This document provides lighting recommendations for various areas in health care premises, including waiting rooms, corridors, staff rooms, wards, examination rooms, operating rooms, laboratories, and more. For each area or task, it specifies the recommended minimum illuminance in lux (lx), maximum uniformity ratio (UGRL), and minimum average room surface reflectance (Ra). The illuminance levels range from 5 lx for night lighting to over 10,000 lx for operating cavities. The document seeks to provide adequate and appropriate lighting for tasks while preventing glare that could hinder examinations, treatments, or recovery.
This document provides lighting recommendations for various areas in health care premises, including waiting rooms, corridors, staff rooms, wards, examination rooms, operating rooms, laboratories, and more. For each area or task, it specifies the recommended minimum illuminance in lux (lx), maximum uniformity ratio (UGRL), and minimum average room surface reflectance (Ra). The illuminance levels range from 5 lx for night lighting to over 10,000 lx for operating cavities. The document seeks to provide adequate and appropriate lighting for tasks while preventing glare that could hinder examinations, treatments, or recovery.
Hak Cipta:
Attribution Non-Commercial (BY-NC)
Format Tersedia
Unduh sebagai PDF, TXT atau baca online dari Scribd
This document provides lighting recommendations for various areas in health care premises, including waiting rooms, corridors, staff rooms, wards, examination rooms, operating rooms, laboratories, and more. For each area or task, it specifies the recommended minimum illuminance in lux (lx), maximum uniformity ratio (UGRL), and minimum average room surface reflectance (Ra). The illuminance levels range from 5 lx for night lighting to over 10,000 lx for operating cavities. The document seeks to provide adequate and appropriate lighting for tasks while preventing glare that could hinder examinations, treatments, or recovery.
Hak Cipta:
Attribution Non-Commercial (BY-NC)
Format Tersedia
Unduh sebagai PDF, TXT atau baca online dari Scribd
Ref. no. Type of interior, task or activity m UGRL Ra Remarks
lx - -
7.11.1 General lighting 100 19 90 At floor level.
7.11.2 Simple examinations 300 19 90 At bed level. 7.11.3 Examination and treatment 1000 19 90 At bed level. 7.11.4 Night watch 20 19 90
7.12 Dentists
Ref. no. Type of interior, task or activity m UGRL Ra Remarks
lx - -
7.12.1 General lighting 500 19 90 Lighting should be glare-free for the
patient. 7.12.2 At the patient 1000 - 90 7.12.3 Operating cavity 5000 - 90 Values higher than 5000 lx may be required. 7.12.4 White teeth matching 5000 - 90 TCP ≥ 6000 K.
7.13 Laboratories and pharmacies
Ref. no. Type of interior, task or activity m UGRL Ra Remarks
lx - -
7.13.1 General lighting 500 19 80
7.13.2 Colour inspection 1000 19 90 TCP ≥ 6000 K.
7.14 Decontamination rooms
Ref. no. Type of interior, task or activity m UGRL Ra Remarks