February 2010 Hazardous Area Classifications
www.Fisher.com
Product Bulletin
9.2:001
Hazardous Area Classifications February 2010
whose MESG is less than 0.45 mm or MIC ratio b. Zone 1—Ignitable concentrations of
is less than 0.40. Typical gases include flammable gases or vapors which are likely to
hydrogen, butadiene, ethylene oxide, propylene occur under normal operating conditions.
oxide, and acrolein.
c. Zone 2—Ignitable concentrations of flammable
c. Group C—Atmospheres containing a gases or vapors which are not likely to occur
flammable gas, flammable liquid−produced under normal operating conditions and do so only
vapor, or combustible liquid−produced vapor for a short period of time.
whose MESG is greater than 0.45 mm but less
than 0.75 mm or MIC ratio is greater than 0.40 Group—Electrical equipment used in gas
but less than 0.80. Typical gases include ethyl atmospheres is divided into two groups.
either, ethylene, acetaldehyde, and
cyclopropane. D Group I—Equipment used in mines with
atmospheres containing methane or gases and
d. Group D—Atmospheres containing a vapors of equivalent hazard.
flammable gas, flammable liquid−produced
vapor, or combustible liquid−produced vapor D Group II—All other equipment; which is
whose MESE is greater than 0.75 mm or MIC further subdivided into three subgroups.
ration is greater than 0.80. Typical gases include
− Group IIA—Atmospheres containing
acetone, ammonia, benzene, butane, ethanol,
propane, or gases and vapors of equivalent
gasoline, methane, natural gas, naphtha, and
hazard.
propane.
− Group IIB—Atmospheres containing
e. Group E—Atmospheres containing ethylene, or gases and vapors of equivalent
combustible metal dusts such as aluminum, hazard.
magnesium, and their commercial alloys.
− Group IIC—Atmospheres containing
f. Group F—Atmospheres containing acetylene or hydrogen, or gases and vapors
combustible carbonaceous dusts with 8% or of equivalent hazard.
more trapped volatiles such as carbon black,
coal, or coke dust. 2. Dust
2
Product Bulletin
9.2:001
February 2010 Hazardous Area Classifications
3
Product Bulletin
9.2:001
Hazardous Area Classifications February 2010
Approved equipment is marked according to which XP—Flameproof approval for Class I Division 1
Class (I, II, or III), Division (1 or 2), Group (A, B, C, EXP—Flameproof approval for Class I Division 1
D, E, F, or G), and temperature code (T1 through NI—Non−incendive approval for Class I Division 2
T6) that it is rated for. For intrinsically safe DIP—Dust Ignition Proof approval for Class II
equipment the words “Intrinsically Safe” or “IS” will Division 1
precede the actual approval marking to indicate it as S—“Suitable For” for Class II Division 2
being intrinsically safe. Examples are listed below: IS—Intrinsically Safe
4
Product Bulletin
9.2:001
February 2010 Hazardous Area Classifications
product approval. Notified Bodies not only approve International Approvals
products for use within their own country, commonly
called national certifications/approvals, but also for
any other country within the union, known as Countries participating in the IECEx Scheme
CENELEC certifications/approvals. CENELEC is the (International Electrotechnical Commission on
acronym for European Committee for explosion protected equipment, known as “Ex”) can
Electrotechnical Standardization. A product which issue either an international certification or a national
has been CENELEC certified or approved by any of certification of explosion protected equipment. Each
the Notified Bodies is automatically accepted for use country within the IECEx scheme establishes an
within all of the participating union countries. In July ExCB (Ex Certification Body) which can approve
2003 a European Directive, called the ATEX products. ExCB’s can issue the national certification
Directive, which pertains to equipment for explosive for their country based upon the IECEx standards
atmospheres, was adopted. All equipment intended (including any national deviations) and the
for use in explosive atmospheres must comply with international certification. Currently, Australia is the
the ATEX Directive in order to be sold into the only country accepting international certifications for
European Union. use in their country.
5
Product Bulletin
9.2:001
Hazardous Area Classifications February 2010
FIELD COMMUNICATOR
Vmax = 30 VDC Voc = 1.9 VDC
Imax = 200 mA Isc = 32 μA
Pi = 1 W Po = 61 μW
Ci = 0 μF Ca = 100 μF
Li = 0 mH La = 5600 mH
6
Product Bulletin
9.2:001
February 2010 Hazardous Area Classifications
Determine Voc and Isc of the barrier. Note that in this Isc of the barrier must meet all of the following
example the output of the 475 (Voc(475) and Isc(475)) conditional requirements.
must also be considered because it can also add
energy to the loop besides just the barrier itself. Voc 1) Isc v Imax(DVC6010) + Isc(475) 226 mA +
of the barrier plus any additional voltage that could 0.032 mA 226.032 mA
be added to the loop from each device must be 2) Isc v Imax(DVC6010) 226 mA
subtracted from Vmax for each device. Isc of the
barrier plus any additional current that could be 3) Isc v Imax(475) 200 mA
added to the loop from each device must not exceed
Isc v 200 mA
Imax for each device.
7
Product Bulletin
9.2:001
Hazardous Area Classifications February 2010
Fisher and FIELDVUE are marks owned by one of the companies in the Emerson Process Management business division of Emerson Electric Co.
Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are
the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they
are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or
applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the
designs or specifications of such products at any time without notice. Neither Emerson, Emerson Process Management, nor any of their affiliated
entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of
any product remains solely with the purchaser and end user.
EFisher
8 Controls International LLC 2006, 2010; All Rights Reserved