ELECTRICAL

Principle

WKL-1/ BAKHEET AL MAMARI

1
F.M.F
FOR TRAINING PURPOSE ONLY

AIM

ELECTRICAL PRINCIPLE is addressed to all the people dealing/working with


electrical equipments, for rating and engineering officers, it is a practical guide
to electrical theory for any one who needs to learn or improve in his
understanding of electrical principles. The manual/book incorporates the basic
theories and techniques of what conceits good and competent electrical
workings.
Divided into sections the manual/book deals with electrical theory, principles,
and examples, in short, is covers every aspect of present day electrical
principles. Every section offers readers, safety, theory, diagrams, and
directions of appeal and dependence of simplicity.
A careful study of ELECTRICAL PRINCIPLE should enable you to understand
theories, behind electricity. It will be excellent guide book in skills of all
electrical aspect that make positive difference in your life.

2
F.M.F
FOR TRAINING PURPOSE ONLY
CHAPTER (1)

1-1 Health and safety at work

It is the duty of each individual at work to ensure his own safety and
safety of others. Dangerous situations should be brought to the attention of an
Officer or Senior Rating to take action to remove/reduce the hazards. In
particular the following safety rules should be observed:-
1. Workshop machinery is dangerous. Only authorized personnel are to
use workshop machines. Do not temper with any machine or appliance
especially (electrical).
2. Goggles are to be worn when using grinding machines, lathes, saws
and battery work.
3. Do not stand beneath anything being lifted.
4. Do not look at welding taking place without wearing welding
goggles/shields.
5. Do not remove safety guards from machines.
6. Do not assume the power supply is (Turned off) from any electrical
appliances, check it.
7. Lifting appliances and overhead cranes are only to be operated by the
authorized personnel.
8. If a fire extinguisher is used do not put it back in its stowage until it is
recharged.
9. Protective or safety clothing is to be worn and correct procedures
followed when working with battery acids or chemical agents.
10. Heavy-duty boots, hard hats and ear defenders are to be worn in
designated areas.
11. Correct handling procedures must be observed during switching
ON/OFF equipment.
12. When moving heavy items or equipment proper slinging must be
provided. If in doubt, consult a qualified slinger or Boson especially
when working aloft.
13. Beware of overhead cranes when in operation.

3
F.M.F
FOR TRAINING PURPOSE ONLY
14. Access on to the ship lift restricted to personnel who operating or
concerned with a vessel on the lift.

Action in Event of Electric Shock:-

When a person is found in a collapsed condition and it is suspected that he


or she has electric shock, the following actions/precautions must be
taken:-
a) Remove power immediately.
b) Remove casualty as quick as possible catching from his/her clothes.
c) Check his breathing, if not, and then start artificial respiration.
d) If pulse not present, start external heart massage giving alternately, five
heart compressions one lungs inflation.
e) Continue treatment until successful or taken over by expert medical
person.
f) Avoid further injury to the casualty.

Working on LIVE AND DEAD equipments

Always keep in mind that 30 Volts dc and 21 Volts ac can be dangerous.


So live terminal should not be touched. It is frequently assumed 24 Volts
dc is safe. However, the 24 Volts coming from TRU may faulty in the line,
so 440 Volts can cause short circuit due to fault.
So, unless the voltage has been personally measured with respect to earth
and found to be less than 30 Volts dc or 21 Volts ac, especially if your skin
is not dry.

4
F.M.F
FOR TRAINING PURPOSE ONLY
Dead Equipment
When working on dead equipment, make sure fuses remove first, and then
start work. Where large capacitors are fitted to equipment on which work is
to be done, they are to be discharged to earth before the work is started.
Capacitors hold their charge for some time. Check that they are fully
discharged before assuming that the equipment is dead.

Live Equipment
The following precautionary measures are to be taken when working on
live equipments:-
1) Inform to your senior proceed as.
2) Take a trained man with you for help in case of accident.
3) Avoid direct contact with any circuit and or component which may be
live.
4) Make sure no direct contact is made with any earthed metal eg.
Equipment casing or chassis, bulkhead, handrail, drawer handle etc.
5) If possible work with one hand and other in your pocket.
6) Use insulated tools, ensuring that tools are dry.
7) Stand on approved insulated deck covering, if in doubt use a rubber
mat.
8) Take care that tools or test equipment do not cause a short circuit.
9) Wear rubber gloves and check them before use.

5
F.M.F
FOR TRAINING PURPOSE ONLY

Electrical Shock Dynamics

Shock is the passage of electrical energy


through the human body. The primary factors
affecting an electrical shock's severity are the
path along which the current travels, the
amount of current, and the duration of
exposure to the current.

Electric Shock

An electric shock is caused to the human body by passing an electric


current through it. Two conditions are necessary before a person will
receive a shock:-
a) A potential difference.
b) A complete circuit.

The basic causes of electric shock are-


a) Equipment failure.
b) Human failure.
c) A combination of both.
Simple examples of the above a and b is as:-
1) Casing of a kettle becoming live.
2) Touching a live terminal.

6
F.M.F
FOR TRAINING PURPOSE ONLY

RADHAZ AND ALOFT

1- RADHAZ:- Radio transmissions can cause hazards by


inducing voltages in such things as wires , stays and riggings which
causing the ignition of certain armament stores and highly inflammable
liquid fuels. It can also do irreparable damage to internal organs, eyes,
as well as causing electric burns to the skin. (Ref BR 2924).

2- ALOFT:- It is defined as all masts, funnels and ship


superstructure to which aerials are secured or which can be excited by
neighbouring aerials.

3. Precaution for working aloft:-


Before commencing work on a mast or funnel
consideration should be given to prevailing weather conditions,
navigation and propulsion requirements and the physical
condition of the man preparing to carry out the work and his
attendant.

a) Clothing and foot wear: - These should be in good condition,


correctly worn and closely adjusted. Coins, Keys etc. should not
be carried in unsealed pockets.

b) Safety Line: - Should be securely attached to the safety harness,


passed over a suitable support and tended at deck level by a
reliable rating. The free end should always be taken twice
around a suitable securing point at deck level and the loose end
retained in the hand of the attendant.

c) Safety harness: - Should be in good repair, correctly worn and


closely adjusted.

7
F.M.F
FOR TRAINING PURPOSE ONLY
d) Isolate Hazardous equipment:- Depending on the location of the
work to be done radar and radio equipment must be shut down,
Sirens should be switched off. Engine should not be started.
Safety valves lifted.

e) Tools and equipment: - Should be secure to the person working


aloft by short lanyards as well as being placed in a pocket. A thin
line may be used to supply and retrieve tools.

g) Attendant: - The life of the person working aloft may well


depend upon the attentiveness of the attendant. The attendant
must pay particular attention to keeping the safety line suitable
adjusted and ready for immediate use if required. The attendant
must also be constantly looking for possible dangers or risks to
the person working aloft.

Note: - When berthed alongside another ship it may be necessary to


take similar precautions on the adjacent craft depending on its
closeness.

Earth and short circuits:-

Earth Potential:-

The earth (and hence the sea) is at a potential of zero volts. Items
connected to the earth (or the sea) e.g. Circuit wiring and electrical
components are said to be earthed or are at earth potential:-

b) This means that there is no difference of potential between the


item and earth. (A ship’s hull being immersed in the sea, is at earth
potential and therefore at zero volts).

c) If the casing of an item of electrical equipment is earthed


therefore, it is impossible for a person standing on earth to get an

8
F.M.F
FOR TRAINING PURPOSE ONLY
electric shock by touching that casing. This applies even if a fault
occurs in the equipment, which allows a current carrying conductor to
touch the casing.

Earthing of equipment:-
a) The earthing of equipment casings by heavy gauge conductors safeguard
against Electric shock.
b) If due to a fault a naked line touched to the body of equipment then
current would flow through the casing to ground / ships hull or Sea.
c) Because of the very low resistance of the earthing conductor the casing will
be at almost zero volts and a person touching it would not receive a shock.
d) Where the earthing conductor not fitted, the casing would be at the
potential of the circuit and anyone touching it, now would receive a shock.
This is because; the only current path to earth would then be through the body
of the person.

9
F.M.F
FOR TRAINING PURPOSE ONLY
3- Portable Equipment:-
Following safety precautions must be taken for check
earth casing of equipment on board ships.

a) Only approved test equipment to be used when testing an


equipment or fuse panel. Test lamp, made-up tester and many
cheaper civilian test instruments are dangerous.
b) All metal cased portable appliances must be fitted with a three
pin plug.
c) The total earth lead continuity resistance between plug and case
must not exceed 0.25 Ohms.

d) The continuity resistance of the earth lead on an extension cable


should not exceed 0.5 ohms.
e) The continuity resistance of the earth lead on an fixed
equipment should not exceed 0.1 ohms.
f) An earth bonding straps must be wide and thick in order to
have zero resistance.
g) Equipment fuses never to be up-rated which is hazard.

4. Fitted Equipment:-
Fitted equipment those which are not portable and have
permanently wired- in cables are often seated on resilient mounting in
order.
a) To protect the machine against ships vibration or shock from
underwater explosion.
b) To prevent machine vibration radiating from the hull in to Sea
water.

10
F.M.F
FOR TRAINING PURPOSE ONLY
5. Safety for Earth Bonding:-

a) There should be no paint, rust, grease or dirt between the


equipment and the hull.
b) It must secure from metal to metal.
c) It must be sufficiently long to avoid taking a strain when the
resilient mounts flex.
d) If found to be damaged an earth bonding strap must be replaced
by a new one as Soon as possible.

e) Fuses are fitted to protect the supply system firstly and the
equipment secondly. The fuse value can be calculated by the
formula.

125
—— X Normal full load.
100
The fuse rating is always 25 % above the circuit.

Q-1 If a motor of 2 HP taking current 5 amps at normal load. Find the


fuse rate which should be fitted in 440 volts D.B?

125 25
—— X 5 = —— = 6.25 amps.
100 4

11
F.M.F
FOR TRAINING PURPOSE ONLY

Electrical safety work practices

The electrical safety work practices applied by personnel in the environment


and around the equipment is the third element in hazard identification.

 Become familiar with the Electrical Safety Manual.


 Read and follow standard operating procedures.
 Become familiar with lockout/tagout procedures.
 Understand the required qualifications of personnel working on the
equipment.
 Wear required Personal Protective Equipment (PPE).

Do not wear loose chains or metal of any kind; this includes watches,
rings, or earrings.

12
F.M.F
FOR TRAINING PURPOSE ONLY
CHAPTER (2)

Static Electricity, Magnetism & Atom principle


Static electricity
It was discovered centuries ago that certain types of materials would
mysteriously attract one another after being rubbed together.

Fig2.1 producing static electricity by friction

It was also noted that when a piece of ROD rubbed with FUR, Fig2.1 the two
materials would attract one another. When two pieces of matter rubbed
together, electrons can be wiped off one material onto the other. If a material
is good conductor, it is difficult to obtain a detectable charge on either, since
equalizing currents can flow easily between the conducting materials. These
current equalize the charges almost as fast as they are created; a static
charge is more easily created between no conducting materials. When a hard
rubbed rubber rod is rubbed with fur, the rod will accumulate electrons given
up by the fur, since both materials are poor conductors, very little equalizing
current can flow, and an electrostatic charge builds up. When charge
becomes great enough, current will flow regardless of the poor conductivity of
the materials. These currents will cause visible sparks and produce a cracking
sound.

13
F.M.F
FOR TRAINING PURPOSE ONLY

MAGNETISM

Fig2.2 Magnet
In order to properly understand the principles of electricity, it is necessary to
study magnetism Fig2.2 and the effects of magnetism on electrical
equipments. Magnetism and electricity are so closely related that the study of
either subject would be incomplete without at least a basic knowledge of the
other.
Much of today's modern electrical and electronic equipment could not function
without magnetism. Electrical motors use magnets to convert electrical energy
into mechanical motion; generators use magnets to convert mechanical
motion into electrical energy.

14
F.M.F
FOR TRAINING PURPOSE ONLY
Magnetic Materials
Magnetism is generally defined as that property of a material which enables it
to attract pieces of iron. A material possessing this property known as a
MAGNET. Materials that are attracted by a magnet, such as iron, steel, nickel,
have the ability to become magnetized. These are called magnetic materials.
Materials, such as paper, wood, glass, or tin, which are not attracted by
magnets, are considered nonmagnetic.

Ferromagnetic Materials
The most important group of materials connected with electricity and
electronics are the ferromagnetic materials. Ferromagnetic materials are
those which are relatively easy to magnetize, such as iron, steel and alloy.

Artificial Magnets
Magnets produced from magnetic materials are called ARTIFICIAL
MAGNETS. Artificial magnets are usually classified as PERMANENT or
TEMPORARY, depending on their ability to retain magnetic properties after
the magnetizing force has been removed. Magnets made from steel and
certain alloys which retain a great deal of their magnetism, are called
PERMANRNT MAGNETS. These materials are difficult to magnetize because
of the opposition offered to the magnetic lines of force as the lines of force try
to distribute themselves throughout the material.
The opposition that a material offers to the magnetic lines of force is called
RELUCTANCE. All permanent magnets are produced from materials having a
high reluctance.
A materials with a low reluctance, such as soft iron is easy to magnetize but
will retain only a small part of its magnetism once the magnetizing force is
removed. Materials of this type that easy lose most of their magnetic strength
are called TEMPORARY MAGNETS.

RESIDUAL MAGNETISM. The ability of a material to retain an amount of


residual magnetism is called the RETENTIVITY of the material.

15
F.M.F
FOR TRAINING PURPOSE ONLY
Magnetic Poles
The magnetic force surrounding a magnet is not uniform. There exists a great
concentration of force at each end of the magnet and a very weak force at the
center. The two ends, which are the regions of concentrated lines of force, are
called the POLES of the magnet. Magnets have two magnetic poles and both
poles have equal magnetic strength.

Magnetic Fields
The space surrounding a magnet where magnetic forces act is known as the
magnetic field.

Lines of Force
The further describe and work with magnet phenomena, lines are used to
represent the force existing in the area surrounding a magnet these lines,
called MAGNETIC LINES OF FORCE Fig2.3.

Fig2.3 Magnetic lines of force


The characteristics of magnetic lines of force can be described as following:
1. Magnetic lines of force are continuous and will always form closed loops.
2. Magnetic lines of force will never cross one another.
3. Parallel magnetic lines of force traveling in the same direction repel one
another.
4. Magnetic lines of force tend to shorten themselves.
5. Magnetic lines of force pass through all materials.
6. Magnetic lines of force always enter or leave a magnetic material at right
angles to the surface.

16
F.M.F
FOR TRAINING PURPOSE ONLY

Voltage Produced by Magnetism


Magnets or magnetic devices are used for thousands of different jobs.
One of the most useful and widely employed applications of magnets is in the
production of vast quantities of electric power from mechanical sources. The
mechanical power may provided by a number of different sources, such as
gasoline or diesel engines, and water or steam turbines.
There are three fundamental conditions which must exist before a voltage can
be produced by magnetism:-
1) There must be a CONDUCTOR in which the voltage will be produced.
2) There must be a MAGNETIC FIELD in the conductor's vicinity.
3) There must be RELATIVE MOTION between the field and conductor.
In accordance with these conditions, when a conductors MOVE ACROSS a
magnetic field so as to cut the lines of force, electrons WITH THE
CONDUCTOR are propelled in one direction or another. An electric force, or
voltage, created Fig2.4.

Fig2.4 Voltage produced by magnetism


In fig2.4 view A, the conductor is moving TOWARD the front of the page and
the electrons move from left to right. The movement of the electrons occurs
because of the magnetically induced emf acting on the electrons in the
copper. The right-hand end becomes negative, and the left-hand end positive.
The conductor is stopped at view B, motion is eliminated and there is no
longer an induced emf. Consequently, there is no longer any difference in

17
F.M.F
FOR TRAINING PURPOSE ONLY
potential between the two ends of the wire. The conductor at view C is moving
away from the front of the page. An induced emf is again created. However,
note carefully that the REVERSAL OF MOTION has caused a REVERSAL OF
DIRECTION in the induced emf. If a path for electron flow is provided between
the ends of the conductor, electrons will leave the negative end and flow to
the positive end. This condition showing in part view D. Electron flow continue
as long as the emf exists.

Matter
Matter is defined as any thing that occupies space and has weight.
Examples of matter are air, water, clothing, and even our own bodies.
An Element is substance which cannot be reduced to a simpler substance by
chemical means. Examples of elements Iron, gold, silver, copper, and
Oxygen. When two or more chemically combined, the resulting substance is
called COMPOUND. A compound is a chemical combination of elements
which can be separated by chemical. Examples of common compounds are
water which consists of hydrogen and oxygen, and table salt, which consists
of sodium and chlorine.
Molecules
A MOLECULE is a chemical combination of two or more atoms.
In a compound the molecule is the smallest particle that has all the
characteristics of the compound.
Consider water, for example. Water is matter, since it occupies space and has
weight. Depending on the temperature, it may exist as a liquid (Water), a solid
(Ice), or gas (Steam).

18
F.M.F
FOR TRAINING PURPOSE ONLY

Fig2.5 Atom
Atom
Molecules are made up of smaller particles called ATOMS Fig2.5. An atom is
the smallest particle of an element that retains the characteristics of that
element.
The atoms of one element, however, differ from the atoms of all other
elements. The atoms of each element are made up of ELECTRON.
PROTONS, and, in most cases, NEUTRONS.
The electrons, protons, and neutrons of one element are identical to those of
any other element. The reason that there are different kinds of elements is
that the number and the arrangement of electrons and protons within the atom
are different for the different elements.
The electron is considered to be a small negative charge of electricity.
The proton has a positive charge of electricity equal and opposite to the
charge of the electron. The electron and proton each have the same quantity
of charge, although the mass of the proton is approximately 1837 times that
of the electron. In some atoms there exists a neutral particle called a neutron.
The neutron has a mass approximately equal to that of a proton, but it has no
electrical charge.
In fig2.6 shows one hydrogen and one helium atom. Each has a relatively
simple structure. The hydrogen atom has only one proton in the nucleus with
one electron rotating about it. The helium atom is a little more complex.

19
F.M.F
FOR TRAINING PURPOSE ONLY
It has a nucleus made up of two protons and two neutrons, with two electrons
rotating about the nucleus.

Fig 2.6 Structures o simple atoms

Elements are classified numerically according to the complexity of their atoms.


The atomic number of an atom is determined by the number of protons in its
nucleus. In a neutral state, an atom contains an equal number of protons and
electrons.
Shells and sub shells

The difference between the atoms, insofar as their chemical activity and
stability are concerned, is dependant upon the number and position of the
electrons included within the atom. The electrons reside in groups of orbits
called shells. These shells are elliptically shaped and are assumed to be
located at fixed intervals. Thus, the shells are arranged in steps that
correspond to fixed energy levels. The shells and the number of electrons
required to fill them. Principle specifies that each shell will contain a
maximum of 2n electrons, where n corresponds to the shell number starting
with the one closest to the nucleus. The second shell, for example, would
contain 2(2) or 8 electrons when full.

20
F.M.F
FOR TRAINING PURPOSE ONLY
The shells are also given letter designations, as pictured in Fig2.7 starting
with the shell closest to the nucleus and progressing outward, the shells are
labeled K, L, M, N, O, P, and Q, respectively. The shells are considered to be
full, or complete, when they contain the following quantities of electrons: 2 in
the K shell, 8 in the L shell, 18 in the M shell, and so on, in accordance with
the exclusion principle. Each of these shells is a major shell and can be
divided into sub shells, of which there are 4, labeled s, p, d, and f.
The sub shells are limited as to the number of electrons which they can
contain. Thus, the s sub shell is complete when it contains 2 electrons, the p
10 and f 14.

Fig 2.7 Shell designation

21
F.M.F
FOR TRAINING PURPOSE ONLY
The copper atom contains 29 electrons in Fig2.8 which completely fill the first
three shells and subs hells, leaving one electron in the s subs hell of N shell.

Fig 2.8Copper atom


The number of electrons in the outermost shell determines the valence of an
atom. For this reason, the outer shell of an atom is called the VALENCE
SHELL; and the electrons contained in this shell are called VALENCE
ELECTRONS. The valence of an atom determines its ability to gain or lose an
electron, which in turn determines the chemical and electrical properties of the
atom. An atom that is lacking only one or two electrons from its outer shell will
easily gain electrons to complete its shell, but a large amount of energy is
require to free any of its electrons.
Ionization
When the atom loses electrons or gains electrons in this process of electron
exchange, it is said to be IONIZED. Thus, ionization is the process by which
an atom loses or gain electrons.

22
F.M.F
FOR TRAINING PURPOSE ONLY
CONDUCTORS, SEMICONDUCTORS, AND INSULATORS

As a means of all elements of which matter is made may be placed into one of
three categories: CONDUCTORS, SEMICONDUCTORS, and INSULATORS,
depending on their ability to conduct an electric current. Conductors are
elements which conduct electricity very readily; Insulators have an extremely
high resistance to the flow of electricity. All matters between these two
extremes may be called Semiconductors.
The electron theory states that all matter is composed of atoms and the atoms
are composed of smaller particles called proton, electrons, and neutrons.
The electrons orbit the nucleus which contains the protons and neutrons. It is
the Valence electrons that we are most concerned with in electricity.
These are the electrons which are easiest to break loose from their parent
atom. Normally, conductors have three or less valence electrons; insulators
have five or more valence electrons; and semiconductors usually have four
valence electrons.
Some metals are better conductors of electricity than others. Silver, copper,
gold, and aluminum are materials with many free electrons and make good
conductors. Silver is the best conductors, followed by copper, gold, and
aluminum. Copper is used more often than silver because of cost. Aluminum
is used where weight is a major consideration, such as in high-tension power
lines, with long spans between supports. Gold is used where oxidation or
corrosion is a consideration and good conductivity is required.

23
F.M.F
FOR TRAINING PURPOSE ONLY

Chapter (3)

Batteries

Introduction:-

Batteries are commonly used as an independent power source for emergency


lighting, alarm systems, low distribution systems, communication systems,
damage control flood lamps and torches etc.

Battery Terminology:-

The following terminology relates to batteries:-


(1) Cell – A cell a device which produces electrical energy by chemical
action.

(2) Primary cell – A primary cell is one in which the electrochemical is not
reversible.

(3) Secondary cell – A secondary cell is one in which the electrochemical


action is reversible.

(4) Battery – A battery is an assembly of two or more cells connected


together and provided with external terminals.

(5) Positive electrode – The positive plate of an electrolytic cell which


electrons leave a system.

(6) Negative electrode – The negative plate of an electrolytic cell by


which electrons enter a system.

(7) Electrolyte – An electrolyte is a substance the conducts electricity


because of it’s a ability to change its chemical state.

(8) Capacity – The capacity of a battery is expression of the quantity of


electricity it can deliver before the end point voltage is reached.
Capacity is normally expressed in terms of the (Ah) at temperature of
20 degrees c. e.g. – a cell having a capacity of (10Ah) will supply 1
Ampere for 10 hours.

(9) An example of a primary cell is the dry cell (e.g. a torch battery) it
consists of a zinc case electrode (Negative plate) a carbon rod
solution of a ammonium chloride in paste form, the (electrolyte). A tar
paper washer is located at the base of the rod to prevent it from
coming into contact with the zinc case. At the top, the case contains
layers of saw dust, sand and pitch, which hold the carbon rod in
position and prevent electrolyte leakage. The max voltage that a
primary cell can supply is 1.5v.( Primary cell Fig3.1and 3.2)

24
F.M.F
FOR TRAINING PURPOSE ONLY
Fig 3.1 different types of primary batteries

Brass
Terminal

Pitch

Sand
Negative plate
Zinc case

Sawdust

Electrolyte
Positive plate (Ammonium
carbon rod Chloride in Paste
form)

Tar
paper
washer

The primary Cell


Fig 3.2

The combination of electrodes and electrolyte used in the primary cell results
in one of the electrodes gradually eroding until eventually dissolving in the
electrolyte.
The secondary cell uses a combination of electrodes and electrolyte that
merely suffer a chemical change during the production of current and can be
restored to their original condition by passing current from an external source
through the cell in the reverse direction.

Lead – Acid BatteriesFig 3.4:-

The solution in a lead-acid cell contains sulfuric acid (H2SO4) in water.


In water, sulfuric acid molecules dissociate into positively charged hydrogen
ions (H+) and negatively charged sulfate ions (SO4). Since hydrogen ions
carry only one positive charge and sulfate ions carry two negative charges,

25
F.M.F
FOR TRAINING PURPOSE ONLY
the electrically neutral solution contains twice as many hydrogen ions as
sulfate ions.
The cells negative electrode is spongy form of lead metal, housed in a non-
reactive lead-alloy lattice. The cells positive electrode is lead dioxide, also
housed in a protective lead-alloy lattice.
Let us start at the lead dioxide electrode; we will assume that two electrons
arrive at the lead dioxide electrode. They are picked up by a lead dioxide
molecule, which reacts with four hydrogen ions and a sulfate ion to produce a
lead sulfate molecule and two water molecules. The lead sulfate molecule
consists of a positively charged lead ion and a negatively charged sulfate ion,
but it’s not soluble in water-the two ions bind together so strongly that water
molecules can’t separate them and carry them about in solution. The lead
sulfate clings to the lead dioxide electrode as a solid.

Fig 3.4 lead- acid Battery

26
F.M.F
FOR TRAINING PURPOSE ONLY

Fig3.5 Hydrometer

The process
Lead Acid Battery
A lead-acid cell
Is powered by
Electrochemical --
Reaction between
Lead, and lead --
Dioxide, and between
Sulfuric acid, which
Create lead sulfate Lead Lead Dioxide
And water. Lead
Dioxide molecule
(PbO2) picks up two
Electrons from the l H2o
Lead dioxide - -
Electrode and reacts - -
With four hydrogen H+ H+
Ions (H++) in the
pb -So4
- -Pb++ pbO2
Solution to form
+H +H
A lead
Pb++ So4--
H2O

Fig3.6 lead-acid battery process

Measurement of Specific Gravity (Fig3.5):-

The specific gravity (or relative density) of an electrolyte is an indication of the


state of charge of the cell. Specific gravity is defined as the ratio of the mass
of a given volume of a substance to the mass of an equal volume of water at a
temperature of 4 degrees c. the specific gravity of a fully charged cell ranges
between 1215 and 1300, the nominal figure being 1250. Specific gravity is
measured by an instrument called (a hydrometer fig3. 5).

27
F.M.F
FOR TRAINING PURPOSE ONLY

The Method used to measure specific gravity is as following:

(1) Ensure that the hydrometer is clean and that the float moves freely in
the float guide.
(2) Record the electrolyte temperature.
(3) Ensure that the hydrometer is at approximately the same temperature
as the electrolyte.
(4) Squeeze the rubber bulb of the hydrometer.
(5) Insert the hydrometer tube into the electrolyte.
(6) Draw electrolyte into the barrel of the hydrometer by releasing the
rubber bulb.
(7) Hold the hydrometer so that the surface of the electrolyte is at eye
level.
(8) Ensure that no electrolyte is split and that the sample is returned to the
cell from which it was drawn.
(9) Rinse the hydrometer with pure distilled water.

Safety precautions when servicing lead acid batteries:

(1) Do not smoke or expose naked lights near any battery on a charge.
(2) Display (No smoking or Naked Lights).
(3) Ensue that the ventilation fans are running.
(4) Wear full protective clothing:-
a- Apron.
b- Gauntlets, PVC.
c- Knee boots, rubber.
d- Goggles, rubber.
(5) Mix electrolyte only as instructed.
(6) Do not allow batteries on charge to gas excessively.
(7) Ensure that temperature limits are not exceeded.
(8) Avoid touching any exposed terminals.
(9) Keep all electrical connections tight.
Ensure that terminals are not accidentally short circuited by tools or
links.
(10) Use insulated tools.

Mixing the electrolyte

(1) Carry out general safety precautions listed in page 6 from 1 to 5.


(2) When mixing always add acid to water, not water to acid. the acid
should be poured on to the water slowly and with care, because heat is
generated as the liquids meet.
(3) Mix the electrolyte as following:
(a) Pour the required volume of water.
(b) Pour most of the required volume of acid slowly into the water
stirring continuously.

28
F.M.F
FOR TRAINING PURPOSE ONLY
(c) Check the specific gravity of the electrolyte with a hydrometer
making temp correction to the reading.
(d) Adjust the specific gravity of the electrolyte by adding more acid.
(e) Allow the electrolyte to cool to 27 degrees c before use.
(f)Rinse all receptacles and utensils before stowage.
(4) After mixing, the volume of electrolyte will always be slightly less than
the sum of the separate volumes of acid and water.

Preparations for charging Batteries

(1) Remove and collect all vent caps.


(2) Top-up all cells as necessary.
(3) Check that the charging supply is switched off.
(4) Use spring clips to the battery for all battery connections.
(5) Ensure that all temporary leads are sound and all connections are
secure.
(6) Connect the positive terminal of the charging supply to the positive
terminal of the battery. And the negative terminal to the negative
terminal.
(7) Check the charging supply is set to give min current or a voltage not
exceeding 2.3 volts per cell.
(8) Switch ON the charging supply.
(9) Adjust the charging supply as detailed for the relevant type of charge.

Discharging

Consider a battery in the fully charged state; the a active materials are
lead(pb) and lead peroxide (Pbo2) at the negative and positive plates
respectively, and the electrolyte diluted sulfuric acid (H2SO4), is at its
maximum specific gravity. When a load is connected across the battery
terminals, a discharge current flows and chemical action takes place within
each cell.
At the negative plate lead is ionized and each positive lead ion combines
with a negative sulfate ion from the electrolyte to form lead sulfate on
the plate. Thus, the active material of the negative plate will contain a
decreasing lead contents and increasing lead sulfate content. This
chemical reaction releases electrons from the active material which flow
through the load to the positive plate.

At the positive plate the positive lead ions combine with the negative
sulfate ions from the electrolyte to form lead sulfate on the plate; at the
same time oxygen is released into the electrolyte. Thus the active
material on the positive plate will contain a decreasing lead peroxide
content and increasing lead sulfate content.

In the electrolyte the sulfate ion combine with the lead in the positive
and negative plates to form lead sulfate. At the same time, positive
hydrogen ion combine with the oxygen ions (released from the positive
plate) to form water. Thus, the acid content of the electrolyte will

29
F.M.F
FOR TRAINING PURPOSE ONLY
decrease and the water content increase, reducing the specific gravity of
the electrolyte.
During battery discharge, the active material on both positive and
negative plates has been converted to lead sulfate and the electrolyte is
at its lowest specific gravity.

Charging

Once the active materials have been converted to lead sulfate and the
specific gravity has been reduced by the formation of water, the
battery can be charged by passing a current through it in the opposite
direction to the discharge current. The electrolyte separates into
positive hydrogen ions and negative sulfate ions.
At the negative plate the lead sulfate is re-converted into lead and the
sulfate ions combine with the hydrogen ions in the electrolyte to form
sulfuric acid. Thus the active material in the negative plate will contain
an increasing lead content and decreasing lead sulfate content.
At the positive plate, the water formed during discharge separates into its
elements of oxygen and hydrogen and combines with the lead sulfate
on the plate and the sulfate ions in the electrolyte. The chemical actions
which take place result in the production of lead peroxide and sulfuric
acid. Thus, the active material in the positive plate will contain an
increasing lead peroxide content and a decreasing lead sulfate
contents. Electrons are released from the active material which flow
through the generator to the negative plate.

In the electrolyte the acid content will increase and the water will
decrease.
During charging, the active material on the positive and negative plates
has reformed to lead peroxide and lead respectively and the electrolyte is
once more at its highest specific gravity.

30
F.M.F
FOR TRAINING PURPOSE ONLY

31
F.M.F
FOR TRAINING PURPOSE ONLY
Chapter (4)

Generator

A generator is a machine that converts mechanical energy into electrical


energy.
The principle is explained as following:-
Whenever a conductor is moved with in a magnetic field in such away that the
conductor cuts across magnetic lines of flux, voltage is generated in the
conductor. The amount of voltage generated depends on the following:-
(1) The strength of the magnetic field.
(2) The angle at which the conductor cuts the magnetic field.
(3) The speed at which the conductor is moved.
(4) The length of the conductor within the magnetic field.
The polarity of the voltage depends on the direction of the magnetic lines of
flux and the direction of movement of the conductor. To determine the
direction of current in a given situation, the LEFT-HAND RULE FOR
GENERATORS is used. Fig 4.1

Fig4.1left hand rule for generator

32
F.M.F
FOR TRAINING PURPOSE ONLY
This rule is explained in the following manner:-
Point your thumb in the direction the conductor is being moved.
Point your forefinger in the direction of magnetic flux (from north to south).
Point your middle finger in the direction of current flow.

Fig4.2 the elementary generator

Basic generating principles are most easily explained through the use of the
elementary ac generator. An elementary generator Fig4.2 consists of a wire
loop placed so that it can be rotated in a stationary magnetic field. This will
produce an induced emf in the loop. Sliding contacts (brushes) connect the
loop to an external circuit load in order to pick up or use the induced emf. The
pole pieces (marked N and S) provide the magnetic field. The loop of wire that
rotates through the field is called the ARMATURE. The ends of the armature
loop are connected to rings called SLIP RINGS. They rotate with the
armature. The brushes, usually made of carbon, with wires attached to them,
ride against the rings. The generated voltage appears across these brushes.

33
F.M.F
FOR TRAINING PURPOSE ONLY

Fig4. 3 Output voltages during one revolution

The generator produces a voltage in the following manner Fig4.3


The armature loop is rotated in a clockwise direction. The initial or starting
point is shown at position A. At (00) the armature loop is perpendicular to the
magnetic field. The instant the conductors are moving parallel to the magnetic
field, they do not cut any lines of flux. Therefore, no emf is induced in the
conductors, and the meter at position A indicates Zero. As the armature
rotates from position A (00) to position B (900) the conductors cut through
more and more lines of flux, at a continually increasing angle. At 900 they are
cutting through a maximum number of lines of flux and at maximum angle.
The result is that between 00 and 900 the induced emf in the conductors builds
up from zero to a maximum value. Observe that from 00 to 900 the black
conductor cuts DOWN through the field. At the same time the white conductor
cuts up through the field. The induced emfs in the conductors are series-
adding. This means the resultant voltage across the brushes is the sum of the
two induced voltages. The meter at position B reads maximum value. As the
armature loop continues rotating from 900 (position B) to 1800 (position C), the
conductors which were cutting through a maximum number of lines of flux at
position B now cut through fewer lines.

34
F.M.F
FOR TRAINING PURPOSE ONLY
They are again moving parallel to the magnetic field at position C. They no
longer cut through any lines of flux. As the armature rotates from 900 to 1800,
the induced voltage will decrease to zero in the same manner that t increased
during the rotation from 00 to 1800, the meter again reads zero. From 00 to
1800 the conductors of the armature loop have been moving in the same
direction through the magnetic field. Therefore, the polarity of the induced
voltage has remained the same. This is shown by points A through C on the
graph. As the loop rotates beyond 1800 (position C), through 2700 (position
D), and back to the initial or starting point (position A), the direction of the
cutting action of the conductors through the magnetic field reverses. Now the
black conductor cuts UP through the field while the white conductor cuts
DOWN through the field.
As a result, the polarity of the induced voltage reverses. Following the
sequence shown by graph points C,D, and back to A, the voltage will be in the
direction opposite to that shown from points, A,B, and C.

Electromagnetic Poles
Nearly all practical generators use electromagnetic poles instead of the
permanent magnets used in our elementary generator. The electromagnetic
field poles consist of coils of insulated copper wire on soft iron cores, as
shown in Fig 4.4.

Fig4. 4 Four pole generator (without armature)

35
F.M.F
FOR TRAINING PURPOSE ONLY
Armature losses
In dc generators, as in most electrical devices, certain forces act to decrease
the efficiency. These forces, as they affect the armature, are considered as
losses and may be defined as follows:
1. I2R, or copper loss in the winding. The power lost in the form of heat in
the armature winding of generator.
2. Eddy current loss in the core. The current that are induced in the
generator armature core.
3. Hysteresis loss (a sort of magnetic friction).

Classification of Generators
Self-excited generators are classed according to the type of field
connection they use. There are three general types of field connections:-
1) Series-wound Generator
In the series-wound generator, shown in fig4.5 the field windings are
connected in series with the armature. Current that flows in the armature
flows through the external circuit and through the field windings.
A series-wound generator uses very low resistance field coils, which
consist of a few turns of large diameter wire.
The voltage output increases as the load circuit starts drawing more
current. Under low-load current conditions, the current that flows in the
load and through the generator is small. Since small current means that a
small magnetic field is set up by the field poles, only a small voltage is
induced in the armature. If the resistance of the load decreases, the load
current increases. Under this condition, more current flows through the
field. This increases the magnetic field and increases the output voltage.
A series-wound dc generator has the characteristic that out put voltage
varies with load current.

36
F.M.F
FOR TRAINING PURPOSE ONLY

To Load Generator Series


Circuit Output Field

Armature

Fig 4.5 Series-wound generator

2) Shunt-Wound Generator
In a shunt-wound generator, like the one shown in Fig6, the field coils
consist of many turns of small wire. They are connected in parallel with the
load. In other words, they are connected across the output voltage of the
armature.

Shunt Field

Generator output
Armature

Fig4.6 Shunt-wound generator


Current in the field windings of a shunt-wound generator is independent of the
load current (Currents in parallel branches are independent of each other).
Since field current, and therefore field strength, is not affected by load current,
the output voltage remains more nearly constant than does the output voltage
of the series-wound generator.

37
F.M.F
FOR TRAINING PURPOSE ONLY
The output voltage in a dc shunt-wound generator varies inversely as load
current varies. The output voltage decreases as load current increases
because the voltage drop across the armature resistance increases (V=IR).
In a series-wound generator, output voltage varies directly with load current.
In the shunt-wound generator, output voltage varies inversely with load current.
3) Compound-Wound Generators
Compound-wound generators have a series-field winding in addition to a
shunt-field winding, as showing in fig4.7

Series Field

Shunt Field

Generator
Output

Armature

Fig4.7 Compound -wound generator


The shunt and series windings are wound on the same pole pieces.
In the compound-wound generator when load current increases, the armature
voltage decreases just as in the shunt-wound generator. This causes the
voltage applied to the shunt-field winding to decrease, which results in a
decrease in the magnetic field. This same increase in load current, since it
flows through the series winding, causes an increase in the magnetic field
Produced by that winding. By proportional the two fields so that the decrease
in the shunt field is just compensated by the increase in the series field, the
output voltage remains constant. This is shown in Fig4.8, which shows the
voltage characteristics of the series-, and compound-wound generators. As
you can see, by proportioning the effects of the two fields (series and shunt),
A compound-wound generator provides a constant output voltage under
varying load conditions.

38
F.M.F
FOR TRAINING PURPOSE ONLY
Output Voltage
Out put Voltage
Load Current Load Current Load Current

C. Compound-Wound B. Series-Wound A. Shunt-Wound


DC Generator DC Generator DC Generator
Fig4.8 Voltage output characteristics of the series-, shunt-, and compound-wound dc generators.

Generator Construction
Fig4.9 views A through E, shows the components parts of dc generators.

Fig4.9 Components of a dc generator

39
F.M.F
FOR TRAINING PURPOSE ONLY
AC GENERATORS
Regardless of size, all electrical generators, whether dc or ac, depend upon
the principle of magnetic induction. An emf is induced in a coil as a result of
(1) a coil cutting through a magnetic field, or (2) a magnetic field cutting
Through a coil. As long as there is relative motion between a conductor and a
magnetic field is called the field. That part in which the voltage is induced is
called the armature. For relative motion to take place between the conductor
and the magnetic field, all generators must have two mechanical parts-a rotor
and a stator. The rotor is the part that rotates; the stator is the part that
remains stationary. In a dc generator, the armature is always the rotor. In
alternators, the armature may be either the rotor or stator.

Fig4.11 Types of ac generators

40
F.M.F
FOR TRAINING PURPOSE ONLY
Rotating-Armature Al ternators
The rotating-armature alternator is similar in construction to the dc generator
in that the armature rotates in a stationary magnetic field as show in Fig4.11
view A. in the dc generator, the emf generated in the armature windings is
converted from ac to dc by means of commutator. In the alternator, the
generated ac is brought to the load unchanged by means of slip rings. The
rotating armature is found only in alternators of low power rating and generally
is not used to supply electric power in large quantities.
The rotating-field alternator has a stationary armature winding and a rotating-
field winding as shows in Fig4.11 view B the advantage of having a stationary
armature winding is that the generated voltage can be connected directly to
the load. A rotating armature requires slip rings and brushes to conduct the
current from the armature to the load. The stationary armature, or stator, of
this type of alternator holds the windings that are cut by the rotating magnetic
field. The voltage generated in the armature as a result of this cutting action is
the ac power that will be applied to the load. The stators of all rotating-field
alternators are about the same. The stator consists of a laminated iron core
with the armature windings embedded in this core as shown in Fig4.12 the
core is secured to the stator frame.

Fig4.12 Stationary armature windings

41
F.M.F
FOR TRAINING PURPOSE ONLY
Generator Operation

Fig4.13
Fig4.13 showed an engine supplies the power to turn shaft (1). Exciter
armature (2) and main fields (4) attached to shaft (1). As shaft (1) turns,
exciter armature (2) and related components generate DC. This DC is
supplied to main field (4) and creates a magnetic field around the poles of
main field (4). As main field (4) turns with shaft (1), the magnetic field also
rotates and induced an AC voltage into stationary main armature (3). Main
armature (3) is a coil with many turns of wire, and the current that flows
through it flows to the load.
The exciter supplies DC to main field (4). The load (terminal) voltage is
controlled by varying the small current to exciter armature (2). There are two
methods for excitation used on SR4 Generators; conventional self-excited
(SE) to satisfy most applications, or an optional permanent magnet pilot
exciter (PMPE) which allows the generator to better sustain an overload for a
short duration. Self-excited generators receive the power for excitation from
the generator armature (the generator output).

42
F.M.F
FOR TRAINING PURPOSE ONLY

Fig4.13a RFA
Fig4.13a showed when the engine starts turning rotating field assembly
(RFA); the residual magnetism in exciter field (L1) causes a small amount of
AC voltage to be generated in exciter armature (L2). This induced voltage in
(L2) causes an AC to flow. This AC flows through the three-phase full wave
bridge rectifier circuit (CR1 thru CR6). DC then flows through main field (L3).
The flow of DC through main field (L3) creates a magnetic field, which adds to
the existing residual magnetism of main field (L3). As main field (L3) rotates,
an AC voltage is induced into main armature (L4) which appears as a three-
phase AC voltage at output terminals T0, T1, T2, and T3. The voltage
regulator taps the AC output through wires 20, 22, and 24. During startup, this
tapped output is sensed by the voltage regulator as a low voltage output
condition. Therefore the voltage regulator output to exciter field (L1) is
increased so that the generator output will continue to increase up to the rated
voltage. The amount of current that flows through the exciter directly affects
the generator output voltage. The function of the voltage regulator is to keep
the generator output voltage constant with changing loads. The voltage
regulator controls the DC voltage that is supplied to the exciter and therefore,
the generator output voltage. The voltage regulator senses and uses the
generator output voltage at wires 20, 22, and 24. The voltage regulator then
supplies a controlled DC voltage to the exciter through wires (F1) and (F2).

43
F.M.F
FOR TRAINING PURPOSE ONLY

Fig 4.13b
Fig4.13b showed when the voltage regulator senses a decrease in output
voltage; it will increase the DC voltage at wires (F1) and (F2). This increases
the DC flow through exciter field (L1), therefore (L1) magnetic field increases
the AC voltage induced in exciter armature (L2). This increased AC voltage
from exciter armature (L2) causes more AC to flow. The AC is then rectified to
DC by the three-phase full wave bridge rectifier circuit, which consists of
rectifiers (CR1-CR6). The increased DC output from the bridge rectifier is
carried to main field coils (L3) by conductors, which are routed through a
passage in the generator shaft. Increased current through main field coils (L3)
increases the magnetic field of the generator. The increased magnetic field
induces a large AC voltage into main armature (L4). Therefore the three-
phase AC voltage at terminals T0. T1, T2 and T3 increases until the voltage
regulator no longer senses a decreased output voltage.
When the voltage regulator senses an increase in output voltage, it will
decrease the DC voltage to the exciter. This decrease will flow on through the
generator output voltage.
Residual magnetism is necessary for start-up of the self-excited generator.
The main field coils are wound on magnetic steel that retains a small amount
of magnetism after shutdown.

44
F.M.F
FOR TRAINING PURPOSE ONLY

Al ternator characteristics and limitations

Al ternators are rated according to the voltage they are designed to produce
and the maximum current they are capable of providing. The maximum
current that can be supplied by an alternator depends upon the maximum
heating loss that can be sustained in the armature. This heating loss (which is
an I2R power loss) acts to heat the conductors, and if excessive, destroys the
insulation.
Single-phase al ternators
A generator that produces a single, continuously alternating voltage is known
as a SINGLE PHASE alternator. This term is used in ac generator when the
windings are at 180 degree apart from each other. The stator (armature)
windings are connected in series. The individual voltage, therefore, add to
produce a single-phase ac voltage. Fig4.14

Fig4.14 Single-phase alternator

Fig4.14 shows a basic alternator with its single-phase output voltage.


Single-phase alternators are found in many applications. They are most often
used when the loads being driven are relatively light. The reason for this will
be more apparent as we get into multiphase alternators.
Power that is used in homes, shops, and ships, to operate portable tools and
small applications is single-phase power.

45
F.M.F
FOR TRAINING PURPOSE ONLY

Two Phase Al ternator

Fig 4.15 shows two-pole, two-phase alternator. The windings of two phases
are connected 90 degree apart from each other.

Fig415 Two Phase alternator

The outputs of each phase 900 apart, with A leading B. there will always be
900 between the phases this is by design. The stator windings consist of two
single-phase windings separated from each other each winding is made up of
two windings that are connected in series so that their voltages add. The rotor
is identical to that used in the single-phase alternator. In the left hand
schematic, the rotor poles are opposite all windings of phase A. Therefore, the
voltage induced in phase A is maximum, and the voltage induced in phase B
is zero. As the rotor continues rotating counterclockwise, it moves away from
the A windings and approaches the B windings. As a result, the voltage
induced in phase a decrease from its maximum value, and the voltage
induced in phase B increases from Zero. In the right-hand schematic, the rotor
poles are opposite the windings of phase B. Now the voltage induced in

46
F.M.F
FOR TRAINING PURPOSE ONLY
phase B is maximum, whereas the voltage induced in phase A has dropped to
Zero.
Three Phase Alternator
The three-phase alternator, as the name implies, has three single-phase
windings spaced such that the voltage induced in any one phase is displaced
by 1200 from the other two. A schematic diagram of a three-phase stator
shows in Fig4.16.

Fig4.16 Three phase alternator connection

View A, shows all the windings of each phase lumped together as one
winding. The rotor is omitted for simplicity. The voltage waveforms generated
across each phase are drawn on a graph, phase-displaced 1200 from each
other. The three phase alternator as shown in this schematic is made up of
three-single-phase alternators whose generated voltages are out of phase by
1200. The three phases are independent of each other.
The neutral connection is brought out to a terminal when a single-phase load
must be supplied. Single-phase voltage is available to A, neutral to B, and
neutral to C. In three-phase, Y connected alternator, the total voltage, or line
voltage, across any two of the three line leads is the vector sum of the
individual phase voltages. Each line voltage is 1.73 times one of the phase

47
F.M.F
FOR TRAINING PURPOSE ONLY
voltages. Because the windings from only one path for current flow between
phases, the line and phase currents are the same (equal).

Three-Phase Connections
The stator coils of three-phase alternators may be joined together in either
wye or delta connections, as shown in Fig4.17 with these connections only
three wires come out of the alternator. This allows convenient connection to
three-phase motors or power distribution transformers.

Fig417Three-phase alternator or transformer connections

A three-phase transformer may be made up of three, single-phase


transformers connected in delta, wye, or a combination of both.

Frequency
The output frequency of alternator voltage depends upon the speed of rotation
of the rotor and the number of poles. The faster the speed, the higher the
frequency. The lower the speed, the lower the frequency. The more poles
there are on the rotor, the higher the frequency is for a given speed.
For a given frequency, the more pairs of poles there are, the lower the speed
of rotation. The frequency of any ac generator in hertz (Hz), which is the
number of cycles per second, is related to the number of poles and the speed
of rotation, as expressed by the equation

48
F.M.F
FOR TRAINING PURPOSE ONLY
F=NP/120
Where P is the number of poles, N is the sped of rotation in revolutions per
minute (rpm), and 120 is a constant to allow for the conversion of minutes to
seconds and from poles to pairs of poles. For example, a 2-pole, 3600-rpm
alternator has a frequency of 60 Hz; determined as follows:
23600/120 = 60Hz

POWER FACTOR
Power factor affects every operation with a 3-phase AC electrical supply to
some degree or other. Power factor is a measure of how efficiently electrical
power is consumed. The ideal power factor is unity, or one. Any thing less
than one, (or 100% efficiency), means that extra power is required to achieve
the actual task at hand. This extra power is known as Reactive Power, which
unfortunately is necessary to provide a magnetizing effect required by motors
and other inductive loads to perform their desired function. Reactive Power
can also be interpreted as wattles, magnetizing or wasted power and extra
burden on the electricity supply.

Power Factor correction is the term given to a technology that has been used
since the turn of the 20th century to restore power factor to as close to unity as
is economically viable. This is normally achieved by the addition of capacitors
to the electrical network which provide or compensate for the Reactive Power
demand of the inductive load, and thus reduce the burden on the supply.

Benefits of Power Factor Correction


Below are just some of the benefits that can be achieved by applying the
correct power factor correction:
 Power consumption reduced.
 Electricity bills reduced.
 Electricity energy efficiency improved.
 Extra KVA availability from the existing supply.
 Transformer & distribution equipment I2R losses reduced.
 Minimized voltage drop in long cables.

49
F.M.F
FOR TRAINING PURPOSE ONLY
How is power factor caused?
Most electrical equipment such as motors, compressors, welding sets and
even fluorescent lighting, create what's known as an inductive load on the
supply. An inductive load requires a magnetic field to operate, and in creating
such a magnetic field causes the current to lag the voltage ( ie. The current is
not in phase with the voltage).
Power factor correction is the process of compensating for the Lagging
current by applying a Leading current in the form of capacitors. This way
power factor is adjusted closer to unity and energy waste is minimized.

Power Factor Explained


AC power supplies comprise three main components:
Active power: The real, usable power measured in KW.
Reactive power: The part of the supply that creates the inductive load,
measured in KVAr (kilo-volt-amperes- reactive).
Apparent power: The resultant of the other two components, measured in
KVA (kilo-volt-amperes).
The power factor of a supply can be expressed in two ways:
1. Power factor = Active power (KW) / Apparent power (KVA)
2. the cosine of the angle between Apparent Power and Active Power is
expressed as the power factor (cos)

50
F.M.F
FOR TRAINING PURPOSE ONLY

Capacitive KVAr (Leading)

Active power KW

Inductive KVAr (Lagging)


Apparent Power KVA
Fig4.17.1

Fig 4.17.1 shows the phasor relationship between active, reactive and
apparent power:-
o Inductive KVAr lags the KW by 90.
o Apparent Power (KVA) is the phasor sum of +KVAr (lag).
o Power Factor is the cosine of angle ø .

Understanding Power Factor


A good analogy to help appreciate the affect of power factor on an electrical
network is to imagine a person running in the direction A to в
As shown in Fig4.17.2 below. The energy required certainly depends upon
the load that the person is carrying (weight) and the distance covered, but the
gradient of the running surface also influences the effort that is needed.

A Fig4.17.2 B

51
F.M.F
FOR TRAINING PURPOSE ONLY
When the running surface is flat, then angle ø is 00.
Cosine ø (00) = 1.00
Or efficiency = 100%
In other words, 100% of the energy burned is being used to move the
running form A to B.
But if the running surface is uphill as shown in Fig4.17.3 say at 300 to the
horizontal, then:
Cosine ø (300) = 0.87.
Or power factor = 0.87
Or efficiency = 87%
In other words, only 87% of the energy burned is being used to move the
runner in the horizontal direction of B, and so extra energy will be required
to achieve the same objective.

A B
Fig4.17.3

Example
A 100KW motor operates at a given power factor of 0.8 lagging. The total or
apparent power required by the motor is actually 100Kw / 0.8 = 125KVA By
improving the power factor of the load to close to unity, say 0.95, then the total
power drawn from the supply will be reduced to 105KVA (100KW / 0.95) A
total power reduction of 20KVA or an overall energy saving of 16%.

52
F.M.F
FOR TRAINING PURPOSE ONLY
The Hidden cost
Electrical networks with a poor power factor draw more power than is strictly
required, forcing electricity generators to increase output.
This extra power means extra generating costs which are subsequently
passed on to the industrial consumer in one form or another. However, due to
the wide variation in the way that industrial/commercial electricity tariffs are
presented, these extra costs or penalties for inefficient use of electricity are
not always readily apparent and sometimes only a power factor survey at the
main incoming electricity supply will determine the presence of a poor power
factor.

53
F.M.F
FOR TRAINING PURPOSE ONLY

A.C MOTORS
Introduction
Motor:-
It is a machine which converts electrical energy in to mechanical energy.
Most of the power-generating systems shore and afloat, produce ac. For this
reason a majority of the motors used throughout the Navy are designed to
operate on ac. There are other advantages in the use of ac motors besides
the wide availability of ac power. In general, ac motors cost less than dc
motors.
Some types of ac motors do not use brushes and commutators. This
eliminates many problems of maintenance and wear. It also eliminates the
problem of dangerous sparking.
An ac motors is well suited for constant-speed applications. This is because
its speed is determined by the frequency of the ac voltage applied to the
motor terminals.
Industry builds ac motors in different sizes, shapes, and ratings for many
different types of jobs. These motors are designed for use with either
polyphase or single-phase power systems.

LENZS LAW
When an electromagnetic force is applied in a conductor (stator), it produces a
current in that conductor and due to changing of current; it induces an other
current in the other conductor (rotor), which always opposes the main field
(stator). So there a torque produces and that is in opposite direction of the
main field.
PRINCIPLE OF INDUCTION MOTOR:-
The stator magnetic field rotates clockwise, cutting the loop as it does so. By
Faradays law this will induce a current in the loop, the direction of which is
given by Flemings Right Hand Rule.

54
F.M.F
FOR TRAINING PURPOSE ONLY

SYNCHRONOUS MOTORS
Basically it is an induction motor, but these motors are used where a constant
speed is required with the load changes. It has a strong power factor
(normally it is called unit power factor), having two fields one stator field
winding its input supply is 440v 60Hz 3phase and the other is rotor field
winding having 115v DC supply though slip rings. Fig4.18
Initially it is started as an induction motor with normal 440v and when it
reaches up to normal speed then applied a DC voltage on rotor winding
through slip rings. These voltages strengthening the rotor field and lock it
electrically at one speed. It is used in heavy load and with continuous run
such as propulsion of ships etc.

Stator Field

440v 60Hz 3ø

L1

L2
L3

Rotor Field

115 DC Supply

+ ve
-ve

Fig4.18 synchronous motor

55
F.M.F
FOR TRAINING PURPOSE ONLY
INDUCTION MOTOR
There are many types of induction motors,
Single phase AC motor
It has two windings connected 900 apart each other. One winding is called
start and other called running winding. One winding is directly connected with
power supply while the other winding is connected to the power supply via a
capacitor connected in series. Fig4.19
Capacitor gives a phase advance to split phase in both windings. So it
produces a torque to start the motor. These are used in portable fans, and
ceiling fans etc. These motors work on 115v, 220v 60Hz single phase supply.

Start Winding
L1

L2 C •

Running Winding

Fig4.19 Single phase AC motor

THREE PHASE AC MOTOR Fig4.19.1


It has three windings, are connected in 1200 apart from each other. Normally
the three phase AC motors are Star/Delta Fig4.19.2 connected with 440v, 3ø
60Hz and mostly the star connected motors are used on ships. These motors
are used as pumps motors, compressor motors; purifier motors and for
exhaust / supply fans etc.

56
F.M.F
FOR TRAINING PURPOSE ONLY

L1

L2 •
L3

Fig4.19.1 Three phase motor (Star connection)

L1 L2 L3
Fig4.19.2 Delta Connection

Important Electrical Terms


Insulation:-
The material which protects the leakage of current through a conductor which
is layered on conductor strain.
Continuity:-
If there is no breakage in a wire or conductor checked by AVO or Bridge
Megger giving Zero reading is called continuity.
Phase Balance:-
If resistance of all three windings of generator or motor having equal value
checked by AVO or Bridge megger is called phase balance.

57
F.M.F
FOR TRAINING PURPOSE ONLY
Single phasing effect:-
When one phase of a three phase motor is open or missing and two phases
are present there, it is called a single phasing effect. Due to this effect the
motor will burn.
Causes of single phase
1) One fuse blown.
2) Loose connection.
3) Unbalance line voltage.
4) One phase earthed.
Causes of motor burning
1- Due to dripping of water over the motors body.
2- Due to hard bearing.
3- Due to hard pump or fan impeller or any type of heavy load.
4- Due to single phasing effect.
5- Draw a heavy current due to short circuit in the body winding or in terminal
box.
6- Due to body deteriorated or life expired.
7- Due to low insulation of windings.
8- Due to loose connections.
Do not attempt to start the motor, if the motor fails to start twice, find out the
fault and then start the motor.

58
F.M.F
FOR TRAINING PURPOSE ONLY

References