e-mail : Kreest3@gmail.com1)
ABSTRACT
Flow Transformer Is a transformer used to take input data input in the form of current by
replacing windings in primary or secondary windings. This transformer is commonly used to
measure the indirect charge that flows to the customer and then limit it. In addition, the
amount of current can also be taken as input data input network security equipment. The
measurement current transformer for metering has high accuracy in the work area (rated area)
5% - 120% the nominal current depends on the class and the relatively low saturation level
compared to the current transformer for protection. Current transformer with a specification
ratio of 200 / 5A, class 0.5 and loaded with 80A then the maximum error ratio is ± 1,5% and
a phase shift of ± 90/60 degrees. The current transformer on the microline machine is
saturated when the current on the secondary side is > 20.62AThe minimum value of
insulation resistance in current transformers is 1Mohm per kV
Key Word : Current transformers, mettring
ABSTRAK
Transformator Arus Adalah trafo yang digunakan untuk mengambil input data masukan
berupa besaran arus dengan cara perbandingan belitan pada belitan primer atau sekunder.
Trafo ini biasa digunakan untuk pengukuran tak langsung beban arus yang mengalir ke
pelanggan kemudian membatasinya. Selain itu bisa juga besaran arusnya diambil sebagai
input data masukan peralatan pengaman jaringan. Trafo arus pengukuran untuk metering
memiliki ketelitian tinggi pada daerah kerja (daerah pengenalnya) 5% - 120% arus
nominalnya tergantung dari kelasnya dan tingkat kejenuhan yang relatif rendah dibandingkan
trafo arus untuk proteksi. Trafo arus dengan spesifikasi ratio 200/5A, klas 0,5 dan dibebani
sebesar 80A maka kesalahan maksimum rationya adalah ±1,5% dan pergeseran fasa sebesar
±90/60 derajat. Transformator arus pada mesin microline mengalami kejenuhan ketika arus
pada sisi sekunder sebesar >20,62A. Nilai minimum tahanan isolasi pada transformator arus
adalah sebesar 1Mohm per kV.
Kata kunci : Transformator arus, metering
2
3. METODOLOGI PENELITIAN
4
Grounding (pentanahan)
In Service Measurement
In Service Measurement adalah kegiatan
pengukuran / pengujian yang dilakukan
pada saat peralatan sedang dalam keadaan
bertegangan / beroperasi.
Shutdown testing/Measurement
Shutdown testing/measurement adalah
pekerjaan pengujian yang dilakukan pada
saat peralatan dalam keadaan padam.
Pekerjaan ini dilakukan pada saat Gambar 3. 1 flowchart penyusunan tugas
pemeliharaan rutin maupun pada saat akhir
investigasi ketidaknormalan.
Shutdown Treatment
Is = 5.025 x Is (A)
Dengan demikian besarnya arus 8
sekunder yang mengalir adalah 5.025A 6
saat arus pada sisi primer sebesar 200A
4
Perhitungan kesalahan rasio 2
Diketahui : 0
2 4 6 8 10 12 14
Kn = 200/5A
Grafik 4.1 kurva Faktor Batas ketelitian CT
Ip (act) = 205A
Tegangan pada sisi sekunder CT adalah:
Is (act) = 5.05A
Vs= IF . (RCT + Rrelai +Rkawat)
Penyelesaian : volt.......................................................(4.1)
x% =
(( . ) )
. 100 Vs = 1453 x . (0,26 +
0,02 + 0,15)
(( . . ) )
x% = . 100 Vs = 15,62v
x% = (202 – 205) . 0.48 Tegangan knee CT adalah :
x% = 1.44 = + .
volt.........................................................(4.2)
6
Vk = + 0,26.5 5 pembersihan
Kondisi Lakukan
Vk = 16,5 volt 2 core Retak penggantian
housing CT
Kejenuhan CT metering tidak melebihi 5x Kondisi Korosi /
In. Maka, structure kendor / Cat ulang /
3
penyangg bengkon perbaiki
FS = Vk : Vd a g
= 16,5 : 4 -
= 4,125 Sambungkan
kembali
Kejenuhan CT = 4,125 x 5A kawat
pentanahan
= 20,625A sehingga
pentanahan
Dari hasil perhitungan didapat nilai
tersambung
kejenuhan sebesar 4,125 x 5A = 20,625A.
dengan mesh
Jika melebihi 20.625A maka CT akan
grounding GI
mulai jenuh
-
Hasil pemeliharaan dan rekomendasi Kencangkan
kembali
In Service Inspection Kondisi Lepas / kawat
4 Groundin kendor / pentanahan
g rantas sehingga
Tabel 4. 1 In Service Inspection pentanahan
tersambung
N Item Hasil dengan mesh
Rekomendasi
o Inspeksi Inspeksi grounding GI
Lakukan -
penggantian Sambungkan
CT bila ganti kawat
pecah tdk pentanahan
bisa sehingga
ditoleransi. pentanahan
(retak tersambung
melingkar) dengan mesh
Lapisi grounding GI
Flek / dengan
Kondisi Shutdown testing/measurement
retak / insulator
1 fisik
pecah / varnish untuk Tahanan Isolasi
isolator
kotor kondisi
isolator flek standar : VDE Batasan yang digunakan :
atau dengan 1Mohm per 1kV (phasa-phasa)
gunakan Tabel 4. 2 Evaluasi dan Rekomendasi
ceramic pengujian tahanan isolasi
sealer/cerami
c rebound N Keterang Rekomend
Hasil uji
untuk kondisi o an asi
pecah kecil 1
>1MOhm/1
Good
Lakukan kV
7
<1Mohm/1k
Lakukan 5. PENUTUP
2 Poor pengujian
V Kesimpulan
lebih lanjut
Dari hasil penelitian pemeliharaan
transformator arus pada mesin MicroLine
di PT. Nayati Indonesia dapat disimpulkan
No Low Nilai Keterangan sebagai berikut:
Voltage Tahanan
Phase Isolasi 1. Perhitungan kesalahan ratio adalah
to 1.44% maka nilai yang terukur adalah
Ground sebesar 2,02A
1 R–g 1,5 Normal 2. Untuk nilai error sebesar 0,5%, maka
M.ohm hasil pengukuran arus pada terminal CT
sekunder tidak melebihi 0,5%
2 S–g 1,5 Normal 3. Trafo arus dengan spesifikasi ratio
M.ohm 200/5A, klas 0,5 dan dibebani sebesar
3 T–g 1,5 Normal 80A (20%) maka kesalahan maksimum
M.ohm ratio yang diijinkan adalah ±1,5% dan
pergeseran fasa sebesar ±45/60 derajat.
Hasil pengukuran tahanan isolasi sisi HV Dari hasil pengujian didapatkan
kesalahan ratio sebesar 1,44% nilai
tersebut masih masuk dalam batas
High
Nilai standart.
voltage
No Tahanan Keterangan 4. Transformator Arus pada mesin
Phase to
isolasi microline akan mengalami kejenuhan
Ground
saat arus yang mengalir disisi
sekunder > 20,625A
11,04
1 U–g Normal 5. Pada pengujian tahanan isolasi sisi HV
M.ohm
kondisi tidak short nilai tahanan
11,03 terukur sebesar 10,03 M.ohm. Nilai
2 V–g Normal tersebut menunjukan tidak adanya
M.ohm
kerusakan pada tahanan isolasi sisi HV
11,02 6. Pada pengujian tahanan isolasi sisi
3 W–g Normal LV kondisi tidak short nilai tahanan
M.ohm
terukur sebesar 1 M.ohm. Nilai
tersebut menunjukan tidak adanya
Hasil pengukutan tahanan isolasi sisi LV kerusakan pada tahanan isolasi sisi LV
kondisi tidak short Saran
Dalam bab ini penulis akan
memberikan saran yang berhubungan dengan
Hasil Pengujian pentanahan pelaksanaan kerja praktek maupun penulisan
laporan. Adapun saran – saran tersebut
High diantaranya :
No Voltage Hasil 1. Diperlukan jadwal rutin untuk
Keterangan
to Pengujian pembersihan trafo secara fisik
Ground 2. Pengecekan sensor pada box terminal
1 U–g 0,14 Ohm Normal harus diperhatikan demi keselamatan.
2 V–g 0,17 Ohm Normal
3 W–g 0,17 Ohm Normal
8