
adjustable speed applications, the field is connected across a constant-voltage
supply and the armature is connected across an independent adjustable-voltage
supply. Permanent magnet motors have
similar control characteristics but differ
primarily by their integral permanent
magnet field excitation.

The speed (N) of a DC motor is


proportional to its armature voltage; the
torque (T) is proportional to armature
current, and the two quantities are independent, as illustrated in Figure 5.

CONSTANT TORQUE APPLICATIONS

Armature voltage controlled DC drives are constant torque drives. They are
capable of providing rated torque at any speed between zero and the base (rated)
speed of the motor as shown by Figure 6. Horsepower varies in direct proportion
to speed, and 100% rated horsepower is developed only at 100% rated motor
speed with rated torque.

CONSTANT HORSEPOWER APPLICATIONS

Armature Controlled DC Drives - Certain applications require constant


horsepower over a specified speed range. The screened area, under the horsepower
curve in Figure 6, illustrates the limits of constant horsepower operation for
armature controlled DC drives. As an example, the motor could provide constant
horsepower between 50% speed and 100% speed, or a 2:1 range. However, the
50% speed point coincides with the 50% horsepower point. Any constant
horsepower application may be easily calculated by multiplying the desired
horsepower by the ratio of the speed range over which horsepower must remain
constant. If 5 HP is required over a 2:1 range, an armature only controlled drive
rated for 10 (5 x 2) horsepower would be required.

Table 3 provides a convenient listing of horsepower output at various operating


speeds for constant torque drives.

27
Field Controlled DC Drives - Another characteristic of a shunt-wound DC motor
is that a reduction in field voltage to less than the design rating will result in an
increase in speed for a given armature voltage. It is important to note, however,
that this results in a higher armature
current for a given motor load. A simple
method of accomplishing this is by
inserting a resistor in series with the field
voltage source. This may be useful for
trimming to an ideal motor speed for the
application. An optional, more
sophisticated method uses a variable
voltage field source as shown by Figure 6.
This provides coordinated automatic
armature and field voltage control for
extended speed range and constant HP
applications. The motor is armature
voltage controlled for constant torque-
variable HP operation to base speed where it is transferred to field control for
constant HP-variable torque operation to motor maximum speed.

2.5 TYPES OF DC DRIVES

SIMOREG 6RA24 Siemens Variable Speed DC Drive


Description & Standard Features

SIMOREG Drive Controller

The Siemens Motor Regulator (SIMOREG) is a state of the art, microprocessor


based DC drive controller. This drive controller converts a three-phase, 50/60 Hz
supply voltage into six pulse adjustable voltage to operate a DC motor. Output
armature voltage varies directly with speed reference to provide constant torque
operation from zero speed to base speed. Above base speed, the motor shunt field
current may be decreased to further increase speed and provide a constant
horsepower output up to maximum speed.

The SIMOREG drive controller is designed to provide precise motor speed control
over a wide range of machine parameters and load conditions. This software based
controller will serve well as a packaged drive or as part of a drive system.

Horsepower ranges include 1-250HP at 230VAC, 2-1750HP at 460VAC input and


1500HP and higher at 600/650V AC input. All HP ratings are available as
regenerative or non-regenerative drive controllers. Listed below are standard
features, a partial list of adjustments, display parameters, service conditions,

28
diagnostics, and protection features. Consult the Technical Information Section for
additional information.

Standard Features Protection

The SIMOREG drive controller • Tachometer loss and over speed


includes the following standard • Field current loss
features: (Refer to the Technical • 12t motor overload
Information Section for additional • Instantaneous over current
details.) • Line tolerance monitoring
• Phase sequence monitoring
• Designed to meet the • Phase loss
requirements of NEMA, IEEE, • dv/dt Protection on the SCR's
NEC, UL Listed and CSA • SCR type high speed AC line
Certified through 510A. fuses
• 6 Pulse SCR (Silicon Controlled • DC output fuse on regenerative
Rectifier) Bridge Microprocessor units
Control Board with 16 bit 38 • Heat sink thermostat on fan
MHz high performance multi- cooled units
tasking microprocessor • Isolated electronics
• User interface keypad and digital
display Diagnostics
• Power and interface control There are more than 120 diagnostic
board Individual pulse messages for troubleshooting, including
transformers per SCR fault and warning indication and
• R/C snubbers across each SCR memory retention of the last four faults.
• Current transformers for current Some of the diagnostics include:
• regulator feedback
• Run/Ready light • Line voltage out of tolerance
• Plug-in wiring harness between • Line frequency unstable/out of
boards tolerance
• Shunt field excitation circuitry • Phase loss
with field current loss protection • Motor stalled
and field economizing circuit • SCR failure detection and
• Terminal blocks for identification
incoming/outgoing • Loss of speed or voltage
• wiring connections feedback
• Wire markers • Current overload
• Fully rated contactor • EEPROM/Microprocessor
• High speed AC power fuses malfunctions
• 460/230: 115V AC control power • Quick Stop

29
transformer • 8 Channel data storage
• Power supply transformer
• Digitally fired burst type SCR Standard Displays include:
gate pulses
• 1400PRV rated thyristors are • Speed reference
standard • Operating speed
• Built-in AID converter accepts • Current reference
external reference sources • Actual current
• Digital and analog tachometer • Gating angle
generator feedback • CEMF
• Serial communication via RS232 • Armature voltage
or RS485 serial ports • CEMF/Speed
• General purpose P-I-D loop for • RMS AC phase to phase voltage
additional regulation modes • All parameter set points
• Freely programmable blocks for • Torque direction
mathematical functions • Operating time
• Software programming package • Field current reference
to aid in start up
• Peer to Peer Link Service Conditions
• Tachometer to Voltage Feedback
switching • 0-40°C Ambient
• Four layer parameter • Altitude: 3300 feet above sea
• 5 Binary and analog outputs level without derating (1000
meters)
Adjustments • 95% Relative humidity (non-
condensing)
• Priority access code protection • AC line voltage tolerance + 10%,
• Minimum speed -5%
• Maximum speed • Frequency tolerance 48 to 62 Hz
• Linear acceleration
• Linear deceleration
• S-Curve rounding
• Jog and thread speed presets Data Subject to Change without Notice
• Current limit
• Tapered current limit
• IR compensation for voltage
feedback drives
• Motor armature current rating
• Motor field current rating
• Self turning routine
automatically adjusts each
SIMOREG drive controller to

30
optimum performance upon
command
• Over speed with tachometer
feedback
• CEMF crossover voltage (for
field weakened speed ranges)

(a) SIMOREG 6RA70 Siemens DC Master Variable Speed DC Drive


Description & Base Drive Catalog Numbers

• Description & Base Drive Catalog Numbers


• Features
• Design and Mode of Operation
o SIMOREG 6RA70 Converters
o Parameterization Devices
o Software Structure
o Closed-Loop Functions in Armature Circuit
o Closed-Loop Functions in Field Circuit
o Optimization Run
o Monitoring and Diagnosis
o Functions of Inputs and Outputs
o Safety Shutdown (E-STOP)
o Serial Interface

(i) Description

Base Drive Description

Series 6RA70 SIMOREG DC MASTER base drive converters are complete drive
assemblies ready to be installed and operated. They include a 3-phase armature
converter, single-phase field converter, main contactor, protective semiconductor
fuses, control power transformer, and power / control terminals.

Base drive converters are fully digital, compact units which supply the armature
and field of variable speed DC drives with rated armature currents from 15A to
1660A. The motor field circuit can be supplied with DC currents of up to 40A
(current levels depend on the armature rated current).

31
General Information

Series 6RA70 SIMOREG DC MASTER Converters are characterized by their


compact, space-saving construction. Their compact design makes them
particularly easy to service and maintain since individual components are readily
accessible. The electronics box contains the basic electronic circuitry as well as
any supplementary option boards.

All SIMOREG DC MASTER Units are equipped with a PMU simple operator
panel mounted in the converter door. The panel consists of a five-digit, seven-
segment display, three LED's as status indicators and three parameterization keys.
The PMU also features connector X300 with an USS interface in accordance with
the RS232 or RS485 standard. The panel provides all the facilities for making
adjustments or settings and displaying measured values required to start-up the
converter.

The OP1 S optional converter operator panel can be mounted directly in the
converter door or externally, e.g., in the cubicle door. When mounted remotely,
the OP1 S can be connected to the converter with cables up to 5 meters (15 feet)
length. Cable up to 200 meter (600 feet) in length can be used if a separate 5 VDC
power supply is available. The OP1 S connects to the SIMOREG through
connector X300 using the RS485 interface. The OP1 S can be installed as an
economic alternative to conventional door mounted metering devices (Le.
voltmeters, ammeters, and speed indicator).

The OP1 S features a liquid crystal display with 4 x 16 characters for displaying
parameter names in plain text. English, German, French, Spanish and Italian can
be selected as the display languages. In addition the OP1 S can store parameter
sets for easy downloading to other drives.

The converter can also be parameterized on a standard PC with appropriate


software connected to the serial interface on the basic unit. This PC interface is
used during start-up, for maintenance during shutdown and for diagnosis in
operation. Furthermore, converter software upgrades can be loaded through this
interface for storage in flash memory.

On single-quadrant converters, a fully controlled three-phase bridge supplies the


armature. On four-quadrant converters, two fully controlled three-phase bridges
are connected in an inverse-parallel connection to allow both positive and negative
armature current. For the field converter, a single-phase, half-controlled 2-pulse
bridge supplies the motor shunt field.

32
The armature and field converters can operate with AC line frequencies from 45 to
65 Hz. If required for a specific application, the frequency of the armature and
field AC supplies can be different. The armature converter 3 phase AC supply is
phase insensitive however on base drives rated 1180 and 1660 amperes, the 3
phase cooling fan must be connected to get the proper direction of rotation. The
power section cooling system is monitored by means of temperature sensors.

The power section for the armature and field converters is constructed of isolated
thyristor modules for converters rated from 15A to 850A at 460V AG-line voltage.
The heat sink in this case is electrically isolated and at ground potential. On
converters rated 1180 and 1660 amperes at 460 VAC, the power section for the
armature circuit is constructed using disk thyristors and the heat sinks are at line
voltage potential. The housing and terminal covers on power connections provide
protection against accidental contact for operators working in the vicinity. All
connecting terminals are accessible from the front.

All open and closed-loop drive control and communication functions are
performed by two powerful microprocessors. Drive control functions are
implemented in the software as program modules that can be "wired up" and
changed by parameters.

Rated DC Current:

The rating plate of the converter module has 3 rated currents listed on it. The first
two are IEG ratings and have no bearing on the base drive rating. The third rating
is the US (NEMA) rating which the base drive rating is derived from.

The US (NEMA) rated current allows operation at rated current followed by an


overload of 150% for 60 seconds in a 45°G ambient. The overload can be applied
no sooner than every 10 minutes. Base drives are designed using the US rating
which means that fuses, contactors, and terminal blocks are sized for the rated US
(NEMA) current.

The IEG class I rating is the maximum current the power module can supply
continuously with no overload. Because an overload is not possible the class I
rated current is higher than the US rating. The IEG class I rating cannot be used
with base drives because the base drive fuses, contactors, and terminal blocks will
be overloaded.

The microprocessor calculates the current 12t value of the power section cyclically
to ensure that the thyristors are not damaged in overload operation.

33
Base Drive Catalog Numbers

US
1-QUAD TYPE 4-QUAD TYPE
RATING
(Catalog No.) (Catalog No.)
(Amps DC)
15 6RA7013-2FS22-0 6RA7013-2FV62-0
30 6RA7018-2FS22-0 6RA7018-2FV62-0
60 6RA7025-2FS22-0 6RA7025-2FV62-0
100 6RA7030-2FS22-0 6RA7030-2FV62-0
140 6RA7072-2FS22-0 6RA7072-2FV62-0
210 6RA7075-2FS22-0 6RA7075-2FV62-0
255 6RA7077-2FS22-0 6RA7077-2FV62-0
430 6RA7082-2FS22-0 6RA7082-2FV62-0
510 6RA7083-2FS22-0 6RA7083-2FV62-0
850 6RA7087-2FS22-0 6RA7087-2FV62-0
1180 6RA7091-2FS22-0 6RA7091-2FV62-0
1660 6RA7094-2FS22-0 6RA7094-2FV62-0

1000Hp DC DRIVE

The drive system will consist of one -1660 ADC/750 VDC six pulse drive cabinet.
The power converter, SCR (Silicon Controlled Rectifier) heat sink bridges and
High Horsepower command modules (6RA70) are manufactured by Siemens.
Siemens control and firing technology is applied for superior operation of SCR
gating, current, speed and monitoring of motor drive. Overload current limit is
150% for 1 min. every 10 min.

The following features are included:

• One - modified Nema 12, two door cabinet. Mild steel construction
measuring (90"x78"x30"). Paint is factory standard, ANSI 61 Gray.
• One - 2000 Amp. Molded Case Switches mounted w/ through the door
manual switch handle (pad lockable).
• One - 1660 ADC 1-Quadrant SCR bridge assembly.

34
• SCR AC line fusing.
• One - cabinet air cooling and filtration package.
• One - 85 ADC, single phase, Siemens field module and transformer.
• Customer supplied encoder feedback speed control as per customer
drawings.
• One - main motor blower circuit 20 HP @ 600V Max.
• Three digital meters for the following: Armature Amps, Armature Volts
and Field Amps. Meters are mounted in the Master drive cabinet door.
• Siemens door mounted programming and fault indication keypad.
• Door mounted Hand/Off/Auto selector switch.
• Copper pad bus areas for incoming and out going AC/DC power
connections.

OPTIONAL ISOLATION TRANSFORMER

(1) 1500 KVA with the following specifications:

• Primary Voltage 25 KV, 60 Hertz, 3 phase Delta, 1500 KVA


• Secondary Voltage 600/347 Wye, 1500 KVA
• Aluminum windings, 150 Deg. C rise, 220 Deg. C Insulation
• K-Factor 9
• Nema 1 enclosure, floor mount

3000Hp DC DRIVE

The drive system will consist of two - 2400 ADC / 750 VDC six pulse drive
cabinet sections. The power converter SCR (Silicon Controlled Rectifier) heat sink
bridges are manufactured by Joliet Technologies and are fitted with Siemens High
Horsepower command modules (6RA70). Siemens control and firing technology
is applied for superior operation of SCR gating, current, speed and monitoring of
motor drive. Each of the 2400 ADC sections work together by load sharing the
high current demand. The drives will be designated as Master / Slave. By
supplying each section with a single isolation transformer with two outputs Delta
& Wye, we can minimize the harmonic distortions caused by SCR type converter
drive systems. The overload current limit rating is 150% for 1 min. every 10 min.

The following features are included:

• Two - two door, modified Nema 12 cabinets, Mild steel construction


measuring (90"x78"x30"). Paint is factory standard, ANSI 61 Gray.

35
• Two - 2500 Amp. Molded Case Switches mounted w/ through the door
manual switch handle (pad lockable).
• Two - 2400 ADC 1-Quadrant SCR bridge assemblies.
• Two Sets - SCR AC line fusing.
• Two - cabinet air cooling and filtration packages.
• Two - Siemens High HP command modules.
• One - 85 ADC/single phase, Siemens field module and transformer.
• Customer supplied encoder feedback speed control as per customer
drawings.
• One main motor blower circuit 20 HP @ 600V Max.
• Three digital meters for the following: Armature Amps, Armature Volts
and Field Amps. Meters are mounted in the Master drive cabinet door.
• Siemens door mounted programming and fault indication keypad.
• Door mounted Hand/Off/Auto selector switch.
• Copper pad bus areas for incoming and out going AC/DC power
connections.

DCS 400
Digital DC Converter
20 to 1000A DC

Introducing the world's most competitive DC package

36
ABB has developed a user-friendly drive Technical Features
system package (DCS 400, DMI Motor)
to meet the demands of machine • Digital 6-pulse converter
builders. • 10 - 600 Hp (10 - 448 kW)
• 20 to 1000 A DC
Our aim is to offer the best combination • Input Voltage from 230 to 500
of reliable products at the most V, 50/60 Hz
affordable price, backed by on-time • Nonregenerative & regenerative
delivery, good partnership and fast drives available
response to inquiries. At the heart of the • IGBT - field supply for field
drive package is the DCS 400 - a new weakening is included
generation of DC drives specifically
designed to meet the ever-changing Supply Voltages
needs of machine builders.
Power and 230 - 500 VAC, 3-
Field: phase
"Total ease of use" was the foundation
of this drive's development. The result is Input 50 - 60 Hz
a drive that is: Frequency:
Converter Fan: 115/230 VAC, single-
• as easy to handle as an analog phase
drive yet incorporates all of the Control 115/230 VAC, single-
features of a digital drive. Power: phase
• easy to design into machine
Control I/O
equipment, with just the right
amount of features. Digital Inputs: Eight (8), 24 VDC
• easy to install and set-up, even by Digital Four (4), 24 VDC
those without special drives Outputs: One (1) relay
experience. Analog Inputs: Two (2), ±10 VDC, 12
bit
Small Design Analog Two (2), ±10 VDC, 12
Outputs: bit
The DCS 400's compact design brings
substantial space savings to machine
Power Spectrum, 2Q, Non-
builders, allowing them to integrate
Regenerative
more accessories within the same space.

Existing DC drives are easily Armature


• Field
replaced with the DCS 400. Module Current
Current kW HP
• At only 103.4 in (270 mm) wide, Type Range (A)
and with all the power cabling (A)
located at the base of the drive 20, 45, 65, 12 to 10 to
A1 0.1 to 6
rather than the side, two DCS 400 90, 125 73 75
units can be installed inside the A2 180, 230 0.3 to 104 to 100 to

37
same 233.4 in (600 mm) cabinet. 12 133 125
• The field supply, including the 315, 405, 0.3 to 183 to 175 to
fuse and choke, are integrated A3
500 14 290 300
into the DCS 400, further 610, 740, 0.3 to 354 to 350 to
contributing to its small size and A4
900 20 402 539
simplicity of design.
• No need for a field voltage Power Spectrum, 4Q, Regenerative
adaptation transformer to match
the line supply voltage with that Armature
of the motor. The DCS 400 uses Module Current Field
fewer components, leading to Current kW HP
Type Range
both smaller size and greater (A)
(A)
reliability. 25, 50, 75, 13 to 10 to
A1 0.1 to 6
100, 140 73 75
0.3 to 104 to 100 to
A2 200, 260
12 135 150
350, 450, 0.3 to 182 to 200 to
A3
550 14 290 300
680, 820, 0.3 to 354 to 400 to
A4
1000 20 448 600

The total integrated package for machine builders


Fieldbus DC Converters DC Motors Speed Feedback
Adapters DCS 400 6-pulse ABB's family of A variety of speed
Multiple serial converters offer DC motors offer a feedback devices
communication accurate torque and compact, modular can be used with
options allow speed control in design, combined PowerPack and are
integration with the low power with low vibration standard features of
higher level control range. Simplicity and noise levels as the DCS 400.
systems. of operation is a well as high output
hallmark of the and energy
drive. efficiency.

38
The user is guided through the An alternative to the control panel is
commissioning procedure by following ABB's PC-based program, Drive
simple steps that are outlined by the Window Light, used for guided on-line
alpha-numeric control panel. commissioning, including:

• Parameter setting
• Reference display and feedback
values
• Trending
• On-line help files

39
The easiest drive to install...

(b) Reduced Wiring

By fully integrating the field supply, ABB's engineers have been able to patent a
design with three wires in and four wires out, reducing wiring and requiring less
installation time.

Fast and Easy Installation

ABB's DCS 400 cuts costs and installation time by incorporating the following
features:

• A simple, step-by-step installation guide


• Bottom plate cable entry, providing rapid and easy access to power
terminals
• Easy to access I/O connection points via bottom cover plate
• The drive's ability to operate directly on any worldwide voltage from 230 -
500 V, 50/60 Hz main, 115 - 230 V aux.

40
The fastest drive to commission...

(c) Commissioning Wizard

The DCS 400 is the first digital drive which can be commissioned without special
knowledge of drives. More importantly, the commissioning and start-up time is
dramatically faster than that of other DC drives.

• The wizard uses either the drive's control panel or ABB's commissioning
tool, Drive Window Light, which is based on RS232 communications using
a standard plug (see illustration above).
• Once the motor and process data have been entered into the drive, the user
is guided through commissioning using the self-tuning functions for
armature current, speed, flux and field current.
• No additional documentation or hardware is needed to commission the
DCS 400.
• Application macros that require setting only a few user-selectable
parameters make the commissioning of specific applications easier
compared to the several hundred parameters that must be set with other DC
drives.

Module Height Depth Width


Type in (mm) in (mm) in (mm)
12-1/2 10-3/4
A1 8 (200)
(310) (270)
12-1/2 10-3/4 10-3/4
A2
(310) (270) (270)
15-3/4 12-1/2 10-3/4
A3
(400) (310) (270)
13-3/4 10-3/4
A4 23 (580)
(345) (270)

41
4.0 RECOMMENDATIONS
A new generation of variable speed drives:

The Hanover Messe saw the launch of the new generation of Emotron AB variable
speed drives, which have grown in terms of function but reduced in size, with a
new application focus

The Hannover Messe saw the launch of the new generation of Emotron AB
variable speed drives, which have grown in terms of function but reduced in size.
At the same time the company presented its new strategy of focusing on selected
applications. This allows cutting edge knowledge and products adapted to specific
needs.

The new Emotron FDU is developed for applications such as pumps, fans,
compressors and blowers, while Emotron VFX is adapted for dynamic
applications such as cranes, crushers and mixers.

Increased functionality in a smaller format.

The Emotron new variable speed drives, FDU and VFX in the 0.75-1,500 kW
output range, offer efficient, reliable and user-friendly control.

Among the new features are.

* An integrated shaft power monitor that detects deviations from normal operation
over the whole speed range.

This prevents unplanned downtime and allows preventive action before


energy is lost or equipment damaged.

* New compact I/O boards allow connection of up to four options, for example
communication, pump control and crane control.

Virtual connection of logic functions, comparators and timers means that more
options can be used.

Different logical functions can be combined without cables or external I/Os.

* Integrated temperature control offers more efficient motor protection and


extends equipment lifetime.

PTC and PT100 sensors can be connected for motor protection and process
feedback without transmitters.

42
Encoder can be connected for more accurate speed control in dynamic
applications.

* Operating parameters are set in selectable process units, which make monitoring
simpler and safer.

The control panel is removable and can easily be moved between variable speed
drives to copy settings.

* The installation is simple and cost effective due to IP54 enclosure and extremely
compact format even for high outputs.

Liquid cooling is available as an option, which saves space and energy because air
conditioning is not required.

43
5.0 CONCLUSIONS
DC drives consist of an SCR (Silicon
Controlled Rectifier) bridge, which
converts incoming three or single-
phase AC volts to DC volts. During
this conversion process DC drives then
can regulate speed, torque, voltage and
current conditions of the DC motor.
This is ideal for industrial processes
such as tube mills, extruders, mixers,
paper machines and various other
controlled applications. Joliet
Technologies can provide several DC
Drives from different reputable
manufactures. Packages can vary from
Onsite Retrofits to custom multi drive
cabinets.

44
Engineering and Integration

Solutions that may be helpful consist of:

• Sizing a drive to a target horsepower, current and voltage required.


• Power and harmonics issues can be addressed and corrected through the use
of isolation transformers, reactors and filter packages.
• Customizing control and analog circuitry to be integrated in with existing
engineered specifications.
• Operator consoles / Door mounted pilot and metering devices
• MCC and Switchgear installation type custom packaging for growing
demands of the industry.
• Peer to Peer and Master/Slave drive configurations for Follower and High
Horsepower applications.
• Engineered cabinet cooling system for any environment. Today's drives are
more compact and can be placed in smaller enclosures only if the correct
cooling is applied.
• Communication Systems for advanced Modbus, Profibus and Data
HighWay linking multiple devices such as power management and
HMI/PLC systems.

45
4.0 REFERENCES

1. www.electricmotors.machinedesign.com

2. www.adcmotors.com

3. www.dcmotorsinc.com

4. www.grainger.com/production/info/dc-motors.htm

5. www.orientalmotor.com/products/ac-dc-speed-motors/index.htm

6. www.processingtalk.com/indexes/categorybrowsedo.html

7. www.axiomatic.com/

46

Anda mungkin juga menyukai