01
Sign:
Name: Mr. Suresh V S
DOCUMENT REVIEW BY
Sign:
Name: Mr.A.Kaleel Ahmed, Mr. Suresh V S
TECHNICAL REVIEW BY
Sign:
Name: Mr. Suresh V S
PROCESS REVIEW BY
Sign:
Name: Mr.A.Kaleel Ahmed
APPROVED BY
Sign:
REVISION HISTORY
S. VER. SECTION (S) DESCRIPTION
VER. DATE CHANGED BY
NO. NO. CHANGED OF CHANGE
Initial version,
Panel Computer
August 2, 2010 Sathishkumar K NA
and SEP3
1 0.01 requirements
August 23, SEP2(OBCS)
Suresh V S 4.4
2010 requirements
August 23, SEP1(EO)
Kandasamy K 4.3
2010 requirements
Review comments
updated (Ref :
September 23,
2 0.02 Suresh V S 1,2,3 YEC1236/SDG/DR
2010
P(SRS)/0V02/2909
10)
Review committee
comment updated
Suresh V S,
October 8, (Ref :
3 0.03 Sathishkumar K, All
2010 YEC1236/SDG/DR
Kandasamy K
P(SRS)/0V05/0912
10)
Suresh V S,
December 10,
4 1.00 Sathishkumar K, All Released version.
2010
Kandasamy K
Customer
comments updated
Kandasamy K, in section 3.1.2,
5 1.01 March 4, 2011 All
Chitra C review of
document, final
formatting.
TABLE OF CONTENTS
1 INTRODUCTION................................................................................................................1
1.1 PURPOSE..................................................................................................................1
1.2 SCOPE.......................................................................................................................1
1.3 ACRONYMS...............................................................................................................1
1.4 REFERENCED DOCUMENTS...................................................................................2
1.5 DOCUMENT OVERVIEW...........................................................................................3
2 OVERALL DESCRIPTION.................................................................................................4
2.1 PRODUCT PERSPECTIVE........................................................................................4
2.1.1 PANEL COMPUTER............................................................................................5
2.1.2 SEP1 (ON - BOARD ELECTRICAL EQUIPMENT)..............................................5
2.1.3 SEP2 (ON-BOARD CONTROL SYSTEM)...........................................................5
2.2 OPERATING ENVIRONMENT...................................................................................6
2.3 PRODUCT FUNCTIONS............................................................................................7
2.4 USER CLASSES AND CHARACTERISTICS.............................................................8
2.5 APPORTIONING OF REQUIREMENTS.....................................................................9
2.6 ASSUMPTIONS AND DEPENDENCIES..................................................................11
3 SPECIFIC REQUIREMENTS...........................................................................................12
3.1 FUNCTIONAL REQUIREMENTS.............................................................................12
3.1.1 PANEL COMPUTER REQUIREMENTS............................................................12
3.1.1.1 SOFTWARE AUTHENTICATION................................................................13
3.1.1.2 SYSTEM CURRENT STATUS....................................................................14
3.1.1.3 POWER SUPPLY STATUS.........................................................................14
3.1.1.4 TEMPERATURE STATUS..........................................................................15
3.1.1.5 ENTRY INTO SYSTEM...............................................................................15
3.1.1.6 ADDITIONAL INFORMATION PROVIDED.................................................16
3.1.1.6.1 BOOKMARK SEQUENCE FOR SELF CHECK....................................19
3.1.1.6.2 BOOKMARK SEQUENCE FOR TYPE A.............................................19
3.1.1.6.3 BOOKMARK SEQUENCE FOR TYPE B.............................................20
3.1.1.7 OPERATIONAL TYPE SELECTION...........................................................20
3.1.1.7.1 SELF CHECK WITH EXTERNAL LOOP BACK...................................21
3.1.1.7.2 TYPE A (RUSSIAN ARTICLE).............................................................22
3.1.1.7.3 TYPE B (INDIAN ARTICLE).................................................................22
3.1.1.7.3.1 CONTROL.....................................................................................22
3.1.1.7.3.2 STAND OF THE PLANT CONTROL CK311 (СЗК СК311)............25
3.1.1.7.3.3 INWARD INSPECTION STAND (СВК/IGI STAND).......................26
1 INTRODUCTION
1.1 PURPOSE
This Software Requirements Specification (SRS) provides the detailed description of all the
functions used in Check-Out Equipment (COE) application and its requirements. It provides
a complete description of all the software requirements of COE application.
The expected audience of this document are review team, internal quality verification team,
and BrahMos team.
1.2 SCOPE
The Scope of this document is to provide the COE Application software requirements. The
requirements provided in this document includes,
• Functional Requirements of the four sub systems (Panel Computer - PC, On-Board
Electrical - SEP1, On-Board Control System - SEP2 and Self Control)
• Performance Requirements
• Design Constraint Requirements
• Software System Attribute Requirements
• External Interface Requirements
• Non Functional Requirements
1.3 ACRONYMS
The acronyms used in this document are listed in Table 1.1.
Table 1.1: ACRONYMS
ACRONYM DESCRIPTION
AMB Ampule Battery
COE Checkout Equipment
DUT Device Under Test
GPS Ground Power Supply
GUI Graphical User Interface
INS Inertial Navigation System
OBC On-Board Computer
OBCS On-Board Control System
OBE On-Board Electrical
PDU Power Distribution Unit
PLP Pre-Launch Phase
RGP Rate Gyro Package
SEP Special Execution Processor
SP Signal Power
TM Telemetry
WS Warhead Simulator
Section 1
This section deals with Introduction, purpose of the document, scope of the document,
acronyms used in this document, referenced documents and document overview.
Section 2
This section gives the overall description about the system including product perspective,
operating environment, product functions, user classes and characteristics, apportioning of
requirements, assumptions and dependencies.
Section 3
This section gives brief description of Specific Requirements including functional
requirements, SEP 1 requirements, SEP 2 requirements, SEP3 requirements, performance
requirements, design constraints, software system attributes, external interface
requirements and non functional requirements.
Section 4
This section gives the requirement traceability matrix along with list of checks and
description, Instruction for executing checks in self-check with loop-back mode , Instruction
for executing Type B checks in automatic mode.
2 OVERALL DESCRIPTION
2.1 PRODUCT PERSPECTIVE
The Check-Out Equipment has four sub-systems namely Panel Computer, Special
Execution Processors (SEP) 1, Special Execution Processors 2 and Special Execution
Processors 3 with its own processor and I/O cards. Each system runs in QNX Neutrino 6.x
real time OS. The four sub-systems communicates via Ethernet.
The Panel computer provides operator interface using Photon Micro GUI. It includes
display, keyboard, joystick and floppy. The panel computer is used as a user interface. The
panel computer will be used for,
1. Configuration of the test
2. Execution of test
3. Scheduling task for SEP's (SEP1, SEP2 and SC) to carryout the test
4. Collecting and displaying status of the test from SEP's to the user
5. Printing test results using the printer
6. Logging the test results
SEP1 will perform tests related to On-Board Electrical(OBE) equipments. The SEP1 will,
1. Monitor the dangerous signals periodically in 10ms interval. In case of emergency, it
will issue emergency shutdown of power supplies and “Termination” command to
stop execution in other subsystems.
2. Execute the tests related to SEP1 based on the request from Panel Computer.
3. Interface with Warhead Simulator, monitor the status of missile warhead signals and
simulate the warhead signal in simulation mode.
SEP2 will perform tests related to On-board Control System (OBCS). The SEP2 will,
1. Monitor the temperature in Instrument Bay (IB) periodically(10 ms) interval. In case
of emergency, it will issue “Termination” command to stop execution in other
subsystems.
2. Execute the tests related to SEP2 based on the request from Panel Computer.
3. Interface with Fin Simulator to simulate fin movement for validating the function of
SEP2 in absence of hydraulics input to missile actuator system.
S. No NAME DESCRIPTION
1 Operating System QNX 6.x
2 Processor Intel core i7 processor at 2.53 GHz, on-chip 4MB L2 cache
3 Bus Architecture VME
4 RAM Up to 8 GB DDR3 SDRAM
5 Video On-Board VGA up to 2048 X 1536 resolution
6 Joystick USB based
7 Keyboard USB based
8 Hard disk 8 GB solid state disk, IDE compact flash interface
3 SPECIFIC REQUIREMENTS
3.1 FUNCTIONAL REQUIREMENTS
This section gives the application specific requirements of COE application (Refer
Table 3.1).
Table 3.1: FUNCTIONAL REQUIREMENTS
S. NO IDENTIFICATION NUMBER REQUIREMENT
1 DP_COE_PC_REQ Panel Computer Operations
2 DP_COE_SEP1_REQ SEP1 Operations
3 DP_COE_SEP2_REQ SEP2 Operations
4 DP_COE_SEP3_REQ SEP3 Operations
Processing
1. The main window will display the type of article selected in “Enter into system” (refer
Section 3.1.1.5).
2. The current system time will be read and displayed
3. The current operation mode will be read and updated by the user.
Outputs
Current system status will be displayed.
1. Test Type - Self check or Type A or Type B).
2. Date and time - user input time or Current system time.
3. Mode of operation.
4. Alive status of SEP's (Self Check, SEP1 and SEP2) – Alive or Not Alive.
BOOKMARK
/ATTRIBUTE BOOKMARK/ATTRIBUTE CONTENTS REMARKS
NO.
SD (Pressure Sensors) "Control"
SD1 (Pressure Sensors)
KSSRS (Booster) (Multiple attributes can
Ish DRR (FIN Sensors) be selected)
6 Execution of self check К312 If Type of operation is
Presence of TSU (Telemetry) "СВК"
(Multiple attributes can
be selected)
7 Engine Related Parameter Numeric
T1 AMD (msec) : 0 to 999
T2 AMD (msec) : 0 to 999
T3 DCL (Sec) – (Response time) : 0 to 99
8 Attributes for INS testing Numeric
Enter INS Time code (sec) : 0 to 9999
(default value : 72)
Time T of warming (Sec) : 0 to 9999
(default value : 40)
Enter attributes of CK43 : 0 to 9999
(default value : 1)
9 Latitude deg.min.sec
eg) XXX.XX.XX (Range : ±90º)
10 Presence of sub-systems: (Multiple attributes can
Antenna AT-59 available (External antenna) be selected)
K312 is available (Seeker)
TM is available (Telemetry)
Presence of K323P (APSN - GPS)
11 Frequency Number Code: Numeric
No. of digits displayed : 4
Eg) XXXX
12 Inaccuracy of Leveling: Numeric
Alpha X (Code), Alpha Z(Code)
No. of digits displayed : 6
Eg) XXXXXX
13 Voltage Priming Selection
14 The azimuth of installation deg.min.sec
BOOKMARK
/ATTRIBUTE BOOKMARK/ATTRIBUTE CONTENTS REMARKS
NO.
±XXX.XX.XX - previous value should be
retained (Range : 0 ºC to 360 ºC)
15 Use the corrections from AI Selection
16 Updating PZ1 (FM1), PZ2 (FM2), KNK Numeric
(MINS), PZ3 (wave point data)
Word number (Max:143) : XXX
Value (6 digit) XXXXXX
17 Mode of recertification : Single Selection
1. RP
2. Recording of ADP of device К314-44
18 Enter the longitude deg.min.sec
eg) XXX.XX.XX
Enter the Altitude above the sea level (m)
and press the button NEXT
±XXXX.XXX
19 Display of parameters on screen in normal Selection
condition
20 Gravitational acceleration (m2/sec) Float value
eg) X.XXXXX
Processing
1. Depending on the Type of operation and attributes, the sequence of bookmark input
will be changed
2. The previous values of some additional inputs will be restored in next execution.
3. The additional information will be sent to all the three SEP's after configuring all
information.
4. For degree to radian conversion, the following convention factor will be used.
For negative value,
Radian value = (Degree value * 0.017453292519943) + (Minute value *
0.000290888208666) + (Second value * 0.000004848136811)
For positive value,
Radian value = (Degree value * 0.017453292519943) - (Minute value *
0.000290888208666) - (Second value * 0.000004848136811)
Output
The additional information will be displayed.
Note : *- bookmarks 15 and 16 will be opened while selecting the attribute "tuning of PLP
checking mode" = 1 in book mark 3. Refer Table 3.3.
Note : * bookmark 16 will be opened only while entering the Attribute “Tuning of PLP
checking mode” = 1 in bookmark 3. Refer Table 3.3.
Processing
The self test is to be performed in the sequence given in Table 3.8.
Table 3.8: COE SELF CHECK WITH EXTERNAL LOOP BACK
TEST NUMBER (IN
S. NO CHECK/OPERATION NAME
EXISTING S/W)
1. Checking potential monitoring circuit 304
2. Checking the correctness of measurement bridge 306
3. Checking the function of dangerous potentials 307
monitoring
4. Checking the functionality of 40 KΩ Measurement 308
Bridge
5. Checking the functionality of 1.5 KΩ Measurement 309
Bridge
6. Checking the control circuits of SEP1 320
Outputs
The test result will be displayed, logged and printed in panel computer (if required).
3.1.1.7.3.1 CONTROL
The tests to be executed in Selective Mode and Step by Step Mode are given in Table
3.12.
Table 3.12: LIST OF CYCLOGRAM (SELECTIVE MODE AND STEP BY STEP MODE)
S. NO TEST NUMBER (IN EXISTING SOFTWARE)
1. 1025, 1026, 1100, 1102, 1112, 1150, 1202, 1500, 1501, 1502, 1503, 1504,
1505, 1506, 1507, 1508, 1005, 1011, 1019, 1022, 1025, 1026, 1027, 1037,
1022*
(* Presence of TM =1)
Output
The test results will be displayed, logged and printed in panel computer (if required).
Output
The test results will be displayed, logged and printed in panel computer (if required).
Output
The test results will be displayed, logged and printed in panel computer (if required).
Processing
1. Checksum of the selected file will be displayed.
2. The tests to be executed in selective mode for loading of programs are given in
Table 3.17.
Output
The checksum of the selected file will be displayed to the user.
3.1.1.7.3.5 LOADING OF THE PASSPORT DATA INTO THE ARTICLE
Processing
The tests listed in Table 3.19 will be executed in selective mode for loading the programs.
Table 3.19: TEST EXECUTED FOR PASSPORT DATA LOADING
CHECK NUMBER
S.NO TEST/OPERATION NAME
(IN EXISTING SW)
1. Loading the PD in to the СК315-1 1503
2. Reading the PD of article in КПА СК351.1 1504
Output
The input given by user will be logged in a file.
Inputs
Attributes/sub-mode (Cyclic or Through)
Processing
1. According to the Article type, operational type and presence of sub system, the
cyclogram will be selected for execution.
2. If the sub-mode is Cyclic, test in the cyclogram will be executed twice.
3. If sub-mode is Through, Cyclogram with list of checks (say cyclogram 10 based on
input) will be executed. If any parameter fails in the test, the execution of current
test will be stopped and the next test in the cyclogram will be executed.
4. The following status will be updated during the execution of test.
a) Receive and display the current executing test with progress from SEP's.
b) Receive and display the first step and final step in the test from SEP's.
c) Receive and display the current step number with progress from SEP's.
d) NONORM (Not Normal) of test parameter should be highlighted.
Outputs
The test results will be displayed, logged and printed in panel computer (if required). If any
parameter fails in the test, it will be highlighted in red color.
Outputs
The test results will be displayed, logged and printed in panel computer (if required).
Requirement : DP_COE_PC_REQ_10_01
Description
For all tests, the parameter validation status will be logged in file. The results can be viewed
in future.
Inputs
The inputs for logging the reports are,
• Result of each parameter checks
• Kind of operation
• Mode of operation
• Additional information (AI) details
• Power supply status
Processing
1. For each test, the result will be logged with the parameter description.
2. AI Value will be logged for all the changes in the value during execution of test.
3. Power supply (SP, NI, OBESEP1, OBCSSEP2) status will be logged if there is any
change in present state power supply compared to previous state.
4. On any failure due to dangerous potentials or temperature, the failure result will be
printed.
5. The user name will be logged in the report.
6. Report files will be removed automatically after three months (if available).
7. The results will be logged in binary format and can be extracted to text format with
respect to user request.
SEP1 will run programs related to On-Board Equipment. It carries out testing of SEP1 units
with in DUT using Digital IO modules and Analog measurement modules. Panel computer
will initiate the execution of tests in SEP1 via Ethernet. It will send the status of parameter
tested via Ethernet and communicate with other SEP's for accessing the remote port data
through Ethernet.
TEST NO
IDENTIFICATION
S. NO REQUIREMENT (EXISTING
NUMBER
SYSTEM)
EQ_11 warhead simulator.
12. DP_COE_SEP1_R Discrete I/O Loop Back Check. -
EQ_12
TYPE B
13. DP_COE_SEP1_R Checking the insulation resistance 1004
EQ_13 and supply circuits.
14. DP_COE_SEP1_R Checking the pyro sources on 1030
EQ_14 commands of СК341-43.
15. DP_COE_SEP1_R Checking the pyro sources on 1032
EQ_15 commands of PTD-5М.
16. DP_COE_SEP1_R Checking the pyro sources on 1034
EQ_16 commands of COE СК351.1.
17. DP_COE_SEP1_R Checking BZP based on 1035
EQ_17 commands К310-61МЭ
18. DP_COE_SEP1_R Checking of On-board Automation 1036
EQ_18 Block.
19. DP_COE_SEP1_R Checking of Pressure restoration 1037
EQ_19 signaling device.
20. DP_COE_SEP1_R Checking Warhead circuits (BS). 1050
EQ_20
21. DP_COE_SEP1_R Checking inclined launch 1052
EQ_21 (КПМРК2).
22. DP_COE_SEP1_R Checking of КПНС1. 1054
EQ_22
23. DP_COE_SEP1_R Check of КПМРК1. 1060
EQ_23
24. DP_COE_SEP1_R Checking of КПНС2 1062
EQ_24
25. DP_COE_SEP1_R Checking the connection of AMB 1064
EQ_25 to SEP1 bus.
26. DP_COE_SEP1_R Checking the Launch Circuits on 1066
EQ_26 command РС.
27. TYPE A Checking the insulation resistance, 1072
TEST NO
IDENTIFICATION
S. NO REQUIREMENT (EXISTING
NUMBER
SYSTEM)
28. DP_COE_SEP1_R Checking the insulation resistance 4
EQ_28 and supply circuits
29. DP_COE_SEP1_R Checking the pyro sources on 30
EQ_29 commands of СК341-43
30. DP_COE_SEP1_R Checking the pyro sources on 32
EQ_30 commands of PTD-5М
31. DP_COE_SEP1_R Checking the pyro sources on 34
EQ_31 commands of COE СК351.1
32. DP_COE_SEP1_R Checking BZP on commands 35
EQ_32 К310-61МЭ
33. DP_COE_SEP1_R Checking of On-board Automation 36
EQ_33 Block
34. DP_COE_SEP1_R Checking of Pressure restoration 37
EQ_34 signaling device
35. DP_COE_SEP1_R Check of circuits of Warhead (BS) 50
EQ_35
36. DP_COE_SEP1_R Checking of inclined launch 52
EQ_36 (КПМРК2)
37. DP_COE_SEP1_R Checking of КПНС1 54
EQ_37
38. DP_COE_SEP1_R Check of КПМРК1 60
EQ_38
39. DP_COE_SEP1_R Checking of КПНС2 62
EQ_39
40. DP_COE_SEP1_R Checking the connection of AMB 64
EQ_40 to SEP1 bus
41. DP_COE_SEP1_R Checking the Launch Circuits on 66
EQ_41 command РС
42. DP_COE_SEP1_R Checking the insulation resistance, 72
EQ_42 initial condition of switching
elements and circuits of article
The list of dangerous signals at various cases are given in Table 3.24.
Table 3.24: LIST OF DANGEROUS SIGNAL MONITORED
S. NO. LIST OF CASES SIGNALS
1 Switch ON of COE E_AMB
E_UMIT
2 Switch ON of SP E_AMB
E_WU
E_PP
E_UMIT
E_AMB_MINUS
E_WU_MINUS
E_PP_MINUS
3 Switch ON of GPS E_AMB
E_WU
E_PP
E_NI_CORPUS
E_UMIT
Output:
The signal in which the voltage variation occur will be displayed in PC.
Output
Issue command to COE, to carryout the test if missile warhead is normal or the “termination
of check” will be issued to stop the test.
SIGNAL EXPECTED
PARAMETER SIGNAL NAME DESCRIPTION
TYPE STATUS
Battery(A)
26. E_PLUS_ZD_DMT_A DIP OFF + Activation of LTE (A)
27. E_PLUS_ZD_GGS_A DIP OFF + Activation of GGS
(A)
28. E_PLUS_ZD_GGS_B DIP OFF + Activation of GGS
(B)
29. E_ZD_BALL_TPS_A DIP OFF Activation of TLC(A)
bottle
30. E_ZD_BALL_TPS_B DIP OFF Activation of TLC (B)
bottle
31. E_PLUS_ZD_DMT_B DIP OFF + Activation of LTE(B)
32. E_ZD_DRK_A DIP OFF Activation of RCM (A)
Emergency
33. E_ZD_DRK_B DIP OFF Activation of RCM (B)
Combat
34. E_ZD_DREN_AMB_B DIP OFF Activation of AMB (B)
drainage
35. E_MINUS_ZD_DMT_ DIP OFF - Activation of LTE,
DBT_DRK_A HTE, RCM (A)
36. E_MINUS_ZD_GGS_ DIP OFF - Activation of GGS,
BALL_B bottles (B)
37. E_MINUS_ZD_DMT_ DIP OFF - Activation of LTE,
DBT_DRK_B HTE, RCM (B)
38. E_MINUS_ZD_GGS_ DIP OFF - Activation of GGS
BALL_A bottles (A)
39. E_PLUS_ZD_AMB_B DIP OFF + Activation of AMB (B)
40. E_RAZR_ST_A DIP OFF Launch permission (А)
41. E_PDKL_NI_BA DIP OFF Connection of GPS to
SEP1 bus
42. E_RAZR_ST_B DIP OFF Launch permission (B)
43. E_ZD_DREN_AMB_A Activation of AMB (A)
drainage
44. E_PDKL_S_AMB_S_ DIP OFF Connect bus AMB to
BA_A buses SEP1 (А)
45. E_OTKL_S_MD DIP OFF Switch OFF of MD bus
46. E_OTKL_S_PP_1_2 DIP OFF Switch OFF of pyros
buses
SIGNAL EXPECTED
PARAMETER SIGNAL NAME DESCRIPTION
TYPE STATUS
47. E_ZD_DBT_A DIP OFF Activation of HTE (A)
48. E_ZD_DBT_B DIP OFF Activation of HTE (B)
49. E_IMIT_SND_WIH DIP OFF Simulation of
command
50. E_IMIT_SWK_WH DIP OFF Simulation of “Out of
canister sensor”
51. E_IMIT_SWW_WH DIP OFF Simulation of “out of
water sensor”
52. E_IMIT_ND_SPS DIP OFF Simulation of SOM of
booster stage and
failure of valves
53. E_COM_STOP_WH DIP OFF Command (Stop)
54. E_COM_NAZAD_WH DIP OFF Command (Back)
55. E_WKL_KAN_B_WH DIP OFF Switch ON of channel
B
56. E_COM_MD_OTKL_ DIP OFF Switch OFF of
WH sustainer
command
57. E_COM_RPT_OTKL DIP OFF Command RPT Switch
OFF
58. E_COM_IMIT_DRR DIP OFF Command for
simulation of “FIN
unfolding sensor”
59. E_COM_SWD_BLOK DIP OFF Locking of Command
SWD
60. E_PDKL_S_AMB_S_ DIP OFF Connection of AMB
BA_B bus to the SEP1 bus
(B)
61. E_WKL_S_R DIP OFF Switch-ON of bus P
62. E_LG157 DIP OFF Reserve
63. E_IMIT_SDA_3_5 DIP OFF Simulator of absolute
pressure sensor 3-5
64. E_WKL_KAN_B DIP OFF Switch ON of channel
B
65. E_ISH_PWU DIP OFF Initial PTD
66. E_IMIT_SD_WH DIP OFF Simulation of SD
SIGNAL EXPECTED
PARAMETER SIGNAL NAME DESCRIPTION
TYPE STATUS
67. E_IMIT_SD_1_WH DIP OFF Simulation of SD1
68. E_PLUS_27_NI_I DIP OFF +27 V GPS
69. E_IMIT_T_5GRAD_C DIP OFF Simulation of t = 5
degrees
70. E_KS_SRS_WH DIP OFF
71. E_MINUS_OTM_ST_ DIP OFF - Cancellation of
A launch (A)
72. E_MINUS_OTM_ST_ DIP OFF + Cancellation of
A launch (A)
Outputs
The test results will be displayed, logged and printed in panel computer (if required).
Note
1. To test the insulation between the signals, the Measurement Bridge 40 KΩ will be
used. The output of bridge will be measured in ADC. The sequence for bridge
measurement is,
(a) Select Check Point 1 and 2
(b) Connect the Check Point 1 and 2 to Measurement Bridge
(c) Measure the bridge output. The output should be ranging 8.0V to 15.0V
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge
2. To test the continuity between the signals, the Measurement Bridge 1.5 KΩ will be
used. The output of bridge will be measured in ADC. The sequence for bridge
measurement is,
(a) Select Check Point 1 and 2
(b) Connect the Check Point 1 and 2 to Measurement Bridge
(c) Measure the bridge output. The output should be ranging -8.0V to -15.0V
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge
Outputs
The test results will be displayed, logged and printed in panel computer (if required).
Outputs
The test results will be displayed, logged and printed in panel computer (if required).
Note:
1. For checking the insulation between the signals, the Measurement Bridge of 40 KΩ
will be used. The output of bridge will be measured in ADC. The sequence for
bridge measurement includes the following steps,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to the Measurement Bridge.
(c) Measure the bridge output. The output should be ranging 8.0V to 15.0V.
(d) Disconnect the Check Point 1 and 2 from the Measurement Bridge.
Inputs
NA
Processing
1. Setting the 40KΩ Measurement Bridge into initial position.
(a) Issue command “Disconnection of Shunt Network”.
(b) Set the Check Points to initial position.
2. Setting the 40 KΩ Measurement bridge in operating condition.
(a) Read the input given to bridge and check whether it is in range of 23.0V to 25.0
V. If it is not within the range, stop the test.
(b) Feed 24V voltage to the Bridge and connect the diagonals to the meter.
The insulation between the signals will be verified by connecting the signals to
Check Points (CP1 & CP2) of 40 KΩ bridge (refer points 3 to 108 in Table 3.26).
The continuity between the signals will be verified by connecting the signals to
Check Points (CP1 & CP2) of 40 KΩ bridge. (refer points 109 to 161 in Table 3.26).
POINT CONNECTIVITY /
STEP DESCRIPTION SIGNALS
NO. DISCONNECTION
16 Check the decoupling between KT_MINUS_WU disconnection
CP (-)BU and CP (+)AMB KT_PLUS_AMB
17 Check the decoupling between KORPUS_OK disconnection
Body OK and CP (+)AMB KT_PLUS_AMB
18 Check the decoupling between PLUS_PP_AMB_A disconnection
bus (+)PP AMB(А) and CP KT_PLUS_AMB
(+)AMB
19 Check the decoupling between MINUS_PP_AMB_A disconnection
bus (-)PP AMB(А) and CP (+)AMB KT_PLUS_AMB
20 Check the decoupling between PLUS_PP_AMB_B disconnection
bus (+)PP AMB(Б) and CP KT_PLUS_AMB
(+)AMB
21 Check the decoupling between MINUS_PP_AMB_B disconnection
bus (-)PP AMB(Б) and CP (+)AMB KT_PLUS_AMB
22 Check the decoupling between PLUS_PP_DBT_A disconnection
bus (+)PP DBT(A) and CP KT_PLUS_AMB
(+)AMB
23 Check the decoupling between MINUS_PP_DBT_A disconnection
bus (-)PP DBT(A) and CP (+)AMB KT_PLUS_AMB
24 Check the decoupling between PLUS_PP_DBT_B disconnection
bus (+)PP DBT(B) and CP KT_PLUS_AMB
(+)AMB
25 Check the decoupling between MINUS_PP_DBT_B disconnection
bus (-)PP DBT(B) and CP (+)AMB KT_PLUS_AMB
26 Check the decoupling between PLUS_PP_GGS_A disconnection
bus (+)PP GGS(A) and CP KT_PLUS_AMB
(+)AMB
27 Checking the decoupling MINUS_PP_GGS_A disconnection
between bus (-) PP GGS(A) and KT_PLUS_AMB
CP (+)AMB
28 Checking the decoupling PLUS_PP_GGS_B disconnection
between bus (+) PP GGS(B) and KT_PLUS_AMB
CP (+)AMB
29 Checking the decoupling MINUS_PP_GGS_B disconnection
between bus (-) PP GGS(B) and KT_PLUS_AMB
CP (+)AMB
POINT CONNECTIVITY /
STEP DESCRIPTION SIGNALS
NO. DISCONNECTION
30 Checking the decoupling NI_27V_PLUS disconnection
between bus (+)27V GPS and KT_PLUS_AMB
CP (+)AMB
31 Checking the decoupling NI_27V_MINUS disconnection
between bus (-)27V GPS and KT_PLUS_AMB
CP (+)AMB
32 Checking the decoupling KT_BZP_APS disconnection
between CP BZP APS and CP KT_PLUS_AMB
(+)AMB
33 Checking the decoupling KT_BZP_TPS disconnection
between CP BZP TPS and CP KT_PLUS_AMB
(+)AMB
34 Checking the decoupling KT_PLUS_PP disconnection
between CP (+) PP and CP KT_PLUS_AMB
(+)AMB
35 Checking the decoupling between KT_MINUS_PP disconnection
CP (-) PP and CP (+)AMB KT_PLUS_AMB
36 Checking the decoupling KT_BZP2_NO_A1 disconnection
between CP BZP2 НО(А1) and KT_PLUS_AMB
CP (+)AMB
37 Checking the decoupling KT_BZP3_NO_A2 disconnection
between CP BZP3 NO(А2) and KT_PLUS_AMB
CP (+)AMB
38 Checking the decoupling between KT_BZP5A_NO_A3 disconnection
CP BZP5A(NO)A3 and CP KT_PLUS_AMB
(+)AMB
39 Checking the decoupling KT_BZP2_F3_A1 disconnection
between CP BZP2 F3(А1) and CP KT_PLUS_AMB
(+)AMB
40 Checking the decoupling KT_BZP2_F3_A3 disconnection
between CP BZP2 F3(А3) and CP KT_PLUS_AMB
(+)AMB
41 Checking the decoupling KT_BZP3_F3_A2 disconnection
between CP BZP3 F3(А2) and CP KT_PLUS_AMB
(+)AMB
42 Checking the decoupling KT_BZP3_F3_A4 disconnection
POINT CONNECTIVITY /
STEP DESCRIPTION SIGNALS
NO. DISCONNECTION
between CP BZP3 F3(А4) and CP KT_PLUS_AMB
(+)AMB
43 Checking the decoupling between KT_BBA disconnection
CP BBA and CP (+)AMB KT_PLUS_AMB
44 Checking the decoupling between KT_BZP5A_SRS_A1 disconnection
CP BZP5A SRS(А1) and CP KT_PLUS_AMB
(+)AMB
45 Checking the decoupling between KT_BZP3_SRS_A2 disconnection
CP BZP3 SRS(А2) and CP KT_PLUS_AMB
(+)AMB
46 Checking the decoupling between KT_BZP3_SRS_A3 disconnection
CP BZP3 SRS(А3) and CP KT_PLUS_AMB
(+)AMB
47 Checking the decoupling KT_BZP7_WNO disconnection
between CP BZP7 ВНО and KT_PLUS_AMB
CP (+)AMB
48 Checking the decoupling KT_PLUS_AMD disconnection
between CP "+" AMD and CP KT_PLUS_AMB
(+)AMB
49 Checking the decoupling KT_MINUS_AMD disconnection
between CP (-)AMB and CP KT_PLUS_AMB
(+)AMB
50 Checking the decoupling PLUS_PP_DRK_A disconnection
between bus (+) PP DRK(A) and KT_PLUS_AMB
CP (+)AMB
51 Checking the decoupling PLUS_PP_DRK_B disconnection
between bus (+) PP DRK(B) and KT_PLUS_AMB
CP (+)AMB
52 Checking the decoupling MINUS_PP_DRK_A disconnection
between bus (-) PP DRK(A) and KT_PLUS_AMB
CP (+)AMB
53 Checking the decoupling MINUS_PP_DRK_B disconnection
between bus (-) PP DRK(B) and KT_PLUS_AMB
CP (+)AMB
54 Checking the decoupling KT_PLUS_BA_B disconnection
between CP (+)SEP1(B) and KT_PLUS_AMB
POINT CONNECTIVITY /
STEP DESCRIPTION SIGNALS
NO. DISCONNECTION
CP (+)AMB
55 Checking the decoupling KT_MINUS_BA_B disconnection
between CP (-)SEP1(B) and KT_PLUS_AMB
CP (+)AMB
56 Checking the decoupling KT_PLUS_AMB disconnection
between CP (+) AMB and CP KT_MINUS_AMB
"-"AMB
57 Checking the decoupling KT_PLUS_AMB disconnection
between CP "+" AMB and CP KT_MINUS_AMB
"-"AMB
58 Checking the decoupling KT_PLUS_BA_A disconnection
between CP "+"SEP1(A) and KT_MINUS_AMB
CP "-"AMB
59 Checking the decoupling KT_MINUS_BA_A disconnection
between CP "-"SEP1(A) and KT_MINUS_AMB
CP "-"AMB
60 Checking the decoupling KT_PLUS_PP1_1_PP2 disconnection
between CP (+) PP1-1, PP2-1 _1
and CP "-"AMB KT_MINUS_AMB
61 Checking the decoupling KT_MINUS_PP1_1_PP disconnection
between CP "-" PP1-1, PP2-1 2_1
and CP "-" AMB KT_MINUS_AMB
62 Checking the decoupling KT_PLUS_PP1_2_PP2 disconnection
between CP "+" PP1-2, PP2-2 _2
and CP "-"AMB KT_MINUS_AMB
63 Checking the decoupling KT_MINUS_PP1_2_PP disconnection
between CP "-" PP1-2, PP2-2 2_2
and CP "-"AMB KT_MINUS_AMB
64 Checking the decoupling KT_PLUS_PP1_3_PP2 disconnection
between CP "+" PP1-3, PP2-3 _3
and CP "-"AMB KT_MINUS_AMB
65 Checking the decoupling KT_MINUS_PP1_3_PP disconnection
between CP "-" PP1-3, PP2-3 2_3
and CP "-"AMB KT_MINUS_AMB
66 Checking the decoupling KT_PLUS_PP1_4_PP2 disconnection
between CP "+"ПП1-4, PP2-4 _4
POINT CONNECTIVITY /
STEP DESCRIPTION SIGNALS
NO. DISCONNECTION
and CP "-"AMB KT_MINUS_AMB
67 Checking the decoupling KT_MINUS_PP1_4_PP disconnection
between CP "-"ПП1-4, PP2-4 2_4
and CP "-" AMB KT_MINUS_AMB
68 Checking the decoupling between KT_PLUS_WU disconnection
CP "+"BU and CP "-"AMB KT_MINUS_AMB
69 Checking the decoupling between KT_MINUS_WU disconnection
CP "-"BU and CP "-"AMB KT_MINUS_AMB
70 Checking the decoupling between KORPUS_OK disconnection
Body and CP "-"AMB KT_MINUS_AMB
71 Checking the decoupling between PLUS_PP_AMB_A disconnection
bus (+) PP AMB(А) and CP KT_MINUS_AMB
"-"AMB
72 Checking the decoupling between MINUS_PP_AMB_A disconnection
bus (-) PP AMB(А) and CP KT_MINUS_AMB
"-"AMB
73 Checking the decoupling between PLUS_PP_AMB_B disconnection
bus (+) PP AMB(Б) and CP KT_MINUS_AMB
"-"AMB
74 Checking the decoupling MINUS_PP_AMB_B disconnection
between bus (-) PP AMB(Б) and KT_MINUS_AMB
CP
"-"AMB
75 Checking the decoupling PLUS_PP_DBT_A disconnection
between bus (+) PP DBT(A) and KT_MINUS_AMB
CP "-"AMB
76 Checking the decoupling MINUS_PP_DBT_A disconnection
between bus (-) PP DBT(A) and KT_MINUS_AMB
CP "-" AMB
77 Checking the decoupling PLUS_PP_DBT_B disconnection
between bus (+) PP DBT(B) and KT_MINUS_AMB
CP
"-"AMB
78 Checking the decoupling MINUS_PP_DBT_B disconnection
between bus (-) PP DBT(B) and KT_MINUS_AMB
CP "-" AMB
POINT CONNECTIVITY /
STEP DESCRIPTION SIGNALS
NO. DISCONNECTION
79 Checking the decoupling PLUS_PP_GGS_A disconnection
between bus (+) PP GGS(A) and KT_MINUS_AMB
CP "-"AMB
80 Checking the decoupling MINUS_PP_GGS_A disconnection
between bus (-) PP GGS(A) and KT_MINUS_AMB
CP "-"AMB
81 Checking the decoupling PLUS_PP_GGS_B disconnection
between bus (+) PP GGS(B) and KT_MINUS_AMB
CP "-"AMB
82 Checking the decoupling MINUS_PP_GGS_B disconnection
between bus (-) PP GGS(B) and KT_MINUS_AMB
CP "-"AMB
83 Checking the decoupling between NI_27V_PLUS disconnection
bus (+) 27V GPS and CP "-" AMB KT_MINUS_AMB
84 Checking the decoupling between NI_27V_MINUS disconnection
bus "-" 27V GPS and CP "-" AMB KT_MINUS_AMB
85 Checking the decoupling between KT_BZP_APS disconnection
CP BZP APS and CP "- KT_MINUS_AMB
"AMB
86 Checking the decoupling between KT_BZP_TPS disconnection
CP BZP TPS and CP "-"AMB KT_MINUS_AMB
87 Checking the decoupling between KT_PLUS_PP disconnection
CP (+) PP and CP "-"AMB KT_MINUS_AMB
88 Checking the decoupling between KT_MINUS_PP disconnection
CP (-) PP and CP "-"AMB KT_MINUS_AMB
89 Checking the decoupling KT_BZP2_NO_A1 disconnection
between CP BZP2 НО(А1) and KT_MINUS_AMB
CP "-" AMB
90 Checking the decoupling KT_BZP3_NO_A2 disconnection
between CP BZP3 NO(А2) and KT_MINUS_AMB
CP "-" AMB
91 Checking the decoupling between KT_BZP5A_NO_A3 disconnection
CP BZP5A(NO)A3 and CP "-" KT_MINUS_AMB
AMB
92 Checking the decoupling KT_BZP2_F3_A1 disconnection
between CP BZP2 F3(А1) and CP KT_MINUS_AMB
POINT CONNECTIVITY /
STEP DESCRIPTION SIGNALS
NO. DISCONNECTION
"-" AMB
93 Checking the decoupling KT_BZP2_F3_A3 disconnection
between CP BZP2 F3(А3) and CP KT_MINUS_AMB
"-" AMB
94 Checking the decoupling KT_BZP3_F3_A2 disconnection
between CP BZP3 F3(А2) and CP KT_MINUS_AMB
"-" AMB
95 Checking the decoupling KT_BZP3_F3_A4 disconnection
between CP BZP3 F3(А4) and CP KT_MINUS_AMB
"-" AMB
96 Checking the decoupling between KT_BBA disconnection
CP BBA and CP "-"AMB KT_MINUS_AMB
97 Checking the decoupling between KT_BZP5A_SRS_A1 disconnection
CP BZP5A SRS(А1) and CP "-" KT_MINUS_AMB
AMB
98 Checking the decoupling between KT_BZP3_SRS_A2 disconnection
CP BZP3 SRS(А2) and CP "-" KT_MINUS_AMB
AMB
99 Checking the decoupling between KT_BZP3_SRS_A3 disconnection
CP BZP3 SRS(А3) and CP "-" KT_MINUS_AMB
AMB
100 Checking the decoupling KT_BZP7_WNO disconnection
between CP BZP7 ВНО and CP KT_MINUS_AMB
"-"AMB
101 Checking decoupling between CP KT_PLUS_AMD disconnection
"+" AMD and CP "-" AMB KT_MINUS_AMB
102 Checking decoupling between CP KT_MINUS_AMD disconnection
"-" AMD and CP "-" AMB KT_MINUS_AMB
103 Checking decoupling between PLUS_PP_DRK_A disconnection
bus (+) PP DRK(A) and CP KT_MINUS_AMB
"-"AMB
104 Checking decoupling between PLUS_PP_DRK_B disconnection
bus (+) PP DRK(B) and CP KT_MINUS_AMB
"-"AMB
105 Checking the decoupling MINUS_PP_DRK_A disconnection
between bus (-) PP DRK(A) and KT_MINUS_AMB
POINT CONNECTIVITY /
STEP DESCRIPTION SIGNALS
NO. DISCONNECTION
CP "-"AMB
106 Checking the decoupling MINUS_PP_DRK_B disconnection
between bus (-) PP DRK(B) and KT_MINUS_AMB
CP "-"AMB
107 Checking decoupling between CP KT_PLUS_BA_B disconnection
"+"SEP1(B) and CP "-"AMB KT_MINUS_AMB
108 Checking decoupling between CP KT_MINUS_BA_B disconnection
"-"SEP1(B) and CP "-"AMB KT_MINUS_AMB
CHECKING CONTINUITY BETWEEN THE SIGNALS
109 Check the message CP (+)AMB KT_PLUS_AMB connectivity
KT_PLUS_AMB
110 Check the message CP (-)AMB KT_MINUS_AMB connectivity
KT_MINUS_AMB
111 Check the message CP +SEP1(A) KT_PLUS_BA_A connectivity
KT_PLUS_BA_A
112 Check the message CP -SEP1(A) KT_MINUS_BA_A connectivity
KT_MINUS_BA_A
113 Check the message CP (+)PP1-1, KT_PLUS_PP1_1_PP2 connectivity
PP2-1 _1
KT_PLUS_PP1_1_PP2
_1
114 Check the message CP (-)PP1-1, KT_MINUS_PP1_1_PP connectivity
PP2-2 2_1
KT_MINUS_PP1_1_PP
2_1
115 Check the message CP (+)PP1-2, KT_PLUS_PP1_2_PP2 connectivity
PP2-2 _2
KT_PLUS_PP1_2_PP2
_2
116 Check the message CP (-)PP1-2, KT_MINUS_PP1_2_PP connectivity
PP2-2 2_2
KT_MINUS_PP1_2_PP
2_2
117 Check the message CP (+)PP1-3, KT_PLUS_PP1_3_PP2 connectivity
PP2-3 _3
KT_PLUS_PP1_3_PP2
POINT CONNECTIVITY /
STEP DESCRIPTION SIGNALS
NO. DISCONNECTION
_3
118 Check the message CP (-)PP1-3, KT_MINUS_PP1_3_PP connectivity
PP2-3 2_3
KT_MINUS_PP1_3_PP
2_3
119 Check the message CP (+)PP1-4, KT_PLUS_PP1_4_PP2 connectivity
PP2-4 _4
KT_PLUS_PP1_4_PP2
_4
120 Check the message CP (-)PP1-4, KT_MINUS_PP1_4_PP connectivity
PP2-4 2_4
KT_MINUS_PP1_4_PP
2_4
121 Check the message CP (+) BU KT_PLUS_WU connectivity
KT_PLUS_WU
122 Check the message CP (-)BU KT_MINUS_WU connectivity
KT_MINUS_WU
123 Check the message Body OK KORPUS_OK connectivity
KORPUS_OK
124 Check the message bus (+)PP PLUS_PP_AMB_A connectivity
AMB(А) PLUS_PP_AMB_A
125 Check the message bus (-)PP MINUS_PP_AMB_A connectivity
AMB(А) MINUS_PP_AMB_A
126 Check the message bus (+)PP PLUS_PP_AMB_B connectivity
AMB(Б) PLUS_PP_AMB_B
127 Check the message bus (-)PP MINUS_PP_AMB_B connectivity
AMB(Б) MINUS_PP_AMB_B
128 Check the message bus (+)PP PLUS_PP_DBT_A connectivity
DBT(A) PLUS_PP_DBT_A
129 Check the message bus (-)PP MINUS_PP_DBT_A connectivity
DBT(A) MINUS_PP_DBT_A
130 Check the message bus (+)PP PLUS_PP_DBT_B connectivity
DBT(B) PLUS_PP_DBT_B
131 Check the message bus (-)PP MINUS_PP_DBT_B connectivity
DBT(B) MINUS_PP_DBT_B
132 Check the message bus (+)PP PLUS_PP_GGS_A connectivity
POINT CONNECTIVITY /
STEP DESCRIPTION SIGNALS
NO. DISCONNECTION
GGS(A) PLUS_PP_GGS_A
133 Check the message bus (-)PP MINUS_PP_GGS_A connectivity
GGS(A) MINUS_PP_GGS_A
134 Check the message bus (+)PP PLUS_PP_GGS_B connectivity
GGS(B) PLUS_PP_GGS_B
135 Check the message bus (-)PP MINUS_PP_GGS_B connectivity
GGS(B) MINUS_PP_GGS_B
136 Check the message bus (+)27V NI_27V_PLUS connectivity
GPS NI_27V_PLUS
137 Check the message bus (-)27V NI_27V_MINUS connectivity
GPS NI_27V_MINUS
138 Check the message CP KT_BZP_APS connectivity
BZP(APS) KT_BZP_APS
139 Check the message CP KT_BZP_TPS connectivity
BZP(TPS) KT_BZP_TPS
140 Check the message CP (+)PP KT_PLUS_PP connectivity
KT_PLUS_PP
141 Check the message CP (-)PP KT_MINUS_PP connectivity
KT_MINUS_PP
142 Check the message CP KT_BZP2_NO_A1 connectivity
BZP2(NО)А1 KT_BZP2_NO_A1
143 Check the message CP KT_BZP3_NO_A2 connectivity
BZP2(НО)А2 KT_BZP3_NO_A2
144 Check the message CP KT_BZP5A_NO_A3 connectivity
BZP5A(NO)A3 KT_BZP5A_NO_A3
145 Check the message CP KT_BZP2_F3_A1 connectivity
BZP2(F3)A1 KT_BZP2_F3_A1
146 Check the message CP KT_BZP2_F3_A3 connectivity
BZP2(F3)А3 KT_BZP2_F3_A3
147 Check the message CP KT_BZP3_F3_A2 connectivity
BZP3(F3)A2 KT_BZP3_F3_A2
148 Check the message CP KT_BZP3_F3_A4 connectivity
BZP3(F3)A4 KT_BZP3_F3_A4
149 Check the message CP BBA KT_BBA connectivity
KT_BBA
150 Check the message CP BZP5A KT_BZP5A_SRS_A1 connectivity
POINT CONNECTIVITY /
STEP DESCRIPTION SIGNALS
NO. DISCONNECTION
SRS А1 KT_BZP5A_SRS_A1
151 Check the message CP BZP3 KT_BZP3_SRS_A2 connectivity
SRS A2 KT_BZP3_SRS_A2
152 Check the message CP BZP3 KT_BZP3_SRS_A3 connectivity
SRS(A3) KT_BZP3_SRS_A3
153 Check the message CP BZP7 KT_BZP7_WNO connectivity
ВНО KT_BZP7_WNO
154 Check the message CP +AMD KT_PLUS_AMD connectivity
KT_PLUS_AMD
155 Check the message CP -AMD KT_MINUS_AMD connectivity
KT_MINUS_AMD
156 Check the message bus (+)PP PLUS_PP_DRK_A connectivity
DRK(A) PLUS_PP_DRK_A
157 Check the message bus (+)PP PLUS_PP_DRK_B connectivity
DRK(B) PLUS_PP_DRK_B
158 Check the message bus (-)PP MINUS_PP_DRK_A connectivity
DRK(A) MINUS_PP_DRK_A
159 Check the message bus (-)PP MINUS_PP_DRK_B connectivity
DRK(B) MINUS_PP_DRK_B
160 Check the message CP +SEP1(B) KT_PLUS_BA_B connectivity
KT_PLUS_BA_B
161 Check the message CP -SEP1(B) KT_MINUS_BA_B connectivity
KT_MINUS_BA_B
Outputs
The test results will be displayed, logged and printed in panel computer (if required).
Note
1. For checking the insulation between the signals, the Measurement Bridge 1.5 KΩ
will be used. The output of bridge will be measured in ADC. The sequence for
bridge measurement includes the following steps,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output will be ranging 8.0V to 16.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
2. For checking the continuity between the signals the Measurement Bridge 1.5 KΩ will
be used. The output of bridge will be measured in ADC. The sequence for bridge
measurement is given below,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output shall be in range -8.0V to -16.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
Inputs
NA
Processing
1. Set the 1.5 KΩ Measurement Bridge into initial position.
(a) Issue command “Disconnection of Shunt Network”.
(b) Set the Check Points to initial position.
2. Set the 1.5 KΩ Measurement Bridge to operating condition.
(a) Read the input to bridge and check whether it is ranging 23.5V to
24.5 V. If it is not within the range, stop the test.
(b) Feed 24V voltage to the Bridge and connect the diagonals to the
meter.
3. Refer Table 3.26 to verify the insulation and continuity between the
signals using 1.5 KΩ bridge.
4. Set the bridge 1.5 KΩ to initial condition.
Outputs
The test results will be displayed, logged and printed in panel computer (if required).
2. For checking the continuity between the signals the Measurement Bridge 1.5 KΩ will
be used. The output of bridge will be measured in ADC. The sequence for bridge
measurement includes the following steps,
(a) Select the Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output should be in range -0.1V to -14.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
Inputs
• Work type
• Control program number if mode is control
• Attribute – dangerous current control line(If checking with dangerous signals)
Processing
1. The initial operation for this test will be,
a) This test should not be performed if the “GPS bus” is switched ON.
b) This test should not be performed if the article is Type A.
c) Issue the command “Disconnect shunt network” (E_OTKL_SHUNT).
d) Set the Check Points to initial position (ISHOD_POL_1).
2. Set the Measurement Bridge (40 KΩ and 1.5 KΩ) in operating condition.
a) Read the input to bridge (E_UMIT) and check whether it is within the range
of 23.0 V to 25.0 V. If it is not within the range, stop the test.
CONNECTIVITY /
S.NO. STEP DESCRIPTION SIGNALS
DISCONNECTION
3 Decoupling of (+) SEP1(А) and KT_PLUS_BA_A disconnection
Body KORPUS_OK
4 Decoupling of Body and (+) KORPUS_OK disconnection
SEP1(А) KT_PLUS_BA_A
5 Decoupling of Body and (-) KORPUS_OK disconnection
SEP1(А) KT_MINUS_BA_A
6 Decoupling Body and (+) 27V KORPUS_OK disconnection
GPS NI_27V_PLUS
7 Decoupling of Body and (-)27V KORPUS_OK disconnection
GPS NI_27V_MINUS
8 Decoupling of (+) 27V GPS NI_27V_PLUS disconnection
and Body KORPUS_OK
9 Decoupling of (-) 27V GPS and NI_27V_MINUS disconnection
Body KORPUS_OK
Note:
1. For checking the insulation between the signals the Measurement Bridge 1.5 KΩ will
be used. The output of bridge will be measured in ADC. The sequence for bridge
measurement is given below,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output shall be in range 0.1V to 14.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
2. For checking the continuity between the signals the Measurement Bridge 1.5 KΩ will
be used. The output of bridge will be measured in ADC. The sequence for bridge
measurement is given below,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output shall be in range -0.1V to -14.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
Inputs
• Work type
• Control program number if mode is control
• Attribute – dangerous current control line(If checking with dangerous signals)
Processing
1. The initial operation for this test will be,
(a) This test should not be performed if the article is Type A.
(b) This test should not be performed if attribute “X2 is connected” is not
selected and input signal for “X2 is connected” (C_X2_SOSTIK) is
not present.
(c) Reset the limits of dangerous signals (Remove the dangerous signals
from monitoring list).
2. Set the Measurement Bridge (40 KΩ and 1.5 KΩ) into operating
condition.
Note:
1. For checking the insulation between the signals the Measurement Bridge 1.5 KΩ will
be used. The output of bridge will be measured in ADC. The sequence for bridge
measurement is given below,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output shall be in range 0.1V to 12.5V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
2. For checking the continuity between the signals the Measurement Bridge 1.5 KΩ will
be used. The output of bridge will be measured in ADC. The sequence for bridge
measurement is given below,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output shall be in range -0.1V to -12.5V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
Processing
1. This test should not be performed if the article is Type A.
2. This test should not be performed if attribute “Simulation of Fin sensor” is
present.
3. This test should not be performed if attribute “X2 is docked” is not
selected and input signal C_X2_SOSTIK is not present.
4. Analysis for the presence of attribute “Dangerous current line control”.
(a) Stop the test if attribute “Dangerous current line control” is selected
and if the signal for “Dangerous current line control” is absent
(b) If attribute “Dangerous current line control” is not selected and if the
signal for “Dangerous current line control” is present.
5. Analysis for the presence of attribute “Additional inputs”
(a) The test shall be stopped on following conditions,
Table 3.31: CONDITIONS FOR THE HALT OFTEST
ATTRIBUTE “DANGEROUS SIGNAL FOR ATTRIBUTE
ATTRIBUTE “RPP”
CURRENT LINE CONTROL” “RPP”
1 1 0
1 0 1
0 1 0
0 1 1
0 0 1
6. Set the Measurement Bridge (40 KΩ and 1.5 KΩ) into operating
condition.
(a) Reset the limits of dangerous signals (Remove the dangerous signals
from monitoring list).
(b) Read the input to bridge and check whether it is in range of 23.5 V to
24.5 V. If it is not within the range, stop the test.
(c) Feed 24V voltage to the Bridge and connect the diagonals to the
meter.
7. Set the Measurement Bridge (40 KΩ and 1.5 KΩ) into initial position
(a) Set the check points to initial position (ISHOD_POL_1).
(b) Issue and remove the signals connection of CP1 and CP2 on Bridge
1.5 KΩ .
Software Requirements Specification March 04, 2010
Confidential
Version 1.01 Page 74 of 330
YEC1236/SDG/SRS/1V01/DRAFT
(c) Issue and remove command “Initial of PTD”.
(d) Issue and remove the command “Cancellation of start A”.
8. Checking the presence of signal "Absence of liquid in TLC”
(a) In presence absence of attribute “RPP”, the presence of signal
“Liquid in TLC is absent” is verified.
(b) In presence / absence of attribute “RPP”, the absence of signal
"Liquid in TLC is absent” is verified.
9. Issue the command “BACK” (E_COM_NAZAD).
10. The commands of PTD (for Steps 10 – 27, 31, 33, 34 in Table 3.32) will
be verified using following sequence.
(a) Issue and removal of the signal “Switch ON channel B”
(E_WKL_KAN_B_WIH). Which initiates sending of PTD of the next
matrix command in duration of 1.1 s.
(b) The connectivity between Check Points will be monitored after
issuing command PTD.
(c) The decoupling between Check Points will be monitored after
removal of command PTD automatically after 1.1 seconds. Refer
Table 3.32.
(c) If attribute “Dangerous current line control” is present and attribute for
“Presence of booster” is present then the decoupling of check points
will be monitored.
STEP COMMAND PTD KT CONNECTIVITY /
NO. DISCONNECTION
ISSUE REMOVE (1.1 SEC)
29 4AА - KT_PLUS_PP1_1_P KT_MINUS_PP1_1 Disconnection
P2_1 _PP2_1
KT_PLUS_PP1_2_P KT_MINUS_PP1_2 Disconnection
P2_2 _PP2_2
KT_PLUS_PP1_3_P KT_MINUS_PP1_3 Disconnection
P2_3 _PP2_3
KT_PLUS_PP1_4_P KT_MINUS_PP1_4 Disconnection
P2_4 _PP2_4
(d) If attribute “Dangerous current line control” is present and attribute for
“presence of booster” is absent,the connectivity between check
points PP1-2 and decoupling of check points PP3-4 will be done.
2. For checking the continuity between the signals the Measurement Bridge 1.5 KΩ will
be used. The output of bridge will be measured in ADC. The sequence for bridge
measurement includes the following steps,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output shall be in range -0.1V to -14.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
Inputs
• Work type
• Attribute – dangerous current control line(If checking with dangerous signals)
• Attribute RPP
Processing
1. This test should not be performed for Type A article.
2. This test should not be performed if attribute “Simulation of Fin sensor” is
present.
3. Analysis of presence of “dangerous current control line” will be done. The
test will stop if the below conditions are true.
(a) If attribute “dangerous current line control” is selected and the signal for
“dangerous current line control” is absent.
(b) If attribute “dangerous current line control” is not selected and the signal
for “dangerous current line control” is present.
4. Analysis for the presence of attribute “RPP” will be done.
CONNECTIVITY /
S.NO COMMAND STATUS CHECK POINTS
DISCONNECTION
1 E_ZAD_DRK_A TRUE Disconnection PLUS_PP_DRK_A and
MINUS_PP_DRK_A
E_MINUS_ZAD_DM TRUE PLUS_PP_DRK_B and
T_DBT_DRK_A MINUS_PP_DRK_B
2 E_ZAD_DRK_A FALSE Disconnection PLUS_PP_DRK_A and
MINUS_PP_DRK_A
E_MINUS_ZAD_DM FALSE PLUS_PP_DRK_B and
T_DRK_DRK_A MINUS_PP_DRK_B
3 E_ZAD_DRK_B TRUE Disconnection PLUS_PP_DRK_A and
MINUS_PP_DRK_A
E_MINUS_ZAD_DM TRUE PLUS_PP_DRK_B and
T_DBT_DRK_B MINUS_PP_DRK_B
4 E_ZAD_DRK_B FALSE Disconnection PLUS_PP_DRK_A and
MINUS_PP_DRK_A
E_MINUS_ZAD_DM FALSE PLUS_PP_DRK_B and
T_DBT_DRK_B MINUS_PP_DRK_B
11. Send command "Activation of DRK(A)(B)" and check dis connectivity after
sending commands and disconnection after removal of command.
S.NO COMMAND STATU CONNECTIVITY / CHECK POINTS
S DISCONNECTION
1 E_ZAD_DBT_A TRUE Disconnection PLUS_PP_DBT_A and
MINUS_PP_DBT_A
E_MINUS_ZAD_D TRUE PLUS_PP_DBT_B and
MT_DBT_DRK_A MINUS_PP_DBT_B
PLUS_PP_DRK_A and
MINUS_PP_DRK_A
PLUS_PP_DRK_B and
MINUS_PP_DRK_B
2 E_ZAD_DBT_A FALSE Disconnection PLUS_PP_DBT_A and
MINUS_PP_DBT_A
E_MINUS_ZAD_D FALSE PLUS_PP_DBT_B and
MT_DBT_DRK_A MINUS_PP_DBT_B
PLUS_PP_DRK_A and
MINUS_PP_DRK_A
PLUS_PP_DRK_B and
MINUS_PP_DRK_B
(a) If the attribute “dangerous current line control” is present, go to Step 19.
In absence of “dangerous current line control” attribute, go to Step 13.
16. Send command "Activation of DRK(A)(B)" and check for disconnection after
sending the command and disconnection after removal of command.
S.NO COMMAND STATUS CONNECTIVITY / SIGNALS
DISCONNECTION
1 E_ZAD_DBT_A TRUE Disconnection PLUS_PP_DBT_A and
MINUS_PP_DBT_A
E_MINUS_ZAD_D TRUE PLUS_PP_DBT_B and
MT_DBT_DRK_A MINUS_PP_DBT_B
PLUS_PP_DRK_A and
MINUS_PP_DRK_A
PLUS_PP_DRK_B and
MINUS_PP_DRK_B
2 E_ZAD_DBT_A FALSE Disconnection PLUS_PP_DBT_A and
MINUS_PP_DBT_A
E_MINUS_ZAD_D FALSE PLUS_PP_DBT_B and
MT_DBT_DRK_A MINUS_PP_DBT_B
PLUS_PP_DRK_A and
MINUS_PP_DRK_A
PLUS_PP_DRK_B and
MINUS_PP_DRK_B
3 E_ZAD_DBT_B TRUE Disconnection PLUS_PP_DBT_A and
MINUS_PP_DBT_A
PLUS_PP_DBT_B and
MINUS_PP_DBT_B
E_MINUS_ZAD_D TRUE PLUS_PP_DRK_A and
MT_DBT_DRK_B MINUS_PP_DRK_A
PLUS_PP_DRK_B and
MINUS_PP_DRK_B
4 E_ZAD_DBT_B FALSE Disconnection PLUS_PP_DBT_A and
MINUS_PP_DBT_A
PLUS_PP_DBT_B and
MINUS_PP_DBT_B
E_MINUS_ZAD_D FALSE PLUS_PP_DRK_A and
MT_DBT_DRK_B MINUS_PP_DRK_A
PLUS_PP_DRK_B and
MINUS_PP_DRK_B
CONNECTIVITY /
S.NO COMMAND STATUS CHECK POINTS
DISCONNECTION
1 E_ZAD_DBT_A TRUE Connectivity PLUS_PP_DBT_A and
MINUS_PP_DBT_A
E_MINUS_ZAD_DM TRUE PLUS_PP_DBT_B and
T_DBT_DRK_A MINUS_PP_DBT_B
PLUS_PP_DRK_A and
MINUS_PP_DRK_A
PLUS_PP_DRK_B and
MINUS_PP_DRK_B
2 E_ZAD_DBT_A FALSE Disconnection PLUS_PP_DBT_A and
MINUS_PP_DBT_A
E_MINUS_ZAD_DM FALSE PLUS_PP_DBT_B and
T_DBT_DRK_A MINUS_PP_DBT_B
PLUS_PP_DRK_A and
MINUS_PP_DRK_A
PLUS_PP_DRK_B and
MINUS_PP_DRK_B
3 E_ZAD_DBT_B TRUE Connectivity PLUS_PP_DBT_A and
MINUS_PP_DBT_A
PLUS_PP_DBT_B and
MINUS_PP_DBT_B
E_MINUS_ZAD_DM TRUE PLUS_PP_DRK_A and
T_DBT_DRK_B MINUS_PP_DRK_A
PLUS_PP_DRK_B and
MINUS_PP_DRK_B
4 E_ZAD_DBT_B FALSE Disconnection PLUS_PP_DBT_A and
MINUS_PP_DBT_A
PLUS_PP_DBT_B and
MINUS_PP_DBT_B
E_MINUS_ZAD_DM FALSE PLUS_PP_DRK_A and
T_DBT_DRK_B MINUS_PP_DRK_A
PLUS_PP_DRK_B and
MINUS_PP_DRK_B
_BALL_A and
MINUS_PP_GGS_B
3 E_ZAD_GGS_B TRUE Connectivity PLUS_PP_GGS_A,MI
NUS_PP_GGS_A
E_MINUS_ZAD_GGS TRUE PLUS_PP_GGS_B,MI
_BALL_B NUS_PP_GGS_B
4 E_ZAD_GGS_B FALSE Disconnection PLUS_PP_GGS_A,MI
NUS_PP_GGS_A
E_MINUS_ZAD_GGS FALSE PLUS_PP_GGS_B,MI
_BALL_B NUS_PP_GGS_B
20. Send command "Activation of bottle TPS(А)(B)" and check for connectivity of
check points after sending commands and disconnection of check points
after removal of command.
CONNECTIVITY /
S.NO COMMAND STATUS CHECKPOINTS
DISCONNECTION
1 E_ZAD_BALL_TPS_ TRUE Connectivity PLUS_PP_GGS_A and
A MINUS_PP_GGS_A
E_MINUS_ZAD_GG TRUE PLUS_PP_GGS_B and
S_BALL_A MINUS_PP_GGS_B
2 E_ZAD_BALL_TPS_ FALSE Disconnection PLUS_PP_GGS_A and
A MINUS_PP_GGS_A
E_MINUS_ZAD_GG FALSE PLUS_PP_GGS_B and
S_BALL_A MINUS_PP_GGS_B
3 E_ZAD_BALL_TPS_ TRUE Connectivity PLUS_PP_GGS_A and
B MINUS_PP_GGS_A
E_MINUS_ZAD_GG TRUE PLUS_PP_GGS_B and
S_BALL_B MINUS_PP_GGS_B
4 E_ZAD_BALL_TPS_ FALSE Disconnection PLUS_PP_GGS_A and
B MINUS_PP_GGS_A
E_MINUS_ZAD_GG FALSE PLUS_PP_GGS_B and
S_BALL_B MINUS_PP_GGS_B
(d) Check the decoupling between the signal after removal of command.
S.NO COMMAND STATUS CONNECTIVITY / SIGNALS
DISCONNECTION
1 E_IMIT_SDA3_5 FALSE Dis Connectivity PLUS_PP_GGS_A and
MINUS_PP_GGS_A
PLUS_PP_GGS_B and
MINUS_PP_GGS_B
(a) If attribute “dangerous current control line” is not selected, check the
decoupling between the signals.
S.NO COMMAND STATUS CONNECTIVITY / SIGNALS
DISCONNECTION
1 E_ZAD_AMB_ TRUE Disconnection PLUS_PP_AMB_A and
A MINUS_PP_AMB_A
PLUS_PP_AMB_B and
MINUS_PP_AMB_B
(c) Check the decoupling between the signal after removal of command.
(d) If attribute “dangerous current control line” is not selected, check the
decoupling between the signals.
S.NO COMMAND STATUS CONNECTIVITY / SIGNALS
DISCONNECTION
1 E_ZAD_AMB_B TRUE Disconnection PLUS_PP_AMB_A and
MINUS_PP_AMB_A
PLUS_PP_AMB_B and
MINUS_PP_AMB_B
(f) Check the decoupling between the signal after removal of command.
S.NO COMMAND STATUS CONNECTIVITY / SIGNALS
DISCONNECTION
1 E_ZAD_AMB_B FALSE Disconnection PLUS_PP_AMB_A and
MINUS_PP_AMB_A
PLUS_PP_AMB_B and
MINUS_PP_AMB_B
(b) If the attribute “dangerous current control line” is selected, check the
connectivity between the signals.
S.NO COMMAND STATUS CONNECTIVITY / SIGNALS
DISCONNECTION
1 E_ZAD_DRN_A TRUE Connectivity PLUS_PP_AMB_A and
MB_A MINUS_PP_AMB_A
PLUS_PP_AMB_B and
MINUS_PP_AMB_B
(c) Check the decoupling between the signal after removal of command.
S.NO COMMAND STATUS CONNECTIVITY / SIGNALS
DISCONNECTION
1 E_ZAD_DRN_A FALSE Disconnection PLUS_PP_AMB_A and
MB_A MINUS_PP_AMB_A
PLUS_PP_AMB_B and
MINUS_PP_AMB_B
(d) If attribute “dangerous current control line” is not selected, check the
decoupling between the signals.
S.NO COMMAND STATUS CONNECTIVITY / SIGNALS
DISCONNECTION
1 E_ZAD_DRN_A TRUE Disconnection PLUS_PP_AMB_A and
MB_B MINUS_PP_AMB_A
PLUS_PP_AMB_B and
MINUS_PP_AMB_B
(f) Check the decoupling between the signal after removal of command.
S.NO COMMAND STATUS CONNECTIVITY / SIGNALS
DISCONNECTION
1 E_ZAD_DRN_A FALSE Disconnection PLUS_PP_AMB_A and
MB_B MINUS_PP_AMB_A
PLUS_PP_AMB_B and
MINUS_PP_AMB_B
25. Reserved.
26. Send command "Activation of GGS(A)(B)" and check for connectivity of
check points after sending commands and disconnection of check points
after removal of command.
(a) If signal C_X2_SOSTIK (X2 is docked) is present, check the decoupling
between the signals.
S.NO COMMAND STATUS CONNECTIVITY / CHECK POINTS
DISCONNECTION
1 E_ZAD_GGS_A TRUE Disconnection PLUS_PP_GGS_A and
MINUS_PP_GGS_A
E_MINUS_ZAD_GGS TRUE PLUS_PP_GGS_B and
_BALL_A MINUS_PP_GGS_B
(b) If attribute “dangerous current control line” is not selected and signal “X2
is docked” is not present, check the decoupling between the signals.
(c) If attribute “dangerous current control line” is selected and signal “X2 is
docked” is not present, check the connectivity between the signals.
S.NO COMMAND STATUS CONNECTIVITY / SIGNALS
DISCONNECTION
1 E_ZAD_GGS_A TRUE Connectivity PLUS_PP_GGS_A and
MINUS_PP_GGS_A
E_MINUS_ZAD_ TRUE PLUS_PP_GGS_B and
GGS_BALL_A MINUS_PP_GGS_B
31. Reserved
32. Issue command "Activation AMB(А)(B)"
(a) If signal “X2 is docked” is present, check the decoupling between the
signals.
S.NO COMMAND STATU CONNECTIVITY / SIGNALS
S DISCONNECTION
1 E_ZAD_AMB_A TRUE Disconnection PLUS_PP_AMB_A and
MINUS_PP_AMB_A
PLUS_PP_AMB_B and
MINUS_PP_AMB_B
(b) If attribute “dangerous current control line” is not selected and signal “X2
is docked” is not present, check the decoupling between the signals.
S.NO COMMAND STATU CONNECTIVITY / SIGNALS
S DISCONNECTION
1 E_ZAD_AMB_A TRUE Disconnection PLUS_PP_AMB_A and
MINUS_PP_AMB_A
PLUS_PP_AMB_B and
MINUS_PP_AMB_B
(c) If attribute “dangerous current control line” is selected and signal “X2 is
docked” is not present, check the connectivity between the signals.
(b) If attribute “dangerous current control line” is not selected and signal “X2
is docked” is not present, check the decoupling between the signals,
S.NO COMMAND STATUS CONNECTIVITY / SIGNALS
DISCONNECTION
1 E_ZAD_BALL_ TRUE Disconnection PLUS_PP_GGS_A and
TPS_A MINUS_PP_GGS_A
E_MINUS_ZAD TRUE PLUS_PP_GGS_B and
_GGS_BALL_A MINUS_PP_GGS_B
(c) If attribute “dangerous current control line” is selected and signal “X2 is
docked” is not present, check the connectivity between the signals.
S.NO COMMAND STATUS CONNECTIVITY / SIGNALS
DISCONNECTION
1 E_ZAD_BALL_ TRUE Connectivity PLUS_PP_GGS_A and
TPS_A MINUS_PP_GGS_A
E_MINUS_ZAD TRUE PLUS_PP_GGS_B and
_GGS_BALL_A MINUS_PP_GGS_B
41. Reserved
42. Set the bridges (1.5KΩ) into initial position.
(a) Set the check point to initial position.
(b) Issue and remove the signals connection of CP1 and CP2 on bridge 1.5
KΩ and Initial of PTD. Send and remove the command “Cancel of start
A(E_OTM_ST_A_WIH and E_OTM_ST_A”
(c) Check the disconnection between the signals.
43. Set the limits for the dangerous signals (Add the dangerous signals to the
monitoring list)
Outputs
The test results will be displayed, logged and printed in panel computer (if required).
Note
1. For checking the insulation between the signals, Measurement Bridge 1.5 KΩ will be
used. The output of bridge will be measured in ADC. The sequence for bridge
measurement includes the following steps,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output shall be in range 0.1V to 14.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
2. For checking the continuity between the signals the Measurement Bridge 1.5 KΩ will
be used. The output of bridge will be measured in ADC. The sequence for bridge
measurement includes the following steps,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output shall be in range -0.1V to -14.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
Inputs
• Work type
• Attribute – dangerous current control line(If checking with dangerous signals)
• Control programmer number
• Attribute – RPP
• Attribute “Technological article”
Processing
1. This test should not be performed if the article is Type A.
2. Verify the following attributes to continue the execution of test.
(a) The test should be performed only in the presence of attribute
“Technological article”.
(b) The test should be performed only if “Control program number” is 3.
(c) The test should be performed only in the absence of signal
“C_X2_SOSTIK”.
16. Set the limits for the dangerous signals (Add the dangerous signals to
the monitoring list).
Outputs
The test results will be displayed, logged and printed in panel computer (if required).
Note:
For S.No. 10 and 20 (Refer Table 3.34) time AMD is verified. If the time for change of
status of expected signal is not 0 < t1, Т1AMD < 26 or 199 < t1, Т1AMD < 226 or 99 <
t2,Т2АМD < 126, the status is set as not normal
Outputs
The test results will be displayed, logged and printed in panel computer (if required).
Note:
1. For checking the insulation between the signals, Measurement Bridge 1.5 KΩ will be
used. The output of bridge will be measured in ADC. The sequence for bridge
measurement includes the following steps,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output will be in range 0.1V to 14.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
2. For checking the continuity between the signals, Measurement Bridge 1.5 KΩ will be
used. The output of bridge will be measured in ADC. The sequence for bridge
measurement includes the following steps,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output will be in range -0.1V to -14.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
Inputs
Additional Information
Processing
1. The initial attributes will be verified.
(a) This test should not be performed if the article is Type A.
(b) This test should not be performed if the control program number is 2 or 3.
(c) Check for presence of attributes given in below table.
S.NO. DESCRIPTION
1. Presence of attribute “RPP”
2. Presence of attribute “Liquid in TLC is absent”
3. Presence of attribute "Simulator of BS"
4. Presence of "Attribute 1 BS"
5. Presence of "Attribute 2 BS"
37. Remove the command "Connection of AMB to SEP1 bus (A)" and
"Connection of AMB to SEP1 bus".
38. Verify the disconnection of РА1-4 of MIU through SEP2.
39. Verify the removal of command "FD" to MIU through SEP2.
40. Verify the removal of command "BFD" to MIU through SEP2.
41. Verify the removal of command "680" to MIU through SEP2.
42. Verify the removal of command "KL" to MIU through SEP2.
43. Removal of command "simulation of CND", "Simulation of СВК" and
“Simulation of NDSRS and failure of FANS”.
44. Issue and remove “Switch ON of bus P”.
45. Issue and remove command “Cancellation of start (А)” and “Switch OFF of
MD bus”.
46. Verify the absence of signals Stop, Back, Normal, Close and Launch
Permitted(A) B).
Note:
1. For checking the insulation between the signals, the Measurement Bridge 1.5 KΩ
will be used. The output of bridge will be measured in ADC. The sequence for
bridge measurement includes the following steps,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output will be in range 0.1V to 14.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
2. For checking the continuity between the signals the Measurement Bridge 1.5 KΩ will
be used. The output of bridge will be measured in ADC. The sequence for bridge
measurement includes the following steps,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
Inputs
Work type
Processing
1. This test should not be performed if the article is Type A.
2. Analyze the attribute of “Fin sensor”, “hydro system”.
(a) This test should not be performed if attribute “X2 is connected” is not
selected and input signal for “X2 is connected” of SEP3 is not
present.
(b) This test should not be performed in presence of attributes
“Simulation of Fin sensor” and “Hydro System”.
3. Set the bridge 1.5 KΩ to operating condition.
(a) Read the input to bridge and check whether it is in range 23.5 to 24.5
V. If it is not in the range, stop the test.
4. Analyze the presence of attribute “dangerous current control line”.
(a) The test will be stopped if attribute “Dangerous current control line” is
selected and if input signal for “Dangerous current control line” is
absent.
(b) The test will be stopped if attribute “Dangerous current control line” is
not selected and if input signal for “Dangerous current control line” is
present.
5. Check for the absence of voltage (0V) on AMB buses, with the tolerance
limit of (+/- 0.5 V).
6. Feed 24V voltage to the Bridge and connected the diagonals to the
meter.
7. Set SEP1 and PTD into initial position.
(a) Set the check point to initial position.
(b) Issue and remove the signals connection of CP1 and CP2 on bridge
1.5 KΩ and bridge 40 KΩ.
(c) Issue and remove command “Initial of PTD”.
(d) Issue and remove command “Cancel of start A”.
8. Check of presence of signal "АМB heated”.
9. Check the decoupling / connectivity between signals given in below
table.
10. Check the absence of signals "Stop", "Back", "Close", "Normal", "Launch
permitted (A)(B)"
11. Verify the issue of command "Command НС” through SEP2.
12. Check the presence of signal “Permission НС” through SEP2.
13. Verify the issue and remove command “Switch OFF of bus MD“.
(a) Issue command “Switch OFF of bus MD“ (E_COM_MD_OTKL).
(b) The test will be stopped if the signal “Switch OFF of bus MD” is not
present.
(c) Remove command “Switch OFF of bus MD”.
(d) The test will be stopped if the signal “Switch OFF of bus MD” is
present.
(e) Remove command “MD bus Switch OFF“ (E_OTKL_MD).
(f) Remove command “Disconnection of bus PP1,2”.
25. Verify the absence of signals “Stop”, “Back”, ”Close” and presence of
“Normal”, “Launch permitted (A)(B)”.
26. Issue command "ОА1" and check the presence of <KND>, <СВК1> and
absence of <Вкл.ДБТ> through SEP2.
27. Check the presence <СВК1>,<Вкл.ДБТ> and remove <KND>.
28. Issue and remove the command "Switch ON bus Р”.
29. Verify the absence of signals “Stop”, “Back”, ”Close” and presence of
“Normal”, “Launch permitted (A)(B)”.
30. Check the disconnection / continuity between CP (+)(-)AMB and CP (+)
(-)BU.
Outputs
The test results will be displayed, logged and printed in panel computer (if required).
Inputs
Work type
Input parameters
Processing
1. This test should not be performed if the article is Type A.
2. Analyze the presence / absence of input attributes.
(a) This test should not be performed if the attribute “Simulation of FIN
sensors” is selected.
(b) This test should not be performed if attribute “X2 is docked” is not
selected and input signal for “X2 is docked” is not present.
(c) This test should not be performed if attribute for presence of “Hydro
system” is selected.
3. Set Bridge 1.5 KΩ into operating condition.
(a) Read the input to bridge and check whether it is in range 23.5 to
24.5V. If it is not in range, stop the test.
(b) Read the voltage on AMB bus and check whether it is in range -0.5 to
0.5 V. If it is not in range, stop the test.
4. Analyze the presence of attribute “Dangerous current control line”.
(a) If attribute “dangerous current control line” is selected and if input
signal for “Dangerous current control line” is absent, stop the test.
25. Check the absence of signal “Stop”, “Back”, “Close” and presence of
“Normal”, “Launch permitted (A)(B)”.
26. Check the messages between CP (+),(-)PP AMB and CP (+),(-)BU.
(a) If Control program number is 1, check the connectivity between the
signals.
STEP STEP DESCRIPTION SIGNAL CONNECTIVITY /
NO. DISCONNECTION
33 Message (+)AMB and CP (+) KT_PLUS_AMB Connectivity
BU KT_PLUS_WU
Message CP (-)BU and (-)AMB KT_MINUS_WU Connectivity
KT_MINUS_AMB
If attribute for “dangerous current line control” is absent, check the decoupling between the
signals,
STEP STEP DESCRIPTION SIGNAL CONNECTIVITY /
NO. DISCONNECTION
39 Decoupling (+)AMB and CP (+) KT_PLUS_AMB Disconnection
BU KT_PLUS_WU
Decoupling CP (-)BU and (-)AMB KT_MINUS_WU Disconnection
KT_MINUS_AMB
37. Check the presence of signals "Close", "Normal", "Launch permitted (A)
(B)" and absence of “Stop”, “Back”.
38. Remove command “switch ON bus Р”.
39. Check the presence of "Stop", "Back", "Normal", “Launch permitted (A)
(B)” and absence of “Close”.
40. Send command "680" using SEP2.
41. Similar to Step 48
42. Similar to Step 10
43. Similar to Step 12
44. Similar to Step 11
45. Similar to Step 20
46. Remove command "680" of MIU through SEP2.
47. Send command "KPZ" of MIU through SEP2
48. Check messages between (+)AMB and CP (+) BU.
MIN MAX
1 PA1 -2.5 2.5
2 PA2 -2.5 2.5
3 PA3 -2.5 2.5
4 PA4 -2.5 2.5
2. For checking the continuity between the signals the Measurement Bridge 1.5 KΩ will
be used. The output of bridge will be measured in ADC. The sequence for bridge
measurement includes the following steps,
(a) Select Check Point 1 and 2
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output will be in range -0.1V to -14.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
Inputs
Work type
Processing
1. This test should not be performed if the article is Type A.
2. Analyze attribute “Control program number of BS”.
(a) If the control program number is not 1 or 3, the test should not be
performed
3. Checking the presence warhead attributes.
(a) Read the presence of signal E_PRZN_RSZ_WH. Attribute for
presence of “RPP”.
(b) Read the attribute “RPP”.
(c) Read the presence of signal E_JIDK_TPS_OTST. Attribute for the
presence of “Liquid in TLC is absent”.
(d) Verify the presence of signals "Simulator of BS", "Attribute 1 BS",
"Attribute 2 BS".
4. Analyze the attributes “X2 is docked”.
(a) This test should not be performed if attribute “X2 is docked” is not
selected and input signal C_X2_SOSTIK is not present.
15. Send command "Connect AMB to SEP1(A)" and verify the presence of
signal "AMB connected".
16. Check presence of voltages on AMB(24.0 to 30.0V) bus and absence of
voltage in BU(-0.3 to 0.3V) bus.
17. Issue the command "Simulation of command".
18. Check passage of signal KND using SEP2.
19. Send command "Simulation of СВК".
20. Check the presence of signals "KND", "СВК1" using SEP2.
21. Send command ОА1 using SEP2.
22. Check the absence of signal KND using SEP2.
23. Check the presence of signal “СВК1”, “Вкл.ДБТ” and absence of signal
“KND" using SEP2.
24. Check voltages on buses BU.
25. Send command "Simulation of acceleration".
(a) Set the signal E_BLOK_KPA_BS as True.
(b) Read the input signal E_KPA_BS_ZABLOK. If it is False, set the
signal E_IMIT_PERGR_K as True.
(c) If E_KPA_BS_ZABLOK is True, stop the test.
26. Send command "Simulation of Booster".
27. Check presence of "Simulation of Booster", <СВК>, <Вкл.ДБТ> and
absence of <KND> using SEP2.
28. Check presence of <Вкл.ДБТ>, "Simulation of Booster" and absence of
<СВК1>, <KND> using SEP2
29. Check the presence of signal <Stop>,<Back>,<OK> and absence of
“Close”, “Launch permitted (A)(B)”.
30. Send command "Permission to activate BU" using SEP2.
31. Send command "Send command "FD" using SEP2.
32. Send command "BFD" using SEP2.
33. Send command "680" using SEP2.
34. Check the presence of signal “Stop”, “Back” and absence of “Normal”,
“Close”, “Launch permitted (A)(B)”
35. Send command "ДП(M30_M05)" using SEP2.
36. Send command "KL" using SEP2.
37. Check of signal "Correctness of BS".
38. Check for connection of "Connection IRA (Fin Simulator)" using SEP2.
55. Check for the absence of voltage in AMB(-0.3 to 0.3V) bus and BU(-0.3
to 0.3V) bus.
56. Check the decoupling between CP +,(-)PP AMB and CP +,(-)PP .
S.NO STEP DESCRIPTION SIGNAL CONNECTIVITY / DISCONNECTION
1 Decoupling of KT_PLUS_AMB Disconnection
(+)AMB and CP KT_PLUS_PP
(+)PP
Decoupling of CP KT_MINUS_PP Disconnection
(-)PP and (-)AMB KT_MINUS_AMB
Note:
1. For checking the insulation between the signals the Measurement Bridge 40 KΩ will
be used. The output of bridge will be measured in ADC. The sequence for bridge
measurement includes the following steps,
(a) Select Check Point 1 and 2
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output will be in range 0.1V to 14.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
2. For checking the continuity between the signals the Measurement Bridge 1.5 KΩ will
be used. The output of bridge will be measured in ADC. The sequence for bridge
measurement includes the following steps,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge.
(c) Measure the bridge output. The output will be in range -0.1V to -14.0V.
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge.
3. For checking the insulation between the signals the Measurement Bridge 1.5 KΩ will
be used for the parameter 51. The sequence for bridge measurement includes the
following steps,
(a) Select Check Point 1 and 2.
(b) Connect the Check Point 1 and 2 to Measurement Bridge
(c) If the INS code if 72, the measurement bridge output is read after time exposure
of T3 AMD or measure the bridge output after 3 seconds. The output should be
in range 0.1V to 14.0V
(d) Disconnect the Check Point 1 and 2 from Measurement Bridge
Input
Work type
(b) If the work type is other than self check with external connections, read
the control program number for warhead(BS). If the number is 1 perform
step (i) and if the number is 3 perform step (ii).
i. Verify the status of following signals of warhead if BS = 1.
S.NO. SIGNAL NAME SIG TYPE STATUS PARAMETER DESCRIPTION
1. E_PRZN_1_BS DIP ON Presence of “Attribute
1 BS”
2. E_PRZN_2_BS DIP ON Presence of “Attribute
2 BS”
3. E_PRZN_2_BS_ DIP ON Presence of “Attribute
KPA 2 BS (COE)(К)”
4. E_ISHODNOE_B DIP ON Presence of “Initial
S BS“
5. E_IMITATOR_BS DIP ON Presence of
“Simulator of BS”
6. E_ZPR_PR_1_K DOP ON Issue of "Query of
program 1"
7. E_RAZR_PR_UK DIP ON Checking the
BS presence <Permission
for check>
(b) The test will be stop stopped if attribute “RPP” is not normal.
ATTRIBUTE “RPP” SIGNAL FOR PRESENCE OF OPERATION
“RPP”
1 0 Stop the test
1 1 Perform step 11
0 1 Stop the test
8. The insulation between the check points given in below table will be verified.
S.NO. STEP DESCRIPTION CHECK POINTS CONNECTIVITY /
DISCONNECTION
1. Check the decoupling between KT_PLUS_BA_A Disconnection
CP +SEP1(A) and bus (+)27V NI_27V_PLUS
GPS
2. Check the decoupling between KT_MINUS_BA_A Disconnection
CP -SEP1(A) and bus (-)27V NI_27V_MINUS
GPS
3. Check the decoupling between KT_PLUS_BA_A Disconnection
CP +SEP1(A) and Body KORPUS_OK
4. Check the decoupling between KORPUS_OK Disconnection
Body and CP +SEP1(A) KT_PLUS_BA_A
5. Check the decoupling between KORPUS_OK Disconnection
Body and CP -SEP1(A) KT_MINUS_BA_A
6. Check the decoupling between KORPUS_OK Disconnection
Body and bus (+)27V GPS NI_27V_PLUS
7. Check the decoupling between KORPUS_OK Disconnection
Body and bus (-)27V GPS NI_27V_MINUS
8. Check the decoupling between NI_27V_PLUS Disconnection
bus (+)27V GPS and Body KORPUS_OK
(a) If work type is CK311 / K312 go to Step 549, else go to Step 14.
10. The insulation between the following check points will be verified.
12. The insulation between the 27V GPS and Body will be verified.
S. STEP DESCRIPTION CHECK POINTS CONNECTIVITY /
NO. DISCONNECTION
1 Decoupling of +PP PLUS_PP_DRK_A Disconnection
DRK(А) and BBA KT_BBA
15. The “Dangerous Circuits Normal” will be set only if insulation of all the signals
are normal.
16. Remove voltage from bridge and disconnect the diagonals from meter.
17. Remove the command “Disconnect shunt network”.
CHECK NO
REQUIREMENT
S. NO REQUIREMENT (EXISTING
IDENTIFICATION NUMBER
SYSTEM)
CHECK NO
REQUIREMENT
S. NO REQUIREMENT (EXISTING
IDENTIFICATION NUMBER
SYSTEM)
command issued by
MIU(СК314-43).
11. DP_COE_SEP2_REQ_11 Checking the integrity of 1012
actuator circuits.
12. DP_COE_SEP2_REQ_12 Checking actuator 1014
deflection as per MIU
signals.
13. DP_COE_SEP2_REQ_13 Checking RGP sensor 1016
device.
14. DP_COE_SEP2_REQ_14 Checking Radio Altimeter 1019
device.
15. DP_COE_SEP2_REQ_15 Checking Russian 1020
Telemetry device
16. DP_COE_SEP2_REQ_16 Checking of device 1022
АСОНД-Ц through M1 & M3
buses.
17. DP_COE_SEP2_REQ_17 INS integrated check. 1024
18. DP_COE_SEP2_REQ_18 Checking INS. 1025
19. DP_COE_SEP2_REQ_19 Checking OBC. 1026
20. DP_COE_SEP2_REQ_20 Checking GPS. 1027
21. DP_COE_SEP2_REQ_21 Checking command 1046
receiving unit of MIU.
22. DP_COE_SEP2_REQ_22 Checking PLP mode. 1202
23. DP_COE_SEP2_REQ_23 Loading program in to OBC. 1500
24. DP_COE_SEP2_REQ_24 Reading and checking sum 1505
of the executable programs
in CK315-1.
25. DP_COE_SEP2_REQ_25 Loading Passport Data of 1503
“type B” article in to OBC.
26. DP_COE_SEP2_REQ_26 Reading the Passport Data 1504
of the “type B” article from
OBC.
27. DP_COE_SEP2_REQ_27 Program loading in to the 1501
devices К312-10В.
28. DP_COE_SEP2_REQ_28 Program loading in to the 1502
devices К312-10A.
29. DP_COE_SEP2_REQ_29 Program for Counting and 1506
Checking sum of the
executable Program in
CHECK NO
REQUIREMENT
S. NO REQUIREMENT (EXISTING
IDENTIFICATION NUMBER
SYSTEM)
K312-10B.
30. DP_COE_SEP2_REQ_30 Program for Counting and 1507
Checking sum of the
executable Program in
K312-10B.
31. DP_COE_SEP2_REQ_31 Writing data and Program in 1508
to the device CK314-1
32. DP_COE_SEP2_REQ_32 Loading of program or 1509/1510
almanac in to the device
K323-1.
SEEKER
33. DP_COE_SEP2_REQ_33 Check of antenna device 1100
K312.
34. DP_COE_SEP2_REQ_34 Check receiving channel of 1102
K312.
35. DP_COE_SEP2_REQ_35 Check support signals, 1110
issued by system К312.
36. DP_COE_SEP2_REQ_36 Check of transmitting device 1112
K312.
37. DP_COE_SEP2_REQ_37 Check of modes «О», «З» 1150
and «С» of system К312.
38. DP_COE_SEP2_REQ_38 Check telemetry signals of 1160
system К312.
TYPE A CHECKS
39. DP_COE_SEP2_REQ_39 Checking external 10
command of device MIU.
40. DP_COE_SEP2_REQ_40 Check the integrity of 12
actuator circuits.
41. DP_COE_SEP2_REQ_41 Checking actuator 14
deflection as per MIU
signals
42. DP_COE_SEP2_REQ_42 Checking RGP sensor 16
device
43. DP_COE_SEP2_REQ_43 Checking Radio Altimeter 19
device
44. DP_COE_SEP2_REQ_44 Checking Russian 20
Telemetry device
45. DP_COE_SEP2_REQ_45 INS integrated check 24
46. DP_COE_SEP2_REQ_46 Checking command 46
receiving unit of MIU
CHECK NO
REQUIREMENT
S. NO REQUIREMENT (EXISTING
IDENTIFICATION NUMBER
SYSTEM)
Outputs
The test results will be displayed, logged and printed in panel computer (if required).
Outputs
In case of presence of signal, the status Not OK of parameter will be printed.
3.1.3.4 1553B SELF CHECK (CHECK 315)
Requirement ID: DP_COE_SEP2_REQ_04
Description
Output
Individual channel test status will be sent to panel computer.
Inputs
Addition information contain the attribute ИК1.
1. If seeker Testing complex (ИК1== 1), checking of ИК1 will be performed.
2. Else ИК1С will be performed.
Processing
1. Check the initial condition of the device ИК1(С) and It will be transferred to
automatic mode by issuing command and the response will be monitored.
SIGNAL NAME DESCRIPTION
B_GOTOWNOCT Check the docking of device ИК1
B_AWTOMAT_REVIM Set the digital out signal as High
C_AWTOMAT_REVIM Read the remote port of SEP3 and declare the parameter
P1
B_KWIT_AWTOMAT_REVIM Check the signal status and declare the Parameter P2
3. Switch ON ГШ1.
SIGNAL NAME DESCRIPTION
B_WKL_GEN_SH_1 Set the digital out signal as High.
C_WKL_GASHENIE_1 Read the remote port of SEP3 and declare the parameter P4.
B_KWIT_WKL_GEN_SH_1 Check the signal status and declare the parameter P5.
B_KNTR_GH1 Read the analog input signal and declare the parameter P6.
Output
Display the status of parameter P1 TO P34.
Processing
The following operation will be carried out during execution of check 1011.
1. Check for the presence of attribute for type “A article”. If it is present, stop the
check.
2. Check whether the connector X2 is connected. If X2 is not connected, stop the
check.
3. Configure the 1553B (channel(1)) as controller on М1 and set the frequency of
operation as 200HZ.
4. Verify the MIU self check result.
5. Ensure number of MIU device is either “0” or “1”, else stop the check.
6. Check the Issue of faulty command “faulty БЦВМ”.
7. Check output voltage of МПКН, МПКН -ТМ and monitor in the absence of “Faulty
БЦВМ” command.
8. Switch OFF the SEP2 power supply and switch it ON after 10 seconds.
9. Set the input voltage of МПНК as 4.49V. Check output voltage of МПНК and МПНК
– ТМ. The output voltage of МПНК should be within the range 4.43 to 4.56 V and
the output voltage of МПНК - ТМ should be within the range 4.41 to 4.51V.
10. Disconnect the 1553B channel.
Output
Display the status of parameter P1 to P5.
Output
Display the status of parameter P1 to P20 and TP1 to TP20.
9. Check the deflection of PA2 for input angles (0.0, 12.5, 25.0, 0.0, -12.5, -25.0) and
analyze the measurement (B_URT1_I, B_URT2_I, B_URT3_I, B_URT4_I).
11. Check the deflection of PA4 for input angles (0.0,12.5, 25.0, 0.0,-12.5, -25.0) and
analyze the measurement (B_URT1_I, B_URT2_I, B_URT3_I, B_URT4_I).
DEFLECTIO INPUT ANGLES ADC SIGNAL CHECKED
N PARAMETER
PARAMETER
PA4 (0.0, 12.5, 25.0, 0.0, (B_URT1_I, B_URT2_I, P19, P20, P21,
-12.5, -25.0) B_URT3_I, B_URT4_I) P22, P23, P24
12. If work mode is “factory tests with К311”, analyze the ТМ signals.
ADC SIGNAL
B_FNC41_STI
B_FNC42_STI
B_FNC43_STI
B_FNC44_STI
B_WIH1_STI
B_WIH2_STI
B_STI3_WIH
B_STI4_WIH
B_MPNK1_STI
13. Initialize К314-43.
14. Check the presence of command «Ликв».
15. Check the deflections of fin actuator and analyze the measurement of initial
deflections (parameters TP1, TP2, TP3, TP4).
16. If work type is “factory tests with К311”, send the command “the permission of
liquidation” (B_RAZRESH_L), else analyze the measurement after sending
command «permission of liquidation» (accordingly parameters Р38, Р39, Р40,
Р41).
17. Check the presence of signal "Error OBC" (B_NEISPR_BCWM_WH).
18. Remove command «permission of liquidation»(B_RAZRESH_L) if work type is
“factory tests with К311”.
19. Analyze the measurement of deflections of РА (parameters Р42, Р43, Р44, Р45).
20. Check the absence of signal "Error OBC".
21. Set the device СК314-43 in initial condition.
22. Switch OFF the Fin simulator from input and output of УРТ.
Output
Output
Not Applicable
Output
Not Applicable
Output
Not Applicable
Output
Store the ADP data in file.
Inputs
1. Select the Device for program loading (CK315-1).
2. Select the Device type for reading the input program (CD or Floppy).
3. Display the checksum of the program in the panel computer.
RT to BC Messages
S.NO CHANNAL RT- SUB- WORDCOUNT BUFFER
ADDRESS ADDRESS
1 1 1 1 2 buf2[0]==0xAAAA
buf2[1]==0x007F
2 1 1 20 32
Processing
Step 1
1. Switch ON the SEP2 power supply.
2. Read the input file and compute the check sum (addition method).
3. Wait for 3 second after switching ON the SEP2 supply.
Step 2
4. Configure the 1553B channel(2) as Controller and disconnect Channel(1) from main
line.
5. Read express-diagnostic result of CK315-1 by scheduling the 1553B message
format (Table RT to BC Messages S.NO 1) and validate the message execution
status. If message execution status results failure, go to Step 4.
6. Analysis the received status(buf2[1] == 7F). If the status is success, send NORM
message. Else send NONORM message for respective NOT OK bit position.
Step 3
7. Issue the command for transfer into technological mode by scheduling 1553B
message format (Table BC to RT Messages S.NO1).
8. Wait for 5.5 second.
Step 4
9. Send the command containing following information (Mode of operation of flash,
Higher Order initial address, Higher Order final Address etc.) by scheduling 1553B
message(Table BC to RT Message S.No 2) to CK315-1. If the status is NOT OK
repeat this step one more time. If again status is NOT OK go end step.
10. Introduce the delay for 8 second.
11. Send query for the result of previous exchange by scheduling 1553B message
(Table RT to BC Message S.No 2).
19. Transfer remaining data (non multiple of block size) by scheduling the message
indicating the start of block transfer(Table BC to RT Message S.NO 6)to CK315-1.
20. Send query for the result of previous exchange by scheduling 1553B
message(Table RT to BC Message S.No 2).
21. Transfer the remaining data block with message format (Table BC to RT Message
S. No 4).
22. After transferring every block of data, send the command to indicate the end of
Block (Table BC to RT 5).
23. Send query for the result of previous exchange by scheduling 1553B
message(Table RT to BC Message S. No 2).
24. After transferring entire data, send the command to read the checksum of
Flash-memory in CK315-1 device (Table BC to RT S.NO 7).
25. Introduce the delay for 20 seconds.
26. Send query for the result of previous exchange by scheduling 1553B message
(Table RT to BC Message S.No 2).
27. Compare the received checksum with computed checksum.
28. Issue the command (Table BC to RT S.No 9) to calculate the checking sum of area
of Flash-memory of the programs and ПД(passport Data).
Step 7
Inputs
1. Article type B
2. Type of operation (“Control”)
RT to BC
S.NO CHANNEL RT- SUB- WORDCOUNT DESCRIPTION
ADDRESS ADDRESS
1 1 1 1 2 Express-diagnostic
result of CK315-1
2 1 1 20 32 Read checksum of
field Flash-memory
3 1 1 20 32 Status checking
command for reading
flash memory
4 1 1 20 32 Status checking for
BC to RT
S.NO CHANNEL RT- SUB- WORDCOUNT DESCRIPTION
ADDRESS ADDRESS
1 1 1 3 3 Start of
Technological Mode
2 1 1 1 8 Command to read
existing checksum in
Flash-memory
3 1 1 1 8 Command for
identifying field
Flash-memory for
reading
4 1 1 1 5 Command to
identifying the
current block number
(varies from1 to
1792) for reading
5 1 1 (2,3...17) 32 Data (Flash memory
content)
6 1 1 1 3 End of Technological
Mode
Processing
The following operation are carried out in Check 1505.
1. Switch ON SEP2 power supply.
2. Configure 1553B channel(2) as Bus Controller(become Controller on M2).
3. Wait for 3 second after switching ON SEP2 power supply.
4. Read the express-diagnostic result of CK315-1 through 1553B.
5. Issue the command(1553B) for transfer into technological mode.
6. Issue the command(1553B) for reading the checksum of the loaded program.
7. Issue the command(1553B) for reading the checksum of the loaded program
8. Before reading flash memory content, identify the block number. it should vary from
1 to 1792.
Output
1. Checksum for block will be displayed.
2. Checksum for area of the program will be displayed.
RT to BC
S.NO CHANNEL RT- SUB- WORDCOUNT DESCRIPTION
ADDRESS ADDRESS
1 1 1 1 2 Express-diagnostic
result of CK315-1
2 1 1 20 32 Status checking for
command “start of
Flash-memory
location for write
passport data”
3 1 1 20 32 Status checking for
command
“identifying the
current block number
for writing passport
data”
BC to RT
S.NO CHANNEL RT- SUB- WORDCOU DESCRIPTION
ADDRESS ADDRESS NT
1 1 1 3 3 Start of Technological
Mode
2 1 1 1 8 Identify start of Flash-
memory location for
write passport data
3 1 1 1 5 Command to identifying
the current block
number( varies from1 to
255 ) for writing
passport data
4 1 1 (2,3...17) 32 Passport data
5 1 1 1 5 Command identifying
the end of block
6 1 1 1 5 Command to identifying
the start of last block
number 256
Processing
The following operation will be carried out during the execution of the check 1503.
1. Switch ON SEP2 power supply.
2. Configure 1553B channel(2) as Bus Controller(become Controller on M2).
3. Wait for 3 seconds after switching ON the SEP2 power supply.
4. Read the express-diagnostic result of CK315-1 through 1553B.
5. Read the Passport data stored in file(from panel computer).
6. Issue the command(1553B) for transfer in to technological mode
7. Issue the command indicating start of flash write(starting and ending address etc)
to CK315 .
8. Before sending every block of data, send the command indicating the start of block
transfer.
9. Send query for the result of previous exchange.
10. Each Block contains 1024 byte of data. Send 32 word data at a time.
11. After transferring every block of data (1024 bytes), send the command to indicate
the end of Block.
12. Send query for the result of previous exchange.
13. Repeat Step 8 to Step 12 until entire block(255) of passport data transfer is
completed.
14. Send the command indicating the start of last block(256) transfer.
15. Send the last block data.
16. Send the command indicating end of last block.
17. Send the command to read the checksum of the flash memory(0xFFDC to 0xFFE0).
18. Send the command to read the checksum of the flash memory
(0xFFC0 to 0xFFE0).
19. Issue the command to indicate the completion of technological mode.
20. Disconnect the 1553B channel(2) from mainline.
21. Switch OFF the supply to SEP2.
3.1.3.26 READING THE PASSPORT DATA OF THE “TYPE B” ARTICLE FROM OBC
(CHECK 1504)
Requirement ID: DP_COE_SEP2_REQ_26
Description
This requirement will read the passport data of “type B” Article from the device CK315-1
through 1553B interface along M2. The passport data will be read from the Flash memory
location(0xFFDC0000 to 0xFFDFFFFF) and display the ten words of first block in the
screen. The SEP2 acts as a BC (Bus Controller) of M2, CK315-1 acts as Remote
Terminal(1).
Input
Type B Article
RT to BC
S.NO CHANNEL RT- SUB- WORDCOU DESCRIPTION
ADDRESS ADDRESS NT
1 1 1 1 2 Express-diagnostic
result of CK315-1
2 1 1 20 32 Status command
for(reading checksum,
passport data, block
command)
BC to RT
S.NO CHANNEL RT- SUB- WORDCOU DESCRIPTION
ADDRESS ADDRESS NT
1 1 1 3 3 Start of Technological
Mode
2 1 1 1 8 Read checksum of
flash memory.
3 1 1 1 8 Read passport data
from flash memory
4 1 1 1 5 Command to identifying
the current block
number (varies from1 to
Processing
The following operation will be carried out during the execution of the check AP 1504.
Outputs
Display the ten words in the first block of passport data.
Input
1. Select the device К312-10В for program loading.
2. Input of additional informations.
3. Read the input file that has to be loaded in to the device K312-10B.
Processing
The following operation will be carried out during the execution of the check 1501.
Determine Mode for loading(Kod())
Output
1. The check sum of file will be displayed.
2. If the second trial in loading the file is unsuccessful, a message “not ok of entry
of programmer flash” will be issued.
3. The results of entry of portion will be displayed after monitoring the logical
parameter tp3_1 or tp3_2. On receiving negative result, a message “not ok of entry
of portion into flash” will be issued.
1. Programmer flash under the name (prg_flsh.com) is loaded in RAM with address
(0913000).
2. Nucleus ОS QNX under the name oszagr or os (on to flash - disc 0*FFE1000)
3. File system with name img... (on to flash - disc 0*FFE9000)
Inputs
1. Select the device К312-10A for loading of program.
2. Input of additional informations.
3. Read the input file that has to be loaded in to the device K312-10A.
Processing
The following operation will be carried out during the execution of the check 1502.
Determine Mode for loading(Kod()).
Output
1. The check sum of file will be calculated and displayed.
2. If the second trial in file loading is not successful, a message “not ok of entry of
programmer flash” will be issued for the information.
3. The results of entry portion will be displayed to the operator after monitoring the
logical parameter tp3_1 or tp3_2.
4. On receiving negative result, a message “not ok of entry of portion into flash” will
be issued.
Input
3. Program for counting the signatures under the name Csign_fls.com; is loaded in
RAM with address 0x0913000.
4. The file monitored for the checksum verification
a) Nucleus ОС QNX oszagr (on to flash - disc of address 0xFFE1000).
b) File system img (on to flash - disc 0xFFE9000).
Processing
The following operation will be carried out during the execution of the check 1507.
1. Switch ON the power supply of SEP2.
2. If the WorkType is not factory tests with К312 and stand for factory check of К312,
realize the initialization of program into device СК315-1 and determine the presence
of “readiness 1”.
3. Configure the channel(1) as controller.
4. If the work type is (factory tests with К312), issue the command «ON. Обр» for
feeding the supply to device К312-10А, else issue the command «ON. Обр» into
device К314-43.(per_com_maj43(K24_43,1)).
5. Read the express-diagnostic status and validate the status.
6. Transfer in to technological mode.
7. Read Programmer flash file(csign_fl.com) and load it with (RAM Address
(0x09130000), Flash adrress(0), checksum(0)).
8. If loading of file results NOT OK, repeat the process one more time. If failure occurs
in repeated loading, disconnect the M1 and switch SEP2 supply.
9. Check whether the nucleus QNX is accomplished by the function
Load_csg(adres_flash,fsize,pribor,cs,&zgr.a[1].path,&zgr.a[0].path).
10. Check whether the file system is accomplished by the function
Load_csg(adres_flash,fsize,pribor,cs,&zgr.a[2].path,&zgr.a[0].path).
11. Accomplish removal of command «ON. Обр» if the type of operation is СЗК К312 or
remove СВК through СЯ or through device СК314-43 and switch OFF the supply to
БАСУ.
12. Switch OFF the supply to БАСУ.
Software Requirements Specification March 04, 2010
Confidential
Version 1.01 Page 241 of 330
YEC1236/SDG/SRS/1V01/DRAFT
13. Disconnect the 1553B channel(1) from mainline.
Output
1. The checksum will be displayed on the screen.
2. If error occurs during successive loading of program Csign_fl.dat, switch OFF the
SEP2 supply and issue the Error message.
Input
1. Select the device СК314-1 for loading of program.
2. Check AP 1508 is executed in selective mode.
3. The following files are loaded into the device CK314-1.
a) Sensor data in to the device CK314-1.
b) Programming of loadable image.
c) Checksum of given sensor and software under a name jvxxxchk.dat
corresponding to the device with serial number № xxx (the file from two
words, first word represents the check sum of the given sensor and second
word represents check sum of the software of device СК314-1.
Processing
The following operation will be carried out during the execution of the check 1508
(NIT_MKIO() ; initialization of types of exchange)
Output
2. Check the operation of antenna for direct controlling - testing and stabilization in the
given angular positions.
a) Give the control angles sequentially.
b) Read 30 measurement of angular position. Compute average, maximum
positive deflection and maximum negative deflection from the average to be
observed. The control angles to be verified and expected range of values for
each angular position are given in below table.
4. Check the rate of scanning and stabilization of vertical angle in the process of
scanning while assigning the mode of scanning: sector – wide, direction – to left.
a) Read status image of device К312-10А. On the appearance of signal
ON.Обн in status word of system К312 (3 bit), which signals about the start
of zones of constant velocity of movement of antenna, memorizes the
number of cycle (start), where the ON.Обн. has appeared and the value of
horizontal angle Ψ1.
b) Get the value of end angle Ψ2, calculate and analyze the scanning rate as
per formula (Ψ2 –Ψ1)/0.025*(15-start) and evaluate the scanning rate of
antenna. It should be between 145-25 to 145+25.
c) The average value of vertical angle of antenna, its deviation from tolerance,
max positive and negative deviation from average are verified.
6. End of check
a) Remove command “On Rev” to stop the programs on devices К312-10В and
К312-0А
b) Switch OFF of “SEP2 bus”
Output
The test results will be displayed, logged and printed in panel computer (if required). The
1553B message transferred along channel 1 to be logged.
S
1. B_GOTOWNOCT DIP ON Readiness of ИК1
c) If the attribute for “RF testing complex” is present, issue the signal Fпчз and
check for the presence of “Perm.Вкл.f пч-з“.
S.NO. SIGNAL NAME SIG TYPE STATUS DESCRIPTION
1. B_WKL_F_PC_Z DOP ON Issue signal Fпчз
2. B_KWIT_WKL_F_PC_Z DIP ON presence of “Perm.Вкл.f пч-з“
b) Issue command to switch ON “IK1” and check for the “Permission for switch
ON of IK1”.
S.NO. SIGNAL NAME SIG TYPE STATUS DESCRIPTION
1 B_WKL_IK1 DOP ON switch ON of “IK1”
2 B_KWIT_WKL_IK1 DIP ON Permission for switch ON of
“IK1”
b) Issue command for switch ON of “IK1” and check for the “Permission for
switch ON of IK1”.
S.NO. SIGNAL NAME SIG TYPE STATUS DESCRIPTION
1 B_WKL_IK1 DOP ON switch ON of “IK1”
2 B_KWIT_WKL_IK1 DIP ON Permission for switch ON of “IK1”
Output
The test results will be displayed, logged and printed in panel computer (if required). The
1553B message transferred along with channel 1 will be logged.
Input
1. Operational mode
2. Additional inputs
3. Presence of ИК1
Processing
1. Verify the “Code of frequency number”
a) The should not be performed if the “Code of frequency number” is not 0066
or 1435
2. Perform initial and switch ON SEP2 bus.
a) Switch ON “SEP2 bus”.
b) Send command “On Rev” to start the program of device К312-10В and
К312-10А.
3. Set antenna into the initial position.
a) To set antenna into zero position, write the following values into registers of
device К312-10А.
Ψa = Ψsc = Θm = dΘm = Θs = Θa = Ψm = dΨm = Ψs = dTd = 0
b) The value of start and width of zone of search (Dn=4266 and Dшз=192),
Ткор=3072 and accomplish zeroing of elements of RAM and registers К312-
0А. Issue command “ON.прив.", "Signal1", "СК=1", "OFF.УВЧ", "OFF. ПЧ",
"Ч2", "Обзор" into К312-10А.
c) Issue command "OFF. УМ" and issue the command "ON. ВН".
12. In initial condition install antenna for mode СЗК К312 or СВК.
a) If work mode is not СЗК К312 or СВК, the test should not be performed.
Output
The test results will be displayed, logged and printed in panel computer (if required). The
1553B message transferred along with channel 1 will be logged.
3.1.3.37 CHECK OF MODES «О», «З» AND «С» OF SYSTEM К312 (CHECK 1150)
Requirement ID: DP_COE_SEP2_REQ_37
Description
This requirement will check the modes «О», «З» and «С» of system К312 with the help of
inbuilt elements for checking without switching on ВН.
Input
1. Operational mode
2. Additional inputs
3. Presence of ИК1
Processing
1. Switch ON OBCS and activate the transparency program. If any failure occurs, stop
the test.
2. Verify the number of detected targets in mode О.
3. Verify the presence of det sim. targets in given quant of range in mode О and verify
the bearing of sim. targets in mode О (with range -2.5 to 2.5).
4. Verify the detected targets in mode З.
5. Verify the increment of range in mode С high quality factor and Increment of Ac in
mode С.
6. Verify the increment of range in mode С low quality factor and Increment of Ac in
mode С.
7. Verify the tracking velocity of PSY(pos.) (with range 23.0 to 93.0) and tracking
velocity of PSY(neg.) (with range -23.0 to -93.0) at high quality factor.
8. Verify the tracking velocity of PSY(pos.) (with range 6.0 to 24.0) and tracking
velocity on PSY(neg.) (with range -6.0 to -24.0) at low quality factor.
9. Verify the tracking velocity of TETA(pos.) (with range 23.0 to 93.0) and tracking
velocity of TETA(neg.) (with range -23.0 to -93.0) at high quality factor.
10. Verify the tracking velocity of TETA(pos.) (with range 6.0 to 24.0) and tracking
velocity of TETA(neg.) (with range -6.0 to -24.0) at low quality factor.
11. Verify the ratio of tracking rates as per PSY at high and low Quality factors (with
range 2.5 to 5.5).
12. Verify the ratio of tracking rates as per TETA at high and low Quality factors (with
range 2.5 to 5.5).
Output
Processing
1. Check for presence of attribute ИК1С
a) Check for presence of attribute ИК1С
2. Perform initial and switch ON SEP2 bus.
a) The test should be performed only if the work type is СЗК К312.
b) Switch ON “SEP2 bus”.
c) Send command “On Rev” to start the programs of devices К312-10В and
К312-10А.
3. Switch ON auto mode and IK1.
a) Issue command to switch ON the “Auto mode” and check for the “Permission
for auto mode”.
S.NO. SIGNAL NAME SIG TYPE STATUS DESCRIPTION
1 B_AWTOMAT_REVIM DOP ON switch ON of “Auto mode”
2 B_KWIT_AWTOMAT_REVIM DIP ON Permission for “Auto mode”
b) Issue command to switch ON the “IK1” and check for the “Permission for
switch ON of IK1”.
S.NO. SIGNAL NAME SIG TYPE STATUS DESCRIPTION
1 B_WKL_IK1 DOP ON switch ON of “IK1”
2 B_KWIT_WKL_IK1 DIP ON Permission for switch ON of
“IK1”
c) Issue command to “Switch ON the f пч-з” and check for the “Perm. Switch
ON of f пч-з”.
S.NO. SIGNAL NAME SIG TYPE STATUS DESCRIPTION
1 B_WKL_F_PC_Z DOP ON Switch ON of f пч-з
2 B_KWIT_WKL_F_PC_Z DIP ON Perm. Switch ON of f пч-з
11. Issue command to switch OFF the “Auto mode” and check for the “Permission for
auto mode”.
S.NO. SIGNAL NAME SIG STATUS DESCRIPTION
TYPE
1. B_AWTOMAT_REVIM DOP OFF switch ON of “Auto mode”
2. B_KWIT_AWTOMAT_REVIM DIP OFF Permission for “Auto
mode”
Output
Output
Display the status of parameter.
1. Frame FM1, FM2 and MINS data from additional input (latitude).
2. Compute the checksum for FM1, FM2 and MINS data.
3. Send FM1, FM2 and MINS data to panel computer.
4. Configure 1553B channel(2) as controller.
5. Issue Initialization of БЦВМ command through1553B.
6. Read ADP data and analyze the data. If successful, generate readiness1 attribute.
7. Send FM1 data and analyze its result by reading ADP data. If FM1 data loading is
successful then generate readiness2 attribute.
8. Transfer sync, MINS, END of MINS data and analyze the result by reading ADP
data.
9. Verify THO above norm and norm register content.
10. Send FM1 data and analyze its result by reading ADP data.
11. Issue unlock command.
Output
ADP data will be stored in the file.
Input
1. Type A Article
2. User input passport data stored in the panel computer.
RT to BC
S.NO RT- SUB-ADDRESS WORD DESCRIPTION
ADDRESS COUNT
1 1 5 1 Self check result
2 1 5 1 Result of exchange
BC to RT
S.NO RT- SUB- WORD MESSAGE
ADDRESS ADDRESS COUNT DESCRIPTION
1 1 4 1 Main mode operation.
2 1 5 10 Passport data
3 1 5 1 Interrupt code
Processing
The following operation will be carried out during the execution of the check 503.
1. Check the article type. If it is type “B” stop the check.
2. Switch ON SEP2 power supply.
3. Configure 1553B channel(2) as controller on M2.
4. Wait for 1 second after switching ON SEP2.
5. Read self check result.
6. Issue command to transfer into main mode operation.
7. Read passport data input file and transfer 10 word to panel computer.
8. Issue command to transfer passport data to k315.
9. Issue command to transfer interrupt code to k315.
10. Read the result of exchange.
11. If error occurs during loading, repeat the loading process one more time.
12. Disconnect the 1553B channel(2).
13. switch OFF SEP2 power supply.
Output
10 words of passport data will be sent to panel computer.
Input
Type A Article.
RT to BC
S. NO RT-ADDRESS SUB-ADDRESS WORD COUNT DESCRIPTION
1 1 5 1 Self check result
2 1 5 32 Passport data
BC to RT
S.NO RT-ADDRESS SUB-ADDRESS WORD COUNT DESCRIPTION
1 1 4 1 Main mode operation.
Processing
The following operation will be carried out during the execution of the check 504.
1. Switch ON SEP2.
2. Configure 1553B channel(2) as controller on M2.
3. Read self check result.
4. Read passport data from K315-1.
5. Analyze the passport data content. If the passport data content are not OK, repeat
the reading up to 12.5 seconds.
6. Switch OFF SEP2.
7. Disconnect the 1553B channel(2).
8. Transfer 10 word of passport data to panel computer.
Output
10 words of passport data will be sent to panel computer.
Input
1. Type A article.
2. Input file for loading(programmer flash(prg_flsh.com), QNX OS(oszagr or os) and
file system (img,img1 etc)).
RT to BC
S.NO RT-ADDRESS SUB-ADDRESS WORD COUNT DESCRIPTION
1 1 5 1 Self check result
BC to RT
S.NO RT-ADDRESS SUB-ADDRESS WORD COUNT DESCRIPTION
1 1 3 1 Technological mode
Processing
The following operation will be carried out during the execution of the check 500.
1. Identify the mode for loading.(Kod()).
2. Switch ON SEP2.
3. Wait for 3 seconds after switching ON SEP2.
4. Configure 1553B channel(2) as controller on M2.
5. Read self check result.
6. Issue 1553B command to transfer operation mode in to technological mode
7. Load the program programmer flash (prg_flsh.com) to K315-1. If failure occurs
during loading, repeat the loading process one more time. On successive failure in
loading switch OFF power supply and stop the check.
8. Load the program QNX OS or file system to K315-1. Depending on user input
repeat the loading of program one after another. If failure occurs in loading, repeat
the loading process one more time. On successive failure in loading switch OFF
power supply and stop the check.
9. Disconnect the 1553B channel(2).
10. Switch off the SEP2 power supply.
Output
Display the parameter status tp1_1, tp1_3,tp1, p001, tp3_1 and tp3_2.
Input
1. Type A article.
2. Input file for loading programmer flash(prg_flsh.com), QNX OS(oszagr or os) and file
system (img,img1 etc).
RT to BC
S.NO RT-ADDRESS SUB-ADDRESS WORD COUNT DESCRIPTION
1 1 5 1 Self check result
BC to RT
S.NO RT-ADDRESS SUB-ADDRESS WORD COUNT DESCRIPTION
1 1 3 1 Technological mode
Processing
The following operation will be carried out during the execution of the check 501.
1. If Work type is “Factory test with K312”, load data with M1 otherwise M2.
2. Identify the mode for loading.(Kod())
3. Switch ON SEP2.
4. Wait for 3 seconds after switching ON SEP2.
5. Configure 1553B-channel as controller based on Work type configuration.
6. Read self check result.
7. Issue 1553B command to transfer operation mode in to technological mode.
8. Load the program programmer flash (prg_flsh.com) to K312-10B. If failure occurs
during loading, repeat the loading process one more time. On successive failure in
loading display error message, switch OFF power supply and stop the check.
9. Load the program QNX OS or file system to K312-10B. Before loading the program,
compute the checksum of OS or file system and display to the user. Depending on
user input, repeat the loading program one after another. If failure occurs during
loading of program, repeat the loading process one more time. On successive
failure in loading display error message, switch OFF power supply and stop the
check.
10. Disconnect the 1553B channel based on configuration.
Input
1. Type A article.
2. Input file for loading programmer flash(prg_flsh.com), QNX OS(oszagr or os) and file
system(img,img1 etc).
RT to BC
S.NO RT-ADDRESS SUB-ADDRESS WORD COUNT DESCRIPTION
1 1 5 1 Self check result
BC to RT
S.NO RT-ADDRESS SUB-ADDRESS WORD COUNT DESCRIPTION
1 1 3 1 Technological mode
Processing
The following operation are carried out during the execution of the check 502
1. If the Work type is “Factory test with K312”, load data with M1, else M2.
2. Identify the mode for loading.(Kod())
3. Switch ON SEP2.
4. If the Work type is “Factory test with K312”, digital ou the signal B_WKL_OBR(high)
else configure 1553B channel(1) as controller, initialize the device k314-43 and
issue command «ON. Обр» to it.
5. Wait for 3 seconds after switching ON SEP2.
6. Configure 1553B-channel as controller based on work type configuration.
7. Read self check result.
8. Issue 1553B command to transfer operation mode in to technological mode.
9. Load the program programmer flash(prg_flsh.com) to K312-10A. If failure occurs
during loading, repeat the loading process one more time. On successive failure in
loading display error message, switch OFF power supply and stop the check.
Processing
1. Switch ON SEP2.
2. Configure 1553B channel(2) as controller.
3. Read express-diagnostic test result.
4. Transfer into technological mode.
5. Load the program csign_fl.com into k315-1. If error occurs during loading, repeat
the loading process one more time.
6. Verify QNX and file system checksum.
7. Switch OFF SEP2.
Output
Processing
1. Switch ON SEP2.
2. Configure 1553B channel(1) as controller.
3. Read express-diagnostic test result.
4. Transfer into technological mode.
5. Load the program csign_fl.com into k315-1. If error occurs during loading, repeat
the loading process one more time.
6. Verify QNX and file system checksum.
7. Switch OFF SEP2.
Processing
The following sequence will be followed for switching ON/OFF the power supplies,
1. Power ON Sequence
a) Switch ON of SP
b) Switch ON of GPS
c) Switch ON of SEP1
d) Switch ON of SEP2
2. Power OFF Sequence
a) Switch ON of SEP2
b) Switch ON of SEP1
c) Switch ON of GPS
d) Switch ON of SP
Initial Step
1. The unblocking of following signals will be verified,
a) Unblocking of “Electrical equipment”
b) Unblocking of “Warhead simulator”
c) Docking of “KPA”
d) Docking of “RF Seeker test complex(IK1)”
e) Docking of IK7
f) Docking of IK8
Self-check mode
2 C_KONTROL_OCP DOP ON Indication for control
mode
b) If the mode is “Control” set the following signals given in below table.
S.NO. BOARD CHANNEL SIGNAL NAME SIG SIGNAL DESCRIPTION
NO NO TYPE STATUS
1. C_KONTROL_ DOP OFF Indication for control
OCP mode
2. C_SAMOKONT DOP ON Indication for
ROL Self-check mode
2. The Power button in control panel is used to switch ON the power supplies. The
software will read the status of the button through DIO interface and based on the
status the respective supply will be switched ON/OFF.
Switch ON of SP bus
1. If the work mode is self-check, the SP power supply should not be switched ON.
2. In the absence of signal C_SIGNAL_OHL_OK(Cooling OK + 27V), the SP power
supply should not be switched ON.
3. The permission for SP power should be provided after providing additional
information.
4. Switch ON the following signals given in below table.
5. Read the signal C_X2_SOSTIK(X2 is docked). If the attribute for “X2 is docked” and
signal “X2 is docked” are not equal, the power supply signals should not be
switched ON.
6. If signal “X2 is docked” then perform the following steps,
a) Indication for “OK is docked”
S.NO SIGNAL NAME SIG TYPE SIGNAL STATUS DESCRIPTION
1. C_OK_SOSTIK DOP ON Indication for “OK is docked”
b) If the work mode is not “self-check with loop back” and attribute for “X2 is
docked” and signal “X2 is docked” are not equal, the power supply signals
should not be switched ON.
c) The signals given in below table are verified.
S. SIGNAL NAME SIG SIGNAL DESCRIPTION
NO. TYPE STATUS
1 C_SIGNAL_KON DOP ON Check for presence of “Docking of SEP1”.
TR_STIK If it is not present, Switching ON of
power supply signals should not be
proceeded.
2 C_KNTR_STIC_B DOP ON Check for presence of “Docking of BASU”.
ASU If it is not present, Switching ON of
8. Send the power supply status to PC and other SEP's indicating switched ON of “SP
bus”.
4. If the insulation check(AP4, AP72, AP1004, AP1072 – dangerous circuits) is not OK,
the switching ON of power supply signals will not be proceeded.
5. If the check for dangerous circuits is normal, the indication for “Dangerous circuits -
Normal” will be enabled.
S.NO SIGNAL NAME SIG SIGNAL DESCRIPTION
TYPE STATUS
1. C_NORMA_CB DOP ON Indication for “Dangerous circuits
Normal”
6. Analyze the attribute article type and the presence of signal for the article type.
a) If signal for the article type A is present and the attribute for article type A is
not selected, check the attribute “presence of seeker”. If seeker is not
present, the switching ON of power supply signals will not be proceeded.
10. If the work mode is “Self-check with loop-back”, check for the presence of signal
“Disconnect of MD bus” of SEP1.
S.NO CHANNEL SIGNAL NAME SIG SIGNAL DESCRIPTION
NO TYPE STATUS
1 E_OTKL_S_MD DOP ON Check for presence of signal
“Disconnect of MD bus”. If it
is not present, Switching
ON of power supply signals
should not be proceeded.
15. If signal “+ 27V NI” is present, the following signals of SEP1 will be set.
S.NO SIGNAL NAME SIG SIGNAL DESCRIPTION
TYPE STATUS
1 E_SHINA_MINUS27_W_NI DOP ON Switch ON the signal “Bus -27V
NI”
2 E_SHINA_PLUS27_W_NI DOP ON Switch ON the signal “Bus +27V
NI”
3 E_CORPUS_B_2 DOP ON Switch ON the signal “Body B”
4 E_AMB_PROGR_WH DIP ON Check for presence of signal
“AMB is heated”
16. If signal “AMB is heated” is present, set the indication in the control panel.
S.NO SIGNAL NAME SIG SIGNAL DESCRIPTION
TYPE STATUS
1 C_AMB_PROGREW DOP ON Indication for “AMB is heated”
17. If the article type is B and the work type is not “Factory test of seeker”(СВК) or “IGI
of seeker”(СЗК К312), perform the following steps.
a) Remove command INS heating from BA.
18. If work type is “Control”, the presence of attributes for “Simulation of SD” and
“Simulation of SD1” is verified.
b) If the attribute “Simulation of SD1” is present, set the signal (refer table given
below) for simulation of SD1. If it is absent, remove the signal for simulation
of SD1.
3. If the article type is type B and work type is not СВК(IGI of seeker), wait for INS
heating upto 115 * 1000 milliseconds .
4. Switch ON and verify the following signals,
5. If the work mode is “Control” and the signal of “X2 is docked” is present, perform the
following steps,
a) Read the following signals of SEP1.
S.NO SIGNAL NAME SIG TYPE SIGNAL STATUS DESCRIPTION
1. E_ISHODHOE_2 DOP ON Switch ON of BA
b) If signal “Initial 2” is absent and attribute “RPP” is present, read the following
signals of SEP1 and send the status to PC.
S.NO SIGNAL NAME SIG TYPE SIGNAL STATUS DESCRIPTION
1. E_KNTR_WENT_WH DOP - Monitoring fans
2. E_KNTR_SD_1_WH DOP - Pressure sensors 1
3. E_KNTR_SD_WH DOP - Pressure sensors
6. Send the power supply status to PC and other SEP's indicating the “BA bus” is
switched ON.
5. Read the signal “Initial of article”. If it is present, switch ON the indication for “initial
of article”.
S.NO SIGNAL NAME SIG TYPE SIGNAL STATUS DESCRIPTION
1 C_ISHODNOE_OK DIP ON Signal “Initial of article”
2 C_ISHODHOE_OK DOP ON Indication for “initial of article”
6. Check for the presence of “Switch ON of SEP2 bus”. If it is not present, remove the
signal “Switch ON of SEP2 bus” and stop the switching On process of power supply
signals.
S.NO SIGNAL NAME SIG TYPE SIGNAL STATUS DESCRIPTION
1 C_WKL_BASU_PLUS DIP ON Presence of “Switch ON of
SEP2 bus(+)”
2 C_WKL_BASU DOP OFF Remove “Switch ON of
SEP2 bus”
7. Check for the presence of “Switch ON of SEP2 (+)”. If it is not present, remove the
signal “Switch ON of SEP2 bus” and stop the switching On process of power supply
signals.
8. Set the following signals,
S.NO SIGNAL NAME SIG TYPE SIGNAL DESCRIPTION
STATUS
1 C_WKL_UPU_1 DOP ON Switch ON of ACD
2 C_OTKL_UPU DIP ON Check for the presence of “Switch
ON of ACD”. If it is not present,
Switching ON of power supply
signals should not be proceeded.
Remove “Switch ON of SEP2 bus”
3 C_WKL_UPU DOP ON Indication for “Switch ON of ACD”
12. Send the power supply status to PC and other SEP's indicating “SEP2 bus” is
switched ON.
2. Check the attribute for “presence of TM”. If it is not present, stop the switching On
process of power supply signals.
3. The TM should not be switched ON if the BA bus is not switched ON.
4. If signal “X2 is docked” is not present, perform the following steps,
a) If signal “X2 is docked” and attribute for “X2 is docked” are not equal, stop
the switching On process of power supply signals.
b) If signal “X2 is docked” and attribute for “X2 is docked” are equal, proceed
the switch ON process.
S.NO SIGNAL NAME SIG TYPE SIGNAL DESCRIPTION
STATUS
1 C_WKL_TM_WIH DOP ON Issue command “switch ON TM”
2 C_WKL_TM_WIH DOP OFF Remove command “switch ON TM”
TYPE STATUS
1 C_WKL_TM_R_WH DIP ON Check for the presence of “switch
ON TM-R”. If it is not present,
Switching ON of power supply
signals should not be proceeded.
d) If the article type is type B, check for the presence of signal “switch ON of
Indian Telemetry” and set the indication for “Indian Telemetry” in Control
Panel.
S.NO SIGNAL NAME SIG TYPE SIGNAL STATUS DESCRIPTION
1 C_WKL_TM_I_ DIP ON Check for the presence of
WH “switch ON TM-I”. If it is not
present, Switching ON of
power supply signals should
not be proceeded.
2 C_TM_I_WKL DOP ON Indication for “switch ON TM-I”
6. Send the power supply status to PC and other SEP's indicating the “Telemetry” is
switched ON.
4. Send the power supply status to PC and other SEP's indicating the “Heating of INS
from SEP1 bus”.
Switch OFF SP
1. Check for the presence of attribute “STOP”(STOP button of Control Panel). If it is
present, switch OFF process should not be proceeded.
2. Check for the presence of “Switch ON of SEP2”. If it is present, switch OFF process
should not be proceeded.
3. Check for the presence of “Switch ON of SEP1”. If it is present, switch OFF process
should not be proceeded.
4. Check for the presence of “Switch ON of NI(GPS)”. If it is present, switch OFF
process should not be proceeded.
5. Check for the presence of “Switch ON of SP”. If it is not present, send abnormal in
SP switch OFF to PC.
6. Issue “End of checks” signal of SEP1.
S.NO SIGNAL NAME SIG TYPE SIGNAL STATUS DESCRIPTION
10. Send the power supply status to PC and other SEP's indicating the “Switch OFF of
SP bus”.
7. Check for the presence of “NI +27V”. If it is not present, remove the signals of
SEP1.
S.NO SIGNAL NAME SIG SIGNAL DESCRIPTION
TYPE STATUS
1 C_PLUS_27_V_NI DIP OFF Check for the presence of “NI
+27V”. If it is present, Switching
OFF of power supply signals
should not be proceeded.
2 E_SHINA_MINUS27_W_NI DOP OFF “Remove -27V of NI” of SEP1
3 E_SHINA_PLUS27_W_NI DOP OFF “Remove +27V of NI” of SEP1
4 E_CORPUS_B_2 DOP OFF Remove “Switch ON of Body B” of
SEP1
5 C_OBOGREW DOP OFF Remove indication “Heating of INS”
8. Send the power supply status to PC and other SEP's indicating “Switch OFF of NI
bus”.
5. If the article type is type B and work mode is not “IGI of seeker” then
S.NO SIGNAL NAME SIG TYPE SIGNAL DESCRIPTION
STATUS
1 C_WKL_INS_1 DOP OFF Remove “Switch ON of INS”
2 C_OTKL_INS DIP OFF Check for the presence of “Switch
OFF of INS”. If it is present,
Switching OFF of power supply
signals should not be proceeded.
3 C_WKL_INS DOP OFF Command “Switch OFF of INS”
6. Send the power supply status to PC and other SEP's indicating the “Switch OFF of
SEP1 bus”.
9. Send the power supply status to PC and other SEP's indicating the “Switch OFF of
SEP2 bus”.
3. Send the power supply status to PC and other SEP's indicating the “Switch OFF of
TM-R”.
3. Send the power supply status to PC and other SEP's indicating the “Switch OFF of
TM-I”.
Switch ON of calibration WTI
1. Switch ON of calibration WTI
S.NO SIGNAL NAME SIG TYPE SIGNAL DESCRIPTION
STATUS
1 C_KALIBR_BTI DOP ON Command “Switch ON of calibration
WTI”.
2. Send the power supply status to PC indicating the “Switch ON of calibration WTI”.
3. Send the power supply status to PC indicating the “Switch ON of calibration WTI”.
(b) If Signal “AMB is heated” is present then set the indication of “AMB
heated” in Control Panel
S.No Signal Name Sig SIGNAL Description
Type STATU
S
1. C_AMB_PROGREW DOP ON Indication for “AMB is heated”
(c) If Signal “AMB is heated” is absent then remove the indication of “AMB
heated” in Control Panel
S.No Signal Name Sig SIGNAL Description
Type STATU
S
1. C_AMB_PROGREW DOP OFF Indication for “AMB is heated”
2. Initial of article
(a) Read the signal for “Initial of Article”
(b) If Signal “Initial of Article” is present then set the indication of “Initial of
Article” in Control Panel
S.No Signal Name Sig SIGNAL Description
Type STATU
S
1. C_ISHODHOE_OK DOP ON Indication for “Initial of article”
(c) If Signal “Initial of Article” is absent then remove the indication of “Initial
of Article” in Control Panel
S.No Signal Name Sig SIGNAL Description
Type STATU
S
1. C_ISHODHOE_OK DOP OFF Indication for “Initial of article”
S. COMMAND SIGNAL
NO.
NAME SIG. DESCRIPTION NAME TYPE DESCRIPTION
TYPE
1. C_KW_WK DOP Acknowledge C_IMIT_ND_S DIP Simulation of
L_GH1_IM switch ON of GH1 RS ND SRS
simulator.
2. C_KW_WK DOP Acknowledge C_IMIT_ND_S DIP (details not
L_GH2_IM switch ON of GH2 WW available)
simulator.
3. C_KW_WK DOP Acknowledge C_IMIT_ND_S DIP (details not
L_US1_IM switch ON of US1 WK available)
simulator.
4. C_KW_WK DOP Acknowledge of C_IMIT_ND_S DIP (details not
L_US2_IM switch ON of US2 ND available)
simulator.
5. The status of 22 signals will be verified as given in below table. If the signal status
is FALSE, corresponding signal will be not OK.
6. If any one of the signal fails, “P002“ status will Not OK.
7. Read the status of “SIGNAL” signal, if it is OFF, ON the corresponding
“COMMAND” and wait 1125 ms and read again “SIGNAL” signal status. If it TRUE
then it is success otherwise it is not OK.
8. Refer below table for “SIGNAL” & “COMMAND” details.
COMMAND SIGNAL
S.NO. DESCRIPTION DESCRIPTION
NAME NAME
1 C_PRIZNAK_IR Attr ИР C_PRIZNAK_IR_05 attr ИР (+27В НИ)
A 0,5А
2 C_OTKL_BASU swicted C_OTKL_BASU_05 switch off SEP1CS
off.SEP1CS A (+27V НИ) 0.5А
3 C_OTKL_UPU switched off УПУ C_OTKL_UPU_05A switch off УПУ (+27V
НИ) 0.5А
4 C_OTKL_INS switched off ИНС C_OTKL_INS_05A switch off INS (+27V
НИ) 0.5А
5 C_PODKL_M1 Connected М1 C_PDKL_M1 connected М1(+27V
НИ) 0.5А
6 C_OTKL_3B_5 Reserve command C_REZERW_KM_B reserve of command
8 БА (switched off A_1 БА (+27V НИ) 0.25А
3Б-58)
7 C_REZERW_K Reserve command C_REZERW_KM_B reserve of command
OMAND_BA_4 БА A_2 БА (+27V НИ)0.25А
8 C_OTKL_UM Switched off УМ C_OTKL_UM_01A switch off УМ (+27В)
0.1А
9 C_REZERW_K Reserve C_REZERW_KM_1 reserved
M_BA_9
10 C_WIHOD_RL exit РЛ C_WIHOD_RL_1 exit РЛ
11 C_KALIBR_BTI Calibration ВТИ C_KN_KALIBR_WTI calibration ВТИ
12 C_LC_160 - C_WTI_WKL ВТИ switch on
(inward signal)
13 C_LC_161 - C_RAZBLOK_SEP1 Unlock ЭО
_1
11. If any one of the signal fails, “P004“ status is Not OK.
Output
Signal status.
Output
In control panel all LEDs should be ON initially and OFF after 12.5 seconds.
The system shall respond to each user input. If the check will take more than a few
seconds, the user shall be warned of this, and given a progress indicator. If any
communication failure that will be updated to user. There are no other performance
requirements.
3.4.1 RELIABILITY
The COE application software shall be able to run continuously for not less than twelve
hours.
3.4.2 AVAILABILITY
This software will be available in the system 24 hours a day. User will be able to run the
software at any time and if the required hardware is available then all functions of the
software can be performed.
3.4.3 SECURITY
The system will be protected from the anonymous users. The system will be provided with
a login feature, which will be password activated . Only the 'root' can install / update the
application software.
3.4.4 MAINTAINABILITY
All code shall be fully documented. Each function shall be commented with description of
functionality. All program files shall include comments concerning authorship and date of
last change. The code shall be modular to permit future modifications.
The software shall be designed to contain the following features for easy maintainability,
• Modularity
• Reusability
• Traceability
3.4.5 PORTABILITY
The software shall be developed based on the following attribute for easy portability,
• Modular design
• Design based on open standard functions like POSIX.
• All interaction between the user and the system will be through a graphical user
interface (GUI) and Control panel of the system.
Control Panel:
• Control panel comprises of Voltmeter, push button switches with indicators,
buzzer(to generate alarm) and LEDs.
• The control panel used for following:
➢ Controlling power to DUT & COE.
➢ Displaying status of signals from COE & DUT.
➢ Measurement of voltage supplied by PDU COE & DUT.
➢ Issuing simulation command to DUT.
➢ Raising alarm for the high temperature.
➢ The control panel is powered from PDU
SEP1
SL. NO BOARD ID DESCRIPTION QTY
1 - Processor module 1
2 DP-VME-4227 64 Chanel Low Thermal Relay Multiplexer Module 2
3 DP-VME-4230 48 CH Form 'C' Relay Module 3
16 Differential Channel 100KHz Isolated ADC
4 DP-VME-1443 1
Module
SEP2 (SEP2)
SL. NO BOARD ID DESCRIPTION QTY
1 - Processor module 1
16 Differential Channel 100KHz Isolated ADC
2 DP-VME-1443 1
Module
3 DP-VME-XXXX 64 Chanel Low Thermal Relay Multiplexer Module 2
4 DP-PMC-5775 64 CH TTL IO Module 1
5 DP-VME-3078 48 CH Digital Input & 48 CH Digital output Module 3
6 DP-VME-XXXX 48 CH Form 'C' Relay Module 2
7 DP-PMC-5535 2 CH of ACE 1553B BC/RT/MT Intelligent Module 2
The communication between the COE subsystem is carried out using the Ethernet
communication. The following are the two techniques COE shall use from sharing
information between sub-systems.
1. Qnet (QNX native protocol) – For sharing files between sub systems
The following files shall be transfer between the sub systems,
• Passport data
• Programs to be loaded into on-board devices
2. TCP / IP – For message passing
The TCP/IP socket communication protocol to send receive the data through Ethernet. The
following communication shall be performed using Ethernet.
4 REQUIREMENTS TRACEABILITY
REQUIREMENT ID IN DESCRIPTION SECTION IN URS (REF:
SRS BM/ECC/TSD/VER.1.0)
DP_COE_PC_REQ_01 User authentication to access the NA
DP_COE_PC_REQ_01 software
SEP3 REQUIREMENTS
DP_COE_SEP3_REQ_ Switch ON/ OFF of power supplies 10.1.6
01
DP_COE_SEP3_REQ_ Processing of remote requests 10.1.9
02
DP_COE_SEP3_REQ_ Starting test SEP SC 10.1.5.(i)
03
DP_COE_SEP3_REQ_ Self check SEP SC 10.3.2
04
DP_COE_SEP3_REQ_ Checking the indicating display of 10.3.2
05 device IK8
DP_COE_SEP3_REQ_ 1553B loop-back check 10.3.2
06
DP_COE_SEP3_REQ_ Discrete I/O Loop back test 10.1.5.(i)
07
DP_COE_SEP3_REQ_ DUT Power Loop back test 10.1.5.(i)
08
SEP1 REQUIREMENTS
DP_COE_SEP1_REQ_ Monitor the dangerous signals is 9.e
01 performed in the period of 10 ms and
issue emergency off in case of any
potential variation
SELF-CHECK
TYPE A
SEP2 REQUIREMENTS
SELF-CHECK
SEEKER
DP_COE_SEP2_REQ_ Check of antenna device K312 10.3.3
33
DP_COE_SEP2_REQ_ Check receiving channel of K312 10.3.3
SEP2 - SEEKER
70. AP 1100 Check of antenna device K312
76. AP 1150 Check of modes «О», «З» and «С» of system К312
PASSPORT DATA
S.NO DESIGNATION NAME OF PARAMETER UNITS RANGE
1 № art Factory number of - 10000 to
article 65535
2 αxр лев Position of mounting
place for device rad -π to π
СК314-1 with
respect to groove of
left flange
3 αyр Position of mounting rad -π to π
place for device
СК314-1 with
respect to axis ОY of
article
4 αzр Position of mounting rad -π to π
place for device
СК314-1 with
respect to axis ОZ of
article
5 αxр пр Position of mounting rad -π to π
place for device
СК314-1 with
respect to groove of
right flange
6 N Configuration of - -
article and type of
fuel
7 V SW version of device - -