Anda di halaman 1dari 7

A) Connect to the Node B

Shutdown the node.

AP Command:
prcboot -s

B) Connect to NODE A

1)
sc config Clussvc start= Disabled
sc config ACS_PRC_ClusterControl start= Disabled

2 )
Set BIOS "Cluster Support" to Disabled (Off).

raidutil +cluster off

3)
Reboot the node ( Node A)

Do not use prcboot. The normal "prcboot" command sets the "Cluster Server" start
up type to automatic.

There may be no response from the terminal until the AP finishes rebooting after
the shutdown command is entered. This will take several minutes.

shutdown /f /r /t 0
3) Delete the RAID
Delete RAID d0b0t0d0:
C:\> raidutil -D d0b0t0d0
d0b0t0d0
Delete RAID d0b0t1d0:
C:\> raidutil -D d0b0t1d0
d0b0t1d0

Delete RAID d0b0t2d0:


C:\> raidutil -D d0b0t2d0
d0b0t2d0

4) Check that the RAID has been deleted. ( see the below note if it faied to de
lete the RAID)

raidutil -D d0b0t0d0
raidutil -D d0b0t1d0
raidutil -D d0b0t2d0
raidutil -l 1 -g d0b0t0d0,d0b1t0d0
raidutil -l 1 -g d0b0t1d0,d0b1t1d0
raidutil -l 1 -g d0b0t2d0,d0b1t2d0
raidutil -a stop d0
raidutil -L logical

Expected Printout:
Failure:Can't find component by address
5) Re-create the RAID.
If it is not possible to re-create the RAID then follow the note "Disconnect SCS
I cables" and continue with this procedure. This will
leave the RAID deleted and allow the AP to run as a single node. The faulty node
should be left shutdown as it will not be able to become active.
The RAID must be re-created when the faulty node is replaced using the
note "RAID re-create during node change" below.

Re-create RAID d0b0t0d0:


C:\> raidutil -l 1 -g d0b0t0d0,d0b1t0d0
Created: RAID 1

Re-create RAID d0b0t1d0:


C:\> raidutil -l 1 -g d0b0t1d0,d0b1t1d0
Created: RAID 1

Re-create RAID d0b0t2d0:


C:\> raidutil -l 1 -g d0b0t2d0,d0b1t2d0
Created: RAID 1

Re-create RAID d0b0t0d0 with size 17432MB:


C:\> raidutil -l 1 -g d0b0t0d0,d0b1t0d0 -i -s 17522
Created: RAID 1

Re-create RAID d0b0t1d0 with size 17432MB:


C:\> raidutil -l 1 -g d0b0t1d0,d0b1t1d0 -i -s 17522
Created: RAID 1

Re-create RAID d0b0t2d0 with size 17432MB:


C:\> raidutil -l 1 -g d0b0t2d0,d0b1t2d0 -i -s 17432
Created: RAID 1

6 ) This step is a precaution in case the wrong node has been chosen as the sour
ce by mistake.
Stop the RAID rebuild.

AP Command:
raidutil -a stop d0

Check that the RAID has been re-created.

If the RAID has not been re-created then contact the next level of support.

AP Command:
raidutil -L logical
Example:
C:\> raidutil -L logical
Address Type Manufacturer/Model Capacity Status
------------------------------------------------------------------------
---
d0b0t0d0 RAID 1 (Mirrored) DPT RAID-1 17522MB
Reconstruct 0%
d0b0t1d0 RAID 1 (Mirrored) DPT RAID-1 17522MB
Reconstruct/Pending
d0b0t2d0 RAID 1 (Mirrored) DPT RAID-1 17522MB
Reconstruct/Pending

7) Set BIOS "Cluster Support" to Enabled (On).

AP Command:
raidutil +cluster on

8)
Windows 2003 Command:
sc config ClusSvc start= Auto
sc config ACS_PRC_ClusterControl start= Auto sc config DisableInactiveUserAccoun
tsService start= Auto

9)

Reboot the node.

AP Command:
prcboot -f

10)
Check the status of the RAIDs.

The re-created RAIDs should have the status Reconstruct or Reconstruct/Pending.


AP Command:
raidutil -L logical

Wait for all resources to come online.

11 ) Reboot the shutdown node.

Note: This step should not be performed if the faulty node should be left shutdo
wn or if RAID was not re-created.

AP Command:
fcc_reset other

Wait for all resources to come online.

12) Make sure the RAID rebuild is set to fast.

AP Command:
raidutil -r fast d0

Example:
C:\> raidutil -r fast d0
Address Type Rate
------------------------------------------------------------------------
---
d0b0t7d0 HBA 9.0s (fast)
d0b0t2d0 RAID 1 (Mirrored) 9.0s (fast)
d0b0t0d0 RAID 1 (Mirrored) 9.0s (fast)
d0b0t1d0 RAID 1 (Mirrored) 9.0s (fast)

13) Rebuild the re-created RAIDs.


AP Command:
raidutil -a rebuild d0b0t<#>d0

Examples:
Rebuild RAID d0b0t0d0:
C:\> raidutil -a rebuild d0b0t0d0
d0b0t0d0

Rebuild RAID d0b0t1d0:


C:\> raidutil -a rebuild d0b0t1d0
d0b0t1d0

Rebuild RAID d0b0t2d0:


C:\> raidutil -a rebuild d0b0t2d0
d0b0t2d0

Note: Additional steps to delete the RAID.

This note contains additional steps for step "Delete the RAID" in the
procecure above.

Disconnect the SCSI cables.

Remove the upper (top) SCSI cable from the good node.
Remove the lower (bottom) SCSI cable from the good node.
Remove the upper (top) SCSI cable from the faulty node.
Remove the lower (bottom) SCSI cable from the faulty node.

Delete the RAID.


Reconnect the SCSI cables.
Connect the upper (top) SCSI cable from the faulty node.
Connect the lower (bottom) SCSI cable from the faulty node.
Connect the upper (top) SCSI cable from the good node.
Connect the lower (bottom) SCSI cable from the good node.

Check that The six SCSI disks are correct and available.

Please note Ericsson is awaiting your inputs to resolve the CSR No.1664639 'RAID
missing'