HV Circuit Breakers
customers
st Siemens Fills The Order

„ Siemens has been a


leader in SF6 circuit
breaker technology for
over 40 years.

„ Breaker products:
− Dead tank breakers
− Live tank breakers
− Vacuum breakers
− GIS
− Circuit switchers
− Reclosers
PTD H 3 World Headquarters in Berlin
− MV and HV Arrester
Products
customers
st Over 30 Years Experience in
Jackson
„ 1973 – Plant opened as Allis Chalmers (Moved from Boston)
− Began production of SDO, BZO, GHO, TDO Breakers
„ 1978 – Became Siemens Allis
„ 1982 – Replace GHO with 3AT
„ 1985 – Purchased SP Breaker from Westinghouse to
replace TDO
− Began Voltage Regulator Production
„ 1992 - Began SPS
„ 1994 – Began Mfg. of TCP Design to replace BZO
− Began Mfg. of SDV to replace SDO
„ 1995 –Began Candlestick type Circuit Switcher production (CPV)
„ 1996 – Replaced TCP Design with SPS1-145
„ 1998 – Replaced SP / SPS / SPS1 with new SPS2 design
„ 1999 - Replaced TCP-245 with SPS2-245
„ 2000 – Replaced CPV with new CPV2 Design
„ Present – SPS2, CPV2, Single and Three Phase Voltage Regulators,
Reclosers, Surge Arrestors
customers World Wide Dead-Tank Breaker
st Center Of Competency

„ SPT&D’s Jackson, Mississippi


operation

„ Over 30 years of power circuit


breaker development,
manufacturing and service

„ State-of the-art circuit breaker


manufacturing

„ Four dedicated assembly lines


„ 2 – SPS2 Circuit Breakers : 15.5 – 245 kV
„ 1 – CPV2 Circuit Switchers : 72.5 – 245 kV
„ 1 – EHV Live Tanks : up to 800 kV
„ 1 – Voltage Regulating Transformers

„ Continuous improvement through


Kaizen techniques
customers
st Siemens Fills The Order

„ World leader in development and


manufacturing of transmission &
distribution equipment

„ ISO 9001:2000 registered quality


system

„ Tested to ANSI and IEC standards in


the world’s largest, privately owned,
electrical laboratory

„ Over 30,000 dead and live tank sold


worldwide – 10,000 SPS-2’s from USA
customers
st 2005 Product Quality Innovation Award

„ In a survey conducted by Frost & Sullivan, end users, developers


and resellers considered Siemens PTD breakers as the highest
quality breaker in the market in the 72 kV to 800 kV voltage
range.

„ Market participants familiar with a range of high voltage breaker


products cited Siemens PTD breakers, more than any other, as
superior in terms of both product design and workmanship.
customers
st SPS2 / CPV2 “The Right Choice”

ƒ Design Commonality

ƒ Increased Operating Life

ƒ Quick and Easy Installation

ƒ Minimal Maintenance

ƒ No Field Adjustments

ƒ Lower Cost of Ownership

ƒ Retrofitable Design

ƒ Added Value
customers
st SPS2 Circuit Breakers
„ Available 15kV – 245kV
„ Proven, global components
− FA2 and FA4 Mechanisms
− 3AP arc-assist interrupter

„ Seismically qualified to IEEE


693 for ‘ High ‘ performance

„ Rupture Disks for each


interrupter

„ Copper / Stainless Steel Gas


Manifolds
„ Porcelain / Composite
Bushings

„ Direct replacement for oil


circuit breakers (end control
cabinets)
customers
st CPV2 Circuit Switcher
„ Low cost protection device
„ Proven, global components
− FA2 and FA4 Mechanisms
− 3AP arc-assist interrupter
„ Designed & Tested for capacitor bank
switching
„ Continuous current rating 1200 – 3150
amps.
„ Interrupting rating up to 40 kA
„ 3 cycle operation
„ Wide variety of phase spacing and
heights
„ Virtually no maintenance
customers
st CPV2 Circuit Switcher

„ Meets the requirements of ANSI C37


„ Seismically qualified
„ Leak rate <1% per year

„ 6000 mechanical operations


„ 3000 operations at 6kA
„ 18 full faults at 40kA
„ Ease of installation
„ No field adjustments
„ Integral accessories:
− visible disconnect switch
− Hook stick operated bypass switch
customers
st SPS2 Performance Features
„ Up to 63kA without
capacitors (145kV and below)

„ Up to 68kA at 245kV

„ Up to 4000 Amp Continuous


Current

„ 10,000 mechanical operations

„ 3,000 operations at 6kA

„ 18 full faults at 40kA

„ Leak rate <1% per year

„ Up to -30 º to 55 º C without
tank heaters
customers Siemens Experience : The 3AP
st
interrupter

„ Over 90,000 pole units installed


throughout the world

„ Superior performance
− 18 full faults
− 6000 operations at 6kA
− 10,000 mechanical operations

„ No solid insulation across


contacts

„ Increased dielectric strength


across interrupters
customers
st FA2/4 Mechanism

„ Proven performance in the field

„ 30,000 installations worldwide

„ Tested to 20,000 operations or 10,000


Close-Open operations

„ Used on Siemens live tank and dead


tank breakers, GIS and circuit
switchers
customers
st SPS2 - Options

ƒ Up to 18 current transformers
ƒ Metering / Relaying accuracy CT’s
ƒ Extra creepage bushings
ƒ Composite bushings
ƒ High seismic withstand
ƒ External pull to trip handle
ƒ Relays for reclosing or non-reclosing applications
customers
st New / Future Offerings

− Increase kA Rating with higher low ambient

− Solon 2TC Density Switch

− Synchronous Close

− 550kV Dead Tank

− Polymer Bushing for 230kV, 3000Amp

− Low Temp. Ratings to -50°C


customers
st
Controlled Switching

SPS2X_US PSD Controller

Ungrounded Capacitor bank


customers
st Synchrounous Close - Main functions

„Output of controlled (synchronous) switching commands


to the closing coil of the circuit breaker

„Reduction of the inrush currents


−Decreasing of the mechanical and electro-magnetic
stresses of the operational equipment -> increasing
of their life time

„Minimising of overvoltages
−Decreasing of the dielectric stress -> lower ageing
−Substitution of closing resistors -> higher reliability
customers
st
Circuit Breaker Type SPS2X_US

„One Mechanism Available on:


„One gear box located „SPS2 72.5/40 US
between A- and B- phase „SPS2 145/40 US
operating linkage „SPS2 145/63 US
„Two phases close at the „SPS2 245/63 US
same time, one phase
mechanically staggered
customers
st PSD Functions

Control of the Closing Instant

„ PSD Controller receive a closing command related to Voltage Zero


Crossing
„ PSD Controller calculate delay time depending on:
− Arcing Time
− Mechanical closing Time
− Control Voltage
− Ambient temperature
„ Adaptive Mode
− PSD Controller calculate the standardized mechanical operating time of the last
3 switching operations , using weighting factors for each 3 previous operations
for the next switching operation to be configured automatically.
− The basis for the functioning of the adaptive control is the reference contacts
located on each phase operating lever. The reference contact signal indicate a
change to the CB switching position.
„ Operate in case of sensor failure
− If not all conditions for successful control of the switching instant are met, the
PSD can be configured to: Not forward a command or Operate in any case.
customers
st

New 550 kV Design


customers Platform 550 kV Circuit-Breaker
st GIS/HIS/Dead-Tank
Common Circuit-Breaker Design
for: GIS/HIS/Dead-Tank
customers Platform 550 kV Circuit-Breaker 3AP2/3 Dead-Tank
st
5600
(220,5)

Porcelain
bushing

8240
(324,4)
Current
transformer

Circuit-breaker
3570
(140,5)
Spring
operator
customers
st Platform 550 kV Circuit-Breaker 3AP2/3 Dead-Tank

5750
(226,4)

Composite
bushing

8570
Current (337)
transformer

Circuit-breaker
3540
(139,4)
Spring
operator
customers Platform 550 kV Circuit-Breaker
st 3AP2/3 Dead-Tank with Closing Resistors

Capacitor Interrupter unit Rupture disc

Closing resistor
Filter material
customers
st

Surge Arresters
Station and Distribution
customers Surge Arresters
Introduction and General Information
st
ƒ Experience of more than...
ƒ 75 years with surge protective devices
ƒ 25 years with metal-oxide surge arresters
ƒ 15 years with polymer (silicone) insulated high-voltage arresters

ƒ Porcelain, polymer (silicone) and GIS arresters up to 800 kV

ƒ Special applications for ...


ƒ SC, SVC and HVDC
ƒ seismic, heavy wind loads or heavy pollution conditions
ƒ customer specific designs, e.g. mounting configuration, etc.
ƒ MV such as plug-in arresters, traction vehicles,
generator protection, limiters

ƒ Developing, manufacturing and testing in accordance with


international standards as IEC and ANSI

ƒ Certified QA accreditation to ISO 9001


customers High Voltage Arresters up to 800 kV
Series 3EL, 3EP, 3EQ, 3ES
st

Monitoring
Devices
3EX5 060/62 3EX6 040 3EX5 030 3EX5 050

3EL2 3EP4 3EP2 3EP3 3EQ1 3EQ4 3EQ3 3ES2 3ES5 3ES7,
3ES9

Silicone Porcelain Silicone GIS


(cage design) (tube design)
customers Low- and Medium Voltage Arresters
st Series 3EA, 3EB, 3EC, 3EE, 3EF, 3EH, 3EK

3EA1 3EF1...5 3EE2 3EK7 3EC3 3EB1 3EB2

Low voltage and


motor/generator Distribution Railway
protection
customers Polymer Housed Surge Arresters for High Voltage
st Comparison of Design Principles

„Tube Design“ „Cage Design“ „Wrapped Design“


SIEMENS „3EQ“ SIEMENS „3EL“ Competition
customers Silicone Housed Surge Arresters for High Voltage
st Type 3EL with directly moulded LSR Housing

Silicone rubber housing


directly moulded onto the
active part

Cage of 8 FRP rods


as reinforcement structure

Column of MO resistors
totally surrounded
by silicone

„Cage Design“
customers Silicone Housed Surge Arresters for High Voltage
st Type 3EL – Design Principle: „Cage Design“
customers Silicone Housed Surge Arresters for High Voltage
st 3EL - Comparison of Cantilever Strength

3EL arresters are up to 2 – 3 times stronger


than other polymer designs!

Rated Cantilever Strength ( inch-lbs)

Siemens Ohio Brass ABB

3EL2 PVN * PEXLIM

WORKING 24,782 10,000 – 3,000 7,000 – 22,125

ULTIMATE 35,400 20,000 – 5,000 11,500 – 35,400

* JOINTS BETWEEN THE RUBBERS – POOR MECHANICALS -- HIGH DEFLECTION


customers Silicone Housed Surge Arresters for High Voltage
st Type 3EL - Specification

Duty Cycle Rating Ur 192 kV


MCOV Uc 152 kV
Nominal discharge current In 10 kA
Energy absorption capability 10 kJ/kV-MCOV
Pressure Relief Rating 65 kA
TOV - 1 sec, no prior duty 1.475 x MCOV
“Working” Cantilever Strength 24782 inch-lbs
Creepage Distance 301 inches
Standard ANSI / IEEE C62.11
customers Silicone Housed Surge Arresters for High Voltage
Series 3EQ - „The Robust One“
st
3EQ3
up to Um = 800 kV

3EQ4
up to Um = 550 kV

3EQ1
up to Um = 362 kV

„Tube Design“
customers Silicone Housed Surge Arresters for High Voltage
st 3EQ – Design Principle: “Tube design”

Pressure relief diaphragm Silicone rubber sheds


Material: Stainless steel Material: RTV-silicone
Thickness: 3EQ1: 0,1 mm directly moulded onto
3EQ3/4: 0,2 mm FRP tube
Opening pressure: approx. 1 bar Housing filled with nitrogen
to avoid oxygen
(causing moisture)

MO column (ZnO resistors)

Support for MO column


Material: FRP rods

Pressure relief vent FRP tube (Fiber glass


Material: Aluminium reinforced plastic) for out-
standing mechanical strength
customers Silicone Housed Surge Arresters for High Voltage
st 3EQ - Silicone Bonding to Flanges and FRP-tube
The silicone rubber is directly moulded onto
the FRP-tube and the aluminium flanges.

2
3

1 ... Aluminium flanges


2 ... Silicone rubber
3 ... FRP-tube
customers Silicone Housed Surge Arresters for High Voltage
st 3EQ - Comparison of Cantilever Strength
3EQ arresters with tube design are
more than 6- 8 times stronger
than other polymer designs!

Rated Cantilever Strength ( inch-lbs)

Siemens Ohio Brass ABB

3EQ PVN * PEXLIM

WORKING 37,000 – N/A 22,125


260,000

ULTIMATE 53,000 – N/A 35,400


370,000

* NO HIGH STRENGTH POLYMER DESIGN AVAILABLE


customers Silicone Housed Surge Arresters for High Voltage
st Comparison: Short Circuit and Overload Performance
3EQ (tube design) 3EP Cage Design

Before the test Successful Arc burns through silicone

3EQ 3EP Cage Design

After the test Successful No mechanical structure left


customers Silicone Housed Surge Arresters for High Voltage
3EQ in a Seismic Shake Table Test
st
Test conditions in accordance with IEEE 693:
• time history test
• 1·g ground acceleration
• max. 50% of specified mechanical stress

3EQ4 442-5PN5 3EQ4 306-3PN4


(≈ Um = 550 kV) (≈ Um = 420 kV)

3EQ4 234-3PN4 3EQ1 156-2PN3


(≈ Um = 300 kV) (≈ Um = 170 kV)
customers Benefits of SIEMENS Surge Arrester Designs
st Minimizing number of segments per arrester

SIEMENS Competition
Example left side (SIEMENS):
3EQ with 2 segments for up to 550 kV system voltage

Example right side (competition):


4 units per stack for the same voltage level or
arrester with additional insulators for stabilisation or
multiple segment arrester built up with MV arresters

Minimizing the number of segments


per arrester means:

ƒ more stability
= higher mechanical cantilever strength
ƒ less segments to mount
= less installation time
--> less installation costs
ƒ less danger of moisture ingress between flanges
ƒ better voltage distribution

all in all:
The lower the number of segments per arrester stack
the better the electrical and mechanical performance is.
customers Arrester Monitoring Devices
st Types 3EX6 040, 3EX5 030, 3EX5 050, 3EX5 060/62

Control Spark Gap Surge Counter Surge Counter with Arrester monitor with
leakage current meter remote indication
3EX6 040 3EX5 030
3EX5 050 3EX5 060/062
customers
st

Voltage Regulators
customers
st

JFR (Single Phase)

2.5 kV to 19.9 kV,


38.1 kVA to 889 kVA,
50/60 Hz
Applications

+ / - 10 % Regulation
in 32 Steps

Equipped with
Controller (MJ-XL)
customers
st Voltage Regulator - Applications

„Pole Mounted
„Platform Mounted
„Substation
customers
st Three Phase Regulators

SFR - 4330 V - 34500 V


500 kVA – 4000 kVA

Smaller foot print compared


to three single phase units
customers
st
Three Phase (SFR) Three Phase (SFR-X)

Tap changer in separate compartment


customers
st Modern Control Panel
customers
st What a Control Panel Does ?
It senses parameters like Voltage, Current, Power Flow direction and
provides commands to the tap changer of VR. Additionally, the modern
microprocessor based controllers are providing efficient communication,
Energy Management and diagnostics capabilities to the power companies.

• Functionality

• Advanced Metering
• Superior Data Logging
• Intuitive User Interface
• Powerful Communications
• Continuing Enhancements
customers
st Advanced Metering
• Instantaneous Voltages, Current, & Power
• Demand Voltages, Current, & Power
• Minimum/Maximum Time Stamps to the second
• Energy Readings
• Support for 3-Phase Calculations
• Harmonics Displays to the 31st harmonic
customers
st Superior Event Logging
• Multiple “Event Types”
• Tap Change, Tap at Neutral, Tap
raise/lower to NN position, VLC/VRC
active, Power Flow reversal,
Configuration change,

• Precise time stamping

• High capacity (200 events)

• Critical data storage

• Non-volatile data storage


customers
st
Multiple Alerting
• Metering

• Tap Tracking

• Remote Control

• Controller Error
customers
st Intuitive User Interface
• Menu-Driven

• Easy - to -read Displays

• Simple Menu Navigation

• Single Keystroke for Frequently


accessed Functions
customers
st Data Port Communications
• Use Industry-accepted Protocol

• Retrieve Data & Status

• Configure the panel

• Select Parity & Address

• Connect with off-the-shelf Cables

• Use off-the-shelf Modems


customers
st Control Panel - Communication Modules

Fiber Optic Communications Port

RS232/RS485 Communications Port

Radio Integration via wireless


communication (Cell Phone)
customers
st Cost Saving – An example
„ Communication Module can provide

− Reduced frequency of site visits


− Data available instantaneously – Preventive
maintenance instead of emergency work
− Use software capability to safely overload VRs
up to 60 %
− Use available data to planning purposes
− Check power quality while sitting in your office
− Control Peak Loads (TO AVOID PENALTIES)
and Reduce Voltage
customers
st Firmware upgrades
Use of a specially developed “Flash Loader”
customers
st Questions?