Anda di halaman 1dari 164

PLANT & PETROCHEM CABLES GENERAL CATALOGUE

Plant &
Petrochem
Cables
technergy

TM

INTEGRATED CABLING SOLUTIONS

TEPLA
Plant & Petrochem Cables

technergy

TM

INTEGRATED CABLING SOLUTIONS

Introduction

All chemical, petrochemical, power and industrial plants require


complex and integrated power, control and instrumentation
systems. TechnergyTM is a central provider of power and
communication network cabling for harsh and demanding
Plant and Petrochemical environments.
Due to the extreme environmental conditions they have to
withstand, this cables must guarantee:

Installation in harsh environments


Direct contact with chemical agents (oils, greases, strong
hydrocarbons)
Resistance to fire
Low emission of dark smokes
Low emission of corrosive gases

TechnergyTM Plant and Petrochemical cables ensure outstanding


performances with advanced and innovative solutions in
terms of materials and design, such as Drylam (chemical and
moisture barrier) and Airbag (revolutionary polymeric shock
absorption system).
A vast experience as a supplier to the hydrocarbon processing
industry and in worldwide power plant projects make
Prysmian a reliable partner for all key players in the Plant and
Petrochemical industry.

Index

Instrumentation cables

TEPLA
Plant & Petrochem Cables

Identification codes

pag. 08

Symbols

pag. 10

>

according to BS 5308

TEPLA I - 0
(PE/PVC or XLPE/LS0H)

pag. 12

TEPLA I - I0
(PE/PVC or XLPE/LS0H)

pag. 14

TEPLA I - 0A
(PE/SWA/PVC or XLPE/SWA/LS0H)

pag. 16

TEPLA I - I0A
(PE/SWA/PVC or XLPE/SWA/LS0H)

pag. 18

TEPLA I - OLA
(PE/Pb/SWA/PVC or XLPE/Pb/SWA/LS0H)

pag. 20

TEPLA I - ODA
(PE/DRYLAM/SWA/PVC or XLPE/DRYLAM/SWA/LS0H)

pag. 22

TEPLA I - 0
(PE/PVC or XLPE/LS0H)

pag. 24

TEPLA I - 0
(PVC/PVC)

pag. 26

TEPLA I - I0
(PVC/PVC)

pag. 28

TEPLA I - OA
(PVC/SWA/PVC)

pag. 30

TEPLA I - I0A
(PVC/SWA/PVC)

pag. 32

TEPLA I - FR - 0
(XLPE/LS0H)

pag. 34

TEPLA I - FR - 0A
2

(XLPE/SWA/LS0H)

pag. 36

technergy

TM

INTEGRATED CABLING SOLUTIONS

Instrumentation cables

>

according to EN 50288

TEPLA I - 0
(PE/PVC or XLPE/PVC or XLPE/LS0H)

pag. 40

TEPLA I - I0
(PE/PVC or XLPE/PVC or XLPE/LS0H)

pag. 42

TEPLA I - 0A
(PE/SWA/PVC or XLPE/SWA/LS0H or XLPE/SWA/PVC)

pag. 44

TEPLA I - I0A
(PE/SWA/PVC or XLPE/SWA/LS0H or XLPE/SWA/PVC)

pag. 46

TEPLA I - OLA
(PE/Pb/SWA/PVC or XLPE/Pb/SWA/PVC or XLPE/Pb/SWA/LS0H)

pag. 48

TEPLA I - ODA
(PE/DRYLAM/SWA/PVC or XLPE/DRYLAM/SWA/PVC or XLPE/DRYLAM/SWA/LS0H)

pag. 50

TEPLA I - FR - O
(XLPE/LS0H)

pag. 52

TEPLA I - FR - O
(G4/PVC or G4/LS0H)

pag. 54

TEPLA I - FR - OA
(XLPE/LS0H)

pag. 56

TEPLA I - FR - OA
(G4/PVC or G4/LS0H)

pag. 58

TEPLA I - O
(PE/PVC or XLPE/PVC or XLPE/LS0H)

pag. 60

TEPLA I - FR - O
(XLPE/LS0H)

pag. 62

TEPLA I - FR - O
(G4/PVC or G4/LS0H)

pag. 64

Index

TEPLA
Plant & Petrochem Cables

Thermocouple cables
Standards of extension & compensating cables
for thermocouples

Thermocouple cables

>

pag. 68

according to BS 5308

TEPLA T - IO
(PE/PVC or XLPE/LS0H)

pag. 72

TEPLA T - IOA
(PE/SWA/PVC or XLPE/SWA/LS0H)

Thermocouple cables

>

pag. 74

according to EN 50288

TEPLA T - I0
(PE/PVC or XLPE/LS0H)

pag. 78

TEPLA T - I0A
(PE/SWA/PVC or XLPE/SWA//LS0H)

Control cables

>

pag. 80

according to BS 5308

TEPLA C - S
(PVC/PVC or XLPE/LS0H)

pag. 84

TEPLA C - SA
(PVC/SWA/PVC or XLPE/SWA/LS0H)

pag. 86

TEPLA C
(XLPE/PVC or XLPE/LS0H)

pag. 88

TEPLA C - A
(XLPE/SWA/PVC or XLPE/SWA/LS0H)

pag. 90

TEPLA C - FR
(XLPE/LS0H)

pag. 92

TEPLA C - FR - A
(XLPE/SWA/LS0H)

Control cables

>

pag. 94

according to EN 50288

TEPLA C - S
(PVC/PVC or XLPE/LS0H)

pag. 98

TEPLA C - SA
4

(PVC/SWA/PVC or XLPE/SWA/LS0H)

pag. 100

technergy

TM

INTEGRATED CABLING SOLUTIONS

Communication cables
TEPLA COM - S
IBM STANDARD

Power cables

>

pag. 104

Low Voltage & Earthing cables

TEPLA E
(PVC)

pag. 108

TEPLA L
(XLPE/PVC or XLPE/LS0H) - single core

pag. 110

TEPLA L - A
(XLPE/AWA/PVC OR XLPE/AWA/LS0H) - single core

pag. 112

TEPLA L
(XLPE/PVC or XLPE/LS0H) - multi-core

pag. 114

TEPLA L - A
(XLPE/SWA/PVC or XLPE/SWA/LS0H) - multi-core

pag. 116

TEPLA L - (AR)
(XLPE/PSA/PVC) - single core

pag. 118

TEPLA L - (AR)
(XLPE/PSA/PVC) - multi-core

pag. 120

TEPLA L - L
(XLPE/Pb/PVC) - single core

pag. 122

TEPLA L - L
(XLPE/Pb/PVC) - multi-core

pag. 124

TEPLA L - LA
(XLPE/Pb/AWA/PVC) - single core

pag. 126

TEPLA L - LA
(XLPE/Pb/PVC/SWA/PVC) - multi-core

pag. 128

TEPLA L - D
(XLPE/DRYLAM/PVC) - single core

pag. 130

TEPLA L - D
(XLPE/DRYLAM/PVC) - multi-core

pag. 132

TEPLA
Plant & Petrochem Cables

Power cables

>

Medium Voltage cables

TEPLA M - S
(XLPE/CuT/PVC or XLPE/CuT/LS0H) - single core

pag. 136

TEPLA M - S
(XLPE/CuT/PVC or XLPE/CuT/LS0H) - multi-core

pag. 138

TEPLA M - SA
(XLPE/CuT/AWA/PVC or XLPE/CuT/AWA/LS0H ) - single core

pag.140

TEPLA M - SA
(XLPE/CuT/SWA/PVC or XLPE/CuT/SWA/LS0H ) - multi-core

pag.142

TEPLA M - S(AR)
(XLPE/CuW/PSA/PVC) - single core

pag. 144

TEPLA M - S(AR)
(XLPE/CuW/PSA/PVC) - multi-core

pag. 146

TEPLA M - L
(XLPE/Pb/PVC) - single core

pag. 148

TEPLA M - SL
(XLPE/CuT/Pb/PVC) - multi-core

pag. 150

TEPLA M - D
(XLPE/DRYLAM/PVC) - single core

pag. 152

TEPLA M - SD
(XLPE/CuT/DRYLAM/PVC) - multi-core

pag. 154

technergy

TM

INTEGRATED CABLING SOLUTIONS

Identification codes

Conductor

Insulation

Assembly

Metallic screen

Armour/metallic sheath

Separation sheath/outer sheath

TEPLA
Plant & Petrochem Cables

round aluminium conductor

round flexible conductor

round rigid conductor

round solid conductor

mica glass tape

polyethylene insulation

E4

XLPE insulation

PVC insulation

G4

silicon

laid-up cores

twisted pairs/triads/quads

aluminium tape screen

H1

copper tape/wire screen

H5

aluminium/polyethylene longitudinally bonded tape screen

steel wires armour

lead alloy sheath

steel tapes armour

(AR)

PSA (AIR BAG)

PVC sheath

R4

polyamide

M1

LS0H thermoplastic sheath

technergy

TM

INTEGRATED CABLING SOLUTIONS

Symbols

TEPLA
Plant & Petrochem Cables

Fire behaviour
ACCORDING TO
IEC 60332-1 flame retardant
IEC 60332-3 cat A fire retardant
IEC 60332-3 cat C fire retardant
IEC 60331 fire resistant

Chemicals resistance
Outer sheath resistance to chemicals

Impacts
Cable mechanical resistance to impacts

Smoke density, corrosivity


and toxicity

low

Low emission of smoke, acid and toxic gases


IEC 61034 (smoke)
IEC 60754 (acid and toxic gases)

Temperature
Permissible minimum ambient temperature during laying

Lead free

Pb

Bending radius
r

Minimum bending radius during installation

10

Note: in case of laying operation with controlled bending (bending over a


shape, careful bending at terminations) at a temperature not lower
than 15 C, the specified bending radius may be halved.

technergy

TM

INTEGRATED CABLING SOLUTIONS

Instrumentation cables according to BS 5308

11

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - O
(PE/PVC or
XLPE/LS0H)
300/500 V

Construction

>
>
>
>
>
>

>
>

Applicable
standards

BS 5308-1
IEC 60332-1
IEC 60332-3C
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3C

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 1 or 2 or 5 of BS 6360
Insulation
polyethylene type 03 according to BS 6234 or XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC type TM1 according to BS 6746 or LS0H thermoplastic compound
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V BS 5308
or
e. g. : PRYSMIAN Afumex year - n x m x csa 300/500 V BS 5308

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3C

12

GOOD

GOOD

LS0H

-5 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA I - O 300/500 V (PE/PVC or XLPE/LS0H)

Type*

UEXHR
UEXOHR

FEXHR
FEXOHR

FEXHR
FEXOHR

UEXHR
UEXOHR

REXHR
REXOHR

(mm2)

(mm)

(/km)

(mm)

Diameter
over
assembly
plastic tape
(mm)

2x0,5
2x2x0,5 Q
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,8
0,8
0,8
0,8
0,8
0,8
0,8

36,0
36,0
36,0
36,0
36,0
36,0
36,0

1,8
1,8
1,8
1,8
1,8
1,8
1,8

3,7
4,4
9,7
12,0
14,2
16,3
19,9

5,4
6,1
12,0
14,5
16,7
19,0
22,6

39
56
138
226
308
400
561

65
73
144
174
200
228
271

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x0,5
2x2x0,5 Q
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,9
0,9
0,9
0,9
0,9
0,9
0,9

39,0
39,0
39,0
39,0
39,0
39,0
39,0

2,1
2,1
2,1
2,1
2,1
2,1
2,1

4,2
5,0
11,0
13,7
16,2
18,6
22,7

5,9
6,7
13,3
16,2
18,9
21,2
24,6

42
59
149
244
341
428
616

71
80
160
194
227
254
295

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x0,75
2x2x0,75 Q
5x2x0,75
10x2x0,75
15x2x0,75
20x2x0,75
30x2x0,75

1,0
1,0
1,0
1,0
1,0
1,0
1,0

26,0
26,0
26,0
26,0
26,0
26,0
26,0

2,3
2,3
2,3
2,3
2,3
2,3
2,3

4,6
5,5
12,1
15,0
17,8
20,4
24,9

6,3
7,2
14,6
17,7
20,4
23,5
28,4

53
81
212
360
500
665
969

76
86
175
212
245
282
341

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x1
2x2x1 Q
5x2x1
10x2x1
15x2x1
20x2x1
30x2x1

1,1
1,1
1,1
1,1
1,1
1,1
1,1

18,4
18,4
18,4
18,4
18,4
18,4
18,4

2,3
2,3
2,3
2,3
2,3
2,3
2,3

4,7
5,7
12,4
15,5
18,3
21,0
25,7

6,4
7,4
14,9
17,9
20,9
24,0
28,7

55
84
218
362
515
685
971

77
89
179
215
251
288
344

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x1,5
2x2x1,5 Q
5x2x1,5
10x2x1,5
15x2x1,5
20x2x1,5
30x2x1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,8
2,8
2,8
2,8
2,8
2,8
2,8

5,7
6,8
14,9
18,5
21,9
25,1
30,7

7,4
8,7
17,4
21,2
24,9
28,2
34,1

71
118
297
517
754
970
1420

89
104
209
254
299
338
409

115
115
85
85
85
85
85

40
40
40
40
40
40
40

Cross
section

Diameter of Maximum DC
resistance
conductor
at 20 C

Diameter
over
insulation

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

Capacitance

L/R

(mm)

(kg/km)

(mm)

(pF/m)

(H/)

* Refers only to PE/PVC construction

13

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - IO
(PE/PVC or
XLPE/LS0H)
300/500 V

Construction

>
>
>
>
>

>
>

>
>

Applicable
standards

BS 5308-1
IEC 60332-1
IEC 60332-3C
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3C

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 1 or 2 or 5 of BS 6360
Insulation
polyethylene type 03 according to BS 6234 or XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Individual screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC type TM1 according to BS 6746 or LS0H thermoplastic compound
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V BS 5308
or
e. g. : PRYSMIAN Afumex year - n x m x csa 300/500 V BS 5308

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3C

14

GOOD

GOOD

LS0H

-5 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA I - IO 300/500 V (PE/PVC or XLPE/LS0H)

(mm2)

(mm)

(/km)

(mm)

Diameter
over
assembly
plastic tape
(mm)

FEXHOHR

2x2x0,5
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,9
0,9
0,9
0,9
0,9
0,9

39,0
39,0
39,0
39,0
39,0
39,0

2,1
2,1
2,1
2,1
2,1
2,1

7,9
11,4
14,2
16,8
19,2
23,5

10,2
13,9
16,9
19,8
22,3
27,0

100
190
319
460
584
848

122
167
203
238
268
324

115
115
115
115
115
115

25
25
25
25
25
25

FEXHOHR

2x2x0,75
5x2x0,75
10x2x0,75
15x2x0,75
20x2x0,75
30x2x0,75

1,1
1,1
1,1
1,1
1,1
1,1

26,0
26,0
26,0
26,0
26,0
26,0

2,3
2,3
2,3
2,3
2,3
2,3

8,6
12,5
15,5
18,3
21,0
25,7

10,9
14,9
18,2
21,4
24,5
29,8

124
245
426
620
821
1212

131
179
218
257
294
358

115
115
115
115
115
115

25
25
25
25
25
25

UEXHOHR

2x2x1
5x2x1
10x2x1
15x2x1
20x2x1
30x2x1

1,1
1,1
1,1
1,1
1,1
1,1

18,4
18,4
18,4
18,4
18,4
18,4

2,3
2,3
2,3
2,3
2,3
2,3

8,9
12,8
15,9
18,8
21,7
26,5

11,1
15,3
18,6
21,9
25,2
29,1

127
253
438
638
851
1230

133
184
223
263
302
349

115
115
115
115
115
115

25
25
25
25
25
25

REXHOHR

2x2x1,5
5x2x1,5
10x2x1,5
15x2x1,5
20x2x1,5
30x2x1,5

1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1

2,8
2,8
2,8
2,8
2,8
2,8

10,5
15,2
18,9
22,3
25,7
31,8

13,0
17,9
22,0
25,8
29,1
33,8

170
342
612
886
1139
1667

156
215
264
310
349
406

115
115
115
115
115
115

40
40
40
40
40
40

Type*

Cross
section

Diameter of Maximum DC
resistance
conductor
at 20 C

Diameter
over
insulation

Min bending Capacitance


radius

L/R

Outer
diameter
approx

Weight
of cable
approx

(mm)

(kg/km)

(mm)

(pF/m)

(H/)

* Refers only to PE/PVC construction

15

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - OA
(PE/SWA/PVC or
XLPE/SWA/LS0H)
300/500 V

Construction

>
>
>
>
>
>

>
>
>

>

Applicable
standards

BS 5308-1
IEC 60332-1
IEC 60332-3C
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3C

STANDARD

EXCELLENT

0 C

Conductor
annealed copper wires according to class 1 or 2 or 5 of BS 6360
Insulation
polyethylene type 03 according to BS 6234 or XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Bedding
polyethylene type 03 according to BS 6234 or LS0H thermoplastic compound
Armour
galvanized steel wire
Outer sheath
PVC type TM1 in accordance with BS 6746 or LS0H thermoplastic
compound
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V BS 5308
or
e. g. : PRYSMIAN Afumex year - n x m x csa 300/500 V BS 5308

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3C

16

GOOD

EXCELLENT

LS0H

-5 C

14 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA I - OA 300/500 V (PE/SWA/PVC or XLPE/SWA/LS0H)

Type*

Cross
section

(mm2)
UEXHEFR
UEXOHEFR

FEXHEFR
FEXOHEFR

FEXHEFR
FEXOHEFR

UEXHEFR
UEXOHEFR

REXHEFR
REXOHEFR

Diameter Diameter Diameter Outer Weight of Min


Diameter Maximum Diameter Diameter Diameter
Capacitance
over
of armour over
over
DC
of
over
cable bending
diameter
conductor resistance insulation assembly
armour
wires
approx approx radius
inner
innr
at 20 C
plastic tape sheath
sheath
(/km)
(mm)
(mm)
(kg/km)
(pF/m)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)

L/R

(H/)

2x0,5
4x0,5
15x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,8
0,8
0,8
0,8
0,8
0,8
0,8

36,0
36,0
36,0
36,0
36,0
36,0
36,0

1,8
1,8
1,8
1,8
1,8
1,8
1,8

3,7
4,4
9,6
12,0
14,2
16,3
19,9

5,4
6,1
12,0
14,5
16,7
19,0
22,6

0,9
0,9
0,9
1,3
1,3
1,6
1,6

7,2
7,9
13,8
17,0
19,2
22,2
25,8

9,8
10,5
16,8
20,2
22,4
25,6
29,4

193
228
447
718
858
1170
1494

137
147
235
283
314
358
412

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x0,5
4x0,5
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,9
0,9
0,9
0,9
0,9
0,9
0,9

39,0
39,0
39,0
39,0
39,0
39,0
39,0

2,1
2,1
2,1
2,1
2,1
2,1
2,1

4,2
5,0
11,0
13,7
16,2
18,6
22,6

5,8
6,7
13,3
16,2
18,9
21,2
25,6

0,9
0,9
1,3
1,3
1,6
1,6
1,6

7,7
8,5
15,8
18,7
22,1
24,4
28,8

10,3
11,1
18,8
21,9
25,5
28,0
32,6

209
240
582
780
1111
1300
1629

144
155
263
307
357
392
456

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x0,75
4x0,75
5x2x0,75
10x2x0,75
15x2x0,75
20x2x0,75
30x2x0,75

1,1
1,1
1,1
1,1
1,1
1,1
1,1

26,0
26,0
26,0
26,0
26,0
26,0
26,0

2,3
2,3
2,3
2,3
2,3
2,3
2,3

4,6
5,5
12,1
15,0
17,8
20,4
24,9

6,3
7,2
14,6
17,7
20,4
23,5
28,4

0,9
0,9
1,3
1,6
1,6
1,6
2,0

8,1
9,0
17,1
20,9
23,6
26,7
32,4

10,7
11,8
20,1
24,3
27,2
30,3
36,4

233
289
714
1112
1374
1651
2425

150
165
281
340
381
424
510

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x1
4x1
5x2x1
10x2x1
15x2x1
20x2x1
30x2x1

1,1
1,1
1,1
1,1
1,1
1,1
1,1

18,4
18,4
18,4
18,4
18,4
18,4
18,4

2,3
2,3
2,3
2,3
2,3
2,3
2,3

4,7
5,7
12,4
15,5
18,3
21,0
25,7

6,4
7,4
14,9
17,9
20,9
24,0
28,7

0,9
0,9
1,3
1,6
1,6
1,6
2,0

8,2
9,2
17,4
21,1
24,1
27,2
32,7

10,8
12,0
20,4
24,5
27,7
30,8
36,7

236
286
715
1113
1386
1658
2395

151
168
286
343
388
431
514

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x1,5
4x1,5
5x2x1,5
10x2x1,5
15x2x1,5
20x2x1,5
30x2x1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,8
2,8
2,8
2,8
2,8
2,8
2,8

5,7
6,8
14,9
18,5
21,9
25,1
30,7

7,4
9,1
17,4
21,2
24,9
28,2
34,1

0,9
0,9
1,3
1,6
1,6
2,0
2,0

9,2
10,9
19,9
24,4
28,1
32,2
38,1

12,0
13,7
23,1
28,0
31,9
36,2
42,3

277
362
876
517
1771
2364
3123

168
192
323
392
447
507
592

115
115
85
85
85
85
85

40
40
40
40
40
40
40

* Refers only to PE/SWA/PVC construction

17

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - IOA
(PE/SWA/PVC or
XLPE/SWA/LS0H)
300/500 V

Construction

>
>
>
>

>
>

>
>
>
>

Applicable
standards

BS 5308-1
IEC 60332-1
IEC 60332-3C
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3C

STANDARD

EXCELLENT

0 C

Conductor
annealed copper wires according to class 1 or 2 or 5 of BS 6360
Insulation
polyethylene type 03 according to BS 6234 or XLPE
Pairs
twisted
Individual screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape 0,023 mm
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape 0,023 mm
Bedding
polyethylene type 03 according to BS 6234 or LS0H thermoplastic compound
Armour
galvanized steel wire
Outer sheath
PVC type TM1 according to BS 6746 or LS0H thermoplastic compound
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V BS 5308
or
e. g. : PRYSMIAN Afumex year - n x m x csa 300/500 V BS 5308

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3C

18

GOOD

EXCELLENT

LS0H

-5 C

14 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA I - IOA 300/500 V (PE/SWA/PVC or XLPE/SWA/LS0H)

Type*

Cross
section

(mm2)

Diameter Maximum Diameter Diameter Diameter Diameter Diameter Outer Weight of Min
Capacitance
over
of armour over
over
DC
of
over
diameter
cable bending
conductor resistance insulation assembly
armour
approx approx radius
wires
inner
at 20 C
plastic tape sheath
(/km)
(mm)
(mm)
(mm)
(kg/km)
(pF/m)
(mm)
(mm)
(mm)
(mm)
(mm)

L/R

(H/)

FEXHOHEFR

2x2x0,5
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,9
0,9
0,9
0,9
0,9
0,9

39,0
39,0
39,0
39,0
39,0
39,0

2,1
2,1
2,1
2,1
2,1
2,1

7,9
11,4
14,2
16,8
19,2
23,5

10,2
13,9
16,9
19,8
22,3
27,0

0,9
1,3
1,6
1,6
1,6
2,0

12,0
16,4
20,1
23,0
25,5
31,0

15,0
19,6
23,7
26,6
29,3
35,2

364
644
1017
1254
1476
2166

210
274
332
372
410
493

115
115
115
115
115
115

25
25
25
25
25
25

FEXHOHEFR

2x2x0,75
5x2x0,75
10x2x0,75
15x2x0,75
20x2x0,75
30x2x0,75

1,1
1,1
1,1
1,1
1,1
1,1

26,0
26,0
26,0
26,0
26,0
26,0

2,3
2,3
2,3
2,3
2,3
2,3

8,6
12,5
15,5
18,3
21,0
25,7

10,9
14,9
18,2
21,4
24,5
29,8

0,9
1,3
1,6
1,6
2,0
2,0

12,7
17,4
21,4
24,6
28,5
33,8

15,7
20,6
25,0
28,4
32,5
38,2

425
771
1212
1534
2079
2774

220
288
350
398
455
535

115
115
115
115
115
115

25
25
25
25
25
25

UEXHOHEFR

2x2x1
5x2x1
10x2x1
15x2x1
20x2x1
30x2x1

1,1
1,1
1,1
1,1
1,1
1,1

18,4
18,4
18,4
18,4
18,4
18,4

2,3
2,3
2,3
2,3
2,3
2,3

8,9
12,8
15,9
18,8
21,7
26,0

11,1
15,3
18,6
21,9
25,1
30,0

0,9
1,3
1,6
1,6
2,0
2,0

12,9
17,8
21,8
25,1
29,1
34,0

15,9
21,0
25,4
28,9
33,1
38,4

412
746
1198
1510
2150
2645

223
294
356
405
463
538

115
115
115
115
115
115

25
25
25
25
25
25

REXHOHEFR

2x2x1,5
5x2x1,5
10x2x1,5
15x2x1,5
20x2x1,5
30x2x1,5

1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1

2,8
2,8
2,8
2,8
2,8
2,8

10,5
15,2
18,9
22,3
25,7
31,3

13,0
17,9
22,0
25,8
29,1
35,4

1,3
1,6
1,6
2,0
2,0
2,0

15,5
21,1
25,2
29,8
33,1
39,4

18,7
24,5
29,0
33,8
37,3
44,2

599
1067
1502
2125
2552
3402

262
343
406
473
522
619

115
115
115
115
115
115

40
40
40
40
40
40

* Refers only to PE/SWA/PVC construction

19

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - OLA
(PE/Pb/SWA/PVC or
XLPE/Pb/SWA/LS0H)
300/500 V

Construction

>
>
>
>
>

>
>
>
>
>

Applicable
standards

Conductor
annealed copper wires according to class 1 or 2 or 5 of BS 6360
Insulation
polyethylene type 03 according to BS 6234 or XLPE
Pairs
twisted
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape 0,023 mm
Bedding
PVC
Lead sheath
inner sheath
Armour
galvanized steel wire
Outer sheath
PVC type TM1 according to BS 6746 or LS0H thermoplastic compound
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V BS 5308
or
e. g. : PRYSMIAN Afumex year - n x m x csa 300/500 V BS 5308

BS 5308-1
IEC 60332-1
IEC 60332-3C
IEC 60754
IEC 61034

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

IEC 60332-1
IEC 60332-3C

EXELLENT

EXCELLENT

0 C

16 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3C

20

EXELLENT

EXCELLENT

LS0H

-5 C

16 D

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA I - OLA 300/500 V (PE/Pb/SWA/PVC or XLPE/Pb/SWA/LS0H)

Type*

UEXHRLRFR
UEXOHRLRFR

FEXHRLRFR
FEXOHRLRFR

FEXHRLRFR
FEXOHRLRFR

UEXHRLRFR
UEXOHRLRFR

REXHRLRFR
REXOHRLRFR

Cross Diameter Maximu Diameter Diameter Diameter Diameter Diameter Diameter Outer Weight
Min
Capacitance L/R
over inner over lead
of
over diameter of cable bending
DC
section
under
of
over
armour armour armour approx approx radius
sheath
conductor resistance insulation sheath
at 20 C
wires
2
(H/)
(/km)
(mm )
(mm)
(mm)
(mm)
(mm) (kg/km) (mm)
(pF/m)
(mm)
(mm)
(mm)
(mm)
2x0,5
2x2x0,5 Q
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,8
0,8
0,8
0,8
0,8
0,8
0,8

36,0
36,0
36,0
36,0
36,0
36,0
36,0

1,8
1,8
1,8
1,8
1,8
1,8
1,8

5,3
6,0
11,8
14,4
16,6
18,9
22,5

7,5
8,2
14,0
16,6
19,0
21,5
25,3

9,1
9,8
15,6
18,6
21,0
23,5
27,3

0,9
0,9
0,9
1,3
1,3
1,6
1,6

10,9
11,6
17,4
21,1
23,5
26,7
30,5

13,7
14,4
20,6
24,5
27,1
30,3
34,3

580
640
1140
1580
1920
2460
3060

219
231
330
392
434
485
549

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x0,5
2x2x0,5 Q
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,9
0,9
0,9
0,9
0,9
0,9
0,9

39,0
39,0
39,0
39,0
39,0
39,0
39,0

2,1
2,1
2,1
2,1
2,1
2,1
2,1

5,8
6,6
13,2
16,1
18,8
21,2
25,6

8,0
8,8
15,4
18,5
21,4
23,8
28,6

9,6
10,4
17,0
20,5
23,4
25,8
31,0

0,9
0,9
1,3
1,6
1,6
1,6
2,0

11,4
12,2
19,5
23,7
26,6
29,0
35,0

14,2
15,0
22,7
27,3
30,2
32,8
39,2

620
690
1240
170
2140
2710
3430

227
240
363
437
483
525
627

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x0,75
2x2x0,75 Q
5x2x0,75
10x2x0,75
15x2x0,75
20x2x0,75
30x2x0,75

1,1
1,1
1,1
1,1
1,1
1,1
1,1

26,0
26,0
26,0
26,0
26,0
26,0
26,0

2,3
2,3
2,3
2,3
2,3
2,3
2,3

6,2
7,1
14,5
17,4
20,4
23,4
27,9

8,4
9,3
16,7
19,8
23,0
26,2
30,9

10,0
10,9
18,7
21,8
25,0
28,6
33,3

0,9
0,9
1,6
1,6
1,6
2,0
2,0

11,8
12,7
21,9
25,0
28,2
32,6
37,3

14,6
15,7
25,3
28,6
32,0
36,6
41,5

660
750
1540
2220
2710
3160
4500

234
252
405
458
512
586
664

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x1
2x2x1 Q
5x2x1
10x2x1
15x2x1
20x2x1
30x2x1

1,1
1,1
1,1
1,1
1,1
1,1
1,1

18,4
18,4
18,4
18,4
18,4
18,4
18,4

2,3
2,3
2,3
2,3
2,3
2,3
2,3

6,3
7,3
14,8
17,9
20,9
24,0
28,7

8,5
9,5
17,0
20,3
23,5
26,8
31,7

10,1
11,1
19,0
22,3
25,5
29,2
34,1

0,9
0,9
1,6
1,6
1,6
2,0
2,0

11,9
12,9
22,2
25,5
28,7
33,2
38,1

14,7
15,9
25,6
29,1
32,5
37,2
42,3

670
770
1760
2260
2780
3660
4590

236
254
410
466
520
595
677

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x1,5
2x2x1,5 Q
5x2x1,5
10x2x1,5
15x2x1,5
20x2x1,5
30x2x1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,8
2,8
2,8
2,8
2,8
2,8
2,8

7,3
8,6
17,3
21,1
24,9
28,1
34,1

9,5
10,8
19,7
23,7
27,7
31,1
37,5

11,1
12,4
21,7
25,7
30,1
33,5
40,3

0,9
1,3
1,6
1,6
2,0
2,0
2,5

12,9
14,9
24,9
28,9
34,1
37,5
45,3

15,9
17,9
28,3
32,7
38,1
41,7
49,9

750
890
2050
2690
3400
4380
5620

254
286
453
523
610
667
798

115
115
85
85
85
85
85

40
40
40
40
40
40
40

* Refers only to PE/LEAD/SWA/PVC construction

21

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - ODA
(PE/DRYLAM/SWA/PVC or
XLPE/DRYLAM/SWA/LS0H)
300/500 V

Construction

>
>
>
>
>

>
>

>
>
>

Applicable
standards

BS 5308-1
IEC 60332-1
IEC 60332-3C
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3C

EXELLENT

EXCELLENT

0 C

Conductor
annealed copper wires according to class 1 or 2 or 5 of BS 6360
Insulation
polyethylene type 03 according to BS 6234 or XLPE
Pairs
twisted
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape 0,023 mm
Bedding
PVC
Chemical moisture barrier
longitudinally applied AI tape bonded with extruded chemical resistant
polymeric layer
Armour
galvanized steel wire
Outer sheath
PVC type TM1 according to BS 6746 or LS0H thermoplastic compound
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V BS 5308
or
e. g. : PRYSMIAN Afumex year - n x m x csa 300/500 V BS 5308

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3C

22

EXELLENT

EXCELLENT

LS0H

-5 C

14 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA I - ODA 300/500 V (PE/DRYLAM/SWA/PVC or XLPE/DRYLAM/SWA/LS0H)

Type*

Cross
section

(mm2)

Diameter Maximum
DC
of
conductor resistance
at 20 C
(/km)
(mm)

Diameter
over
insulation
(mm)

Diameter Diameter of Diameter


over
armour
over
inner
wires
armour
sheath
(mm)
(mm)
(mm)

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

Capacitance

L/R

(mm)

(kg/km)

(mm)

(pF/m)

(H/)

RE4OHRH5R4FR
RE4XOHRH5R4FR

1x2x0,5
2x2x0,5
4x2x0,5
5x2x0,5
6x2x0,5
10x2x0,5
12x2x0,5
15x2x0,5
20x2x0,5
24x2x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16

8,77
12,45
14,11
15,95
16,26
18,94
19,85
21,73
24,41
26,25

0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25

10,57
14,24
15,91
17,75
18,06
20,74
21,65
23,53
26,91
28,75

13,3
17,1
18,8
20,6
21,0
23,8
24,7
26,8
30,1
32,2

324,4
490,6
569,1
645,9
679,2
852,6
925,6
1057,2
1412,9
1584,8

186
240
263
289
293
334
346
376
422
450

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

RE4OHRH5R4FR
RE4XOHRH5R4FR

1x2x0,75
2x2x0,75
4x2x0,75
5x2x0,75
6x2x0,75
10x2x0,75
12x2x0,75
15x2x0,75
20x2x0,75
24x2x0,75

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28

8,99
12,86
14,62
16,61
16,93
19,95
20,66
22,65
25,49
27,62

0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25

10,79
14,66
16,42
18,41
18,73
21,75
22,45
25,15
27,99
30,12

13,5
17,6
19,3
21,3
21,8
24,8
25,6
28,4
31,2
33,5

336,6
511,7
602,4
686,8
733,7
929,3
991,4
1295,4
1533,3
1735,9

189
246
270
298
306
348
358
397
437
469

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

RE4OHRH5R4FR
RE4XOHRH5R4FR

1x2x1
2x2x1
4x2x1
5x2x1
6x2x1
10x2x1
12x2x1
15x2x1
20x2x1
24x2x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49

9,37
13,65
15,76
17,87
18,02
21,33
22,11
24,51
27,56
29,67

0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25

11,17
15,45
17,56
19,67
19,82
23,13
24,61
27,01
30,06
32,17

13,9
18,4
20,5
22,8
22,9
26,4
27,8
30,2
33,5
35,6

354,9
559,4
677,2
778,9
813,9
1055,1
1291,5
1491,6
1781,4
1976,0

194
257
286
319
321
370
389
423
468
498

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

RE4OHRH5R4FR
RE4XOHRH5R4FR

1x2x1,5
2x2x1,5
4x2x1,5
5x2x1,5
6x2x1,5
10x2x1,5
12x2x1,5
15x2x1,5
20x2x1,5
24x2x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79

10,11
14,95
17,09
19,69
19,86
23,69
24,59
27,02
30,45
33,2

0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,6

11,91
16,75
18,89
21,49
21,66
26,19
27,09
29,52
32,95
36,4

14,8
19,9
22,0
24,6
25,0
29,6
30,5
33,1
36,6
40,2

403,6
647,1
781,8
913,2
971,2
1459,7
1573,5
1806,5
2163,9
2727,4

207
278
308
344
349
414
427
464
512
563

150
150
150
150
150
150
150
150
150
150

40
40
40
40
40
40
40
40
40
40

RE4OHRH5R4FR
RE4XOHRH5R4FR

1x2x2,5
2x2x2,5
4x2x2,5
5x2x2,5
6x2x2,5
10x2x2,5
12x2x2,5
15x2x2,5
20x2x2,5
24x2x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18

10,92
16,56
19,2
21,93
22,32
26,66
27,68
30,65
34,75
37,62

0,9
0,9
1,25
1,25
1,25
1,25
1,25
1,6
1,6
1,6

12,72
18,36
21,7
24,43
24,82
29,16
30,18
33,85
37,95
40,82

15,6
21,5
25,0
27,9
28,3
32,9
34,1
38,0
42,3
45,3

448,5
754,5
1095,5
1283,6
1365,8
1815,8
1983,5
2537,5
3090,5
3509,7

219
300
350
391
396
460
477
531
592
634

150
150
150
150
150
150
150
150
150
150

60
60
60
60
60
60
60
60
60
60

* Refers only to PE/DRYLAM/SWA/PVC construction

23

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - O
(PE/PVC or
XLPE/LS0H)
300/500 V

Construction

>
>
>
>
>
>

>
>

Applicable
standards

BS 5308-1
IEC 60332-1
IEC 60332-3C
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3C

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 1 or 2 or 5 of IEC 60228
Insulation
polyethylene type 03 according to BS 6234 or XLPE
Triples
twisted
Identification triples
blue, brown, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC type TM1 according to BS 6746 or LS0H thermoplastic compound
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V BS 5308
or
e. g. : PRYSMIAN Afumex year - n x m x csa 300/500 V BS 5308

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3C

24

GOOD

GOOD

LS0H

-5 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA I - O 300/500 V (PE/PVC or XLPE/LS0H)

Cross
section

Diameter of
conductor

Maximum DC
resistance
at 20 C

Diameter
over
insulation

(mm2)

(mm)

(/km)

UEXHR
UEXOHR

3x0,5
2x3x0,5
5x3x0,5
10x3x0,5
15x3x0,5
20x3x0,5
30x3x0,5

0,8
0,8
0,8
0,8
0,8
0,8
0,8

FEXHR
FEXOHR

3x0,5
2x3x0,5
5x3x0,5
10x3x0,5
15x3x0,5
20x3x0,5
30x3x0,5

FEXHR
FEXOHR

Outer
diameter
approx

Weight
of cable
approx

Min bending
radius

(mm)

Diameter
over
assembly
plastic tape
(mm)

(mm)

(kg/km)

(mm)

36,0
36,0
36,0
36,0
36,0
36,0
36,0

1,8
1,8
1,8
1,8
1,8
1,8
1,8

3,9
7,4
10,3
13,5
16,6
19,0
23,5

5,5
9,6
12,7
16,1
19,6
22,0
26,9

40
90
170
290
420
540
790

66
115
153
193
235
264
323

0,9
0,9
0,9
0,9
0,9
0,9
0,9

39,0
39,0
39,0
39,0
39,0
39,0
39,0

2,1
2,1
2,1
2,1
2,1
2,1
2,1

4,4
8,4
11,7
15,4
18,9
21,6
26,8

6,0
10,6
14,1
18,0
21,9
24,6
30,2

50
100
190
320
470
600
880

72
127
170
216
262
29
362

3x0,75
2x3x0,75
5x3x0,75
10x3x0,75
15x3x0,75
20x3x0,75
30x3x0,75

1,1
1,1
1,1
1,1
1,1
1,1
1,1

26,0
26,0
26,0
26,0
26,0
26,0
26,0

2,3
2,3
2,3
2,3
2,3
2,3
2,3

4,9
9,3
12,9
16,9
20,8
23,8
29,5

6,5
11,5
15,3
19,5
23,8
27,2
33,5

60
115
220
395
580
765
1135

78
138
184
234
285
327
402

UEXHR
UEXOHR

3x1
2x3x1
5x3x1
10x3x1
15x3x1
20x3x1
30x3x1

1,1
1,1
1,1
1,1
1,1
1,1
1,1

18,4
18,4
18,4
18,4
18,4
18,0
18,4

2,3
2,3
2,3
2,3
2,3
2,3
2,3

5,0
9,5
13,3
17,4
21,3
24,4
30,3

6,6
11,7
15,7
20,0
24,3
27,8
34,3

65
130
260
470
690
915
1360

79
141
188
240
292
334
412

REXHR
REXOHR

3x1,5
2x3x1,5
5x3x1,5
10x3x1,5
15x3x1,5
20x3x1,5
30x3x1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,8
2,8
2,8
2,8
2,8
2,8
2,8

6,0
11,4
15,9
20,8
25,6
29,3
36,3

8,2
13,8
18,5
23,8
29,0
32,7
40,3

95
185
380
700
1030
1330
1990

98
166
222
286
347
392
483

Type*

* Refers only to PE/PVC construction

25

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - O
(PVC/PVC)
300/500 V

Construction

>
>
>
>
>
>

>
>

Applicable
standards

BS 5308-2
Design guidelines
IEC 60332-1 Flame retardant
IEC 60332-3C Fire retardant on bunched cables (if required)

IEC 60332-1
IEC 60332-3C

26

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 1 or 2 or 5 of BS 6360
Insulation
PVC type TI1 according to BS 6746
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC type TM1 according to BS 6746
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V BS 5308

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-2


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA I - O 300/500 V (PVC/PVC)

Type

FRXHR
FRXOHR

FRXHR
FRXOHR

RRXHR
RRXOHR

Cross
section

Diameter
of
conductor

Maximum DC
resistance
at 20 C

Diameter
over
insulation

Diameter over
assembly plastic
tape

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

(mm2)

(mm)

(/km)

(mm)

(mm)

(mm)

(kg/km)

(mm)

2x0,5
2x2x0,5 Q
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,9
0,9
0,9
0,9
0,9
0,9
0,9

39,0
39,0
39,0
39,0
39,0
39,0
39,0

2,1
2,1
2,1
2,1
2,1
2,1
2,1

4,2
5,0
11,0
13,7
16,2
18,6
22,7

5,9
6,7
13,3
16,2
18,9
21,2
25,8

52
72
169
284
401
508
745

70
80
160
195
230
250
310

2x0,75
2x2x0,75 Q
5x2x0,75
10x2x0,75
15x2x0,75
20x2x0,75
30x2x0,75

1,1
1,1
1,1
1,1
1,1
1,1
1,1

26,0
26,0
26,0
26,0
26,0
26,0
26,0

2,3
2,3
2,3
2,3
2,3
2,3
2,3

4,6
5,5
12,1
15,0
17,8
20,4
24,9

6,3
7,2
14,6
17,7
20,4
23,5
28,4

53
81
212
360
500
665
969

80
90
180
210
250
280
340

2x1,5
2x2x1,5 Q
5x2x1,5
10x2x1,5
15x2x1,5
20x2x1,5
30x2x1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,8
2,8
2,8
2,8
2,8
2,8
2,8

5,7
6,9
14,9
18,5
21,9
25,1
30,7

7,6
9,1
17,4
21,2
24,9
28,2
34,1

94
150
328
581
850
1097
1612

90
110
210
255
300
340
410

27

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - IO
(PVC/PVC)
300/500 V

Construction

>
>
>
>
>

>
>

>
>

Applicable
standards

BS 5308-2
Design guidelines
IEC 60332-1 Flame retardant
IEC 60332-3C Fire retardant on bunched cables (if required)

IEC 60332-1
IEC 60332-3C

28

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 1 or 2 or 5 of BS 6360
Insulation
PVC type TI1 according to BS 6746
Pairs
twisted
Identification pairs
blue, black numbered
Individul screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC type TM1 according to BS 6746
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V BS 5308

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-2


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA I - IO 300/500 V (PVC/PVC)

Cross
section

Diameter
of
conductor

Maximum DC
resistance
at 20 C

Diameter
over
insulation

Diameter over
assembly plastic
tape

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

(mm2)

(mm)

(/km)

(mm)

(mm)

(mm)

(kg/km)

(mm)

FRXHOHR

2x2x0,5
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,9
0,9
0,9
0,9
0,9
0,9

39,0
39,0
39,0
39,0
39,0
39,0

2,1
2,1
2,1
2,1
2,1
2,1

7,9
11,4
14,2
16,8
19,2
23,5

10,2
13,9
16,9
19,8
22,3
27,0

108
210
359
519
664
968

120
170
200
240
270
320

FRXHOHR

2x2x0,75
5x2x0,75
10x2x0,75
15x2x0,75
20x2x0,75
30x2x0,75

1,1
1,1
1,1
1,1
1,1
1,1

26,0
26,0
26,0
26,0
26,0
26,0

2,3
2,3
2,3
2,3
2,3
2,3

8,6
12,5
15,5
18,3
21,0
25,7

10,9
14,9
18,2
21,4
24,5
29,8

124
245
426
620
821
1212

130
180
220
260
295
360

RRXHOHR

2x2x1,5
5x2x1,5
10x2x1,5
15x2x1,5
20x2x1,5
30x2x1,5

1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1

2,8
2,8
2,8
2,8
2,8
2,8

10,6
15,2
18,9
22,3
25,7
31,4

13,3
17,9
22,0
25,8
29,1
35,4

230
373
676
982
1267
1877

160
215
260
310
350
430

Type

29

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - OA
(PVC/SWA/PVC)
300/500 V

Construction

>
>
>
>
>

>
>
>
>

Applicable
standards

BS 5308-2
Design guidelines
IEC 60332-1 Flame retardant
IEC 60332-3C Fire retardant on bunched cables (if required)

IEC 60332-1
IEC 60332-3C

30

STANDARD

EXCELLENT

0 C

Conductor
annealed copper wires according to class 1 or 2 or 5 of BS 6360
Insulation
PVC type TI1 according to BS 6746
Pairs
twisted
Identification pairs
blue, black numbered
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Bedding
PVC type TM1 according to BS 6746
Armour
galvanized steel wire
Outer sheath
PVC type TM1 according to BS 6746
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V BS 5308

14 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-2


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA I - OA 300/500 V (PVC/SWA/PVC)

Type

FRXHRFR
FRXOHRFR

FRXHRFR
FRXOHRFR

RRXHRFR
RRXOHRFR

Cross
section

Diameter
of
conductor

Maximum DC
resistance
at 20 C

Diameter
over
insulation

(mm2)

(mm)

(/km)

2x0,5
4x0,5
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,9
0,9
0,9
0,9
0,9
0,9
0,9

2x0,75
4x0,75
5x2x0,75
10x2x0,75
15x2x0,75
20x2x0,75
30x2x0,75
2x1,5
4x1,5
5x2x1,5
10x2x1,5
15x2x1,5
20x2x1,5
30x2x1,5

Diameter
over
inner
sheath
(mm)

Diameter of
armour
wires

Diameter
over
armour

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

(mm)

Diameter
over
assembly
plastic tape
(mm)

(mm)

(mm)

(mm)

(kg/km)

(mm)

39,0
39,0
39,0
39,0
39,0
39,0
39,0

2,1
2,1
2,1
2,1
2,1
2,1
2,1

4,2
5,1
11,0
13,7
16,2
18,6
23,1

5,9
6,8
13,3
16,2
18,9
21,2
26,2

0,9
0,9
1,3
1,3
1,6
1,6
1,6

7,7
8,6
15,8
18,7
22,1
24,4
29,4

10,3
11,2
18,8
21,9
25,5
28,0
33,2

218
267
630
840
1196
1406
1882

144
157
263
307
357
392
465

1,1
1,1
1,1
1,1
1,1
1,1
1,1

26,0
26,0
26,0
26,0
26,0
26,0
26,0

2,3
2,3
2,3
2,3
2,3
2,3
2,3

4,6
5,5
12,1
15,0
17,8
20,4
24,9

6,3
7,2
14,6
17,7
20,4
23,5
28,4

0,9
0,9
1,3
1,6
1,6
1,6
2,0

8,1
9,0
17,1
20,9
23,6
26,7
32,4

10,7
11,8
20,1
24,3
27,2
30,3
36,4

233
289
714
1112
1374
1651
2425

150
165
281
340
381
424
510

1,6
1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,8
2,8
2,8
2,8
2,8
2,8
2,8

5,7
6,8
12,3
18,5
21,9
25,1
30,7

7,4
8,7
14,8
21,2
24,9
28,2
34,1

0,9
0,9
1,3
1,6
1,6
2,0
2,0

9,2
10,5
17,3
24,4
28,1
32,2
38,1

12,0
13,3
20,5
28,0
31,9
36,2
42,3

299
370
826
1478
1899
2525
3358

168
186
287
392
447
507
595

31

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - IOA
(PVC/SWA/PVC)
300/500 V

Construction

>
>
>
>

>
>

>
>
>
>

Applicable
standards

BS 5308-2
Design guidelines
IEC 60332-1 Flame retardant
IEC 60332-3C Fire retardant on bunched cables (if required)

IEC 60332-1
IEC 60332-3C

32

STANDARD

EXCELLENT

0 C

Conductor
annealed copper wires according to class 1 or 2 or 5 of BS 6360
Insulation
PVC type TI1 according to BS 6746
Pairs
twisted
Individual screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Bedding
PVC type TM1 according to BS 6746
Armour
galvanized steel wire
Outer sheath
PVC type TM1 according to BS 6746
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V BS 5308

14 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-2


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA I - IOA 300/500 V (PVC/SWA/PVC)

Cross
section

Diameter
of
conductor

Maximum DC
resistance
at 20 C

Diameter
over
insulation

(mm2)

(mm)

(/km)

FRXHOHRFR

2x2x0,5
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
20x2x0,5
30x2x0,5

0,9
0,9
0,9
0,9
0,9
0,9
0,9

FRXHOHRFR

2x2x0,75
5x2x0,75
10x2x0,75
15x2x0,75
20x2x0,75
30x2x0,75

RRXHOHRFR

2x2x1,5
5x2x1,5
10x2x1,5
15x2x1,5
20x2x1,5
30x2x1,5

Type

Diameter
over
inner
sheath
(mm)

Diameter of
armour
wires

Diameter
over
armour

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

(mm)

Diameter
over
assembly
plastic tape
(mm)

(mm)

(mm)

(mm)

(kg/km)

(mm)

39,0
39,0
39,0
39,0
39,0
39,0
39,0

2,1
2,1
2,1
2,1
2,1
2,1
2,1

7,9
11,4
14,2
16,8
19,2
19,2
23,5

10,2
13,9
16,9
19,8
22,3
22,3
27,0

0,9
1,3
1,6
1,6
1,6
1,6
2,0

12,0
16,4
20,1
23,0
25,5
25,5
31,0

15,0
19,6
23,7
26,6
29,3
29,3
35,2

393
696
1129
1411
1621
1621
2375

210
274
332
372
410
410
493

1,1
1,1
1,1
1,1
1,1
1,1

26,0
26,0
26,0
26,0
26,0
26,0

2,3
2,3
2,3
2,3
2,3
2,3

8,6
12,5
15,5
18,3
21,0
25,7

10,9
14,9
18,2
21,4
24,5
29,8

0,9
1,3
1,6
1,6
2,0
2,0

12,7
17,4
21,4
24,6
28,5
33,8

15,7
20,6
25,0
28,4
32,5
38,2

425
771
1212
1534
2079
2774

220
288
350
398
455
535

1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1

2,8
2,8
2,8
2,8
2,8
2,8

10,5
15,2
18,9
22,3
25,7
31,4

13,0
17,9
22,0
25,8
29,1
35,4

1,3
1,6
1,6
2,0
2,0
2,0

15,5
21,1
25,2
29,8
33,1
39,4

18,7
24,5
29,0
33,8
37,3
44,2

641
1144
1630
2306
2776
3732

262
343
406
473
522
619

33

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - FR - O
(XLPE/LS0H)
300/500 V

Construction

>
>
>
>
>
>
>

>
>

Applicable
standards

Conductor
annealed copper wires according to class 1 or 2 or 5 of IEC 60228
Fire barrier
mica/glass tape
Insulation
XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
LS0H compound
Marking
e. g. : PRYSMIAN Afumex year - n x m x csa 300/500 V IEC 60331

BS 5308-1
IEC 60332-1
IEC 60332-3C
IEC 60331
IEC 60754
IEC 61034

Design guideline
Flame retardant
Fire retardant on bunched cables (if required)
Fire resistant test
Halogen free properties
Low smoke emission

low
r

34

IEC 60332-1
IEC 60332-3C
IEC 60331

GOOD

GOOD

LS0H

0 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C
> Fire resistant cables according to IEC 60331
TEPLA I - FR - O 300/500 V (XLPE/LS0H)

Type

UTE4XHM1
UTE4XOHM1

FTE4XHM1
FTE4XOHM1

FTE4XHM1
FTE4XOHM1

UTE4XHM1
UTE4XOHM1

RTE4XHM1
RTE4XOHM1

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

Capacitance

L/R

(mm)

Diameter
over
assembly
plastic tape
(mm)

(mm)

(kg/km)

(mm)

(pF/m)

(H/)

36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,3
2,3
2,3
2,3
2,3
2,3
2,3

4,8
5,7
12,4
15,4
18,2
20,9
25,6

6,4
7,3
14,6
17,8
20,6
23,5
28,2

45
65
165
275
380
490
640

76
88
175
214
247
282
338

115
115
75
75
75
75
75

25
25
25
25
25
25
25

0,9
0,9
0,9
0,9
0,9
0,9
0,9

39,0
39,0
39,0
39,0
39,0
39,0
39,0

2,6
2,6
2,6
2,6
2,6
2,6
2,6

5,2
6,2
13,6
17,0
20,1
23,0
28,1

6,8
7,8
15,8
19,4
22,7
25,6
31,1

50
70
175
290
410
520
680

82
94
190
232
272
307
373

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x0,75
2x2x0,75 Q
5x2x0,75
10x2x0,75
15x2x0,75
20x2x0,75
30x2x0,75

1,1
1,1
1,1
1,1
1,1
1,1
1,1

26,0
26,0
26,0
26,0
26,0
26,0
26,0

3,3
3,3
3,3
3,3
3,3
3,3
3,3

6,6
8,0
17,5
21,7
25,7
29,5
35,9

8,2
9,6
19,9
24,3
28,3
32,5
39,3

55
83
210
360
500
550
700

99
115
238
291
340
389
472

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x1
2x2x1 Q
5x2x1
10x2x1
15x2x1
20x2x1
30x2x1

1,1
1,1
1,1
1,1
1,1
1,1
1,1

18,4
18,4
18,4
18,4
18,4
18,4
18,4

2,8
2,8
2,8
2,8
2,8
2,8
2,8

5,7
6,9
15,1
18,8
22,2
25,5
31,2

7,3
8,5
17,5
21,2
24,8
28,5
34,2

60
95
250
420
600
790
850

88
102
210
255
298
342
411

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2x1,5
2x2x1,5 Q
5x2x1,5
10x2x1,5
15x2x1,5
20x2x1,5

1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1

3,3
3,3
3,3
3,3
3,3
3,3

6,8
8,1
17,7
22,0
26,1
29,9

8,4
9,9
20,1
24,6
29,1
32,9

78
130
330
580
850
1090

101
119
242
295
349
394

115
115
85
85
85
85

40
40
40
40
40
40

Cross
section

Diameter
of
conductor

Maximum DC
resistance
at 20 C

Diameter
over
insulation

(mm2)

(mm)

(/km)

2x0,5
2x2x0,5 Q
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,8
0,8
0,8
0,8
0,8
0,8
0,8

2x0,5
2x2x0,5 Q
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

35

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - FR - OA
(XLPE/SWA/LS0H)
300/500 V

Construction

>
>
>
>
>
>
>

>
>
>
>

Applicable
standards

Conductor
annealed copper wires according to class 1 or 2 or 5 of IEC 60228
Fire barrier
mica /glass tape
Insulation
XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Bedding
LS0H compound
Armour
galvanized steel wire
Outer sheath
LS0H compound
Marking
e. g. : PRYSMIAN Afumex year - n x m x csa 300/500 V IEC 60331

BS 5308-1
IEC 60332-1
IEC 60332-3C
IEC 60754
IEC 61034

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties
Low smoke emission

low
r

36

IEC 60332-1
IEC 60332-3C
IEC 60331

GOOD

EXCELLENT

LS0H

-5 C

14 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables according to BS 5308-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C
> Fire resistant cables according to IEC 60331
TEPLA I - FR - OA 300/500 V (XLPE/SWA/LS0H)

Type

UTE4XHM1FM1
UTE4XOHM1FM1

FTE4XHM1FM1
FTE4XOHM1FM1

FTE4XHM1FM1
FTE4XOHM1FM1

UTE4XHM1FM1
UTE4XOHM1FM1

RTE4XHM1FM1
RTE4XOHM1FM1

Cross
section

Diameter Maximu DC Diameter


resistance
of
over
conductor at 20 C insulation

Diameter Diameter
Diameter
over inner of armour
over
assembly
sheath
wires
plastic tape
(mm)
(mm)
(mm)

(mm2)

(mm)

(/km)

(mm)

2x0,5
2x2x0,5 Q
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,8
0,8
0,8
0,8
0,8
0,8
0,8

36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,3
2,3
2,3
2,3
2,3
2,3
2,3

4,8
5,7
12,4
15,4
18,2
20,9
25,6

6,4
7,3
14,6
17,8
20,6
23,5
28,2

2x0,5
2x2x0,5 Q
5x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
30x2x0,5

0,9
0,9
0,9
0,9
0,9
0,9
0,9

39,0
39,0
39,0
39,0
39,0
39,0
39,0

2,6
2,6
2,6
2,6
2,6
2,6
2,6

5,2
6,2
13,6
17,0
20,1
23,0
28,1

2x0,75
2x2x0,75 Q
5x2x0,75
10x2x0,75
15x2x0,75
20x2x0,75
30x2x0,75

1,1
1,1
1,1
1,1
1,1
1,1
1,1

26,0
26,0
26,0
26,0
26,0
26,0
26,0

3,3
3,3
3,3
3,3
3,3
3,3
3,3

2x1
2x2x1 Q
5x2x1
10x2x1
15x2x1
20x2x1
30x2x1

1,1
1,1
1,1
1,1
1,1
1,1
1,1

18,4
18,4
18,4
18,4
18,4
18,4
18,4

2x1,5
2x2x1,5 Q
5x2x1,5
10x2x1,5
15x2x1,5
20x2x1,5
30x2x1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1
12,1

Diameter
Capacitance
Outer Weight of
Min
over
cable
diameter
bending
approx
armour
approx
radius

L/R

(mm)

(mm)

(kg/km)

(mm)

(pF/m)

(H/)

0,9
0,9
0,9
1,3
1,3
1,6
1,6

8,2
9,1
16,4
20,3
23,1
26,7
31,4

10,8
11,7
19,4
23,5
26,3
30,1
35,0

215
270
670
960
1240
1490
1860

89
102
204
249
288
329
394

115
115
75
75
75
75
75

25
25
25
25
25
25
25

6,8
7,8
15,8
19,4
22,7
25,6
31,1

0,9
0,9
1,3
1,3
1,6
1,6
1,6

8,6
9,6
18,3
21,9
25,9
28,8
34,3

11,2
12,2
21,3
25,1
29,3
32,4
38,1

240
290
620
1100
1380
1620
2025

95
110
221
271
317
359
435

115
115
75
75
75
75
75

25
25
25
25
25
25
25

6,6
8,0
17,5
21,7
25,7
29,5
35,9

8,2
9,6
19,9
24,3
28,3
32,5
39,3

0,9
0,9
1,3
1,6
1,6
1,6
2,0

10,0
11,4
22,4
27,5
31,5
35,7
43,3

12,6
14,2
25,4
30,9
35,1
39,3
47,3

255
310
735
1200
1520
1935
2420

115
134
278
340
396
454
551

115
115
75
75
75
75
75

25
25
25
25
25
25
25

2,8
2,8
2,8
2,8
2,8
2,8
2,8

5,7
6,9
15,1
18,8
22,2
25,5
31,2

7,3
8,5
17,5
21,2
24,8
28,5
34,2

0,9
0,9
1,3
1,6
1,6
1,6
2,0

9,1
10,3
20,0
24,4
28,0
31,7
38,2

11,7
13,1
23,0
27,8
31,6
35,3
42,2

270
330
850
1300
1660
2250
2800

103
119
244
297
348
399
479

115
115
75
75
75
75
75

25
25
25
25
25
25
25

3,3
3,3
3,3
3,3
3,3
3,3
3,3

6,8
8,1
17,7
22,0
26,1
29,9
36,5

8,4
9,9
20,1
24,6
29,1
32,9
39,9

0,9
0,9
1,3
1,6
1,6
2,0
2,0

10,2
11,7
22,6
27,8
32,3
36,9
43,9

13,0
14,5
25,8
31,4
36,1
40,9
48,1

320
400
1175
1640
2360
2800
3500

117
138
282
345
407
460
559

115
115
85
85
85
85
85

40
40
40
40
40
40
40

37

TEPLA
Plant & Petrochem Cables

38

technergy

TM

INTEGRATED CABLING SOLUTIONS

Instrumentation cables according to EN 50288

39

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - O
(PE/PVC or
XLPE/PVC or
XLPE/LS0H)
300 or 500 V

Construction

>
>
>
>
>
>

>
>

Applicable
standards

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3A

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 2
Insulation
polyethylene or XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3A

40

GOOD

GOOD

LS0H

-5 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A

TEPLA I - O 300 V (PE/PVC or XLPE/PVC or XLPE/LS0H)

Cross
section

Diameter
of
conductor

(mm2)

(mm)

RE4OHR
RE4XOHR

1x2x0,5
2x2x0,5
4x2x0,5
5x2x0,5
6x2x0,5
10x2x0,5
12x2x0,5
15x2x0,5
20x2x0,5
24x2x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

RE4OHR
RE4XOHR

1x2x0,75
2x2x0,75
4x2x0,75
5x2x0,75
6x2x0,75
10x2x0,75
12x2x0,75
15x2x0,75
20x2x0,75
24x2x0,75

RE4OHR
RE4XOHR

RE4OHR
RE4XOHR

Type*

Min
bending
radius

Capacitance

L/R

(mm)

(pF/m)

(H/)

44
81
121
152
168
254
290
349
454
530

74
120
140
164
166
201
209
232
264
286

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

6,4
10,4
12,2
14,3
14,5
17,5
18,2
20,4
23,1
25,2

48
89
136
171
191
291
338
412
525
626

77
125
146
172
174
210
219
245
277
302

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49

6,9
11,2
13,3
15,5
15,6
18,9
19,9
22,1
25,2
27,3

57
105
171
208
234
361
425
516
672
789

83
134
160
185
187
227
239
265
302
327

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79

7,7
12,5
14,8
17,2
17,4
21,3
22,2
24,8
28,3
30,6

74
138
229
280
317
502
581
718
937
1102

92
150
178
207
209
255
266
298
339
367

150
150
150
150
150
150
150
150
150
150

40
40
40
40
40
40
40
40
40
40

8,4
14,1
16,8
19,5
19,9
24,2
25,3
28,3
32,2
35,2

95
186
315
386
449
712
827
1022
1334
1604

101
169
201
234
239
291
303
339
386
423

150
150
150
150
150
150
150
150
150
150

60
60
60
60
60
60
60
60
60
60

Diameter
over
insulation

Outer
diameter
approx

(mm)

(mm)

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16

6,2
10,0
11,7
13,7
13,8
16,7
17,4
19,3
22,0
23,8

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28

1x2x1
2x2x1
4x2x1
5x2x1
6x2x1
10x2x1
12x2x1
15x2x1
20x2x1
24x2x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

1x2x1,5
2x2x1,5
4x2x1,5
5x2x1,5
6x2x1,5
10x2x1,5
12x2x1,5
15x2x1,5
20x2x1,5
24x2x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

Maximum DC
resistance
at 20 C
(/km)

Weight
of cable approx
(kg/km)

TEPLA I - O 500 V (PE/PVC or XLPE/PVC or XLPE/LS0H)


RE4OHR
RE4XOHR

1x2x2,5
2x2x2,5
4x2x2,5
5x2x2,5
6x2x2,5
10x2x2,5
12x2x2,5
15x2x2,5
20x2x2,5
24x2x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18

* Refers only to XLPE/PVC construction

41

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - IO
(PE/PVC or
XLPE/PVC or
XLPE/LS0H)
300 or 500 V

Construction

>
>
>
>
>

>
>

>
>

Applicable
standards

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3A

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 2
Insulation
polyethylene or XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Individual screen
aluminium/polyester tape 0.024 mm in electrical contact with tinned
annealed copper wires of a total section of 0.5 mm2 polyester tape 0.023 mm
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3A

42

GOOD

GOOD

LS0H

-5 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A

TEPLA I - IO 300 V (PE/PVC or XLPE/PVC or XLPE/LS0H)

Type*

Cross
section

Diameter
of
conductor

(mm2)

(mm)

RE4OHR
RE4XHOHR

1x2x0,5
2x2x0,5
4x2x0,5
5x2x0,5
6x2x0,5
12x2x0,5
10x2x0,5
15x2x0,5
20x2x0,5
24x2x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

RE4OHR
RE4XHOHR

1x2x0,75
2x2x0,75
4x2x0,75
5x2x0,75
6x2x0,75
10x2x0,75
12x2x0,75
15x2x0,75
20x2x0,75
24x2x0,75

RE4OHR
RE4XHOHR

RE4OHR
RE4XHOHR

Min
bending
radius

Mutual
capacitance
maximum

L/R
maximum

(mm)

(pF/m)

(H/)

44
98
159
193
217
394
334
477
622
741

74
125
149
173
174
222
211
246
280
306

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

6,4
10,9
13,0
15,0
15,4
18,6
19,3
21,6
24,4
26,7

48,1
106
174
212
246
379
437
541
693
826

77
131
155
180
184
223
232
260
293
320

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49

6,9
11,9
13,9
16,3
16,5
19,9
21,0
23,3
26,5
28,9

57
131
209
262
297
461
544
661
864
1030

83
142
167
196
198
239
252
279
318
347

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79

7,7
12,9
15,4
18,1
18,3
22,3
23,3
26,0
29,6
32,3

74
158
267
335
381
604
700
866
1130
1346

92
155
185
217
220
268
279
312
355
387

150
150
150
150
150
150
150
150
150
150

40
40
40
40
40
40
40
40
40
40

8,4
14,8
17,5
20,4
20,8
25,3
26,4
29,7
33,7
36,7

95
213
363
445
518
821
955
1193
1556
1852

101
177
210
245
249
303
316
356
404
440

150
150
150
150
150
150
150
150
150
150

60
60
60
60
60
60
60
60
60
60

Diameter
over
insulation

Outer
diameter
approx

(mm)

(mm)

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16

6,2
10,5
12,4
14,4
14,5
18,5
17,6
20,5
23,4
25,5

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28

1x2x1
2x2x1
4x2x1
5x2x1
6x2x1
10x2x1
12x2x1
15x2x1
20x2x1
24x2x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

1x2x1,5
2x2x1,5
4x2x1,5
5x2x1,5
6x2x1,5
10x2x1,5
12x2x1,5
15x2x1,5
20x2x1,5
24x2x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

Maximum DC
resistance
at 20 C
(/km)

Weight
of cable approx
(kg/km)

TEPLA I - IO 500 V (PE/PVC or XLPE/PVC or XLPE/LS0H)


RE4OHR
RE4XHOHR

1x2x2,5
2x2x2,5
4x2x2,5
5x2x2,5
6x2x2,5
10x2x2,5
12x2x2,5
15x2x2,5
20x2x2,5
24x2x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18

* Refers only to XLPE/PVC construction

43

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - OA
(PE/SWA/PVC or
XLPE/SWA/LS0H or
XLPE/SWA/PVC)
300 or 500 V

Construction

>
>
>
>
>
>

>
>
>
>

Applicable
standards

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3A

STANDARD

EXCELLENT

0 C

Conductor
annealed copper wires according to class 2
Insulation
polyethylene or XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Inner sheath
PVC or LS0H
Armour
galvanized steel wire
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3A

44

GOOD

EXCELLENT

LS0H

-5 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A

TEPLA I - OA 300 V (PE/SWA/PVC or XLPE/SWA/LS0H or XLPE/SWA/PVC)

Diameter
over
insulation

(mm)

Maximum
DC
resistance
at 20 C
(/km)

1x2x0,5
2x2x0,5
4x2x0,5
5x2x0,5
6x2x0,5
10x2x0,5
12x2x0,5
15x2x0,5
20x2x0,5
24x2x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

RE4OHRFR
RE4XOHRFR

1x2x0,75
2x2x0,75
4x2x0,75
5x2x0,75
6x2x0,75
10x2x0,75
12x2x0,75
15x2x0,75
20x2x0,75
24x2x0,75

RE4OHRFR
RE4XOHRFR

RE4OHRFR
RE4XOHRFR

Type*

Diameter of
armour
wires

Diameter
over
armour

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

Capacitance

L/R

(mm)

Diameter
over
inner
sheath
(mm)

(mm)

(mm)

(mm)

(kg/km)

(mm)

(pF/m)

(H/)

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16

6,2
10,0
11,7
13,7
13,8
16,7
17,4
19,3
22,0
23,8

0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25

8,0
11,8
13,5
15,5
15,6
18,5
19,2
21,1
23,8
26,3

10,7
14,5
16,3
18,4
18,5
21,6
22,3
24,2
27,1
29,5

229
374
458
534
553
728
781
893
1082
1380

149
202
229
258
259
303
312
339
380
413

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28

6,4
10,4
12,2
14,3
14,5
17,5
18,2
20,4
23,1
25,2

0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25

8,2
12,2
14,0
16,1
16,3
19,3
20,0
22,2
25,6
27,7

10,9
14,9
16,9
19,0
19,2
22,4
23,1
25,3
28,8
30,9

241
399
483
571
594
785
845
986
1347
1524

153
209
236
267
268
314
324
355
403
433

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

1x2x1
2x2x1
4x2x1
5x2x1
6x2x1
10x2x1
12x2x1
15x2x1
20x2x1
24x2x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49

6,9
11,2
13,3
15,5
15,6
18,9
19,9
22,1
25,2
27,3

0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25

8,7
13,0
15,1
17,3
17,4
20,7
21,7
24,6
27,7
29,8

11,3
15,9
18,0
20,2
20,3
23,8
24,8
27,8
30,9
33,2

260
443
552
641
670
897
988
1308
1572
1780

159
222
252
282
284
333
347
389
432
464

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

1x2x1,5
2x2x1,5
4x2x1,5
5x2x1,5
6x2x1,5
10x2x1,5
12x2x1,5
15x2x1,5
20x2x1,5
24x2x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79

7,7
12,5
14,8
17,2
17,4
21,3
22,2
24,8
28,3
30,6

0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,25

9,5
14,3
16,6
19,0
19,2
23,8
24,7
27,3
30,8
33,1

12,1
17,2
19,7
22,1
22,3
27,0
28,1
30,7
34,4
36,7

299
516
664
769
816
1268
1389
1621
1980
2239

170
240
276
310
312
378
393
430
481
514

150
150
150
150
150
150
150
150
150
150

40
40
40
40
40
40
40
40
40
40

13,1
19,0
21,9
25,2
25,8
30,3
31,4
35,3
39,4
42,6

345
624
817
1094
1186
1615
1762
2296
2798
3221

184
266
306
353
361
425
439
494
551
597

150
150
150
150
150
150
150
150
150
150

60
60
60
60
60
60
60
60
60
60

Cross
section

Diameter
of
conductor

(mm2)
RE4OHRFR
RE4XOHRFR

TEPLA I - OA 500 V (PE/SWA/PVC or XLPE/SWA/LS0H or XLPE/SWA/PVC)


RE4OHRFR
RE4XOHRFR

1x2x2,5
2x2x2,5
4x2x2,5
5x2x2,5
6x2x2,5
10x2x2,5
12x2x2,5
15x2x2,5
20x2x2,5
24x2x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18

8,5
14,1
16,8
19,5
19,9
24,2
25,3
28,3
32,2
35,2

0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,6
1,6
1,6

10,3
15,9
18,6
22,0
22,4
26,7
27,8
31,5
35,4
38,4

* Refers only to XLPE/PVC/SWA/PVC construction

45

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - IOA
(PE/SWA/PVC or
XLPE/SWA/LS0H or
XLPE/SWA/PVC)
300 or 500 V

Construction

>
>
>
>
>

>
>

>
>
>
>

Applicable
standards

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3A

STANDARD

EXCELLENT

0 C

Conductor
annealed copper wires according to class 2
Insulation
polyethylene or XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Individual screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Inner sheath
PVC or LS0H
Armour
galvanized steel wire
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3A

46

GOOD

EXCELLENT

LS0H

-5 C

14 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A

TEPLA I - IOA 300 V (PE/SWA/PVC or XLPE/SWA/LS0H or XLPE/SWA/PVC)

Diameter
over
insulation

(mm)

Maximum
DC
resistance
at 20 C
(/km)

1x2x0,5
2x2x0,5
4x2x0,5
5x2x0,5
6x2x0,5
10x2x0,5
12x2x0,5
15x2x0,5
20x2x0,5
24x2x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

RE4OHRFR
RE4XHOHRFR

1x2x0,75
2x2x0,75
4x2x0,75
5x2x0,75
6x2x0,75
10x2x0,75
12x2x0,75
15x2x0,75
20x2x0,75
24x2x0,75

RE4OHRFR
RE4XHOHRFR

RE4OHRFR
RE4XHOHRFR

Type*

Diameter of
armour
wires

Diameter
over
armour

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

Capacitance

L/R

(mm)

Diameter
over
inner
sheath
(mm)

(mm)

(mm)

(mm)

(kg/km)

(mm)

(pF/m)

(H/)

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16

6,2
10,5
12,5
14,4
14,6
17,6
18,6
20,6
23,4
25,6

0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25

8,0
12,3
14,3
16,2
16,4
19,4
20,4
23,1
25,9
28,1

10,7
15,1
17,1
19,1
19,2
22,5
23,4
26,2
29,3
31,4

229
416
514
594
626
835
914
1220
1472
1668

149
212
240
267
269
314
327
367
410
439

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28

6,4
10,9
13,0
15,0
15,4
18,6
19,3
21,7
24,5
26,7

0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25

8,2
12,7
14,8
16,8
17,2
20,4
21,1
24,2
27,0
29,2

10,9
15,6
17,6
19,7
20,3
23,7
24,4
27,3
30,3
32,6

241
435
546
630
684
917
994
1318
1577
1799

153
218
247
276
284
331
342
383
425
456

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

1x2x1
2x2x1
4x2x1
5x2x1
6x2x1
10x2x1
12x2x1
15x2x1
20x2x1
24x2x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49

6,9
12,0
14,0
16,5
16,6
20,1
21,2
23,5
26,8
29,2

0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,25

8,7
13,8
15,8
18,3
18,4
22,6
23,7
26,0
29,3
31,7

11,3
16,5
18,6
21,2
21,4
25,6
26,7
29,2
32,4
35,0

260
496
609
732
771
1192
1306
1516
1840
2106

159
231
260
297
299
359
373
409
454
490

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

1x2x1,5
2x2x1,5
4x2x1,5
5x2x1,5
6x2x1,5
10x2x1,5
12x2x1,5
15x2x1,5
20x2x1,5
24x2x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79

7,7
13,0
15,5
18,2
18,4
22,4
23,3
26,1
29,7
32,4

0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,6
1,6

9,5
14,8
17,3
20,0
20,9
24,9
25,8
28,6
32,9
35,6

12,1
17,8
20,3
23,0
24,0
28,2
29,2
32,1
36,6
39,5

299
562
721
852
1056
1427
1554
1832
2472
2812

170
250
284
322
336
395
408
450
512
552

150
150
150
150
150
150
150
150
150
150

40
40
40
40
40
40
40
40
40
40

13,1
19,7
23,2
26,3
26,7
32,3
33,4
36,9
41,1
45,3

345
679
1021
1198
1289
1974
2154
2558
3118
3896

184
275
325
368
374
452
467
516
575
634

150
150
150
150
150
150
150
150
150
150

60
60
60
60
60
60
60
60
60
60

Cross
section

Diameter
of
conductor

(mm2)
RE4OHRFR
RE4XHOHRFR

TEPLA I - IOA 500 V (PE/SWA/PVC or XLPE/SWA/LS0H or XLPE/SWA/PVC)


RE4OHRFR
RE4XHOHRFR

1x2x2,5
2x2x2,5
4x2x2,5
5x2x2,5
6x2x2,5
10x2x2,5
12x2x2,5
15x2x2,5
20x2x2,5
24x2x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18

8,4
14,8
17,6
20,5
20,9
25,4
26,5
29,9
33,8
36,8

0,9
0,9
1,25
1,25
1,25
1,6
1,6
1,6
1,6
2

10,2
16,6
20,1
23,0
23,4
28,6
29,7
33,0
37,0
40,8

* Refers only to XLPE/PVC/SWA/PVC construction

47

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - OLA
(PE/Pb/SWA/PVC or
XLPE/Pb/SWA/PVC or
XLPE/Pb/SWA/LS0H)
300 or 500 V

Construction

>
>
>
>
>
>

>
>
>
>
>
>

Applicable
standards

Conductor
annealed copper wires according to class 2
Insulation
polyethylene or XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Bedding
PVC or LS0H
Lead sheath
Inner sheath
PVC or LS0H
Armour
galvanized steel wire
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60754
IEC 61034

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

IEC 60332-1
IEC 60332-3A

EXELLENT

EXCELLENT

0 C

16 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3A

48

EXELLENT

EXCELLENT

LS0H

-5 C

16 D

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A

TEPLA I - OLA 300 V (PE/Pb/SWA/PVC or XLPE/Pb/SWA/PVC or XLPE/Pb/SWA/LS0H)

Diameter
over
insulation

(mm)

Maximum
DC
resistance
at 20 C
(/km)

1x2x0,5
2x2x0,5
4x2x0,5
5x2x0,5
6x2x0,5
10x2x0,5
12x2x0,5
15x2x0,5
20x2x0,5
24x2x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

RE4OHRLRFR
RE4XOHRLRFR

1x2x0,75
2x2x0,75
4x2x0,75
5x2x0,75
6x2x0,75
10x2x0,75
12x2x0,75
15x2x0,75
20x2x0,75
24x2x0,75

RE4OHRLRFR
RE4XOHRLRFR

RE4OHRLRFR
RE4XOHRLRFR

Type*

Diameter of
armour
wires

Diameter
over
armour

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

Capacitance

L/R

(mm)

Diameter
over
inner
sheath
(mm)

(mm)

(mm)

(mm)

(kg/km)

(mm)

(pF/m)

(H/)

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16

9,9
13,8
15,5
17,6
17,9
20,8
21,5
23,6
26,3
28,3

0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,25

11,7
15,6
17,3
19,4
19,7
23,3
24
26,1
28,8
30,8

14,6
18,6
20,4
22,5
22,8
26,5
27,2
29,3
32,2
34,2

566
889
1033
1186
1274
1716
1807
2094
2424
2739

233
297
327
360
365
424
435
469
515
548

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28

10,1
14,3
16,0
18,4
18,5
21,8
22,5
24,7
27,5
29,7

0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,25

11,9
16,1
17,8
20,2
20,3
24,3
25,0
27,2
30,0
32,2

14,8
19,2
21,0
23,3
23,5
27,5
28,2
30,6
33,5
35,8

585
934
1083
1312
1346
1887
1989
2255
2680
2966

237
307
336
373
376
440
452
490
536
573

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

1x2x1
2x2x1
4x2x1
5x2x1
6x2x1
10x2x1
12x2x1
15x2x1
20x2x1
24x2x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49

10,8
15,0
17,4
19,5
19,7
23,1
24,1
26,5
29,6
31,9

0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,25

12,6
16,8
19,2
21,3
21,5
25,6
26,6
29,0
32,1
34,4

15,4
20,0
22,3
24,5
24,8
29,1
30,1
32,5
35,8
38,1

659
1000
1252
1429
1475
2088
2228
2583
3012
3426

247
320
357
391
397
465
481
520
572
609

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

1x2x1,5
2x2x1,5
4x2x1,5
5x2x1,5
6x2x1,5
10x2x1,5
12x2x1,5
15x2x1,5
20x2x1,5
24x2x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79

11,5
16,5
18,9
21,5
21,7
25,7
26,6
29,5
33,1
35,9

0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,25
1,6
1,6

13,3
18,3
20,7
24,0
24,2
28,2
29,1
32,0
36,3
39,1

16,2
21,5
24,0
27,2
27,6
31,9
32,8
35,6
40,2
43,1

722
1182
1428
1865
1926
2518
2679
3141
4041
4510

260
343
385
436
442
510
524
570
642
690

150
150
150
150
150
150
150
150
150
150

40
40
40
40
40
40
40
40
40
40

804
1561
1889
2244
2358
3477
3695
4335
5204
6386

275
385
432
479
488
588
604
659
727
802

150
150
150
150
150
150
150
150
150
150

60
60
60
60
60
60
60
60
60
60

Cross
section

Diameter
of
conductor

(mm2)
RE4OHRLRFR
RE4XOHRLRFR

TEPLA I - OLA 500 V (PE/Pb/SWA/PVC or XLPE/Pb/SWA/PVC or XLPE/Pb/SWA/LS0H)


RE4OHRLRFR
RE4XOHRLRFR

1x2x2,5
2x2x2,5
4x2x2,5
5x2x2,5
6x2x2,5
10x2x2,5
12x2x2,5
15x2x2,5
20x2x2,5
24x2x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18

12,3
18,4
21,0
24,0
24,4
29,5
30,5
33,7
37,8
41,5

0,9
1,25
1,25
1,25
1,25
1,6
1,6
1,6
1,6
2

14,1
20,9
23,5
26,5
26,
32,7
33,7
36,9
41,0
45,5

17,2
24,1
27,0
29,9
30,5
36,7
37,8
41,2
45,5
50,1

* Refers only to XLPE/LS/SWA/PVC construction

49

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - ODA
(PE/DRYLAM/SWA/PVC or
XLPE/DRYLAM/SWA/PVC or
XLPE/DRYLAM/SWA/LS0H)
300 or 500 V

Construction

>
>
>
>
>
>

>

>
>
>

Applicable
standards

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3A

EXELLENT

EXCELLENT

0 C

Conductor
annealed copper wires according to class 2
Insulation
polyethylene or XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Chemical moisture barrier
longitudinally applied AI tape bonded with extruded chemical resistant
polymeric layer
Armour
galvanized steel wire
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3A

50

EXELLENT

EXCELLENT

LS0H

-5 C

14 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A

TEPLA I - ODA 300 V (PE/DRYLAM/SWA/PVC or XLPE/DRYLAM/SWA/PVC or XLPE/DRYLAM/SWA/LS0H)

Type*

Cross
section

(mm2)

Diameter Maximum
DC
of
conductor resistance
at 20 C
(/km)
(mm)

Diameter
over
insulation
(mm)

Diameter Diameter of Diameter


over
armour
over
inner
wires
armour
sheath
(mm)
(mm)
(mm)

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

Capacitance

L/R

(mm)

(kg/km)

(mm)

(pF/m)

(H/)

RE4OHRH5R4FR
RE4XOHRH5R4FR

1x2x0,5
2x2x0,5
4x2x0,5
5x2x0,5
6x2x0,5
10x2x0,5
12x2x0,5
15x2x0,5
20x2x0,5
24x2x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16

8,7
12,4
14,1
15,9
16,2
18,9
19,8
21,7
24,4
26,2

0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25

10,5
14,2
15,9
17,7
18,0
20,7
21,6
23,5
26,9
28,7

13,3
17,1
18,8
20,6
21,0
23,8
24,7
26,8
30,1
32,2

324
491
569
646
679
853
926
1057
1413
1585

186
240
263
289
293
334
346
376
422
450

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

RE4OHRH5R4FR
RE4XOHRH5R4FR

1x2x0,75
2x2x0,75
4x2x0,75
5x2x0,75
6x2x0,75
10x2x0,75
12x2x0,75
15x2x0,75
20x2x0,75
24x2x0,75

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28

8,9
12,8
14,6
16,6
16,9
19,9
20,6
22,6
25,4
27,6

0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25

10,7
14,6
16,4
18,4
18,7
21,7
22,4
25,1
27,9
30,1

13,5
17,6
19,3
21,3
21,8
24,8
25,6
28,4
31,2
33,5

337
512
602
687
734
929
991
1295
1533
1736

189
246
270
298
306
348
358
397
437
469

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

RE4OHRH5R4FR
RE4XOHRH5R4FR

1x2x1
2x2x1
4x2x1
5x2x1
6x2x1
10x2x1
12x2x1
15x2x1
20x2x1
24x2x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49

9,3
13,6
15,7
17,8
18,0
21,3
22,1
24,5
27,5
29,6

0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25

11,1
15,4
17,5
19,6
19,8
23,1
24,6
27,0
30,0
32,1

13,9
18,4
20,5
22,8
22,9
26,4
27,8
30,2
33,5
35,6

355
559
677
779
814
1055
1291
1492
1781
1976

194
257
286
319
321
370
389
423
468
498

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

RE4OHRH5R4FR
RE4XOHRH5R4FR

1x2x1,5
2x2x1,5
4x2x1,5
5x2x1,5
6x2x1,5
10x2x1,5
12x2x1,5
15x2x1,5
20x2x1,5
24x2x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79

10,1
14,9
17,0
19,6
19,8
23,6
24,5
27,0
30,4
33,2

0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,6

11,9
16,7
18,8
21,4
21,6
26,1
27,0
29,5
32,9
36,4

14,8
19,9
22,0
24,6
25,0
29,6
30,5
33,1
36,6
40,2

404
647
782
913
971
1460
1573
1806
2164
2727

207
278
308
344
349
414
427
464
512
563

150
150
150
150
150
150
150
150
150
150

40
40
40
40
40
40
40
40
40
40

150
150
150
150
150
150
150
150
150
150

60
60
60
60
60
60
60
60
60
60

TEPLA I - ODA 500 V (PE/DRYLAM/SWA/PVC or XLPE/DRYLAM/SWA/PVC or XLPE/DRYLAM/SWA/LS0H)


RE4OHRH5R4FR
RE4XOHRH5R4FR

1x2x2,5
2x2x2,5
4x2x2,5
5x2x2,5
6x2x2,5
10x2x2,5
12x2x2,5
15x2x2,5
20x2x2,5
24x2x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18

10,9
16,5
19,2
21,9
22,3
26,6
27,6
30,6
34,7
37,6

0,9
0,9
1,25
1,25
1,25
1,25
1,25
1,6
1,6
1,6

12,7
18,3
21,7
24,4
24,8
29,1
30,1
33,8
37,9
40,8

15,6
21,5
25,0
27,9
28,3
32,9
34,1
38,0
42,3
45,3

448
754
1095
1284
1366
1816
1983
2537
3090
3510

219
300
350
391
396
460
477
531
592
634

* Refers only to XLPE/PVC/DRYLAM/SWA/PVC construction

51

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - FR - O
(XLPE/LS0H)
300 or 500 V

Construction

>
>
>
>
>
>
>

>
>

Applicable
standards

Conductor
annealed copper wires according to class 2
Fire barrier
mica/glass tape
Insulation
XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60331
IEC 60754
IEC 61034

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Fire resistant
Halogen free properties
Low smoke emission

low
r

52

IEC 60332-1
IEC 60332-3A
IEC 60331

GOOD

GOOD

LS0H

0 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A
> Fire resistant cables according to IEC 60331-23
TEPLA I - FR - O 300 V (XLPE/LS0H)

Cross
section

Diameter
of
conductor

(mm2)

(mm)

RTE4OHM1
RTE4XOHM1

1x2x0,5
2x2x0,5
4x2x0,5
5x2x0,5
6x2x0,5
10x2x0,5
12x2x0,5
15x2x0,5
20x2x0,5
24x2x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

RTE4OHM1
RTE4XOHM1

1x2x0,75
2x2x0,75
4x2x0,75
5x2x0,75
6x2x0,75
10x2x0,75
12x2x0,75
15x2x0,75
20x2x0,75
24x2x0,75

RTE4OHM1
RTE4XOHM1

RTE4OHM1
RTE4XOHM1

Type

Min
bending
radius

Capacitance

L/R

(mm)

(pF/m)

(H/)

57
105
165
200
230
346
394
473
614
730

90
148
176
205
210
254
265
294
336
366

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

7,8
12,8
15,1
17,5
17,9
21,7
22,6
25,3
28,7
31,3

64
118
179
218
251
380
434
535
680
809

94
154
181
210
215
260
271
304
344
376

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

3,10
3,10
3,10
3,10
3,10
3,10
3,10
3,10
3,10
3,10

8,3
13,6
16,0
18,9
19,0
23,1
24,3
27,0
30,8
33,6

73
136
211
266
297
455
534
646
839
999

99
163
192
226
228
277
291
324
369
403

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

3,40
3,40
3,40
3,40
3,40
3,40
3,40
3,40
3,40
3,40

8,9
14,7
17,5
20,6
20,8
25,4
26,5
33,8
29,7
36,9

87
165
272
342
386
606
699
1121
862
1333

106
176
210
248
250
305
318
406
356
443

150
150
150
150
150
150
150
150
150
150

40
40
40
40
40
40
40
40
40
40

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,80
3,80
3,80
3,80
3,80
3,80
3,80
3,80
3,80
3,80

9,9
16,5
19,5
22,9
23,3
28,4
29,7
33,2
38,0
41,4

114
224
363
455
527
829
959
1183
1558
1850

118
198
234
275
280
341
356
398
456
496

150
150
150
150
150
150
150
150
150
150

60
60
60
60
60
60
60
60
60
60

Diameter
over
insulation

Outer
diameter
approx

(mm)

(mm)

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,80
2,80
2,80
2,80
2,80
2,80
2,80
2,80
2,80
2,80

7,5
12,3
14,7
17,1
17,5
21,2
22,1
24,5
28,0
30,5

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,90
2,90
2,90
2,90
2,90
2,90
2,90
2,90
2,90
2,90

1x2x1
2x2x1
4x2x1
5x2x1
6x2x1
10x2x1
12x2x1
15x2x1
20x2x1
24x2x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

1x2x1,5
2x2x1,5
4x2x1,5
5x2x1,5
6x2x1,5
10x2x1,5
12x2x1,5
20x2x1,5
15x2x1,5
24x2x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

Maximum DC
resistance
at 20 C
(/km)

Weight
of cable approx
(kg/km)

TEPLA I - FR - O 500 V (XLPE/LS0H)


RTE4OHM1
RTE4XOHM1

1x2x2,5
2x2x2,5
4x2x2,5
5x2x2,5
6x2x2,5
10x2x2,5
12x2x2,5
15x2x2,5
20x2x2,5
24x2x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

53

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - FR - O
(G4/PVC or
G4/LS0H)
300 or 500 V

Construction

>
>
>
>
>
>

>
>

Applicable
standards

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60331
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3A
IEC 60331

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 2
Insulation
silicon
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Fire resistant
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

PVC
LS0H

low
r

54

IEC 60332-1
IEC 60332-3A
IEC 60331

GOOD

GOOD

LS0H

-5 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A
> Fire resistant cables according to IEC 60331
TEPLA I - FR - O 300 V (G4/PVC or G4/LS0H)

Type*

Cross
section

Diameter
of
conductor

(mm2)

(mm)

RG4OHM1-FR
RG4XOHM1-FR

1x2x0,5
2x2x0,5
4x2x0,5
5x2x0,5
6x2x0,5
10x2x0,5
12x2x0,5
15x2x0,5
20x2x0,5
24x2x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

RG4OHM1-FR
RG4XOHM1-FR

1x2x0,75
2x2x0,75
4x2x0,75
5x2x0,75
6x2x0,75
10x2x0,75
12x2x0,75
15x2x0,75
20x2x0,75
24x2x0,75

RG4OHM1-FR
RG4XOHM1-FR

RG4OHM1-FR
RG4XOHM1-FR

Min
bending
radius

Capacitance

L/R

(mm)

(pF/m)

(H/)

55
116
157
192
213
319
363
439
569
666

74
120
140
164
166
201
209
232
264
286

250
250
250
250
250
250
250
250
250
250

25
25
25
25
25
25
25
25
25
25

6,4
10,4
12,2
14,3
14,5
17,5
18,2
20,4
23,1
25,2

60
128
175
215
240
362
413
511
651
775

77
125
146
172
174
210
219
245
277
302

250
250
250
250
250
250
250
250
250
250

25
25
25
25
25
25
25
25
25
25

2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49

6,9
11,2
13,3
15,5
15,6
18,9
19,9
22,1
25,2
27,3

71
151
217
259
291
443
518
630
819
961

83
134
160
185
187
227
239
265
302
327

250
250
250
250
250
250
250
250
250
250

25
25
25
25
25
25
25
25
25
25

2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79

7,7
12,5
14,8
17,2
17,4
21,3
22,2
24,8
28,3
30,6

91
195
286
345
387
603
694
858
1116
1312

92
150
178
207
209
255
266
298
339
367

250
250
250
250
250
250
250
250
250
250

40
40
40
40
40
40
40
40
40
40

3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18

8,4
14,1
16,8
19,5
19,9
24,2
25,3
28,3
32,2
35,2

116
259
387
465
538
839
968
1197
1558
1870

101
169
201
234
239
291
303
339
386
423

250
250
250
250
250
250
250
250
250
250

60
60
60
60
60
60
60
60
60
60

Diameter
over
insulation

Outer
diameter
approx

(mm)

(mm)

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16

6,2
10,0
11,7
13,7
13,8
16,7
17,4
19,3
22,0
23,8

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28

1x2x1
2x2x1
4x2x1
5x2x1
6x2x1
10x2x1
12x2x1
15x2x1
20x2x1
24x2x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

1x2x1,5
2x2x1,5
4x2x1,5
5x2x1,5
6x2x1,5
10x2x1,5
12x2x1,5
15x2x1,5
20x2x1,5
24x2x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

Maximum DC
resistance
at 20 C
(/km)

Weight
of cable approx
(kg/km)

TEPLA I - FR - O 500 V (G4/PVC or G4/LS0H)


RG4OHM1-FR
RG4XOHM1-FR

1x2x2,5
2x2x2,5
4x2x2,5
5x2x2,5
6x2x2,5
10x2x2,5
12x2x2,5
15x2x2,5
20x2x2,5
24x2x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

* Refers only to G4/LS0H construction

55

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - FR - OA
(XLPE/SWA/LS0H)
300 or 500 V

Construction

>
>
>
>
>
>
>

>
>
>

Applicable
standards

Conductor
annealed copper wires according to class 2
Fire barrier
mica/glass tape
Insulation
XLPE
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Armour
galvanized steel wire
Outer sheath
LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60331
IEC 60754
IEC 61034

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Fire resistant
Halogen free properties
Low smoke emission

low
r

56

EC 60332-1
IEC 60332-3A
IEC 60331

GOOD

EXCELLENT

LS0H

-5 C

14 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A
> Fire resistant cables according to IEC 60331-23
TEPLA I - FR - OA 300 V (XLPE/SWA/LS0H)

Type

Cross
section

(mm2)

Diameter Maximum
DC
of
conductor resistance
at 20 C
(/km)
(mm)

Diameter
over
insulation
(mm)

Diameter Diameter of Diameter


over
armour
over
inner
wires
armour
sheath
(mm)
(mm)
(mm)

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

Capacitance

L/R

(mm)

(kg/km)

(mm)

(pF/m)

(H/)

RTE4OHM1FM1
RTE4XOHM1FM1

1x2x0,5
2x2x0,5
4x2x0,5
5x2x0,5
6x2x0,5
10x2x0,5
12x2x0,5
15x2x0,5
20x2x0,5
24x2x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,80
2,80
2,80
2,80
2,80
2,80
2,80
2,80
2,80
2,80

7,4
12,3
14,7
17,1
17,4
21,1
22,0
24,5
27,9
30,5

0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25

9,2
14,1
16,5
18,9
19,2
22,9
23,8
27,0
30,4
33,0

12,0
17,0
19,4
21,8
22,4
26,1
27,2
30,2
33,9
36,4

276
480
582
675
727
942
1027
1352
1629
1828

167
238
272
305
313
365
380
423
474
510

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

RTE4OHM1FM1
RTE4XOHM1FM1

1x2x0,75
2x2x0,75
4x2x0,75
5x2x0,75
6x2x0,75
10x2x0,75
12x2x0,75
15x2x0,75
20x2x0,75
24x2x0,75

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,90
2,90
2,90
2,90
2,90
2,90
2,90
2,90
2,90
2,90

7,84
12,8
15,0
17,5
17,9
21,6
22,6
25,3
28,6
31,3

0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25

9,6
14,6
16,8
19,3
19,7
23,4
25,1
27,8
31,1
33,8

12,3
17,5
19,8
22,2
22,8
26,8
28,3
31,0
34,6
37,4

292
504
606
703
758
1000
1240
1434
1715
1957

172
245
277
311
319
375
396
435
484
524

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

RTE4OHM1FM1
RTE4XOHM1FM1

1x2x1
2x2x1
4x2x1
5x2x1
6x2x1
10x2x1
12x2x1
15x2x1
20x2x1
24x2x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

3,10
3,10
3,10
3,10
3,10
3,10
3,10
3,10
3,10
3,10

8,28
13,5
15,9
18,8
19,0
23,0
24,2
26,9
30,7
33,5

0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,25

10,0
15,3
17,7
20,6
20,8
25,5
26,7
29,4
33,2
36,0

12,7
18,3
20,7
23,7
23,9
28,8
30,0
32,9
36,9
39,7

316
549
665
798
839
1279
1400
1622
1971
2230

178
256
290
332
335
403
419
460
516
555

150
150
150
150
150
150
150
150
150
150

25
25
25
25
25
25
25
25
25
25

RTE4OHM1FM1
RTE4XOHM1FM1

1x2x1,5
2x2x1,5
4x2x1,5
5x2x1,5
6x2x1,5
10x2x1,5
12x2x1,5
15x2x1,5
20x2x1,5
24x2x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

3,40
3,40
3,40
3,40
3,40
3,40
3,40
3,40
3,40
3,40

8,85
14,6
17,5
20,6
20,8
25,4
26,5
29,7
33,8
36,8

0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,6
1,6

10,6
16,4
19,3
22,4
23,3
27,9
29,0
32,2
37,0
40,0

13,3
19,6
22,4
25,5
26,5
31,3
32,4
35,8
40,8
44,1

346
622
782
927
1140
1535
1660
1954
2631
2999

187
274
314
357
371
439
454
501
572
617

150
150
150
150
150
150
150
150
150
150

40
40
40
40
40
40
40
40
40
40

9,8
16,5
19,4
22,9
23,3
28,4
29,6
33,1
37,9
41,3

0,9
0,9
1,25
1,25
1,25
1,6
1,6
1,6
1,6
2

11,6
18,3
21,9
25,4
25,8
31,6
32,8
36,3
41,1
45,3

14,5
21,4
25,3
28,8
29,2
35,4
36,7
40,4
45,4
49,8

406
741
1090
1297
1388
2103
2281
2691
3291
4118

203
300
354
403
409
496
513
565
635
697

150
150
150
150
150
150
150
150
150
150

60
60
60
60
60
60
60
60
60
60

TEPLA I - FR - OA 300 V (XLPE/SWA/LS0H)


RTE4OHM1FM1
RTE4XOHM1FM1

1x2x2,5
2x2x2,5
4x2x2,5
5x2x2,5
6x2x2,5
10x2x2,5
12x2x2,5
15x2x2,5
20x2x2,5
24x2x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,80
3,80
3,80
3,80
3,80
3,80
3,80
3,80
3,80
3,80

57

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - FR - OA
(G4/SWA/PVC or
G4/SWA/LS0H)
300 or 500 V

Construction

>
>
>
>
>
>

>
>
>
>

Applicable
standards

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60331
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3A
IEC 60331

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 2
Insulation
silicon
Pairs
twisted
Identification pairs
blue, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Inner sheath
PVC or LS0H
Armour
galvanized steel wire
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Fire resistant
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

PVC
LS0H

low
r

58

IEC 60332-1
IEC 60332-3A
IEC 60331

GOOD

EXCELLENT

LS0H

-5 C

14 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A
> Fire resistant cables according to IEC 60331
TEPLA I - FR - OA 300 V (G4/SWA/PVC or G4/SWA/LS0H)

Type*

Cross
section

(mm2)

Diameter Maximum Diameter


DC
of
over
conductor resistance insulation
at 20 C
(/km)
(mm)
(mm)

Diameter
over
inner
sheath
(mm)

Diameter
of armour
wires

Diameter
over
armour

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

Capacitance

L/R

(mm)

(mm)

(mm)

(kg/km)

(mm)

(pF/m)

(H/)

RG4OHM1FM1-FR
RG4XOHM1FM1-FR

1x2x0,5
2x2x0,5
4x2x0,5
5x2x0,5
6x2x0,5
10x2x0,5
12x2x0,5
15x2x0,5
20x2x0,5
24x2x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16

6,2
9,9
11,6
13,7
13,8
16,7
17,4
19,3
22,0
23,8

0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25

8
11,7
13,4
15,5
15,6
18,5
19,2
21,1
23,8
26,3

10,7
14,5
16,3
18,4
18,5
21,6
22,3
24,2
27,1
29,5

234
381
472
551
574
761
820
941
1146
1457

149
202
229
257
259
302
312
339
379
413

250
250
250
250
250
250
250
250
250
250

25
25
25
25
25
25
25
25
25
25

RG4OHM1FM1-FR
RG4XOHM1FM1-FR

1x2x0,75
2x2x0,75
4x2x0,75
5x2x0,75
6x2x0,75
10x2x0,75
12x2x0,75
15x2x0,75
20x2x0,75
24x2x0,75

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28

6,42
10,4
12,1
14,3
14,4
17,5
18,2
20,4
23,0
25,2

0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25

8,2
12,2
13,9
16,1
16,2
19,3
20,0
22,2
25,5
27,7

10,9
14,9
16,9
19,0
19,2
22,4
23,1
25,3
28,8
30,9

246
406
499
589
617
820
887
1037
1416
1606

153
208
236
266
268
313
324
354
403
433

250
250
250
250
250
250
250
250
250
250

25
25
25
25
25
25
25
25
25
25

RG4OHM1FM1-FR
RG4XOHM1FM1-FR

1x2x1
2x2x1
4x2x1
5x2x1
6x2x1
10x2x1
12x2x1
15x2x1
20x2x1
24x2x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49

6,9
11,1
13,3
15,4
15,6
18,8
19,8
22,0
25,1
27,2

0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25

8,7
12,9
15,1
17,2
17,4
20,6
21,6
24,5
27,6
29,7

11,3
15,9
18,0
20,1
20,3
23,8
24,8
27,8
30,9
33,2

265
452
569
662
695
937
1035
1368
1650
1879

158
222
252
282
284
333
347
389
432
464

250
250
250
250
250
250
250
250
250
250

25
25
25
25
25
25
25
25
25
25

RG4OHM1FM1-FR
RG4XOHM1FM1-FR

1x2x1,5
2x2x1,5
4x2x1,5
5x2x1,5
6x2x1,5
10x2x1,5
12x2x1,5
15x2x1,5
20x2x1,5
24x2x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79

7,67
12,4
14,8
17,2
17,4
21,2
22,1
24,8
28,2
30,6

0,9
0,9
0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,25

9,4
14,2
16,6
19,0
19,2
23,7
24,6
27,3
30,7
33,1

12,1
17,2
19,7
22,1
22,3
27,0
28,1
30,7
34,4
36,7

305
526
683
794
844
1315
1446
1691
2072
2349

170
240
276
310
312
378
393
430
481
514

250
250
250
250
250
250
250
250
250
250

40
40
40
40
40
40
40
40
40
40

0,9
0,9
0,9
1,25
1,25
1,25
1,25
1,6
1,6
1,6

10,2
15,9
18,5
22,0
22,4
26,7
27,7
31,4
35,3
38,4

13,1
19,0
21,9
25,2
25,8
30,3
31,4
35,3
39,4
42,6

352
635
840
1124
1222
1672
1830
2380
2909
3353

183
266
306
353
361
425
439
494
551
597

250
250
250
250
250
250
250
250
250
250

60
60
60
60
60
60
60
60
60
60

TEPLA I - FR - OA 500 V (G4/SWA/PVC or G4/SWA/LS0H)


RG4OHM1FM1-FR
RG4XOHM1FM1-FR

1x2x2,5
2x2x2,5
4x2x2,5
5x2x2,5
6x2x2,5
10x2x2,5
12x2x2,5
15x2x2,5
20x2x2,5
24x2x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18

8,4
14,1
16,7
19,5
19,9
24,2
25,2
28,2
32,1
35,2

* Refers only to G4/LS0H/SWA/LS0H construction

59

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - O
(PE/PVC or
XLPE/PVC or
XLPE/LS0H)
300 or 500 V

Construction

>
>
>
>
>
>

>
>

Applicable
standards

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3A

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 2
Insulation
polyethylene or XLPE
Triples
twisted
Identification triples
blue, brown, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape 0,023 mm
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3A

60

GOOD

GOOD

LS0H

-5 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A

TEPLA I - O 300 V (PE/PVC or XLPE/PVC or XLPE/LS0H)

Cross
section

Diameter
of
conductor

Maximum DC
resistance
at 20 C

Diameter
over
insulation

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

(mm2)

(mm)

(/km)

(mm)

(mm)

(kg/km)

(mm)

RE4OHR
RE4XOHR

1x3x0,5
2x3x0,5
6x3x0,5
10x3x0,5
12x3x0,5
15x3x0,5
20x3x0,5
24x3x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16

6,5
10,9
15,7
18,6
20,2
22,4
25,5
27,9

54
101
226
345
402
497
636
760

78
131
189
223
242
269
306
335

RE4OHR
RE4XOHR

1x3x0,75
2x3x0,75
6x3x0,75
10x3x0,75
12x3x0,75
15x3x0,75
20x3x0,75
24x3x0,75

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28

6,8
11,4
16,5
19,5
21,3
23,5
27,0
29,3

60
113
259
399
476
576
753
885

82
136
198
234
256
282
324
352

RE4OHR
RE4XOHR

1x3x1
2x3x1
6x3x1
10x3x1
12x3x1
15x3x1
20x3x1
24x3x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49

7,4
12,4
18,0
21,2
23,1
25,7
29,4
32,2

74
142
330
510
598
739
967
1154

89
149
216
255
277
308
353
386

RE4OHR
RE4XOHR

1x3x1,5
2x3x1,5
6x3x1,5
10x3x1,5
12x3x1,5
15x3x1,5
20x3x1,5
24x3x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79

8,1
13,7
20,1
23,7
25,9
28,8
33,0
36,1

94
180
450
701
836
1033
1352
1612

97
164
241
284
311
346
396
433

3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18

9,1
15,7
22,9
27,2
29,5
33,0
37,7
41,2

127
254
639
1013
1192
1488
1949
2322

109
188
275
326
354
396
452
494

Type*

TEPLA I - O 500 V (PE/PVC or XLPE/PVC or XLPE/LS0H)


RE4OHR
RE4XOHR

1x3x2,5
2x3x2,5
6x3x2,5
10x3x2,5
12x3x2,5
15x3x2,5
20x3x2,5
24x3x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

* Refers only to XLPE/PVC construction

61

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - FR - O
(XLPE/LS0H)
300 or 500 V

Construction

>
>
>
>
>
>
>

>
>

Applicable
standards

Conductor
annealed copper wires according to class 2
Fire barrier
mica/glass tape
Insulation
XLPE
Triples
twisted
Identification triples
blue, brown, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60331
IEC 60754
IEC 61034

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Fire resistant
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

low
r

62

IEC 60332-1
IEC 60332-3A
IEC 60331

GOOD

GOOD

LS0H

0 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A
> Fire resistant cables according to IEC 60331
TEPLA I - FR - O 300 V (XLPE/LS0H)

Cross
section

Diameter
of
conductor

Maximum DC
resistance
at 20 C

Diameter
over
insulation

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

(mm2)

(mm)

(/km)

(mm)

(mm)

(kg/km)

(mm)

RTE4OHM1
RTE4XOHM1

1x3x0,5
2x3x0,5
6x3x0,5
10x3x0,5
12x3x0,5
15x3x0,5
20x3x0,5
24x3x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

2,80
2,80
2,80
2,80
2,80
2,80
2,80
2,80

8,1
13,7
19,9
23,6
25,8
28,5
32,7
35,8

73
138
308
467
556
670
872
1039

97
165
239
283
310
342
393
430

RTE4OHM1
RTE4XOHM1

1x3x0,75
2x3x0,75
6x3x0,75
10x3x0,75
12x3x0,75
15x3x0,75
20x3x0,75
24x3x0,75

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,90
2,90
2,90
2,90
2,90
2,90
2,90
2,90

8,3
14,0
20,4
24,4
26,5
29,5
33,5
36,7

79
149
339
529
616
758
970
1156

99
168
245
292
318
353
402
441

RTE4OHM1
RTE4XOHM1

1x3x1
2x3x1
6x3x1
10x3x1
12x3x1
15x3x1
20x3x1
24x3x1

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

3,10
3,10
3,10
3,10
3,10
3,10
3,10
3,10

8,7
14,9
21,9
25,9
28,2
31,4
36,0
39,4

90
174
416
638
746
921
1202
1432

105
179
263
311
338
377
432
472

RTE4OHM1
RTE4XOHM1

1x3x1,5
2x3x1,5
6x3x1,5
10x3x1,5
12x3x1,5
15x3x1,5
20x3x1,5
24x3x1,5

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,
12,1
12,1
12,1
12,1
12,1
12,1
12,1

3,40
3,40
3,40
3,40
3,40
3,40
3,40
3,40

9,4
16,3
24,0
28,6
31,0
34,5
39,5
43,2

111
223
543
853
1000
1232
1610
1916

113
196
288
343
372
414
474
519

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,80
3,80
3,80
3,80
3,80
3,80
3,80
3,80

10,4
18,1
26,9
31,9
34,7
38,7
44,3
48,6

147
294
744
1171
1375
1716
2240
2687

125
217
322
383
416
465
531
583

Type

TEPLA I - FR - O 500 V (XLPE/LS0H)


RTE4OHM1
RTE4XOHM1

1x3x2,5
2x3x2,5
6x3x2,5
10x3x2,5
12x3x2,5
15x3x2,5
20x3x2,5
24x3x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

63

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA I - FR - O
(G4/PVC or
G4/LS0H)
300 or 500 V

Construction

>
>
>
>
>
>

>
>

Applicable
standards

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60331
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3A
IEC 60331

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 2
Insulation
silicon
Triples
twisted
Identification triples
blue, brown, black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300 V EN 50288-7
or
e. g. : PRYSMIAN year - n x m x csa 500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Fire resistant
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

PVC
LS0H

low
r

64

IEC 60332-1
IEC 60332-3A
IEC 60331

GOOD

GOOD

LS0H

0 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A
> Fire resistant cables according to IEC 60331-23
TEPLA I - FR - O 300 V (G4/PVC or G4/LS0H)

Type*

Cross
section

Diameter
of
conductor

(mm2)

(mm)

RG4OHM1-FR
RG4XOHM1-FR

1x3x0,5
2x3x0,5
6x3x0,5
10x3x0,5
12x3x0,5
15x3x0,5
20x3x0,5
24x3x0,5

0,96
0,96
0,96
0,96
0,96
0,96
0,96
0,96

36,0
36,0
36,0
36,0
36,0
36,0
36,0
36,0

RG4OHM1-FR
RG4XOHM1-FR

1x3x0,75
2x3x0,75
6x3x0,75
10x3x0,75
12x3x0,75
15x3x0,75
20x3x0,75
24x3x0,75

1,08
1,08
1,08
1,08
1,08
1,08
1,08
1,08

RG4OHM1-FR
RG4XOHM1-FR

1x3x1
2x3x1
6x3x1
10x3x1
12x3x1
15x3x1
20x3x1
24x3x1

RG4OHM1-FR
RG4XOHM1-FR

1x3x1,5
2x3x1,5
6x3x1,5
10x3x1,5
12x3x1,5
15x3x1,5
20x3x1,5
24x3x1,5

Maximum DC
resistance
at 20 C
(/km)

Diameter
over
insulation

Min
bending
radius

Outer
diameter approx

Weight
of cable approx

(mm)

(kg/km)

2,16
2,16
2,16
2,16
2,16
2,16
2,16
2,16

6,5
10,9
15,7
18,6
20,2
22,4
25,5
27,9

64,8
143,8
284,8
430,6
501,2
617,1
790,8
943,1

78
131
189
223
242
269
306
335

24,5
24,5
24,5
24,5
24,5
24,5
24,5
24,5

2,28
2,28
2,28
2,28
2,28
2,28
2,28
2,28

6,8
11,4
16,5
19,5
21,3
23,5
27,0
29,3

72,5
159,9
323,2
492,0
584,1
707,5
922,4
1085,4

82
136
198
234
256
282
324
352

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

18,1
18,1
18,1
18,1
18,1
18,1
18,1
18,1

2,49
2,49
2,49
2,49
2,49
2,49
2,49
2,49

7,4
12,4
18,0
21,2
23,1
25,7
29,4
32,2

88,8
197,3
404,7
618,8
723,4
891,6
1163,5
1386,8

89
149
216
255
277
308
353
386

1,59
1,59
1,59
1,59
1,59
1,59
1,59
1,59

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

2,79
2,79
2,79
2,79
2,79
2,79
2,79
2,79

8,1
13,7
20,1
23,7
25,9
28,8
33,0
36,1

111,3
249,2
540,4
832,9
988,7
1218,2
1590,4
1894,9

97
164
241
284
311
346
396
433

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,18
3,18
3,18
3,18
3,18
3,18
3,18
3,18

9,1
15,7
22,9
27,2
29,5
33,0
25,6
27,9

149,1
342,2
753,3
1179,0
1383,7
1721,0
1656,7
1972,7

109
188
275
326
354
396
308
335

(mm)

(mm)

TEPLA I - FR - O 500 V (G4/PVC or G4/LS0H)


RG4OHM1-FR
RG4XOHM1-FR

1x3x2,5
2x3x2,5
6x3x2,5
10x3x2,5
12x3x2,5
15x3x2,5
20x3x2,5
24x3x2,5

1,98
1,98
1,98
1,98
1,98
1,98
1,98
1,98

* Refers only to G4/LS0H construction

65

TEPLA
Plant & Petrochem Cables

66

technergy

TM

INTEGRATED CABLING SOLUTIONS

Thermocouple cables

67

Thermocouple
cables

TEPLA
Plant & Petrochem Cables

Standards of extension & compensating cables for thermocouples


(temperature ranges and tolerances of conductors, colour codes of insulations and outer sheaths)

platinum-10% rhodium
platinum

platinum-30% rhodium
platinum-6% rhodium

iron
copper-nickel

copper
copper-nickel

nickel-chromium
copper-nickel

nickel-chromium
nickel

> RCA/SCA

copper/copper-nickel
0 C up to +100 C (class 2: 30 V / 2,5 C)

> RCB/SCB

copper/copper-nickel
0 C up to +200 C (class 2: 60 V / 5 C)
+
-

> BC

copper/copper
0 C up to +100 C (40 V / 3,5 C)
+
-

> JX

iron/copper-nickel
-25 C up to +200 C (class 1: 85 V / 1,5 C)
(class 2: 140 V / 2,5 C)

> SX

copper/copper-nickel
0 C up to +200 C (57 V / 5 C)
+
-

> BX

copper-alloy/copper (copper/copper)
0 C up to +100 C (+0,0 V / +0 C)
(-33 V / -3,7 C)
+
-

> JX

iron/copper-nickel
0 C up to +200 C (special: 1,1 C)
(standard: 2,2 C)

+
-

> TX

copper/copper-nickel
-25 C up to +100 C (class 1: 30 V / 0,5 C)
(class 2: 60 V / 1,0 C)

+
-

> TX

copper/copper-nickel
0 C up to +100 C (special: 0,5 C)
(standard: 1,0 C)

+
-

> EX

nickel-chromium/copper-nickel
-25 C up to +200 C (class 1: 120 V / 1,5 C)
(class 2: 200 V / 2,5 C)

+
-

> EX

nickel-chromium/copper-nickel
0 C up to +200 C (17 C)

+
-

> KX

nickel-chromium/nickel
-25 C up to +200 C (class 1: 60 V / 1,5 C)
(class 2: 100 V / 2,5 C)

+
-

> KX

nickel-chromium/nickel
0 C up to +200 C (2,2 C)
+
-

> KCB

copper/copper-nickel
0 C up to +100 C (class 2: 100 V / 2,5 C)

> KCA

iron/copper-nickel
0 C up to +150 C (class 2: 100 V / 2,5 C)
+
-

nickel-chromium-silicon
nickel-silicon

> NX

nickel-chromium-silicon and nickel-silicon


-25 C up to +200 C (class 1: 60 V / 1,5 C)
(class 2: 100 V / 2,5 C)

> NC

copper/copper-nickel
0 C up to +150 C (class 2: 100 V / 2,5 C)

68

ANSI MC 96.1

ANSI MC 96.1

platinum-13% rhodium
platinum

IEC 60584 DIN IEC 60584

R
S

Thermocouple type and material

IEC 60584 DIN IEC 60584

+
-

> VX

copper/copper-nickel
ISARP 1.1
0 C up to +100 C (2,2 C)
+
-

technergy

TM

INTEGRATED CABLING SOLUTIONS

BPC
BPX

BNC
BNX

IEC
ANSI

JPX
JPX

JNX
JNX

IEC
ANSI

TPC
TPX

TNC
TNX

IEC
ANSI

EPX
EPX

ENX
ENX

IEC
IEC
IEC
ANSI
ISA

KPX
KPCA
KPCB
KPX
VPX

KNX
KNCA
KNCB
KNX
VNX

IEC
IEC
ANSI

NPX
NPC
NPX

NNX
NNC
NNX

IEC
IEC
ANSI

Loop
inductance
(mH/km)

(+) leg

(-) leg

0,017
0,017
0,017

0,12
0,12
0,12

0,017
0,125

0,017
0,017

0,13
0,13

0,49
0,49

0,017
0,017

0,49
0,49

0,71
0,71

0,49
0,49

0,71
0,017
0,13
0,71
0,017

0,29
0,49
0,52
0,29
0,49

0,98
0,017
0,98

0,36
0,52
0,36

Loop inductance (mH/km)

IEC
ANSI

R
S

Volume resistivity ( mm2/m)

(-) leg
RNCA/SNCA
RNCA/SNCA
SNX

Code

(+) leg
RPCA/SPCA
RPCB/SPCB
SPX

Standard

Electrical characteristics (approx values)

Volume
resistivity
(mm2 /m)

Code

Standard

1
1
1

1
1

8
8

1
1

3
3

3
1
8
3
1

3
1
3

69

TEPLA
Plant & Petrochem cables

70

technergy

TM

INTEGRATED CABLING SOLUTIONS

Thermocouple cables according to BS 5308

71

Thermocouple
cables

TEPLA
Plant & Petrochem Cables

TEPLA T - IO
(PE/PVC or
XLPE/LS0H)
300/500 V

Construction

>
>
>
>
>
>

>
>

Applicable
standards

BS 5308-1
IEC 60332-1
IEC 60332-3C
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3C

STANDARD

GOOD

0 C

Conductor
solid alloy conductor
Insulation
polyethylene type 03 according to BS 6234 or XLPE
Pairs
twisted
Identification pairs
numbered pairs and colour code according to ANSI MC 96.1 or IEC 60584
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC type TM1 according to BS 6746 or LS0H thermoplastic compound
Marking
e. g. : PRYSMIAN year - n x m x AWG 300/500 V thermocouple type

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3C

72

STANDARD

GOOD

LS0H

-5 C

12 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Thermocouple cables generally according to BS 5308-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA T - IO 300/500 V (PE/PVC or XLPE/LS0H)

Cross
section

Diameter of
conductor

Diameter
over
insulation

Diameter
over lay up

Outer
diameter approx

Weight of cable
approx

Min
bending radius

(AWG)

(mm)

(mm)

(mm)

(mm)

(kg/km)

(mm)

UEXHOHR

2x2x20
4x2x20
6x2x20
8x2x20
10x2x20
12x2x20
16x2x20
20x2x20
24x2x20

0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0

7,7
9,3
11,3
12,2
13,9
14,5
16,8
18,8
20,6

10,0
11,0
13,0
14,0
16,0
17,0
19,0
21,0
23,0

90
140
200
250
300
350
440
550
650

120
132
156
168
192
204
228
252
276

UEXHOHR

2x2x18
4x2x18
6x2x18
8x2x18
10x2x18
12x2x18
16x2x18
20x2x18
24x2x18

1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0

2,2
2,2
2,2
2,2
2,2
2,2
2,2
2,2
2,2

8,5
10,3
12,4
13,4
15,2
16,0
18,5
20,7
22,6

11,0
12,0
14,0
16,0
18,0
19,0
22,0
24,0
27,0

120
190
260
320
390
450
600
720
870

132
144
168
192
216
228
264
288
324

UEXHOHR

2x2x16
4x2x16
6x2x16
8x2x16
10x2x16
12x2x16
16x2x16
20x2x16
24x2x16

1,3
1,3
1,3
1,3
1,3
1,3
1,3
1,3
1,3

2,5
2,5
2,5
2,5
2,5
2,5
2,5
2,5
2,5

9,3
11,3
13,7
14,8
16,8
17,6
20,4
22,8
25,0

12,0
15,0
17,0
18,0
20,0
21,0
24,0
27,0
29,0

150
240
330
410
500
600
770
960
1120

144
180
204
216
240
252
288
324
348

Type*

* Refers only to PE/PVC construction

73

Thermocouple
cables

TEPLA
Plant & Petrochem Cables

TEPLA T - IOA
(PE/SWA/PVC or
XLPE/SWA/LS0H)
300/500 V

Construction

>
>
>
>
>

>
>

>
>
>

>

Applicable
standards

BS 5308-1
IEC 60332-1
IEC 60332-3C
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3C

STANDARD

EXCELLENT

0 C

Conductor
solid alloy conductor
Insulation
polyethylene type 03 according to BS 6234 or XLPE
Pairs
twisted
Identification pairs
numbered pairs and colour code according to ANSI MC 96.1 or IEC 60584
Individual screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape 0,023 mm
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape 0,023 mm
Bedding
polyethylene type 03 according to BS 6234 or LS0H thermoplastic compound
Armour
galvanized steel wire
Outer sheath
PVC type TM1 according to BS 6746 or hydrocarbon resistant or LS0H
thermoplastic compound
Marking
e. g. : PRYSMIAN year - n x m x AWG 300/500 V thermocouple type

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3C

74

STANDARD

EXCELLENT

LS0H

-6 C

14 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Thermocouple cables generally according to BS 5308-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA T - IOA 300/500 V (PE/SWA/PVC or XLPE/SWA/LS0H)

Diameter
of armour
wires

Diameter
over
armour

Weight
of cable
approx

Weight
of cable
approx

Min bending
radius

(mm)

Diameter
over
separation
sheath
(mm)

(mm)

(mm)

(kg/km)

(kg/km)

(mm)

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0

7,7
9,3
11,3
12,2
13,9
14,5
16,8
18,8
20,6

9,5
11,0
13,0
14,0
15,5
16,2
18,2
20,5
22,0

0,9
0,9
1,3
1,3
1,3
1,3
1,6
1,6
1,6

11,3
12,8
15,5
16,5
18,0
18,7
21,4
23,7
25,2

13,9
15,4
18,5
19,5
21,2
21,9
24,8
27,3
28,8

350
440
640
720
810
890
1200
1400
1550

195
216
259
273
297
307
347
382
403

1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0

2,2
2,2
2,2
2,2
2,2
2,2
2,2
2,2
2,2

8,5
10,3
12,4
13,4
15,2
16,0
18,5
20,7
22,6

10,8
12,8
15,2
16,2
18,0
18,8
21,7
24,0
26,3

0,9
1,3
1,3
1,3
1,6
1,6
1,6
1,6
1,6

12,6
15,3
17,7
18,7
21,2
22,0
24,9
27,2
29,5

15,2
18,3
20,9
21,9
24,6
21,9
24,8
27,3
33,5

410
630
770
870
1130
1220
1480
1700
1950

213
256
293
307
344
195
195
195
469

1,3
1,3
1,3
1,3
1,3
1,3
1,3
1,3
1,3

2,5
2,5
2,5
2,5
2,5
2,5
2,5
2,5
2,5

9,3
11,3
13,7
14,8
16,8
17,6
20,4
22,8
25,0

12,0
14,2
16,6
17,7
19,8
21,0
23,8
26,7
28,8

0,9
1,3
1,3
1,6
1,6
1,6
1,6
1,6
2,0

13,8
16,7
19,1
20,9
23,0
24,2
27,0
29,9
32,8

16,6
19,7
22,3
19,5
26,6
27,8
30,8
33,9
36,8

460
720
890
1130
1310
1450
1750
2030
2530

232
276
312
195
372
389
431
475
515

Cross
section

Diameter of
conductor

Diameter
over
insulation

Diameter
over
lay up

(AWG)

(mm)

(mm)

UEXHOHRFR

2x2x20
4x2x20
6x2x20
8x2x20
10x2x20
12x2x20
16x2x20
20x2x20
24x2x20

0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8
0,8

UEXHOHRFR

2x2x18
4x2x18
6x2x18
8x2x18
10x2x18
12x2x18
16x2x18
20x2x18
24x2x18

UEXHOHRFR

2x2x16
4x2x16
6x2x16
8x2x16
10x2x16
12x2x16
16x2x16
20x2x16
24x2x16

Type*

* Refers only to PE/SWA/PVC construction

75

TEPLA
Plant & Petrochem Cables

76

technergy

TM

INTEGRATED CABLING SOLUTIONS

Thermocouple cables according to EN 50288

77

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA T - IO
(PE/PVC or
XLPE/LS0H)
300/500 V

Construction

>
>
>
>
>

>
>

>
>

Applicable
standards

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3A

STANDARD

GOOD

0 C

Conductor
solid alloy
Insulation
polyethylene or XLPE
Pairs
twisted
Identification pairs
according to ANSI MC 96.1 or IEC 60584
Individual screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3A

78

STANDARD

GOOD

LS0H

-5 C

12 D

Pb

technergy

> Instrumentation cables generally according to EN 50288-7

TM

INTEGRATED CABLING SOLUTIONS

> Flame retardant cables according to IEC 60332-1


> Fire retardant cables according to (if required) IEC 60332-3A

TEPLA T - IO 300/500 V (PE/PVC or XLPE/LS0H)

Type*

Cross
section

Diameter of
conductor

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

(mm2)

(mm)

(mm)

(kg/km)

(mm)

UEOHR
UEXHOHR

1x2x20
2x2x20
4x2x20
6x2x20
8x2x20
10x2x20
12x2x20
16x2x20
20x2x20
24x2x20

0,81
0,81
0,81
0,81
0,81
0,81
0,81
0,81
0,81
0,81

5,1
7,7
8,9
10,6
11,9
13,6
14,0
15,6
17,4
19,4

51
100
150
220
260
320
360
480
580
690

61
93
107
128
143
163
168
187
209
233

UEOHR
UEXHOHR

1x2x18
2x2x18
4x2x18
6x2x18
8x2x18
10x2x18
12x2x18
16x2x18
20x2x18
24x2x18

1,02
1,02
1,02
1,02
1,02
1,02
1,02
1,02
1,02
1,02

5,8
8,9
10,3
12,4
13,9
15,9
16,4
18,3
20,5
22,8

63
140
200
280
350
430
490
630
790
930

69
106
124
148
167
190
197
220
246
274

UEOHR
UEXHOHR

1x2x16
2x2x16
4x2x16
6x2x16
8x2x16
10x2x16
12x2x16
16x2x16
20x2x16
24x2x16

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

6,8
10,7
12,6
15,1
17,1
19,5
20,3
22,6
25,4
28,4

60
180
270
360
460
560
640
860
1040
1250

82
129
151
182
205
235
243
272
305
341

* Refers only to PE/PVC construction

79

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA T - IOA
(PE/SWA/PVC or
XLPE/SWA/LS0H)
300/500 V

Construction

>
>
>
>
>

>
>

>
>
>
>

Applicable
standards

EN 50288-7
EN 50290-2
IEC 60332-1
IEC 60332-3A
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3A

STANDARD

EXCELLENT

0 C

Conductor
solid alloy
Insulation
polyethylene or XLPE
Pairs
twisted
Identification pairs
according to ANSI MC 96.1 or IEC 60584
Individual screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape 0,023 mm
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape 0,023 mm
Inner sheath
PVC or LS0H
Armour
galvanized steel wire
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

PVC
LS0H

low
r

IEC 60332-1
IEC 60332-3A

80

STANDARD

EXCELLENT

LS0H

-6 C

14 D

Pb

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A

TEPLA T - IOA 300/500 V (PE/SWA/PVC or XLPE/SWA/LS0H)

Cross
section

Diameter of
conductor

(mm2)

(mm)

Diameter
over
inner
sheath
(mm)

UEOHRFR
UEXHOHRFR

1x2x20
2x2x20
4x2x20
6x2x20
8x2x20
10x2x20
12x2x20
16x2x20
20x2x20
24x2x20

0,81
0,81
0,81
0,81
0,81
0,81
0,81
0,81
0,81
0,81

5,1
7,7
8,9
10,6
11,9
13,6
14,0
15,6
17,4
19,4

UEOHRFR
UEXHOHRFR

1x2x18
2x2x18
4x2x18
6x2x18
8x2x18
10x2x18
12x2x18
16x2x18
20x2x18
24x2x18

1,02
1,02
1,02
1,02
1,02
1,02
1,02
1,02
1,02
1,02

UEOHRFR
UEXHOHRFR

1x2x16
2x2x16
4x2x16
6x2x16
8x2x16
10x2x16
12x2x16
16x2x16
20x2x16
24x2x16

1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29
1,29

Type*

Diameter
over
armour

Outer
diameter
approx

(mm)

(mm)

0,90
0,90
0,90
0,90
0,90
0,90
0,90
1,25
1,25
1,25

6,92
9,52
10,74
12,44
13,75
15,36
15,82
18,10
19,94
21,89

9,5
12,3
13,5
15,3
16,7
18,4
18,9
21,3
23,3
25,3

217
369
451
666
739
841
901
1302
1482
1647

133
172
190
215
234
258
265
298
326
354

5,8
8,9
10,3
12,4
13,9
15,9
16,4
18,3
20,5
22,8

1,25
1,25
1,25
1,25
1,25
1,25
1,25
1,25
1,25
1,25

8,26
11,37
12,84
14,86
16,44
18,36
18,92
20,81
23,01
25,35

10,9
14,2
15,8
17,9
19,6
21,6
22,2
24,2
26,5
29,0

252
423
652
787
876
1230
1327
1572
1852
2074

153
199
221
251
274
302
310
338
371
406

6,8
10,7
12,6
15,1
17,1
19,5
20,3
22,6
25,4
28,4

1,25
1,25
1,25
1,25
1,25
1,25
1,25
1,25
1,60
1,60

9,30
13,21
15,07
17,63
19,62
22,05
22,75
25,14
28,62
31,58

12,0
16,2
18,1
20,8
22,9
25,5
26,2
28,7
32,4
35,5

283
473
742
911
1189
1452
1496
1915
2092
2663

168
226
254
291
321
357
367
402
454
498

Diameter
of armour wires
(mm)

Weight
of cable approx
(kg/km)

Min
bending
radius
(mm)

* Refers only to PE/SWA/PVC construction

81

TEPLA
Plant & Petrochem Cables

82

technergy

TM

INTEGRATED CABLING SOLUTIONS

Control cables according to BS 5308

83

Control
cables

TEPLA
Plant & Petrochem Cables

TEPLA C - S
(PVC/PVC or
XLPE/LS0H)
300/500 V

Construction

>
>
>
>
>

>
>

Applicable
standards

BS 5308
IEC 60332-1
IEC 60332-3C
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3C

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 1 or 2 or 5 of BS 6360
Insulation
PVC type TI1 according to BS 6746 or XLPE
Identification cores
black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC type TM1 according to BS 6746 or LS0H thermoplastic compound
Marking
e. g. : PRYSMIAN year - n x csa 300/500 V BS 5308
or
e. g. : PRYSMIAN Afumex year - n x csa 300/500 V BS 5308

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

low
r

IEC 60332-1
IEC 60332-3C

84

STANDARD

GOOD

LS0H

-5 C

12 D

70C

160C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Control cables generally according to BS 5308


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA C - S 300/500 V (PVC/PVC or XLPE/LS0H)

Cross
section

Diameter of
conductor

Maximum DC
resistance
at 20 C

Diameter
over insulation

Outer
diameter approx

Weight of cable
approx

Min
bending radius

(AWG)

(mm)

(mm)

(mm)

(mm)

(kg/km)

(mm)

FROHR

2x0,5
3x0,5
4x0,5
6x0,5
10x0,5
20x0,5

0,9
0,9
0,9
0,9
0,9
0,9

39,00
39,00
39,00
39,00
39,00
39,00

2,1
2,1
2,1
2,1
2,1
2,1

5,9
6,2
6,7
8,1
10,6
13,5

46
56
67
100
152
276

71
74
80
97
127
162

FROHR

2x0,75
3x0,75
4x0,75
6x0,75
10x0,75
20x0,75

1,1
1,1
1,1
1,1
1,1
1,1

26,00
26,00
26,00
26,00
26,00
26,00

2,3
2,3
2,3
2,3
2,3
2,3

6,3
6,6
7,2
8,8
11,4
14,6

53
66
81
123
186
341

76
79
86
106
137
175

RROHR

2x1,5
3x1,5
4x1,5
6x1,5
10x1,5
20x1,5

1,6
1,6
1,6
1,6
1,6
1,6

12,10
12,10
12,10
12,10
12,10
12,10

2,8
2,8
2,8
2,8
2,8
2,8

7,3
8,0
8,7
10,7
13,7
17,6

77
105
130
204
303
569

88
96
104
128
164
211

Type*

* Refers only to PVC/PVC construction

85

Control
cables

TEPLA
Plant & Petrochem Cables

TEPLA C - SA
(PVC/SWA/PVC or
XLPE/SWA/LS0H)
300/500 V

Construction

>
>
>
>
>

>
>
>
>

Applicable
standards

BS 5308
IEC 60332-1
IEC 60332-3C
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3C

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 1 or 2 or 5 of BS 6360
Insulation
PVC type TI1 according to BS 6746 or XLPE
Identification cores
black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Bedding
PVC type TM1 according to BS 6746 or LS0H thermoplastic compound
Armour
galvanized steel wire
Outer sheath
PVC type TM1 according to BS 6746 or LS0H thermoplastic compound
Marking
e. g. : PRYSMIAN year - n x csa 300/500 V BS 5308
or
e. g. : PRYSMIAN Afumex year - n x csa 300/500 V BS 5308

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

low
r

IEC 60332-1
IEC 60332-3C

86

STANDARD

GOOD

LS0H

-5 C

14 D

70C

160C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Control cables generally according to BS 5308


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA C - SA 300/500 V (PVC/SWA/PVC or XLPE/SWA/LS0H)

Type*

Cross
section

Diameter of Maximum DC
conductor resistance
at 20 C

Diameter
over
insulation

Diameter
over
inner sheath

Diameter
of armour
wires

Diameter
over
armour

Outer
diameter
approx

Weight
of cable
approx

Min bending
radius

(mm2)

(mm)

(/km)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg/km)

(mm)

FROHRFR

2x0,5
3x0,5
4x0,5
6x0,5
10x0,5
20x0,5

0,9
0,9
0,9
0,9
0,9
0,9

39,00
39,00
39,00
39,00
39,00
39,00

2,1
2,1
2,1
2,1
2,1
2,1

5,9
6,2
6,7
8,1
10,6
13,5

0,9
0,9
0,9
0,9
0,9
1,3

7,7
8,0
8,5
9,9
12,4
16,0

10,3
10,6
11,1
12,7
15,4
19,2

217
235
255
330
446
759

144
148
155
178
216
269

FROHRFR

2x0,75
3x0,75
4x0,75
6x0,75
10x0,75
20x0,75

1,1
1,1
1,1
1,1
1,1
1,1

26,00
26,00
26,00
26,00
26,00
26,00

2,3
2,3
2,3
2,3
2,3
2,3

6,3
6,6
7,2
8,8
11,4
14,6

0,9
0,9
0,9
0,9
0,9
1,3

8,1
8,4
9,0
10,6
13,2
17,1

10,7
11,0
11,8
13,4
16,2
20,3

233
254
289
369
502
854

150
154
165
188
227
284

RROHRFR

2x1,5
3x1,5
4x1,5
6x1,5
10x1,5
20x1,5

1,6
1,6
1,6
1,6
1,6
1,6

12,10
12,10
12,10
12,10
12,10
12,10

2,8
2,8
2,8
2,8
2,8
2,8

7,3
8,0
8,7
10,7
13,7
17,6

0,9
0,9
0,9
0,9
1,3
1,6

9,1
9,8
10,5
12,5
16,2
20,8

11,9
12,6
13,3
15,3
19,4
24,2

286
329
369
496
788
1320

167
176
186
214
272
339

* Refers only to PVC/SWA/PVC construction

87

Control
cables

TEPLA
Plant & Petrochem Cables

TEPLA C
(XLPE/PVC or
XLPE/LS0H)
0,6/1 kV

Construction

>
>
>
>
>
>

Applicable
standards

IEC 60502-1
IEC 60228
IEC 60332-1
IEC 60332-3 C
IEC 60754
IEC 61034

IEC 60332-1

STANDARD

GOOD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Identification cores
black numbered
Assembly
concentric layers
Penetrant. sheath
PVC compound ST2 quality or LS0H thermoplastic compound ST8 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV
or
e. g. : PRYSMIAN Afumex year - n x csa 0,6/1 kV

Design and tests guidelines


Conductors
Flame retardant
Fire retardant on bunched cables(if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

low
r

IEC 60332-1
IEC 60332-3C

88

GOOD

GOOD

LS0H

-5 C

12 D

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Control cables according to IEC 60502-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA C 0,6/1 kV (XLPE/PVC or XLPE/LS0H)

Type*

RE4OR/RE4OM1

RE4OR/RE4OM1

RE4OR/RE4OM1

Voltage

Cross
section

Diameter
of
conductor

Maximum
DC
resistance
at 20 C

Diameter
over
insulation

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

Phase
reactance
at 50 Hz
approx (*)

Conductor
short circuit
current
for 1 sec

Current
rating
in air
at 30 C

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(kg/km)

(mm)

(/km)

(kA)

(A)

Current
rating in
ground at
20 C (gr.
therm.res.
1 Km/W;
depth of
laying
0,8 m)
(A)

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

7x1,5
10x1,5
12x1,5
14x1,5
16x1,5
19x1,5
24x1,5
27x1,5
30x1,5
33x1,5
37x1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

3,0
3,0
3,0
3,0
3,0
3,0
3,0
3,0
3,0
3,0
3,0

12,6
15,6
16,1
16,8
17,7
18,6
21,6
22,0
22,8
23,7
24,6

250
340
380
430
480
550
660
730
790
880
970

150
185
195
200
210
225
260
265
275
285
295

0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10

0,25
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3

17
16
15
14
13
12
12
11
10
9,0
8,0

22
20
18
17
16
15
13
12
11
10
9

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

7x2,5
10x2,5
12x2,5
14x2,5
16x2,5
19x2,5
24x2,5
27x2,5
30x2,5
33x2,5
37x2,5

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,4
3,4
3,4
3,4
3,4
3,4
3,4
3,4
3,4
3,4
3,4

13,8
17,2
17,7
18,6
19,5
20,5
23,9
24,4
25,3
26,3
27,3

330
440
500
570
640
740
900
990
1080
1200
1320

165
205
210
225
235
245
285
295
305
315
330

0,094
0,09
0,09
0,09
0,09
0,09
0,09
0,09
0,09
0,09
0,09

0,41
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4

23
21
20
18
18
17
16
15
14
13
12

29
26
24
22
21
19
18
17
16
15
14

( )

* two adiacent cores

89

Control
cables

TEPLA
Plant & Petrochem Cables

TEPLA C - A
(XLPE/SWA/PVC or
XLPE/SWA/LS0H)
0,6/1 kV

Construction

>
>
>
>
>
>
>
>

Applicable
standards

IEC 60502-1
IEC 60228
IEC 60332-1
IEC 60332-3 C
IEC 60754
IEC 61034

IEC 60332-1

STANDARD

EXCELLENT

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Identification cores
black numbered
Assembly
concentric layers
Fillers
non hygroscopic compound or LS0H non hygroscopic compound
Armour
galvanized steel wire
Sheath
PVC compound ST2 quality or LS0H thermoplastic compound ST8 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV
or
e. g. : PRYSMIAN Afumex year - n x csa 0,6/1 kV

Design and tests guidelines


Conductors
Flame retardant
Fire retardant on bunched cables(if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

low
r

IEC 60332-1
IEC 60332-3C

90

GOOD

EXCELLENT

LS0H

-5 C

14 D

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Control cables according to IEC 60502-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA C - A 0,6/1 kV (XLPE/SWA/PVC or XLPE/SWA/LS0H)

Type*

RE4OFR/RE4OFM1

Phase Conductor Current Current


Min
rating in
rating
bending reactance short ground at
at 50 Hz circuit
in air
radius
20 C
approx (*) current at 30 C
(gr.therm.
for 1 sec
res. 1
Km/W;
depth of
laying
0,8 m)
(A)
(/km)
(kA)
(A)
(kg/km)
(mm)

Voltage Cross Diameter Maximum Diameter Diameter Diameter Diameter Outer Weight
DC
of
section
over
of
over diameter
of
over
conductor resistance insulation extruded armour armour approx cable
at 20 C
approx
inner
wires
covering/
taping

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(mm)

(mm)

(mm)

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

7x1,5
10x1,5
12x1,5
14x1,5
16x1,5
19x1,5
24x1,5
27x1,5
30x1,5
33x1,5
37x1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

3,0
3,0
3,0
3,0
3,0
3,0
3,0
3,0
3,0
3,0
3,0

11,0
14,0
14,5
15,2
16,1
17,0
20,0
20,4
21,2
22,1
23,0

0,8
1,25
1,25
1,25
1,25
1,25
1,6
1,6
1,6
1,6
1,6

12,6
16,5
17,0
17,7
18,6
19,5
23,2
23,6
24,4
25,3
26,2

16,2
20,1
20,6
21,3
22,2
23,1
26,8
27,2
28,0
28,9
29,8

490
770
830
890
970
1050
1400
1480
1560
1690
1790

225
280
290
300
310
325
375
380
390
405
415

0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10

0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3

17
16
15
14
13
12
12
11
10
9
8

22
20
18
17
16
15
13
12
11
10
9

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

7x2,5
10x2,5
12x2,5
14x2,5
16x2,5
19x2,5
24x2,5
27x2,5
30x2,5
33x2,5
37x2,5

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

3,4
3,4
3,4
3,4
3,4
3,4
3,4
3,4
3,4
3,4
3,4

12,2
15,6
16,1
17,0
17,9
18,9
22,3
22,8
23,7
24,7
25,7

1,25
1,25
1,25
1,25
1,6
1,6
1,6
1,6
1,6
1,6
1,6

14,7
18,1
18,6
19,5
21,1
22,1
25,5
26,0
26,9
27,9
28,9

18,3
21,7
22,2
23,1
24,7
25,7
29,1
29,6
30,7
31,7
32,7

710
910
990
1070
1320
1430
1710
1820
1960
2100
2250

255
305
310
325
345
360
405
415
430
445
460

0,094
0,09
0,09
0,09
0,09
0,09
0,09
0,09
0,09
0,09
0,09

0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4

23
21
20
18
18
17
16
15
14
13
12

29
26
24
22
21
19
18
17
16
15
14

( )

* two adiacent cores

91

Control
cables

TEPLA
Plant & Petrochem Cables

TEPLA C - FR
(XLPE/LS0H)
0,6/1 kV

Construction

>
>
>
>
>
>
>
>
>

Applicable
standards

IEC
IEC
IEC
IEC
IEC
IEC

Conductor
annealed copper wires according to class 2 of IEC 60228
Fire barrier
mica/glass tape
Insulation
XLPE according to IEC 60502
Identification cores
black numbered
Assembly
concentric layers
Identification cores
black numbered
Assembly
concentric layers
Outer sheath
LS0H thermoplastic compound ST8 quality
Marking
e. g. : PRYSMIAN Afumex year - n x csa 0,6/ 1 kV IEC 60331

60502
60332-1
60332-3A
60331
60754
61034

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Fire resistant test
Halogen free properties
Low smoke emission

low
r

92

IEC 60332-1
IEC 60332-3A
IEC 60331

GOOD

GOOD

LS0H

-5 C

12 D

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Control fire resistant cables according to IEC 60502-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A
> Fire resistant cables according to IEC 60331
TEPLA C - FR 0,6/1 kV (XLPE/LS0H)

Cross
section

Type*

Diameter Maximum
DC
of
conductor resistance
at 20 C

Diameter
over
insulation

Nominal
thickness
of
outer sheath

Outer
diameter
approx

Diameter
over
armour

Weight
of
cable
approx

Min
bending
radius

Phase
reactance
at 50 Hz
approx (*)

Conductor
short circuit
current
for 1 sec

Current
rating
in air
at 30 C

(mm)

(/km)

(mm)

(mm)

(mm)

(mm)

(kg/km)

(mm)

(/km)

(kA)

(A)

Current
rating in
ground at
20 C
(gr.therm.
res. 1 Km/W;
depth of
laying
0,8 m)
(A)

2x1,5
3x1,5
4x1,5
5x1,5
7x1,5
10x1,5
12x1,5
14x1,5
16x1,5
19x1,5
RTE4OM1-FR 24x1,5
27x1,5
30x1,5
33x1,5
37x1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7

3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5

1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8

10,7
11,2
12,2
13,2
14,2
17,8
18,3
19,2
20,2
21,2
24,8
25,3
26,2
27,3
28,5

120
150
180
210
260
360
410
460
510
590
730
803
880
950
1060

128
134
146
158
170
214
220
230
242
254
298
304
314
328
342

0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11

0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3

28
23
23
23
17
16
15
14
13
12
12
11
10
9
8

37
31
31
29
22
20
18
17
16
15
13
12
11
10
9

RTE4OM1-FR

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7

3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8

1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,9
1,9

11,2
11,8
12,8
14,0
15,1
18,9
19,5
20,4
21,6
22,7
26,5
27,1
28,1
29,4
30,5

140
180
220
250
330
450
520
590
660
760
950
1040
1150
1260
1300

135
142
154
168
181
227
233
245
259
272
318
325
337
353
366

0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10

0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4

37
31
31
31
23
21
20
18
18
17
16
15
14
13
12

49
41
41
37
29
26
24
22
21
19
18
17
16
15
14

(mm2)

RTE4OM1-FR

2x2,5
3x2,5
4x2,5
5x2,5
7x2,5
10x2,5
12x2,5
14x2,5
16x2,5
19x2,5
24x2,5
27x2,5
30x2,5
33x2,5
37x2,5

( )

* two adiacent cores

93

Control
cables

TEPLA
Plant & Petrochem Cables

TEPLA C - FR - A
(XLPE/SWA/LS0H)
0,6/1 kV

Construction

>
>
>
>
>
>
>
>
>

Applicable
standards

IEC
IEC
IEC
IEC
IEC
IEC

Conductor
annealed copper wires according to class 2 of IEC 60228
Fire barrier
mica/glass tape
Insulation
XLPE according to IEC 60502
Identification cores
black numbered
Assembly
concentric layers
Separation sheath
LS0H thermoplastic compound ST8 quality
Armour
galvanized steel wire
Outer sheath
LS0H thermoplastic compound ST8 quality
Marking
e. g. : PRYSMIAN Afumex year - n x csa 0,6/ 1 kV IEC 60331

60502
60332-1
60332-3A
60331
60754
61034

Design guidelines
Flame retardant
Fire retardant on bunched cables (if required)
Fire resistant test
Halogen free properties
Low smoke emission

low
r

94

IEC 60332-1
IEC 60332-3A
IEC 60331

GOOD

EXCELLENT

LS0H

-5 C

14 D

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Control fire resistant cables according to IEC 60502-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A
> Fire resistant cables according to IEC 60331
TEPLA C - FR - A 0,6/1 kV (XLPE/SWA/LS0H)

Phase Conductor Current Current


Cross Diameter Maximum Nominal Diameter Inner Diameter Diameter Diameter Nominal Outer Weight Min
DC
insulation over
sheath
over
of
over thickness diameter of cable bending reactance short rating rating in
section
of
armour armour
of
approx approx radius at 50 Hz circuit
in air ground at
conductor resistance thickness insulation thickness inner
at 20 C
approx (*) current at 30 C 20 C (gr.
sheath
wires
outer sheath
for 1 sec
therm.res.
1 Km/W;
depth of
laying 0,8
m)
2
(/km)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm) (kg/km) (mm) (/km)
(kA)
(A)
(mm )
(mm)
(A)

Type*

RTE4OFM1-FR 2x1,5
3x1,5
4x1,5
5x1,5
7x1,5
10x1,5
12x1,5
14x1,5
RTE4OFM1-FR16x1,5
19x1,5
24x1,5
27x1,5
30x1,5
33x1,5
37x1,5

1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1

0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7

3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5
3,5

1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0

9,0
9,6
10,5
11,6
12,6
16,1
16,6
17,5
18,5
19,6
23,1
23,6
24,6
25,6
26,6

0,8
0,8
0,8
1,3
1,3
1,6
1,6
1,6
1,6
1,6
1,6
1,6
1,6
2,0
2,0

10,6
11,2
12,1
14,1
15,1
19,3
19,8
20,7
21,7
22,8
26,3
26,8
27,8
29,6
30,6

1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,9
1,9
2,0
2,0
2,0

14,2
14,8
15,7
17,7
18,7
22,9
23,4
24,3
25,3
26,4
30,1
30,6
31,8
33,6
34,6

350
380
510
590
680
1000
1080
1150
1250
1360
1630
1720
1830
2180
2350

199
207
220
247
261
320
328
341
355
370
422
429
445
470
485

0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11

0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3
0,3

28
23
23
23
17
16
15
14
13
12
12
11
10
9
8

37
31
31
31
22
20
18
17
16
15
13
12
11
10
9

RTE4OFM1-FR 2x2,5
3x2,5
4x2,5
5x2,5
7x2,5
10x2,5
12x2,5
14x2,5
16x2,5
19x2,5
24x2,5
27x2,5
30x2,5
33x2,5
37x2,5

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0

7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7
0,7

3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8
3,8

1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,2
1,2

9,6
10,2
11,2
12,4
13,5
17,3
17,9
18,8
20,0
21,1
24,9
25,5
26,5
28,0
29,1

0,8
0,8
1,3
1,3
1,3
1,6
1,6
1,6
1,6
1,6
1,6
2,0
2,0
2,0
2,0

11,2
11,8
13,7
14,9
16,0
20,5
21,1
22,0
23,2
24,3
28,1
29,5
30,5
32,0
33,1

1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
1,8
2,0
2,0
2,0
2,1
2,1

14,8
15,4
17,3
18,5
19,6
24,1
24,7
25,6
26,8
27,9
32,1
33,5
34,5
36,2
37,3

380
520
600
670
780
1140
1230
1310
1430
1580
1920
2250
2400
2600
2750

208
216
242
259
274
337
345
359
375
391
450
469
483
507
523

0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10

0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4
0,4

37
31
31
31
23
21
20
18
18
17
16
15
14
13
12

49
41
41
37
29
26
24
22
21
19
18
17
16
15
14

( )

* two adiacent cores

95

TEPLA
Plant & Petrochem Cables

96

technergy

TM

INTEGRATED CABLING SOLUTIONS

Control cables according to EN 50288

97

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA C - S
(PVC/PVC or
XLPE/LS0H)
300/500 V

Construction

>
>
>
>
>

>
>

Applicable
standards

EN 50288-7
EN 50290-2
HD 383
IEC 60332-1
IEC 60332-3A
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3C

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 2
Insulation
PVC or XLPE
Identification cores
black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x csa 300/500 V BS 5308
or
e. g. : PRYSMIAN year - n x csa 300/500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Conductors
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

low
r

IEC 60332-1
IEC 60332-3C

98

STANDARD

GOOD

LS0H

-5 C

12 D

70C

160C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A

TEPLA C - S 300/500 V (PVC/PVC or XLPE/LS0H)

Type*

RE4OHM1*

Diameter
over
insulation

Outer
diameter
approx

(mm)

Maximum
DC
resistance
at 20 C
(/km)

(mm)

(mm)

0,96
0,96
0,96
0,96
0,96
0,96
1,08
1,08
1,08
1,08
1,08
1,08
1,29
1,29
1,29
1,29
1,29
1,29

36,0
36,0
36,0
36,0
36,0
36,0
24,5
24,5
24,5
24,5
24,5
24,5
18,1
18,1
18,1
18,1
18,1
18,1

2,16
2,16
2,16
2,16
2,16
2,16
2,28
2,28
2,28
2,28
2,28
2,28
2,49
2,49
2,49
2,49
2,49
2,49

6,6
7,0
7,6
9,2
11,9
16,4
6,9
7,2
8,1
9,5
12,6
17,3
8,1
8,5
9,3
11,2
14,9
20,6

Cross
section

Diameter of
conductor

(mm2)
2x0,5
3x0,5
4x0,5
7x0,5
12x0,5
24x0,5
2x0,75
3x0,75
4x0,75
7x0,75
12x0,75
24x0,75
2x1,5
3x1,5
4x1,5
7x1,5
12x1,5
24x1,5

Weight
of cable approx
(kg/km)

57
66
76
114
173
308
62
72
89
128
201
361
92
110
134
205
329
605

Min bending
radius

(mm)
80
84
91
110
142
197
82
87
97
114
151
208
97
102
112
135
178
247

* or RROHR

99

Instrumentation
cables

TEPLA
Plant & Petrochem Cables

TEPLA C - SA
(PVC/SWA/PVC or
XLPE/SWA/LS0H)
300/500 V

Construction

>
>
>
>
>

>
>
>
>

Applicable
standards

EN 50288-7
EN 50290-2
HD 383
IEC 60332-1
IEC 60332-3A
IEC 60754
IEC 61034

IEC 60332-1
IEC 60332-3C

STANDARD

GOOD

0 C

Conductor
annealed copper wires according to class 2
Insulation
PVC or XLPE
Identification cores
black numbered
Assembly
concentric layers
Overall screen
aluminium/polyester tape 0,024 mm in electrical contact with tinned
annealed copper wires of a total section of 0,5 mm2 polyester tape
0,023 mm
Inner sheath
PVC or LS0H
Armour
galvanized steel wire comply with EN 10244 classe D
Outer sheath
PVC or LS0H
Marking
e. g. : PRYSMIAN year - n x m x csa 300/500 V EN 50288-7

Design guidelines
Specification for insulation and sheath material
Conductors
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

low
r

IEC 60332-1
IEC 60332-3C

100

STANDARD

GOOD

LS0H

-5 C

14 D

70C

160C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Instrumentation cables generally according to EN 50288-7


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3A

TEPLA C - SA 300/500 V (PVC/SWA/PVC or XLPE/SWA/LS0H)

Type*

RE4OHM1FM1*

Diameter
over
insulation

(mm)

Maximum
DC
resistance
at 20 C
(/km)

0,96
0,96
0,96
0,96
0,96
0,96
1,08
1,08
1,08
1,08
1,08
1,08
1,29
1,29
1,29
1,29
1,29
1,29

36,0
36,0
36,0
36,0
36,0
36,0
24,5
24,5
24,5
24,5
24,5
24,5
18,1
18,1
18,1
18,1
18,1
18,1

Cross
section

Diameter of
conductor

(mm2)
2x0,5
3x0,5
4x0,5
7x0,5
12x0,5
24x0,5
2x0,75
3x0,75
4x0,75
7x0,75
12x0,75
24x0,75
2x1,5
3x1,5
4x1,5
7x1,5
12x1,5
24x1,5

Diameter
of armour
wires

Diameter
over
armour

Outer
diameter
approx

Weight
of cable
approx

Min bending
radius

(mm)

Diameter
over
inner
sheath
(mm)

(mm)

(mm)

(mm)

(kg/km)

(mm)

2,16
2,16
2,16
2,16
2,16
2,16
2,28
2,28
2,28
2,28
2,28
2,28
2,49
2,49
2,49
2,49
2,49
2,49

6,6
6,9
7,5
9,1
11,8
16,4
6,8
7,2
8,0
9,5
12,5
17,3
8,0
8,5
9,3
11,2
14,8
20,6

0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
0,9
1,25

8,4
8,7
9,3
10,9
13,6
18,2
8,6
9,0
9,8
11,3
14,3
19,1
9,8
10,3
11,1
13,0
16,6
23,1

10,5
10,8
11,4
13,0
15,9
20,7
10,7
11,1
11,9
13,4
16,6
21,6
11,9
12,4
13,4
15,3
19,2
25,9

229
249
268
344
466
713
240
257
293
366
508
787
296
322
371
484
698
1286

146
151
160
182
223
290
150
155
167
187
233
303
167
173
187
214
268
363

* or RROHRFR

101

TEPLA
Plant & Petrochem Cables

102

technergy

TM

INTEGRATED CABLING SOLUTIONS

Communication cables

103

Communication
cables

TEPLA
Plant & Petrochem Cables

TEPLA COM - S
IBM STANDARD
MIL C 17

Construction

>
>
>
>
>
>

Applicable
standards

104

Conductor
solid or stranded plain copper wire according to MIL C 17
Insulation
polyethylene or polyethylene/air
Outer conductor
tinned or plain copper braid
Fillers
halogen free non hygroscopic compound
Sheath
non contaminating PVC compound, black colour
Marking
e. g. : M17... RG... PRYSMIAN

Coaxial cables with solid insulation or semiair spaced (mose + spiral in


polyethylene tube) for data network, used in radio frequency and power
transmission

technergy

TM

INTEGRATED CABLING SOLUTIONS

> RG coaxial cables


> Cable for high frequency and data transmission

TEPLA COM - S MIL C 17, IBM STANDARD

Type

Inner conductor
type

MG17/155RG58
(RG58C/U)
M17/136RG213
(RG213/U)
M17/29RG59
(RG59B/U)
2RG59B/U
M17/6RG11
(RG11A/U)
M17/30RG62
(RG62A/U)
RX93
TWINAX
P/N IBM
7362211

Legend
R: Plain copper

RS
19x0,18
R
7x0,7
CW
SOLID
R
SOLID
RS
7x0,44
CW
SOLID
RS
R
7x0,3
RS
7x0,3

Insulation

Outer
conductor
type

Outer
diameter
nominal

Cable
weight

Impedance
nominal
value

Max
capac.

Velocity
ratio

Attenuation
at 400 MHz

(mm)

(kg/km)

()

(pF/m)

(%)

(max dB/100 m)

nominal
diameter
(mm)

type

0,9

PE

3,0

RS

5,0

40

50

100

66

49,2

2,25

PE

7,3

10,3

150

50

100

66

6,1

0,58

PE

7,3

6,2

54

75

67

66

29,5

0,58

PE

3,7

6,2x12,3

110

75

67

66

24,6

1,2

PE

7,3

10,3

136

75

67

66

17,0

0,64

PE/A

3,8

6,2

53

93

43

83

26,3

0.4
0,97

PE/A
PE

2,4
2,2

RS
RS

3,9
8,4

24
85

93
100

43
51

83
66

28,0
14,8

RS: Tinned copper

nominal
diameter
(mm)

CW: Copperweld

105

TEPLA
Plant & Petrochem Cables

106

technergy

TM

INTEGRATED CABLING SOLUTIONS

Power cables Low Voltage & Earthing


cables

107

Earthing
cables

TEPLA
Plant & Petrochem Cables

TEPLA E
(PVC)
0,45/0,75 kV

Construction

>
>
>

Applicable
standards

CENELEC HD 21 Design and tests guidelines


IEC 60228
Conductors
IEC 60332-1 Flame retardant
IEC 60332-3A Fire retardant on bunched cables (if required)
IEC 60227/03 Design and tests guidelines

IEC 60332-1
IEC 60332-3A

108

STANDARD

GOOD

0 C

Conductor
bare copper circular flexible, according to class 5 of IEC 60228
Insulation
PVC compound
Marking
e. g. : PRYSMIAN year - n x csa 0,45/0,75 kV

4D

Pb

70C

160C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Earthing cables according to CENELEC HD 21


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA E 0,45/0,75 kV (PVC)

Type

N07V-K

Voltage

Cross
section

Diameter of
conductor

Maximum DC
resistance
at 20 C

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

Current
rating in air
at 30 C

(kV)

(mm2)

(mm)

(/km)

(mm)

(kg/km)

(mm)

(A)

0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75
0,45/0,75

1
1,5
2,5
4
6
10
16
25
35
50
70
95
120
150
185
240

1,3
1,5
1,9
2,5
3,0
3,9
5,0
6,5
7,6
9,3
11,0
12,5
15,4
16,5
18,3
21,5

19,5
13,3
7,98
4,95
3,30
1,91
1,21
0,780
0,554
0,386
0,272
0,206
0,161
0,129
0,106
0,0801

3,2
3,5
4,2
4,8
6,3
7,6
8,8
11,0
12,5
14,5
17,0
19,0
21,0
23,5
26,0
29,5

14
19
30
45
63
100
160
260
350
490
670
890
1200
1400
1800
2400

13
14
17
19
25
30
35
45
50
60
70
80
85
95
100
120

12
16
21
28
36
50
68
89
110
134
171
207
239
275
314
369

109

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA L
(XLPE/PVC or
XLPE/LS0H)

single core

0,6/1 kV

Construction

>
>
>
>

Applicable
standards

IEC 60502-1
IEC 60228
IEC 60332-1
IEC 60332-3 C
IEC 60754
IEC 61034

IEC 60332-1

STANDARD

GOOD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Sheath
PVC compound ST2 quality or LS0H thermoplastic compound ST8 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV
or
e. g. : PRYSMIAN Afumex year - n x csa 0,6/1 kV

Design and tests guidelines


Conductors
Flame retardant
Fire retardant on bunched cables(if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

low
r

EC 60332-1
IEC 60332-3C

110

GOOD

GOOD

LS0H

-5 C

12 D

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA L 0,6/1 kV (XLPE/PVC or XLPE/LS0H) - single core

Type*

RE4M1/RE4R

Voltage

Cross
section

Diameter
of
conductor

Maximum
DC
resistance
at 20 C

Diameter
over
insulation

Outer
diameter
approx

Weight
of cable
approx

Min
bending
radius

Phase
reactance
at 50 Hz
approx (*)

Conductor
short circuit
current
for 1 sec

Current
rating
in air
at 30 C

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(kg/km)

(mm)

(/km)

(kA)

(A)

Current
rating in
ground at
20 C (gr.
therm.res.
1 Km/W;
depth of
laying
0,8 m)
(A)

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

1x1,5
1x2,5
1x4
1x6
1x10
1x16
1x25
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12,0
13,6
15,4
17,2
19,0
21,9
24,2
27,0
30,7
34,8

5,8
6,2
6,8
7,3
8,1
9,1
10,7
11,8
13
14,9
16,7
18,5
20,5
22,3
25,5
27,9
31,0
34,8
39,4

50
60
80
110
150
210
310
400
520
720
980
1220
1490
1840
2380
3000
3800
4870
6300

70
75
80
90
100
110
130
140
155
180
200
220
245
270
305
335
370
420
465

0,14
0,13
0,12
0,11
0,11
0,10
0,10
0,09
0,09
0,09
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9
34,8
43,4
57,8
72,2
90,9

25
33
44
56
77
101
137
167
205
261
323
378
435
504
603
698
811
947
1095

35
46
59
74
97
125
161
192
227
278
333
379
424
478
553
623
703
794
889

( )

* trefoil formation

111

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA L - A
(XLPE/AWA/PVC or
XLPE/AWA/LS0H)

single core

0,6/1 kV

Construction

>
>
>
>
>
>

Applicable
standards

IEC 60502-1
IEC 60228
IEC 60332-1
IEC 60332-3 C
IEC 60754
IEC 61034

IEC 60332-1

STANDARD

EXCELLENT

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Bedding
non hygroscopic compound or LS0H non hygroscopic compound
Armour
aluminium wires
Sheath
PVC compound ST2 quality or LS0H thermoplastic compound ST8 quality
Marking
e. g. : PRYSMIAN - n x csa 0,6/1
or
e. g. : PRYSMIAN Afumex year - n x csa 0,6/1 kV

Design and tests guidelines


Conductors
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

low
r

IEC 60332-1
IEC 60332-3C

112

GOOD

EXCELLENT

LS0H

-5 C

14 D

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA L - A 0,6/1 kV (XLPE/AWA/PVC or XLPE/AWA/LS0H) - single core

Type*

Voltage

(kV)
RE4FM1/RE4FR

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

Phase Conductor Current Current


Cross Diameter Maximum Diameter Diameter Diameter Diameter Outer Weight
Min
DC
section
of
over
over
of
over
diameter
of
bending reactance short rating rating in
conductor resistance insulation extruded armour armour approx cable radius at 50 Hz circuit
in air ground at
( )
at 20 C
approx * current at 30 C 20 C
inner
wires
approx
covering/
for 1 sec
(gr.therm.
taping
res. 1
Km/W;
depth of
laying
0,8 m)
2
(/km)
(/km)
(mm )
(mm)
(mm)
(mm)
(mm)
(mm)
(mm) (kg/km) (mm)
(kA)
(A)
(A)
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,1
15,7
18,4
20,5
22,8
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

10,1
12,0
13,6
15,4
17,2
19,0
21,9
24,2
27,0
30,7
34,8

12,1
14,0
15,6
17,4
19,2
21,0
23,9
26,2
29,4
33,1
37,2

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0

16,1
18,0
19,6
21,4
23,2
25,0
27,9
30,2
33,4
37,1
41,2

19,7
21,6
23,2
25,0
26,8
28,6
31,7
34,2
37,6
41,5
45,8

850
1080
1360
1630
1940
2320
2920
3580
4490
5630
7140

275
305
325
350
375
400
445
480
530
580
640

0,12
0,11
0,10
0,10
0,10
0,10
0,09
0,09
0,09
0,09
0,09

7,4
10,2
13,9
17,5
21,8
26,9
34,8
43,4
57,8
72,2
90,9

230
288
350
404
457
521
611
692
785
889
994

233
284
338
382
424
474
542
600
665
732
796

( )

* trefoil formation

113

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA L
(XLPE/PVC or
XLPE/LS0H)

multi-core

0,6/1 kV

Construction

>
>
>
>
>

Applicable
standards

IEC 60502-1
IEC 60228
IEC 60332-1
IEC 60332-3 C
IEC 60754
IEC 61034

IEC 60332-1

STANDARD

GOOD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Fillers
non hygroscopic compound or LS0H non hygroscopic compound
Sheath
PVC compound ST2 quality or LS0H thermoplastic compound ST8 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV
or
e. g. : PRYSMIAN Afumex year n x csa 0,6/1 kV

Design and tests guidelines


Conductors
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

12 D

low
r

IEC 60332-1
IEC 60332-3C

114

GOOD

GOOD

LS0H

-5 C

12 D

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA L 0,6/1 kV (XLPE/PVC or XLPE/LS0H) - multi-core

Diameter Maximum Diameter


DC
of
over
conductor resistance insulation
at 20 C

Diameter
over
extruded
inner
covering

Outer
diameter
approx

Weight
of
cable
approx

Min
bending
radius

(mm)

(/km)

(mm)

(mm)

(mm)

(kg/km)

(mm)

(/km)

(kA)

(A)

Current
rating in
ground at
20 C
(gr.therm.
res. 1 Km/W;
depth of
laying
0,8 m)
(A)

2x1,5
2x2,5
2x4
2x6
2x10
2x16
2x25
2x35
2x50
2x70
2x95
2x120
2x150
2x185

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12,0
13,6
15,4
17,2
19,0

11,4
13,3
16,5
18,6
21,1
24,9
28,1
32,2
35,9
39,6

9,6
10,4
11,5
12,6
15,1
17,0
20,2
22,3
24,8
28,6
32,2
36,6
40,4
44,3

130
160
210
270
420
580
860
1110
1440
1970
2640
3370
4120
5060

115
125
140
150
180
205
245
270
300
345
385
440
485
530

0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,07
0,07
0,07
0,07
0,07
0,07
0,07

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

28
37
49
63
86
113
152
186
226
287
354
410
468
538

37
49
64
80
106
137
177
213
253
312
374
424
475
536

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

3x1,5
3x2,5
3x4
3x6
3x10
3x16
3x25
3x35
3x50
3x70
3x95
3x120
3x150
3x185

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12,0
13,6
15,4
17,2
19,0

12,2
14,2
17,8
20,0
22,7
26,8
30,2
34,7
38,6
42,6

10,1
10,9
12,1
13,3
15,9
17,9
21,5
23,7
26,4
30,7
34,3
39,0
43,3
47,5

150
190
250
330
510
720
1080
1400
1830
2550
3430
4360
5350
6600

120
130
145
160
190
215
260
285
315
370
410
470
520
570

0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,07
0,07
0,07
0,07
0,07
0,07
0,07

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

23
31
41
53
72
96
129
158
193
245
302
351
399
460

31
41
53
67
88
114
149
179
212
261
314
355
397
449

RE4OM1/RE4OR

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

4x1,5
4x2,5
4x4
4x6
4x10
4x16
4x25
4x35
4x50
4x70
4x95
4x120
4x150
4x185

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12,0
13,6
15,4
17,2
19,0

13,5
15,8
19,8
22,3
25,3
29,9
34,4
38,7
43,0
47,5

10,9
11,8
13,1
14,4
17,2
19,5
23,5
26,0
29,2
34,0
38,7
43,4
47,9
53,0

180
220
300
400
630
890
1340
1760
2330
3250
4430
5580
6820
8480

130
140
160
175
205
235
280
310
350
410
465
520
575
635

0,11
0,10
0,09
0,09
0,09
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

23
31
41
53
72
96
129
158
193
245
302
351
399
460

31
41
53
67
88
114
149
179
212
261
314
355
397
449

RE4OM1/RE4OR

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

3x35/25
3x50/25
3x70/35
3x95/70
3x120/70
3x150/95
3x185/95
3x240/150
3x300/150

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601

7,8
7,8
8,8
10,1
12,0
13,6
13,6
17,2
17,2

21,7
24,1
28,3
32,6
36,9
41,2
44,7
52,5
56,8

25,4
27,8
32,2
36,9
41,4
46,1
49,8
58,2
62,9

1650
2060
2860
3920
4980
6210
7420
9960
12040

305
335
385
445
495
555
600
700
755

0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

5,2
7,4
10,2
13,9
17,5
21,8
26,9
34,8
43,4

158
193
245
302
351
399
460
546
626

179
212
261
314
355
397
449
520
584

Voltage

Cross
section

(kV)

(mm2)

RE4OM1/RE4OR

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

RE4OM1/RE4OR

Type

Phase
Conductor Current
reactance short rating
at 50 Hz
circuit
in air
approx
current at 30 C
for 1 sec

115

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA L - A
(XLPE/SWA/PVC or
XLPE/SWA/LS0H)

multi-core

0,6/1 kV

Construction

>
>
>
>
>
>

Applicable
standards

IEC 60502-1
IEC 60228
IEC 60332-1
IEC 60332-3 C
IEC 60754
IEC 61034

IEC 60332-1

STANDARD

EXCELLENT

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Inner covering
non hygroscopic compound or LS0H non hygroscopic compound
Armour
galvanized steel wire
Sheath
PVC compound ST2 quality or LS0H thermoplastic compound ST8 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV
or
e. g. : PRYSMIAN Afumex year - n x csa 0,6/1kV

Design and tests guidelines


Conductors
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

low
r

IEC 60332-1
IEC 60332-3C

116

GOOD

EXCELLENT

LS0H

-5 C

14 D

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-1


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA L - A 0,6/1 kV (XLPE/SWA/PVC or XLPE/SWA/LS0H) - multi-core

Type

Voltage

(kV)

Phase Conductor Current Current


Cross Diameter Maximum Diameter Diameter Diameter Diameter Outer
Weight
Min
DC
section
of
over
over
of
over diameter
of
bending reactance short rating rating in
conductor resistance insulation extruded armour armour approx
cable
radius at 50 Hz circuit
in air ground at
at 20 C
approx current at 30 C
inner
wires
approx
20 C
covering
for 1 sec
(gr.therm.
res. 1
Km/W;
depth of
laying
0,8 m)
2
(/km)
(/km)
(mm )
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(kg/km)
(mm)
(kA)
(A)
(A)

RE4OFM1/RE4OFR 0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

2x1,5
2x2,5
2x4
2x6
2x10
2x16
2x25
2x35
2x50
2x70
2x95
2x120
2x150
2x185

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12,0
13,6
15,4
17,2
19,0

8,1
8,8
9,9
11,0
12,4
14,3
17,5
19,6
22,1
25,9
29,5
33,1
36,7
40,8

0,8
0,8
0,8
0,8
1,3
1,3
1,6
1,6
1,6
1,6
2,0
2,0
2,0
2,5

9,7
10,4
11,5
12,6
14,9
16,8
20,7
22,8
25,3
29,1
33,5
37,1
40,7
45,8

13,3
14,0
15,1
16,2
18,5
20,4
24,3
26,4
28,9
33,1
37,7
41,5
45,3
50,8

330
370
440
530
800
1010
1510
1820
2230
2930
3990
4810
5690
7300

185
195
210
225
260
285
340
370
405
465
530
580
635
710

0,1
0,09
0,09
0,08
0,08
0,08
0,08
0,07
0,07
0,07
0,07
0,07
0,07
0,07

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

29
38
50
64
88
116
157
191
231
291
358
414
469
538

36
47
62
78
105
136
177
212
252
308
369
419
468
526

RE4OFM1/RE4OFR 0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

3x1,5
3x2,5
3x4
3x6
3x10
3x16
3x25
3x35
3x50
3x70
3x95
3x120
3x150
3x185

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12,0
13,6
15,4
17,2
19,0

8,5
9,4
10,5
11,7
13,2
15,2
18,8
21,0
23,7
28,2
31,6
35,5
39,8
43,8

0,8
0,8
0,8
0,8
1,3
1,3
1,6
1,6
1,6
2,0
2,0
2,0
2,5
2,5

10,1
11,0
12,1
13,3
15,7
17,7
22,0
24,2
26,9
32,2
35,6
39,5
44,8
48,8

13,7
14,6
15,7
16,9
19,3
21,3
25,6
27,8
30,7
36,2
40,0
44,1
49,8
54,0

360
410
500
600
910
1170
1760
2160
2700
3850
4880
5900
7550
9010

190
205
220
235
270
300
360
390
430
505
560
620
695
755

0,1
0,09
0,09
0,08
0,08
0,08
0,08
0,07
0,07
0,07
0,07
0,07
0,07
0,07

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

23
31
41
53
72
96
129
158
193
245
302
351
399
460

31
41
53
67
88
114
149
179
212
259
310
353
392
440

RE4OFM1/RE4OFR 0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

4x1.5
4x2.5
4x4
4x6
4x10
4x16
4x25
4x35
4x50
4x70
4x95
4x120
4x150
4x185

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12,0
13,6
15,4
17,2
19,0

9,3
10,2
11,6
12,9
14,5
16,8
20,8
23,3
26,3
31,3
35,2
39,9
44,2
48,7

0,8
0,8
0,8
1,3
1,3
1,6
1,6
1,6
1,6
2,0
2,0
2,5
2,5
2,5

10,9
11,8
13,2
15,4
17,0
20,0
24,0
26,5
29,5
35,3
39,2
44,9
49,2
53,7

14,5
15,4
16,8
19,0
20,6
23,6
27,6
30,3
33,5
39,7
43,8
49,9
54,4
59,3

400
460
570
830
1060
1510
2080
2610
3270
4680
5970
7770
9240
11090

205
215
235
265
290
330
385
425
470
555
615
700
760
830

0,11
0,1
0,1
0,09
0,09
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

23
31
41
53
72
96
129
158
193
245
302
351
399
460

31
41
53
67
88
114
149
179
212
259
310
353
392
440

RE4OFM1/RE4OFR 0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

3x35/25
3x50/25
3x70/35
3x95/70
3x120/70
3x150/95
3x185/95
3x240/150
3x300/150

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601

7,8
7,8
8,8
10,1
12,0
13,6
13,6
17,2
17,2

22,7
25,1
29,7
33,4
37,7
42,4
45,9
53,7
58,0

1,6
1,6
2,0
2,0
2,0
2,5
2,5
2,5
2,5

25,9
28,3
33,7
37,4
41,7
47,4
50,9
58,7
63,0

29,5
32,1
37,9
41,8
46,5
52,4
56,3
64,5
69,0

2460
2960
4220
5350
6610
8510
9920
12840
15110

410
450
530
585
650
735
790
905
965

0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

5,2
7,4
10,2
13,9
17,5
21,8
26,9
34,8
43,4

158
193
245
302
351
399
460
539
618

179
212
259
310
353
392
440
505
567

117

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA L - (AR)
(XLPE/PSA/PVC)

single core

0,6/1 kV

Construction

>
>
>
>
>

Applicable
standards

IEC 60502-1 Design and tests guidelines


IEC 60228
Conductors
IEC 60332-1 Flame retardant
Prysmian document GPD-001 for PSA layer

IEC 60332-1

118

STANDARD

EXCELLENT

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Mechanical protective layer
PSA (AIR BAG)
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV

12 D

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA L - (AR) 0,6/1 kV (XLPE/PSA/PVC) - single core

Type*

RE4(AR)R

Diameter Maximum Diameter Approx Diameter


Outer
DC
of
over
thickness
over
diameter
conductor resistance insulation
of
PSA
approx
at 20 C
PSA

Weight
of
cable
approx

Phase
Min
Conductor
bending reactance short at 50 Hz
radius
circuit
approx (*) current
for 1 sec

Voltage

Cross
section

Current
rating
in air
at 30 C

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(kg/km)

(mm)

(kg/km)

(mm)

(/km)

(kA)

(A)

Current
rating in
ground at
20 C
(gr.therm.
res. 1
Km/W;
depth of
laying
0,8 m)
(A)

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,1
15,7
18,4
20,5
22,8
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

10,1
12,0
13,6
15,4
17,2
19,0
21,9
24,2
27,0
30,7
34,8

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0

14,1
16,0
17,6
19,4
21,1
23,1
25,7
28,2
31,0
34,7
38,8

16,9
18,8
20,6
22,3
24,2
26,4
29,2
31,7
34,9
38,8
43,1

1018
1409
1912
2379
2913
3624
4712
5861
7452
9549
12338

202
225
247
267
290
317
350
380
419
465
517

0,105
0,100
0,096
0,093
0,093
0,092
0,088
0,086
0,086
0,084
0,082

7,4
10,2
13,9
17,5
21,8
26,9
34,8
43,4
>50
>50
>50

205
260
319
372
427
494
589
680
789
918
1062

216
266
319
364
409
463
537
607
688
779
877

( )

* trefoil formation

119

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA L - (AR)
(XLPE/PSA/PVC)

multi-core

0,6/1 kV

Construction

>
>
>
>
>
>

Applicable
standards

IEC 60502-1 Design and tests guidelines


IEC 60228
Conductors
IEC 60332-1 Flame retardant
Prysmian document GPD-001 for PSA layer

IEC 60332-1

120

STANDARD

EXCELLENT

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Fillers
non hygroscopic compound
Mechanical protective layer
PSA AIR BAGTM
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV

12 D

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA L - (AR) 0,6/1 kV (XLPE/PSA//PVC) - multi-core

Type

Voltage

Cross Diameter Maximum Diameter Diameter Approx Diameter Outer


DC
section
of
over
under thickness
over
diameter
conductor resistance insulation
PSA
of
PSA
approx
at 20 C
approx
PSA
approx

Weight
of
cable
approx

Phase Conductor Current Current


Min
bending reactance short rating rating in
radius at 50 Hz circuit
in air ground at
approx current at 30 C
20 C
for 1 sec
(gr.therm.
res. 1
Km/W;
depth of
laying
0,8 m)
(/km)
(mm)
(kA)
(A)
(A)

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg/km)

RE4O(AR)R 0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

2x1,5
2x2,5
2x4
2x6
2x10
2x16
2x25
2x35
2x50
2x70
2x95
2x120
2x150
2x185

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12,0
13,6
15,4
17,2
19

8,1
8,9
10,0
11,0
12,4
14,3
17,6
19,7
22,2
26,0
29,2
32,7
36,2
40,2

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,5

12,1
12,9
14,0
15,0
16,4
18,3
21,6
23,7
26,2
30,0
33,2
36,7
40,2
45,2

15,6
16,4
17,4
18,5
19,9
21,8
25,1
27,2
29,7
33,5
37,1
40,8
44,4
49,6

262
300
361
430
545
717
1018
1282
1620
2183
2872
3553
4311
5354

187
196
209
222
239
262
301
326
356
402
445
489
533
595

0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,07
0,07
0,07
0,07
0,07
0,07
0,07

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

25
34
46
58
78
105
141
173
210
266
328
380
434
500

31
42
55
68
90
126
164
197
234
289
346
392
439
496

RE4O(AR)R 0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

3x1,5
3x2,5
3x4
3x6
3x10
3x16
3x25
3x35
3x50
3x70
3x95
3x120
3x150
3x185

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12,0
13,6
15,4
17,2
19,0

8,6
9,4
10,6
11,7
13,2
15,3
18,8
21,1
23,8
27,9
31,3
35,1
38,9
43,2

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,5
2,5

12,6
13,4
14,6
15,7
17,2
19,3
22,8
25,1
27,8
31,9
35,3
39,1
43,9
48,2

16,1
16,9
18,1
19,2
20,7
22,8
26,3
28,6
31,3
35,6
39,2
43,1
48,3
52,8

284
331
405
491
640
860
1241
1584
2026
2774
3669
4551
5612
6912

193
203
217
231
248
273
316
343
375
427
470
518
579
633

0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,07
0,07
0,07
0,07
0,07
0,07
0,07

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

22
29
38
49
66
88
120
148
179
228
280
325
371
428

27
35
46
58
76
106
137
166
197
242
290
329
368
416

RE4O(AR)R 0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

4x1.5
4x2.5
4x4
4x6
4x10
4x16
4x25
4x35
4x50
4x70
4x95
4x120
4x150
4x185

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12,0
13,6
15,4
17,2
19,0

9,4
10,3
11,6
12,9
14,6
16,9
20,9
23,4
26,4
31,0
34,9
39,1
43,3
48,1

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,5
2,5
2,5

13,4
14,3
15,6
16,9
18,6
20,9
24,9
27,4
30,4
35,0
38,9
44,1
48,3
53,1

16,8
17,8
19,1
20,4
22,1
24,4
28,3
30,9
34,1
38,8
42,9
48,5
52,9
58,1

317
374
468
574
763
1043
1522
1960
2537
3488
4635
5836
7090
8774

202
213
229
245
265
292
340
370
409
466
515
582
635
697

0,11
0,10
0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

22
29
38
49
66
88
120
148
179
228
280
325
371
428

27
35
46
58
76
106
137
166
197
242
290
329
368
416

RE4O(AR)R 0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

3x35/25
3x50/25
3x70/35
3x95/70
3x120/70
3x150/95
3x185/95
3x240/150
3x300/150

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601

7,8
7,8
8,8
10,1
12,0
13,6
13,6
17,2
17,2

22,8
25,2
29,4
33,1
37,3
41,5
45,3
51,1
56,7

2,0
2,0
2,0
2,0
2,0
2,5
2,5
2,5
3,0

26,8
29,2
33,4
37,1
41,3
46,5
50,3
56,1
62,7

30,3
32,7
37,0
41,1
45,6
51,1
55,1
61,3
68,2

1849
2273
3101
4127
5206
6518
7780
9993
12425

364
392
444
493
547
613
661
735
819

0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

5,2
7,4
10,2
13,9
17,5
21,8
26,9
34,8
43,4

148
179
228
280
325
371
428
507
584

166
197
242
290
329
368
416
481
542

121

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA L - L
(XLPE/Pb/PVC)

single core

0,6/1 kV

Construction

>
>
>
>
>

Applicable
standards

EC 60332-1

122

EXCELLENT

STANDARD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Metallic sheath
lead alloy
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV

IEC 60502-1
IEC 60228
IEC 60332-1

Design and tests guidelines


Conductors
Flame retardant

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

16 D

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA L - L 0,6/1 kV (XLPE/Pb/PVC) - single core

Type*

RE4LR

Voltage

Cross
section

Diameter
of
conductor

Maximum
DC
resistance
at 20 C

Diameter
under
lead
sheath

Outer
diameter
approx

Weight
of
cable
approx

Min
bending
radius

Phase
Conductor
reactance
short at 50 Hz
circuit
( )
approx *
current
for 1 sec

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(kg/km)

(mm)

(/km)

(kA)

(A)

Current
rating in
ground
at 20 C
(gr.therm.
res. 1
Km/W;
depth of
laying
0,8 m)
(A)

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,2
15,8
18,2
20,5
22,9
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

10,1
12,0
13,6
15,4
17,1
19,1
21,7
24,2
27,0
30,7
34,8

15,5
17,6
19,2
21,1
23,2
25,4
28,2
31,1
34,3
38,6
43,1

1454
1925
2482
3026
3701
4566
5780
9461
11940
15232
14577

248
282
307
338
371
406
451
498
549
618
690

0,100
0,096
0,092
0,090
0,090
0,089
0,087
0,085
0,085
0,083
0,082

7,4
10,2
13,9
17,5
21,8
26,9
34,8
43,4
>50
>50
>50

220
279
342
398
457
529
628
722
839
970
1113

232
283
338
383
429
485
560
640
709
796
887

Current
rating
in air
at 30 C

( )

* trefoil formation

123

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA L - L
(XLPE/Pb/PVC)

multi-core

0,6/1 kV

Construction

>
>
>
>
>
>

Applicable
standards

IEC 60332-1

124

EXCELLENT

STANDARD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Fillers
non hygroscopic compound
Metallic sheath
lead alloy
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV

IEC 60502-1
IEC 60228
IEC 60332-1

Design and tests guidelines


Conductors
Flame retardant

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

16 D

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA L - L 0,6/1 kV (XLPE/Pb/PVC) - multi-core

Type

Diameter Maximum Diameter Diameter


DC
of
over
under
conductor resistance insulation
lead
at 20 C
sheath

Voltage

Cross
section

(kV)

(mm2)

(mm)

(/km)

(mm)

RE4OLR

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

2x1,5
2x2,5
2x4
2x6
2x10
2x16
2x25
2x35
2x50
2x70
2x95
2x120
2x150
2x185

1,6
2,0
2,5
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,2
15,8

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

RE4OLR

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

3x1,5
3x2,5
3x4
3x6
3x10
3x16
3x25
3x35
3x50
3x70
3x95
3x120
3x150
3x185

1,6
2,0
2,5
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,2
15,8

RE4OLR

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

4x1,5
4x2,5
4x4
4x6
4x10
4x16
4x25
4x35
4x50
4x70
4x95
4x120
4x150
4x185

RE4OLR

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

3x35/25
3x50/25
3x70/35
3x95/70
3x120/70
3x150/95
3x185/95
3x240/150
3x300/150

Phase
Conductor
reactance short at 50 Hz
circuit
approx
current
for 1 sec

Outer
diameter
approx

Weight
of
cable
approx

Min
bending
radius

Current
rating
in air
at 30 C

(mm)

(mm)

(kg/km)

(mm)

(/km)

(kA)

(A)

Current
rating in
ground at
20 C
(gr.therm.
res. 1
Km/W;
depth of
laying
0,8 m)
(A)

3,1
3,4
4,0
4,5
5,2
6,2
7,8
8,9
10,1
12,0
13,6
15,4
17,1
19,1

8,1
8,9
10
11,1
13,5
15,4
18,7
20,8
23,3
27,1
30,3
34,3
37,8
42,2

14,2
15,0
16,1
17,2
19,5
21,4
24,7
26,8
29,5
33,7
37,5
41,9
45,8
50,6

604
672
772
881
1147
1397
1834
2184
2726
3582
4548
5644
6757
8229

228
240
257
275
313
343
396
429
473
540
600
671
733
810

0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,07
0,07
0,07
0,07
0,07
0,07
0,07

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

30
39
51
65
89
118
158
193
233
293
362
417
474
545

37
48
63
79
104
136
176
212
252
309
372
421
472
531

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,1
3,4
4,0
4,5
5,2
6,2
7,8
8,9
10,1
12,0
13,6
15,4
17,1
19,1

8,6
9,5
10,6
11,8
14,3
16,3
19,9
22,2
24,8
28,9
32,4
36,7
40,9
45,2

14,7
15,5
16,7
17,9
20,3
22,4
25,9
28,4
31,5
36,0
39,8
44,7
49,3
54,2

646
724
842
971
1275
1581
2107
2632
3321
4378
5587
6949
8401
10186

235
248
267
286
325
358
415
454
504
576
637
715
788
867

0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,07
0,07
0,07
0,07
0,07
0,07
0,07

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

25
33
43
55
75
99
134
164
198
251
307
354
402
460

31
41
53
66
88
114
148
178
211
260
310
351
391
440

1,6
2,0
2,5
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,2
15,8

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,1
3,4
4,0
4,5
5,2
6,2
7,8
8,9
10,1
12,0
13,6
15,4
17,1
19,1

9,4
10,4
11,7
13
15,6
17,9
21,9
24,4
27,4
32
36,5
41,1
45,3
50,1

15,5
16,4
17,7
19,0
21,7
24,0
28,2
30,7
34,5
39,5
44,6
49,5
54,3
59,9

709
802
945
1100
1455
1831
2560
3110
4071
5386
7017
8637
10385
12782

247
262
283
304
347
383
450
491
552
632
713
791
868
958

0,11
0,10
0,09
0,09
0,09
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

25
33
43
55
75
99
134
164
198
251
307
354
402
460

31
41
53
66
88
114
148
178
211
260
310
351
391
440

7,0
8,1
9,8
11,4
12,9
14,2
15,8
18,2
20,5

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601

8,9
10,1
12,0
13,6
15,4
17,1
19,1
21,7
24,2

23,9
26,3
30,4
34,7
39
43,5
47,3
53,2
58,7

30,1
32,9
37,7
42,3
46,9
52,3
56,5
62,9
69,3

2971
3632
4795
6234
7713
9639
11345
14195
17417

482
526
603
677
751
836
904
1007
1108

0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

5,2
7,4
10,2
13,9
17,5
21,8
26,9
34,8
43,4

164
198
251
307
354
402
460
541
615

178
211
260
310
351
391
440
506
565

125

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA L - LA
(XLPE/Pb/AWA/PVC)

single core

0,6/1 kV

Construction

>
>
>
>
>
>
>

Applicable
standards

IEC 60332-1

126

EXCELLENT

EXCELLENT

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Metallic sheath
Lead alloy
Separation sheath
PVC compound ST2 quality
Armour
aluminium wires
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV

IEC 60502-1
IEC 60228
IEC 60332-1

Design and tests guidelines


Conductors
Flame retardant

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

16 D

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA L - LA 0,6/1 kV (XLPE/Pb/AWA//PVC) - single core

Type*

Voltage

RE4LRFR

Cross Diameter Maximum Diameter Diameter Diameter Diameter Outer


DC
section
of
over
over
of
over
diameter
conductor resistance insulation extruded armour armour approx
at 20 C
inner
wires
sheath

Weight
of
cable
approx

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg/km)

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,1
15,7
18,4
20,5
22,8
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

10,1
12,0
13,6
15,4
17,2
19,0
21,9
24,2
27,0
30,7
34,8

14,4
16,3
17,9
19,6
21,6
23,8
26,5
29,2
32,4
36,4
40,8

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,5
2,5

18,4
20,3
21,9
23,6
25,6
27,8
30,5
33,2
36,4
41,5
45,9

22,4
24,3
25,9
27,6
29,8
32,2
35,0
37,8
41,5
46,8
51,6

1783
2282
2864
3425
4137
5050
6313
10043
12615
16130
15594

Phase Conductor Current Current


Min
bending reactance short rating rating in
radius at 50 Hz circuit
in air ground at
( )
approx * current at 30 C
20 C
for 1 sec
(gr.therm.
res. 1
Km/W;
depth of
laying
0,8 m)
(/km)
(mm)
(kA)
(A)
(A)

359
389
415
442
476
515
560
605
664
749
825

0,26
0,26
0,25
0,25
0,25
0,25
0,24
0,24
0,24
0,24
0,23

7,4
10,2
13,9
17,5
21,8
26,9
34,8
43,4
>50
>50
>50

241
299
362
415
470
534
621
700
787
865
956

234
284
336
379
420
468
532
587
645
686
738

( )

* trefoil formation

127

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA L - LA
(XLPE/Pb/SWA/PVC)

multi-core

0,6/1 kV

Construction

>
>
>
>
>
>
>
>

Applicable
standards

IEC 60332-1

128

EXCELLENT

EXCELLENT

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Fillers
non hygroscopic compound
Metallic sheath
lead alloy
Separation sheath
PVC compound ST2 quality
Armour
galvanized steel wires
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV

IEC 60502-1
IEC 60228
IEC 60332-1

Design and tests guidelines


Conductors
Flame retardant

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

16 D

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA L - LA 0,6/1 kV (XLPE/Pb/SWA//PVC) - multi-core

Type

Voltage

Cross Diameter Maximum Diameter Diameter Diameter Diameter Outer


DC
section
of
over
over
of
over
diameter
conductor resistance insulation extruded armour armour approx
at 20 C
inner
wires
sheath

Weight
of
cable
approx

Phase Conductor Current Current


Min
bending reactance short rating rating in
radius at 50 Hz circuit
in air
ground
approx current at 30 C at 20 C
for 1 sec
(gr.therm.
res. 1
Km/W;
depth of
laying
0,8 m)
(/km)
(mm)
(kA)
(A)
(A)

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg/km)

RE4OLRFR

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

2x1,5
2x2,5
2x4
2x6
2x10
2x16
2x25
2x35
2x50
2x70
2x95
2x120
2x150
2x185

1,6
2,0
2,5
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,2
15,8

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,1
3,4
4,0
4,5
5,2
6,2
7,8
8,9
10,1
12,0
13,6
15,4
17,1
19,1

12,4
13,2
14,2
15,3
17,7
19,6
22,9
25
27,9
31,9
35,5
39,9
43,6
48,4

1,25
1,25
1,25
1,25
1,6
1,6
1,6
1,6
2,0
2,0
2,0
2,5
2,5
2,5

14,9
15,7
16,7
17,8
20,9
22,8
26,1
28,2
31,9
35,9
39,5
44,9
48,6
53,4

18,0
18,7
19,8
20,9
24,0
25,9
29,2
31,4
35,3
39,7
43,4
49,0
53,1
58,0

986
1075
1199
1341
1802
2107
2652
3087
3986
5029
6140
7862
9176
10938

287
300
317
334
383
414
467
503
565
634
694
784
849
928

0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,07
0,07
0,07
0,07
0,07
0,07
0,07

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

30
39
51
65
89
118
158
193
233
293
362
417
474
545

37
48
63
79
104
136
176
212
252
309
372
421
472
531

RE4OLRFR

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

3x1,5
3x2,5
3x4
3x6
3x10
3x16
3x25
3x35
3x50
3x70
3x95
3x120
3x150
3x185

1,6
2,0
2,5
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,2
15,8

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,1
3,4
4,0
4,5
5,2
6,2
7,8
8,9
10,1
12,0
13,6
15,4
17,1
19,1

12,9
13,7
14,9
16
18,5
20,6
24,1
26,6
29,7
34,1
37,9
42,5
47
51,7

1,25
1,25
1,25
1,25
1,6
1,6
1,6
1,6
2,0
2,0
2,5
2,5
2,5
2,5

15,4
16,2
17,4
18,5
21,7
23,8
27,3
29,8
33,7
38,1
42,9
47,5
52,0
56,7

18,4
19,3
20,4
21,6
24,8
26,8
30,6
33,0
37,2
41,9
47,1
51,8
56,7
61,6

1039
1140
1281
1443
1966
2326
2990
3589
4666
5912
7732
9300
11021
13074

295
308
327
345
396
429
489
528
596
670
753
828
907
985

0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,07
0,07
0,07
0,07
0,07
0,07
0,07

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

25
33
43
55
75
99
134
164
198
251
307
354
402
460

31
41
53
66
88
114
148
178
211
260
310
351
391
440

RE4OLRFR

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

4x1.5
4x2.5
4x4
4x6
4x10
4x16
4x25
4x35
4x50
4x70
4x95
4x120
4x150
4x185

1,6
2,0
2,5
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,2
15,8

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,1
3,4
4,0
4,5
5,2
6,2
7,8
8,9
10,1
12,0
13,6
15,4
17,1
19,1

13,7
14,6
15,9
17,2
19,9
22,2
26,4
29,1
32,6
37,4
42,3
47,3
51,9
57,3

1,25
1,25
1,25
1,6
1,6
1,6
1,6
2,0
2,0
2,0
2,5
2,5
2,5
2,5

16,2
17,1
18,4
20,4
23,1
25,4
29,6
33,1
36,6
41,4
47,3
52,3
56,9
62,3

19,2
20,2
21,5
23,5
26,1
28,4
32,8
36,6
40,4
45,4
51,6
56,9
61,8
67,4

1124
1240
1417
1737
2182
2629
3516
4441
5547
7063
9367
11299
13299
15969

307
322
343
375
418
455
524
586
647
726
825
910
989
1079

0,11
0,10
0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

25
33
43
55
75
99
134
164
198
251
307
354
402
460

31
41
53
66
88
114
148
178
211
260
310
351
391
440

RE4OLRFR

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

3x35/25
3x50/25
3x70/35
3x95/70
3x120/70
3x150/95
3x185/95
3x240/150
3x300/150

7,0
8,1
9,8
11,4
12,9
14,2
15,8
18,2
20,5

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601

8,9
10,1
12,0
13,6
15,4
17,1
19,1
21,7
24,2

28,5
31,1
35,6
40,3
44,9
50
54,1
60,3
66,6

2,0
2,0
2,0
2,5
2,5
2,5
2,5
2,5
3,15

32,5
35,1
39,6
45,3
49,9
55,0
59,1
65,3
72,9

35,9
38,7
43,5
49,6
54,4
59,9
64,1
70,6
78,7

4259
5033
6387
8514
10239
12460
14353
17551
22612

574
619
697
793
870
958
1025
1130
1260

0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

5,2
7,4
10,2
13,9
17,5
21,8
26,9
34,8
43,4

164
198
251
307
354
402
460
541
615

178
211
260
310
351
391
440
506
565

129

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA L - D
(XLPE/DRYLAM/PVC)

single core

0,6/1 kV

Construction

>
>
>

>
>

Applicable
standards

IEC 60502-1 Design and tests guidelines


IEC 60228
Conductors
IEC 60332-1 Flame retardant
Prysmian document GPD-003 for chemical moisture barrier

IEC 60332-1

130

EXCELLENT

STANDARD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Chemical moisture barrier
longitudinally applied Al tape bonded with extruded chemical resistant
polymeric layer
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV

14 D

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA L - D 0,6/1 kV (XLPE/DRYLAM/PVC) - single core

Type*

RE4H5R4R

Voltage

Cross
section

Diameter
of
conductor

Maximum
DC
resistance
at 20 C

Diameter
Drylam

Outer
diameter
approx

Weight
of
cable
approx

Min
bending
radius

Phase
Conductor
reactance
short at 50 Hz
circuit
( )
approx *
current
for 1 sec

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(kg/km)

(mm)

(/km)

(kA)

(A)

Current
rating in
ground at
20 C
(gr.therm.
res. 1
Km/W;
depth of
laying
0,8 m)
(A)

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,1
15,7
18,4
20,5
22,8
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

10,1
12
13,6
15,4
17,2
19
21,9
24,2
27
30,7
34,8

15,6
17,7
19,3
21,2
23,1
25,1
27,9
30,6
33,6
37,6
42,0

1042
1440
1936
2414
2954
3655
4750
8224
10455
13427
12400

218
247
270
296
324
352
390
428
470
527
588

0,12
0,11
0,10
0,10
0,10
0,10
0,09
0,09
0,09
0,09
0,09

7,4
10,2
13,9
17,5
21,8
26,9
34,8
43,4
>50
>50
>50

214
271
332
387
444
512
609
702
812
941
1082

223
273
327
372
417
471
546
614
694
781
874

Current
rating
in air
at 30 C

( )

* trefoil formation

131

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA L - D
(XLPE/DRYLAM/PVC)

multi-core

0,6/1 kV

Construction

>
>
>
>

>
>

Applicable
standards

IEC 60502-1 Design and tests guidelines


IEC 60228
Conductors
IEC 60332-1 Flame retardant
Prysmian document GPD-003 for chemical moisture barrier

IEC 60332-1

132

EXCELLENT

STANDARD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Insulation
XLPE compound
Fillers
non hygroscopic compound
Chemical moisture barrier
longitudinally applied Al tape bonded with extruded chemical resistant
polymeric layer
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 0,6/1 kV

14 D

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA L - D 0,6/1 kV (XLPE/DRYLAM/PVC) - multi-core

Type

Diameter Maximum Diameter Diameter


DC
of
over
under
conductor resistance insulation Drylam
at 20 C

Voltage

Cross
section

(kV)

(mm2)

(mm)

(/km)

(mm)

RE4OH5R4R

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

2x1,5
2x2,5
2x4
2x6
2x10
2x16
2x25
2x35
2x50
2x70
2x95
2x120
2x150
2x185

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

RE4OH5R4R

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

3x1,5
3x2,5
3x4
3x6
3x10
3x16
3x25
3x35
3x50
3x70
3x95
3x120
3x150
3x185

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7

RE4OH5R4R

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

4x1.5
4x2.5
4x4
4x6
4x10
4x16
4x25
4x35
4x50
4x70
4x95
4x120
4x150
4x185

RE4OH5R4R

0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1

3x35/25
3x50/25
3x70/35
3x95/70
3x120/70
3x150/95
3x185/95
3x240/150
3x300/150

Phase
Conductor
reactance short at 50 Hz
circuit
approx
current
for 1 sec

Outer
diameter
approx

Weight
of
cable
approx

Min
bending
radius

Current
rating
in air
at 30 C

(mm)

(mm)

(kg/km)

(mm)

(/km)

(kA)

(A)

Current
rating in
ground
at 20 C
(gr.therm.
res. 1
Km/W;
depth of
laying
0,8 m)
(A)

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12
13,6
15,4
17,2
19,0

8,1
8,9
10,0
11,1
12,5
14,2
17,7
19,7
22,3
26,5
29,3
33,0
36,6
40,4

14,4
15,2
16,3
17,3
18,7
20,6
23,9
26,0
28,5
32,4
35,8
39,7
43,6
47,9

267
303
364
432
544
711
1001
1255
1590
2146
2800
3469
4225
5205

202
212
228
243
262
288
334
363
398
454
501
555
610
671

0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,07
0,07
0,07
0,07
0,07
0,07
0,07

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

28
37
48
62
85
113
151
185
223
281
347
400
455
523

36
47
61
77
102
133
173
208
247
303
366
414
464
522

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12
13,6
15,4
17,2
19

8,5
9,3
10,6
11,7
13,2
15,2
18,8
21,0
24,0
28,1
31,6
35,5
39,4
43,2

14,9
15,7
16,8
18,0
19,5
21,5
25,1
27,3
30,2
34,5
38,3
42,2
46,6
51,1

290
337
408
494
641
857
1230
1565
2023
2750
3648
4511
5524
6804

208
220
236
252
273
301
351
383
423
483
536
591
652
715

0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,07
0,07
0,07
0,07
0,07
0,07
0,07

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

24
31
41
52
72
95
128
157
190
240
294
339
385
441

30
40
52
64
86
112
145
175
207
255
305
345
384
432

1,6
2,0
2,6
3,1
3,8
4,7
6,0
7,0
8,1
9,8
11,4
12,9
14,3
15,7

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991

3,0
3,4
4,0
4,5
5,2
6,1
7,8
8,8
10,1
12,0
13,6
15,4
17,2
19,0

9,3
10,2
11,7
12,9
14,6
16,8
20,9
23,3
26,6
31,2
35,1
39,5
43,8
48,2

15,7
16,6
17,9
19,2
20,8
23,1
27,1
29,6
33,0
38,0
42,0
46,8
51,2
56,4

324
379
473
578
765
1041
1510
1942
2535
3481
4616
5774
7027
8669

220
232
250
269
292
324
379
415
462
531
588
655
717
789

0,11
0,10
0,10
0,09
0,09
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

0,3
0,4
0,6
0,9
1,5
2,4
3,7
5,2
7,4
10,2
13,9
17,5
21,8
26,9

24
31
41
52
72
95
128
157
190
240
294
339
385
441

30
40
52
64
86
112
145
175
207
255
305
345
384
432

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601

7,8
7,8
8,8
10,1
12,0
13,6
13,6
17,2
17,2

22,9
25,2
29,4
33,1
37,6
41,7
45,5
51,8
57,3

29,1
31,7
36,0
40,2
44,7
49,2
53,4
60,0
65,7

1831
2275
3083
4114
5178
6421
7683
9929
12218

407
443
504
563
625
689
747
840
920

0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08
0,08

5,2
7,4
10,2
13,9
17,5
21,8
26,9
34,8
43,4

157
190
240
294
339
385
441
519
590

175
207
255
305
345
384
432
497
555

133

TEPLA
Plant & Petrochem Cables

134

technergy

TM

INTEGRATED CABLING SOLUTIONS

Power cables Medium Voltage cables

135

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA M - S
(XLPE/CuT/PVC or
XLPE/CuT/LS0H)

single core

from 3,6/6 (7,2) kV to 18/30 (36) kV

Construction

>
>
>
>
>
>
>

Applicable
standards

IEC 60502-2
IEC 60228
IEC 60332-1
IEC 60332-3 C
IEC 60754
IEC 61034

IEC 60332-1

STANDARD

GOOD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Semiconducting layer
extruded compound
Insulation
XLPE compound
Semiconducting layer
extruded compound
Metallic screen
copper tapes
Sheath
PVC compound ST2 quality or LS0H thermoplastic compound ST8 quality
Marking
e. g. : PRYSMIAN year - n x csa 3,6/6 kV
or
e. g. : PRYSMIAN Afumex year - n x csa 3,6/6 kV

Design and tests guidelines


Conductors
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

low
r

IEC 60332-1
IEC 60332-3C

136

GOOD

GOOD

LS0H

-5 C

14 D

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA M - S from 3,6/6 (7,2) kV to 18/30 (36) kV (XLPE/CuT/PVC or XLPE/CuT/LS0H) - single core

Type*

Voltage

Cross Diameter Maximum Diameter Diameter Outer


DC
section
of
over
over
diameter
conductor resistance insulation screen
approx
at 20 C approx
approx

Weight
of
cable
approx

Max
Phase
Min
Phase Conductor
current
bending reactance capacity
short
carrying
at 50 Hz approx
radius
circuit
approx (*)
current capacity in
air 30 C
(single
core in
trefoil
format)
(/km) (F/km) (kA/sec)
(mm)
(A)

Max
current
carrying
capacity
in gound
(T 20 C,
depth 1 m,
gtr Km/W)

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(mm)

(kg/km)

RE4H1R/RE4H1M1

3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6

1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

13,2
14,4
15,9
17,6
19,1
20,5
22,0
24,8
27,8
30,6
34,2
38,5

14,4
15,6
17,1
18,8
20,3
21,7
23,2
26,0
28,9
31,7
35,3
39,7

18,0
19,2
20,7
22,4
23,9
25,3
26,8
29,8
32,9
35,9
39,7
44,3

620
750
970
1240
1470
1780
2130
2730
3390
4260
5390
6880

250
270
290
320
340
360
380
520
460
500
560
620

0,12
0,11
0,11
0,10
0,10
0,10
0,09
0,09
0,09
0,09
0,09
0,08

0,28
0,31
0,35
0,40
0,44
0,47
0,52
0,57
0,59
0,61
0,65
0,74

5,2
7,4
10,3
13,9
17,5
21,9
26,9
34,8
43,5
>50
>50
>50

187
225
281
344
398
454
522
621
717
830
963
1113

188
222
272
326
370
415
469
542
611
691
780
877

RE4H1R/RE4H1M1

6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10

1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

14
16,2
17,7
19,4
20,9
22,3
23,8
26,4
29,0
31,4
34,6
38,9

16,2
17,4
18,9
20,6
22,1
23,5
25,0
27,6
30,1
32,5
35,7
40,1

19,8
21,0
22,5
24,2
25,7
27,1
28,8
31,6
34,1
36,7
40,1
44,7

680
810
1040
1320
1570
1850
2230
2830
3460
4310
5420
6910

280
300
320
340
360
380
410
450
480
520
560
630

0,13
0,12
0,11
0,11
0,10
0,10
0,10
0,09
0,09
0,09
0,09
0,09

0,20
0,25
0,28
0,31
0,34
0,37
0,40
0,45
0,5
0,55
0,61
0,7

5,2
7,4
10,3
13,9
17,5
21,9
26,9
34,8
43,5
>50
>50
>50

190
229
285
349
404
460
526
627
721
833
964
1114

188
222
272
326
370
416
468
542
611
692
781
878

RE4H1R/RE4H1M1

8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15

1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

17,2
18,4
19,9
21,6
23,1
24,5
26,0
28,6
31,2
33,6
36,8
41,1

18,4
19,6
21,1
22,8
24,2
25,6
27,2
29,8
32,3
34,7
37,9
42,3

22,0
23,2
24,7
26,4
28,0
29,4
31,2
33,8
36,5
39,1
42,5
47,1

760
900
1130
1410
1690
1970
2360
2950
3610
4470
5590
7100

310
330
350
370
390
410
440
470
510
550
600
660

0,13
0,13
0,12
0,11
0,11
0,10
0,10
0,10
0,10
0,09
0,09
0,09

0,18
0,20
0,22
0,25
0,27
0,29
0,32
0,36
0,40
0,43
0,48
0,55

5,2
7,4
10,3
13,9
17,5
21,9
26,9
34,8
43,5
>50
>50
>50

194
233
290
354
408
464
532
632
727
839
971
1121

189
223
272
326
370
415
468
543
612
693
783
882

RE4H1R/RE4H1M1

12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20

1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

19,2
20,4
21,9
23,6
25,1
26,5
28,0
30,6
33,2
35,6
38,8
43,1

20,4
21,6
23,1
24,8
26,2
27,6
29,2
31,8
34,3
36,7
39,9
44,3

24,0
25,2
26,7
28,6
30,0
31,6
33,2
36,0
38,7
41,3
44,7
49,3

840
980
1130
1520
1790
2090
2460
3080
3750
4620
5760
7280

340
350
370
400
420
440
470
500
540
580
630
690

0,14
0,13
0,12
0,12
0,11
0,11
0,11
0,10
0,10
0,10
0,09
0,09

0,16
0,17
0,19
0,22
0,24
0,25
0,27
0,30
0,34
0,37
0,41
0,46

5,2
7,4
10,3
13,9
17,5
21,9
26,9
34,8
43,5
>50
>50
>50

197
236
293
357
412
468
536
637
731
844
976
1127

189
223
272
326
370
415
468
543
612
693
785
885

RE4H1R/RE4H1M1

18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

25,4
26,9
28,8
30,1
31,5
33,0
35,6
38,2
40,6
43,8
48,1

26,5
28,1
29,8
31,2
32,6
34,2
36,8
39,3
41,7
44,9
49,3

30,3
32,1
34,0
35,4
36,8
38,6
41,4
43,9
46,7
49,9
54,7

1230
1500
1820
2100
2390
2800
3450
4120
5030
6170
7760

420
450
480
500
520
540
580
620
650
700
770

0,14
0,13
0,13
0,12
0,12
0,12
0,11
0,11
0,10
0,10
0,10

0,14
0,15
0,17
0,18
0,19
0,21
0,23
0,25
0,27
0,30
0,34

7,4
10,3
13,9
17,5
21,9
26,9
34,8
43,5
>50
>50
>50

241
299
364
419
475
544
644
739
852
985
1136

223
272
325
370
415
468
543
613
695
788
889

( )

* trefoil formation

(A)

137

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA M - S
(XLPE/CuT/PVC or
XLPE/CuT/LS0H)

multi-core

from 3,6/6 (7,2) kV to 18/30 (36) kV

Construction

>
>
>
>
>
>
>
>

Applicable
standards

IEC 60502-2
IEC 60228
IEC 60332-1
IEC 60332-3 C
IEC 60754
IEC 61034

IEC 60332-1

STANDARD

GOOD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Semiconducting layer
extruded compound
Insulation
XLPE compound
Semiconducting layer
extruded compound
Metallic screen
copper tapes
Fillers
non hygroscopic compound or LS0H non hygroscopic compound
Sheath
PVC compound ST2 quality or LS0H thermoplastic compound ST8 quality
Marking
e. g. : PRYSMIAN year - n x csa 3,6/6 kV
or
e. g. : PRYSMIAN Afumex year - n x csa 3,6/6 kV

Design and tests guidelines


Conductors
Flame retardant
Fire retardant on bunched cables(if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

low
r

IEC 60332-1
IEC 60332-3C

138

GOOD

GOOD

LS0H

-5 C

14 D

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA M - S from 3,6/6 (7,2) kV to 18/30 (36) kV (XLPE/CuT/PVC or XLPE/CuT/LS0H) - multi-core

Type

Voltage

(kV)

Phase
Cross Diameter Maximum Diameter Diameter Diameter Outer Weight
Min
Phase Conductor Max
Max
DC
section
of
over
over
over diameter
of
bending reactance capacity short
current current
conductor resistance insulation screen extruded approx cable
radius at 50 Hz approx
circuit carrying carrying
at 20 C approx approx
approx
inner
approx
current capacity capacity
covering
in air
in
30 C
ground
(single (T 20 C,
core in depth 1
trefoil
m, gtr
format) Km/W)
(/km)
(/km) (F/km) (kA/sec)
(mm2)
(mm)
(mm)
(mm)
(mm)
(mm) (kg/km) (mm)
(A)
(A)

RE4H1OR/RE4H1OM1 3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6

3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300
3x400

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470

13,2
14,4
15,9
17,6
19,1
20,5
22,0
24,8
27,8
30,6

14,4
15,6
17,1
18,8
20,3
21,7
23,2
26,0
28,9
31,7

32,7
35,2
38,5
42,2
45,3
48,3
51,6
58,0
64,3
70,4

37,0
39,7
43,2
47,3
50,8
54,0
57,5
64,3
71,0
77,5

2430
2950
3750
4790
5750
6760
8060
10320
12780
15880

520
560
610
660
710
760
810
900
1000
1090

0,11
0,10
0,09
0,09
0,09
0,09
0,08
0,08
0,08
0,08

0,28
0,31
0,35
0,4
0,44
0,47
0,52
0,57
0,59
0,61

5,0
7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0

180
216
268
327
376
427
488
571
654
751

183
216
263
314
356
399
450
517
581
657

RE4H1OR/RE4H1OM1 6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10

3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300
3x400

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470

14,0
16,2
17,7
19,4
20,9
22,3
23,8
26,4
29,0
31,4

16,2
17,4
18,9
20,6
22,1
23,5
25,0
27,6
30,1
32,5

36,6
39,0
42,4
46,0
49,2
52,6
55,8
61,4
66,9
72,5

41,3
44,0
47,5
51,5
54,9
58,5
61,9
67,9
73,8
79,8

2790
3330
4180
5250
6220
7320
8630
10840
13210
16290

580
620
670
720
770
820
870
950
1030
1120

0,11
0,11
0,10
0,10
0,09
0,09
0,09
0,09
0,08
0,08

0,2
0,25
0,28
0,31
0,34
0,37
0,4
0,45
0,5
0,55

5
7,2
10
13,6
17,2
21,5
26,5
34,4
43,0
>50,0

183
219
272
330
380
430
487
575
656
749

183
216
263
314
357
398
447
517
581
655

RE4H1OR/RE4H1OM1 8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15

3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300
3x400

7,0
8,2
9,7
11,4
12,9
14,3
15,8
18,4
20,6
23,0

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470

17,2
18,4
19,9
21,6
23,1
24,5
26,0
28,6
31,2
33,6

18,4
19,6
21,1
22,8
24,2
25,6
27,2
29,8
32,3
34,7

41,3
43,8
47,1
50,8
54,2
57,2
60,6
66,2
71,7
77,2

46,4
49,3
52,8
56,7
60,3
63,5
67,1
73,1
78,8
84,9

3290
3880
4760
5850
6900
7970
9350
11610
14010
17200

650
690
740
790
850
890
940
1020
1100
1190

0,12
0,11
0,11
0,10
0,10
0,10
0,09
0,09
0,09
0,09

0,18
0,2
0,22
0,25
0,27
0,29
0,32
0,36
0,4
0,43

5,0
7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0

186
222
275
334
380
430
491
578
660
753

183
215
263
314
354
396
447
517
582
656

RE4H1OR/RE4H1OM1 12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20

3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300
3x400

7
8,2
9,7
11,4
12,9
14,3
15,8
18,4
20,6
23,0

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470

19,2
20,4
21,9
23,6
25,1
26,5
28,0
30,6
33,2
35,6

20,4
21,6
23,1
24,8
26,2
27,6
29,2
31,8
34,3
36,7

45,6
48,1
51,4
55,4
58,5
61,5
64,9
70,5
76,4
81,5

51,1
53,8
57,3
61,5
64,8
68,0
71,8
77,6
83,9
89,4

3790
4380
5300
6470
7510
8610
10050
12330
14920
18030

720
750
800
860
910
950
1000
1090
1170
1250

0,13
0,12
0,11
0,11
0,10
0,10
0,10
0,09
0,09
0,09

0,16
0,17
0,19
0,22
0,24
0,25
0,27
0,3
0,34
0,37

5,0
7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0

188
224
277
333
383
433
493
581
660
756

183
215
263
312
354
396
447
517
581
657

RE4H1OR/RE4H1OM1 18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30

3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300

8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601

25,4
26,9
28,8
30,1
31,5
33,0
35,6
38,2

26,5
28,1
29,8
31,2
32,6
34,2
36,8
39,3

59,2
62,5
66,2
69,3
72,7
76,0
81,6
87,1

65,7
69,2
73,1
76,4
80,0
83,5
89,5
95,4

5920
6920
8140
9260
10530
12020
14490
17130

920
970
1020
1070
1120
1170
1250
1340

0,13
0,13
0,12
0,12
0,11
0,11
0,10
0,10

0,14
0,15
0,17
0,18
0,19
0,21
0,23
0,25

7,2
10
13,6
17,2
21,5
26,5
34,4
43

225
279
337
387
436
497
583
664

213
260
311
353
395
446
516
581

139

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA M - SA
(XLPE/CuT/AWA/PVC or
XLPE/CuT/AWA/LS0H)

single core

from 3,6/6 (7,2) kV to 18/30 (36) kV

Construction

>
>
>
>
>
>
>
>
>

Applicable
standards

IEC 60502-2
IEC 60228
IEC 60332-1
IEC 60332-3 C
IEC 60754
IEC 61034

IEC 60332-1

STANDARD

EXCELLENT

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Semiconducting layer
extruded compound
Insulation
XLPE compound
Semiconducting layer
extruded compound
Metallic screen
copper tapes
Separation sheath
PVC compound ST2 quality or LS0H thermoplastic compound ST8 quality
Armour
aluminium wires
Sheath
PVC compound ST2 quality or LS0H thermoplastic compound ST8 quality
Marking
e. g. : PRYSMIAN year - n x csa 3,6/6 kV
or
e. g. : PRYSMIAN Afumex year - n x csa 3,6/6 kV

Design and tests guidelines


Conductors
Flame retardant
Fire retardant on bunched cables(if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

low
r

IEC 60332-1
IEC 60332-3C

140

GOOD

EXCELLENT

LS0H

-5 C

14 D

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA M - SA from 3,6/6 (7,2) kV to 18/30 (36) kV (XLPE/CuT/AWA/PVC or XLPE/CuT/AWA/LS0H) - single core

Phase Phase Conductor Max


Voltage Cross Diameter Maximum Diameter Diameter Diameter Diameter Diameter Outer Weight Min
Max
DC
over
over
over
of
over diameter of bending reactance capacity short
current current
section
of
50Hz approx circuit carrying carrying
conductor resistance insulation screen separation armour armour approx cable radius
at 20 C approx approx sheath
approx(*)
wires
approx
current capacity capacity
in air
in
30 C ground
(single (T 20 C,
core
depth 1
in trefoil m, gtr
format) Km/W)
(/km)
(mm)
(kV) (mm2)
(mm)
(mm)
(mm)
(mm)
(mm) (kg/km) (mm) (/km) (F/km) (kA/sec)
(A)
(mm)
(A)

Type*

RE4H1RFR/
RE4GHM1FM1 3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1X630

8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

14,4
15,9
17,6
19,1
20,5
22,0
24,8
27,8
30,6
34,2
38,5

15,6
17,1
18,8
20,3
21,7
23,2
26,0
28,9
31,7
35,3
39,7

17,7
19,4
21,0
22,5
23,9
25,4
28,4
31,3
34,1
37,9
42,5

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,5
2,5

21,7
23,4
25,0
26,5
27,9
29,4
32,4
35,3
38,1
42,9
47,5

25,4
27,7
28,8
30,4
32,0
33,4
37,2
40,3
43,3
48,5
52,7

1140
1380
1700
1970
2280
2660
3410
4130
5060
6480
7900

360
390
400
430
450
470
520
570
610
680
740

0,13
0,13
0,12
0,11
0,11
0,11
0,10
0,10
0,10
0,10
0,10

0,31
0,35
0,4
0,44
0,47
0,52
0,57
0,59
0,61
0,65
0,74

7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

239
295
358
410
461
523
610
688
777
854
948

223
271
322
363
403
450
511
565
625
666
720

RE4H1RFR/
RE4GHM1FM1 6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

16,2
17,7
19,4
20,9
22,3
23,8
26,4
29,0
31,4
34,6
38,9

17,4
18,9
20,6
22,1
23,5
25,0
27,6
30,1
32,5
35,7
40,1

19,6
21,3
23,0
24,5
25,9
27,4
30,0
32,5
34,9
38,3
42,9

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,5
2,5

23,6
25,3
27,0
28,5
29,9
31,4
34,0
36,5
38,9
43,3
47,9

27,3
29,2
31,0
32,5
34,7
36,2
39,0
41,5
44,3
48,9
53

1230
1500
1820
2100
2490
2880
3540
4230
5150
6510
7950

380
410
430
460
490
510
550
580
620
690
740

0,14
0,13
0,12
0,12
0,12
0,11
0,11
0,10
0,10
0,10
0,10

0,25
0,28
0,31
0,34
0,37
0,4
0,45
0,5
0,55
0,61
0,7

7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

241
298
360
412
464
525
612
690
777
856
950

223
271
321
362
402
449
511
565
624
667
721

RE4H1RFR/
RE4GHM1FM1 8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

18,4
19,9
21,6
23,1
24,5
26,0
28,6
31,2
33,6
36,8
41,1

19,6
21,1
22,8
24,2
25,6
27,2
29,8
32,3
34,7
37,9
42,3

21,9
23,5
25,2
26,6
28,0
29,6
32,2
34,7
37,3
40,5
45,1

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,5
2,5
2,5

25,9
27,5
29,2
30,6
32,0
33,6
36,2
38,7
42,3
45,5
50,1

29,7
31,6
33,8
35,4
36,8
38,6
41,4
43,9
47,9
51,3
55,5

1380
1650
2020
2320
2640
3070
3730
4420
5530
6750
8180

420
440
470
500
520
540
580
620
670
720
780

0,14
0,13
0,13
0,12
0,12
0,12
0,11
0,11
0,11
0,10
0,10

0,2
0,22
0,25
0,27
0,29
0,32
0,36
0,4
0,43
0,48
0,55

7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

243
300
362
414
466
527
614
692
767
858
952

223
270
321
361
402
447
510
564
609
665
720

RE4H1RFR/
RE4GHM1FM1 12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

20,4
21,9
23,6
25,1
26,5
28,0
30,6
33,2
35,6
38,8
43,1

21,6
23,1
24,8
26,2
27,6
29,2
31,8
34,3
36,7
39,9
44,3

23,8
25,5
27,2
28,6
30,0
31,6
34,2
36,9
39,3
42,7
47,1

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,5
2,5
2,5
2,5

27,8
29,5
31,2
32,6
34,0
35,6
38,2
41,9
44,3
47,7
52,1

31,9
33,6
36,0
37,4
39,0
40,6
43,4
47,3
49,9
53,5
57,7

1510
1770
2170
2470
2800
3210
3890
4770
5710
6960
8410

450
470
500
520
550
570
610
660
700
750
810

0,15
0,14
0,13
0,13
0,12
0,12
0,11
0,11
0,11
0,10
0,10

0,17
0,19
0,22
0,24
0,25
0,27
0,3
0,34
0,37
0,41
0,46

7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

244
301
364
416
468
529
616
686
770
860
954

222
270
320
361
401
447
509
553
609
665
720

RE4H1RFR/
RE4GHM1FM1 18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

25,4
26,9
28,8
30,1
31,5
33,0
35,6
38,2
40,6
43,8
48,1

26,5
28,1
29,8
31,2
32,6
34,2
36,8
39,3
41,7
44,9
49,3

28,9
30,5
32,2
33,6
35,2
36,8
39,4
42,1
44,5
47,9
52,3

2,0
2,0
2,0
2,0
2,5
2,5
2,5
2,5
2,5
2,5
2,5

32,9
34,5
36,2
37,6
40,2
41,8
44,4
47,1
49,5
52,9
57,3

37,9
39,5
41,4
42,8
45,6
47,4
50,0
52,9
55,5
59,1
63,1

1950
2220
2580
2890
3410
3850
4540
5320
6280
7560
9000

530
550
580
600
640
660
700
740
780
830
880

0,16
0,15
0,14
0,14
0,13
0,13
0,12
0,12
0,12
0,11
0,11

0,14
0,15
0,17
0,18
0,19
0,21
0,23
0,25
0,27
0,3
0,34

7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

247
304
367
419
469
529
614
688
772
863
959

221
269
319
359
396
440
500
551
606
663
719

( )

* trefoil formation

141

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA M - SA
(XLPE/CuT/SWA/PVC or
XLPE/CuT/SWA/LS0H)

multi-core

from 3,6/6 (7,2) kV to 18/30 (36) kV

Construction

>
>
>
>
>
>
>
>
>
>

Applicable
standards

IEC 60502-2
IEC 60228
IEC 60332-1
IEC 60332-3 C
IEC 60754
IEC 61034

IEC 60332-1

STANDARD

EXCELLENT

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Semiconducting layer
extruded compound
Insulation
XLPE compound
Semiconducting layer
extruded compound
Metallic screen
copper tapes
Fillers
non hygroscopic compound or LS0H non hygroscopic compound
Separation sheath
PVC compound ST2 quality or LS0H thermoplastic compound ST8 quality
Armour
galvanized steel wires
Sheath
PVC compound ST2 quality or LS0H thermoplastic compound ST8 quality
Marking
e. g. : PRYSMIAN year - n x csa 3,6/6 kV
or
e. g. : PRYSMIAN Afumex year - n x csa 3,6/6 kV

Design and tests guidelines


Conductors
Flame retardant
Fire retardant on bunched cables (if required)
Halogen free properties (only for LS0H)
Low smoke emission (only for LS0H)

Pb

14 D

low
r

IEC 60332-1
IEC 60332-3C

142

GOOD

EXCELLENT

LS0H

-5 C

14 D

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

PVC
LS0H

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1
> Fire retardant cables according to (if required) IEC 60332-3C

TEPLA M - SA 3,6/6 (7,2) kV TO 18/30 (36) kV (XLPE/CuT/SWA/PVC or XLPE/CuT/SWA/LS0H) - multi-core

Type

Phase Phase Conductor Max


Voltage Cross Diameter Maximum Diameter Diameter Diameter Diameter Diameter Outer Weight Min
Max
DC
over
current current
over
over
of
over diameter of bending reactance capacity short
section
of
50Hz approx circuit carrying carrying
conductor resistance insulation screen separation armour armour approx cable radius
at 20 C approx approx sheath
approx
current capacity capacity
wires
approx
in air
in
30 C ground
(single (T 20 C,
core
depth 1
in trefoil m, gtr
format) Km/W)
(/km)
(mm)
(kV) (mm2)
(A)
(A)
(mm)
(mm)
(mm)
(mm)
(mm) (kg/km) (mm) (/km) (F/km) (kA/sec)
(mm)

RE4H1ORFR/
RE4H1OF1M1 3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6

3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601

13,2
14,4
15,9
17,6
19,1
20,5
22,0
24,8
27,8

14,4
15,6
17,1
18,8
20,3
21,7
23,2
26,0
28,9

35,1
37,8
41,3
45,0
48,3
51,3
54,8
61,4
67,7

2,0
2,5
2,5
2,5
2,5
2,5
2,5
2,5
3,2

39,1
42,8
46,3
50
53,3
56,3
59,8
66,4
74,0

44,0
48,1
51,8
55,7
59,2
62,4
66,1
72,8
81,0

4210
5300
6330
7590
8710
9920
11450
13620
17400

620
670
730
780
830
880
930
1020
1130

0,11
0,1
0,09
0,09
0,09
0,09
0,08
0,08
0,08

0,28
0,31
0,35
0,4
0,44
0,47
0,52
0,57
0,59

5,0
7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0

182
218
269
326
374
423
479
557
629

180
213
259
308
349
390
437
499
552

3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754

14,0
16,2
17,7
19,4
20,9
22,3
23,8
26,4

16,2
17,4
18,9
20,6
22,1
23,5
25,0
27,6

39,2
41,8
45,2
49,0
52,4
55,8
59
65

2,5
2,5
2,5
2,5
2,5
2,5
2,5
3,2

44,2
46,8
50,2
54
57,4
60,8
64,0
71,3

49,5
52,3
55,9
60,1
63,7
67,3
70,4
78,1

5220
5940
6980
8290
9490
10790
11900
15300

700
730
780
840
890
940
960
1100

0,11
0,11
0,1
0,1
0,09
0,09
0,09
0,09

0,2
0,25
0,28
0,31
0,34
0,37
0,40
0,45

5,0
7,2
10,0
13,6
17,2
21,5
26,5
34,4

185
220
272
329
376
423
476
556

181
213
259
308
348
388
433
495

RE4H1ORFR/
RE4H1OF1M1 8,7/15 3x35
8,7/15 3x50
8,7/15 3x70
8,7/15 3x95
8,7/15 3x120
8,7/15 3x150
8,7/15 3x185

7,0
8,2
9,7
11,4
12,9
14,3
15,8

0,524
0,387
0,268
0,193
0,153
0,124
0,0991

17,2
18,4
19,9
21,6
23,1
24,5
26,0

18,4
19,6
21,1
22,8
24,2
25,6
27,2

44,1
46,8
50,1
54,0
57,6
60,6
64,0

2,5
2,5
2,5
2,5
2,5
2,5
3,2

49,1
51,8
55,1
59,0
62,6
65,6
70,3

54,8
57,7
61,2
65,3
68,8
72,0
77,0

6040
6780
7870
9190
10100
11340
13790

770
810
860
920
960
1010
1080

0,12
0,11
0,11
0,1
0,1
0,1
0,09

0,18
0,20
0,22
0,25
0,27
0,29
0,32

5,0
7,2
10,0
13,6
17,2
21,5
26,5

187
222
274
331
375
424
480

180
212
259
308
346
387
432

RE4H1ORFR/
RE4H1OF1M1 12/20 3x35
12/20 3x50
12/20 3x70
12/20 3x95
12/20 3x120
12/20 3x150
12/20 3x185

7,0
8,2
9,7
11,4
12,9
14,3
15,8

0,524
0,387
0,268
0,193
0,153
0,124
0,0991

19,2
20,4
21,9
23,6
25,1
26,5
28,0

20,4
21,6
23,1
24,8
26,2
27,6
29,2

48,6
51,3
54,6
58,7
61,9
65,1
68,4

2,5
2,5
2,5
2,5
3,2
3,2
3,2

53,6
56,3
59,6
63,7
68,2
71,4
74,7

59,5
62,4
66,1
70,1
74,8
78,2
82,0

6790
7570
8720
9790
11830
13170
14900

830
870
930
980
1050
1100
1150

0,13
0,12
0,11
0,11
0,1
0,1
0,1

0,16
0,17
0,19
0,22
0,24
0,25
0,27

5,0
7,2
10,0
13,6
17,2
21,5
26,5

188
224
276
330
378
426
481

180
212
258
306
346
385
431

RE4H1ORFR/
RE4H1OF1M1 18/30
18/30

8,1
9,8

0,387
0,268

25,4
26,9

26,5
28,1

62,5
66,2

3,2
3,2

68,8
72,5

75,6
79,5

10290
11600

1060
1110

0,13
0,13

0,14
0,15

7,2
10,0

224
276

210
256

RE4H1ORFR/
RE4H1OF1M1

6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10

3X50
3X70

143

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA M - S(AR)
(XLPE/CuW/PSA/PVC)

single core

from 3,6/6 (7,2) kV to 18/30 (36) kV

Construction

>
>
>
>
>
>
>
>

Applicable
standards

IEC 60502-2 Design and tests guidelines


IEC 60228
Conductors
IEC 60332-1 Flame retardant
Prysmian document GPD-001 for PSA layer

IEC 60332-1

144

STANDARD

EXCELLENT

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Semiconducting layer
extruded compound
Insulation
XLPE compound
Semiconducting layer
extruded compound
Metallic screen
copper wires
Mechanical protective layer
PSA AIR BAGTM
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 3,6/61 kV

12 D

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA M - S(AR) from 3,6/6 (7,2) to 18/30 (36) kV (XLPE/CuW/PSA/PVC) - single core

Phase
Voltage Cross Diameter Maximum Diameter Diameter Diameter Approx Diameter Outer Weight Min
Max
Phase Conductor Max
DC
over
over
under thickness over diameter of cable bending reactance capacity short
current current
section
of
50Hz approx circuit carrying carrying
PSA
of
PSA
approx approx radius
conductor resistance insulation screen
at 20 C approx approx
approx (*)
PSA
current capacity capacity
in air in ground
30 C (T 20 C,
single core depth 1
in trefoil m, gtr
format) Km/W)

Type*

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

RE4H1(AR)R

3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6

1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1X630

9,8
11,4
12,9
14,2
15,8
18,2
20,5
22,9
26,2
29,9

0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

15,9
17,6
19,1
20,5
22,0
24,8
27,8
30,6
34,2
38,5

17,1
18,8
20,3
21,7
23,2
26,0
28,9
31,7
35,3
39,7

18,9
20,4
21,8
23,2
24,8
27,4
30,4
33,2
36,8
41,2

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,5
2,5

22,9
24,4
25,8
27,2
28,8
31,4
34,4
37,2
41,8
46,2

26,2
27,7
29,3
30,7
32,4
35,2
38,2
41,4
46,3
50,8

1091
1358
1619
1895
2271
2866
3520
4386
5564
7074

314
332
352
368
389
423
459
497
555
609

0,12
0,11
0,11
0,11
0,10
0,10
0,10
0,10
0,09
0,09

0,35
0,40
0,44
0,47
0,52
0,57
0,59
0,61
0,65
0,74

RE4H1(AR)R

6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,2
15,8
18,2
20,5
22,9
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

16,2
17,7
19,4
20,9
22,3
23,8
26,4
29,0
31,4
34,6
38,9

17,4
18,9
20,6
22,1
23,5
25,0
27,6
30,1
32,5
35,7
40,1

18,9
20,5
22,0
23,5
24,9
26,5
28,9
31,6
34,0
37,3
41,6

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,5
2,5

22,9
24,5
26,0
27,5
28,9
30,5
32,9
35,6
38,0
42,3
46,6

26,2
27,8
29,5
31,0
32,6
34,2
36,8
39,6
42,2
46,7
51,2

935
1152
1445
1699
1990
2361
2953
3607
4441
5593
7111

314
333
354
372
391
410
441
475
507
560
614

0,13
0,12
0,12
0,11
0,11
0,11
0,10
0,10
0,10
0,09
0,09

RE4H1(AR)R 8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,2
15,8
18,2
20,5
22,9
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

18,4
19,9
21,6
23,1
24,5
26,0
28,6
31,2
33,6
36,8
41,1

19,6
21,1
22,8
24,2
25,6
27,2
29,8
32,3
34,7
37,9
42,3

20,8
22,5
24,1
25,6
27,0
28,6
31,0
33,6
36,1
39,3
43,7

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,5
2,5
2,5

24,8
26,5
28,1
29,6
31,0
32,6
35,0
37,6
41,1
44,3
48,7

28,3
30,0
31,8
33,3
34,8
36,4
39,0
41,9
45,5
48,9
53,5

1024
1256
1554
1813
2112
2489
3092
3760
4649
5765
7302

339
360
381
399
418
437
468
502
546
587
642

RE4H1(AR)R 12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,2
15,8
18,2
20,5
22,9
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

20,4
21,9
23,6
25,1
26,5
28,0
30,6
33,2
35,6
38,8
43,1

21,6
23,1
24,8
26,2
27,6
29,2
31,8
34,3
36,7
39,9
44,3

22,7
24,4
26,0
27,5
28,8
30,5
32,9
35,5
38,0
41,2
45,6

2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,0
2,5
2,5
2,5

26,7
28,4
30,0
31,5
32,8
34,5
36,9
39,5
43,0
46,2
50,6

30,2
32,1
33,7
35,3
36,7
38,5
41,1
43,8
47,4
51,0
55,6

1109
1358
1650
1928
2216
2617
3226
3884
4783
5933
7482

RE4H1(AR)R 18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30
18/30

1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

8,1
9,8
11,4
12,9
14,2
15,8
18,2
20,5
22,9
26,2
29,9

0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

25,4
26,9
28,8
30,1
31,5
33,0
35,6
38,2
40,6
43,8
48,1

26,5
28,1
29,8
31,2
32,6
34,2
36,8
39,3
41,7
44,9
49,3

27,4
29,1
30,7
32,2
33,6
35,2
37,6
40,3
42,7
46,0
50,3

2,0
2,0
2,0
2,0
2,0
2,5
2,5
2,5
2,5
2,5
2,5

31,4
33,1
34,7
36,2
37,6
40,2
42,6
45,3
47,7
51,0
55,3

35,3
37,2
38,8
40,4
41,8
44,6
47,0
49,9
52,5
55,9
60,5

1371
1640
1944
2242
2535
2999
3617
4313
5185
6344
7914

(kg/km) (mm)

(/km)

(A)

(A)

10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

277
338
389
442
507
602
693
794
922
1066

261
312
355
398
446
516
582
655
741
832

0,25
0,28
0,31
0,34
0,37
0,40
0,45
0,50
0,55
0,61
0,70

7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

226
281
343
392
447
510
607
696
796
923
1067

213
261
312
355
398
445
516
582
659
741
833

0,14
0,13
0,12
0,12
0,11
0,11
0,11
0,10
0,10
0,10
0,10

0,20
0,22
0,25
0,27
0,29
0,32
0,36
0,40
0,43
0,48
0,55

7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

231
286
348
398
452
517
613
702
803
930
1074

213
261
312
355
398
446
517
583
657
742
836

362
385
404
424
440
462
493
525
569
612
667

0,14
0,13
0,13
0,12
0,12
0,11
0,11
0,11
0,10
0,10
0,10

0,17
0,19
0,22
0,24
0,25
0,27
0,30
0,34
0,37
0,41
0,46

7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

234
289
352
402
457
521
617
707
807
935
1080

213
261
312
355
397
446
517
583
658
744
838

423
446
465
485
501
535
564
598
630
671
726

0,15
0,14
0,14
0,13
0,13
0,12
0,12
0,11
0,11
0,11
0,10

0,14
0,15
0,17
0,18
0,19
0,21
0,23
0,25
0,27
0,30
0,34

7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

240
295
359
409
464
529
624
714
816
943
1089

213
261
312
355
397
446
520
584
659
747
843

(F/km) (kA/sec)

( )

* trefoil formation

145

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA M - S(AR)
(XLPE/CuW/PSA/PVC)

multi-core

from 3,6/6 (7,2) kV to 18/30 (36) kV

Construction

>
>
>
>
>
>
>
>
>

Applicable
standards

IEC 60502-2 Design and tests guidelines


IEC 60228
Conductors
IEC 60332-1 Flame retardant
Prysmian document GPD-001 for PSA layer

IEC 60332-1

146

STANDARD

EXCELLENT

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Semiconducting layer
extruded compound
Insulation
XLPE compound
Semiconducting layer
extruded compound
Metallic screen
copper tapes
Fillers
non hygroscopic compound
Mechanical protective layer
PSA AIR BAGTM
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 3,6/6 kV

12 D

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA M - S(AR) from 3,6/6 (7,2) to 18/30 (36) kV (XLPE/CuW/PSA/PVC) - multi-core

Type

Phase
Voltage Cross Diameter Maximum Diameter Diameter Diameter Approx Diameter Outer Weight Min
Max
Phase Conductor Max
DC
current current
over
over
under thickness over diameter of cable bending reactance capacity short
of
section
50Hz approx circuit carrying carrying
PSA
approx approx radius
PSA
of
conductor resistance insulation screen
approx
at 20 C approx approx
current capacity capacity
PSA
in air in ground
30 C (T 20 C,
single core depth 1
in trefoil m, gtr
format) Km/W)
(mm2)

(mm)

(/km)

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg/km) (mm)

RE4H1O(AR)R 3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6
3,6/6

3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601

13,2
14,4
15,9
17,6
19,1
20,5
22,0
24,8
27,8

14,4
15,6
17,1
18,8
20,3
21,7
23,2
26,0
28,9

32,0
34,2
37,9
41,3
44,6
47,5
50,9
56,5
63,0

2,0
2,0
2,5
2,5
2,5
2,5
3,0
3,0
3,0

36
38,2
42,9
46,3
49,6
52,5
56,9
62,5
69,0

40,1
42,5
47,3
51,1
54,5
57,6
62,3
68,2
75,1

2492
2987
3854
4873
5807
6800
8166
10285
12733

481
510
568
614
654
692
747
818
901

0,11
0,10
0,09
0,09
0,09
0,09
0,08
0,08
0,08

0,28
0,31
0,35
0,40
0,44
0,47
0,52
0,57
0,59

RE4H1O(AR)R 6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10

3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754

14,0
16,2
17,7
19,4
20,9
22,3
23,8
26,4

16,2
17,4
18,9
20,6
22,1
23,5
25,0
27,6

35,7
37,9
41,6
45,0
48,2
51,1
54,6
59,7

2,5
2,5
2,5
2,5
2,5
3,0
3,0
3,0

40,7
42,9
46,6
50,0
53,2
57,1
60,6
65,7

45,1
47,5
51,3
55,0
58,4
62,5
66,1
71,7

2895
3405
4263
5288
6249
7329
8650
10770

541
570
616
660
701
750
793
860

0,11
0,11
0,10
0,10
0,09
0,09
0,09
0,09

RE4H1O(AR)R 8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15
8,7/15

3x35
3x50
3x70
3x95
3x120
3x150
3x185

7,0
8,2
9,7
11,4
12,9
14,3
15,8

0,524
0,387
0,268
0,193
0,153
0,124
0,0991

17,2
18,4
19,9
21,6
23,1
24,5
26,0

18,4
19,6
21,1
22,8
24,2
25,6
27,2

40,1
46,0
49,5
52,7
55,6
59,0
64,2

2,5
3,63
2,5
2,5
3,0
3,0
3,0

45,1
47,4
51,0
54,5
58,7
61,6
65,0

49,9
52,3
56,2
59,8
64,3
67,3
71,0

3359
3900
4798
5856
6919
7952
9324

599
628
674
718
771
808
852

RE4H1O(AR)R 12/20
12/20
12/20
12/20
12/20
12/20
12/20

3x35
3x50
3x70
3x95
3x120
3x150
3x185

7,0
8,2
9,7
11,4
12,9
14,3
15,8

0,52
0,39
0,27
0,19
0,15
0,12
0,1,0

19,2
20,4
21,9
23,6
25,1
26,5
28,0

20,4
21,6
23,1
24,8
26,2
27,6
29,2

44,2
46,4
50,1
53,6
56,8
59,7
63,1

2,5
2,5
3,0
3,0
3,0
3,0
3,0

49,2
51,4
56,1
59,6
62,8
65,7
69,1

54,2
56,6
61,5
65,1
68,5
71,6
75,4

3810
4374
5364
6460
7471
8548
9984

RE4H1O(AR)R 18/30 3X50


18/30 3X70

8,1
9,8

0,39
0,27

25,4
26,9

26,5
28,1

56,6
60,3

3,0
3,0

62,6
66,3

68,5
72,4

5814
6826

(kV)

(/km)

(F/km) (kA/sec)

(A)

(A)

5,0
7,2
10,0
13,6
17,2
21,5
26,5
34,4
43

165
196
245
298
344
391
447
527
602

172
201
246
294
333
374
421
486
545

0,20
0,25
0,28
0,31
0,34
0,37
0,40
0,45

5,0
7,2
10,0
13,6
17,2
21,5
26,5
34,4

167
199
248
301
347
394
449
529

171
201
246
294
333
373
420
486

0,12
0,11
0,11
0,10
0,10
0,10
0,09

0,18
0,20
0,22
0,25
0,27
0,29
0,32

5,0
7,2
10,0
13,6
17,2
21,5
26,5

169
202
252
305
350
396
531

170
201
246
294
333
372
421

650
679
737
781
822
859
905

0,13
0,12
0,11
0,11
0,10
0,10
0,10

0,16
0,17
0,19
0,22
0,24
0,25
0,27

5,0
7,2
10,0
13,6
17,2
21,5
26,5

172
204
253
308
353
399
454

170
201
246
294
332
372
419

822
868

0,13
0,13

0,14
0,15

7,2
10,0

207
257

200
244

147

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA M - L
(XLPE/Pb/PVC)

single core

from 3,6/6 (7,2) kV to 18/30 (36) kV

Construction

>
>
>
>
>
>
>

Applicable
standards

IEC 60332-1

148

EXCELLENT

STANDARD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Semiconducting layer
extruded compound
Insulation
XLPE compound
Semiconducting layer
extruded compound
Metallic sheath
lead alloy
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 3,6/6 kV

IEC 60502-2
IEC 60228
IEC 60332-1

Design and tests guidelines


Conductors
Flame retardant

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

16 D

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA M - L from 3,6/6 (7,2) to 18/30 (36) kV (XLPE/Pb/PVC) - single core

Diameter Maximum Diameter Diameter


DC
of
over
over
conductor resistance insulation screen
at 20 C
approx
approx

Max
Phase Conductor
current
capacity
short
carrying
approx
circuit
current capacity in
air 30 C
(single
core in
trefoil
format)
(F/km)
(kA/sec)
(A)

Outer
diameter
approx

Weight
of
cable
approx

Min
bending
radius

Phase
reactance
at 50 Hz
approx (*)

(mm)

(mm)

(kg/km)

(mm)

(/km)

14,0
16,2
17,7
19,4
20,9
22,3
23,8
26,4
29,0
31,4
34,6
38,9

16,2
17,4
18,9
20,6
22,1
23,5
25,0
27,6
30,1
32,5
35,7
40,1

21,5
22,6
24,7
26,3
28,2
29,5
31,5
34,1
36,9
40,0
43,6
48,1

1385
1566
1943
2290
2713
3053
3607
4322
5203
6309
7736
9509

344
361
394
420
450
472
504
545
591
639
697
770

0,13
0,12
0,12
0,11
0,11
0,10
0,10
0,10
0,10
0,09
0,09
0,09

0,20
0,25
0,28
0,31
0,34
0,37
0,40
0,45
0,5
0,55
0,61
0,70

5,0
7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

194
232
292
357
413
470
539
635
732
846
971
1112

189
224
274
328
373
419
471
541
610
684
772
859

19,2
20,4
21,9
23,6
25,1
26,5
28,0
30,6
33,2
35,6
38,8
43,1

20,4
21,6
23,1
24,8
26,2
27,6
29,2
31,8
34,3
36,7
39,9
44,3

25,9
27,3
29,0
31,0
32,5
34,0
35,8
38,4
41,5
44,3
47,9
52,7

1795
2084
2398
2872
3214
3583
4155
4893
5836
6965
8442
10428

414
437
464
496
520
545
573
615
664
709
767
843

0,14
0,13
0,13
0,12
0,12
0,11
0,11
0,10
0,10
0,10
0,10
0,09

0,16
0,17
0,19
0,22
0,24
0,25
0,27
0,30
0,34
0,37
0,41
0,46

5,0
7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

201
241
300
366
423
481
551
645
743
857
983
1125

189
224
274
329
373
418
472
542
611
686
776
865

Voltage

Cross
section

(kV)

(mm2)

(mm)

(/km)

(mm)

RE4LR

6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10

1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

RE4LR

12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20

1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

Type*

Max
current
carrying
capacity
in ground
(T 20 C,
depth 1 m,
gtr Km/W)
(A)

( )

* trefoil formation

149

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA M - SL
(XLPE/CuT/Pb/PVC)

multi-core

from 3,6/6 (7,2) kV to18/30 (36) kV

Construction

>
>
>
>
>
>
>
>
>

Applicable
standards

IEC 60332-1

150

EXCELLENT

STANDARD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Semiconducting layer
extruded compound
Insulation
XLPE compound
Semiconducting layer
extruded compound
Metallic screen
copper tapes
Fillers
non hygroscopic compound
Metallic sheath
lead alloy
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 3,6/6 kV

IEC 60502-2
IEC 60228
IEC 60332-1

Design and tests guidelines


Conductors
Flame retardant

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

16 D

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA M - SL from 3,6/6 (7,2) to 18/30 (36) kV (XLPE/CuT/Pb/PVC) - multi-core

Type

Voltage

Cross Diameter Maximum Diameter Diameter Diameter Outer


DC
section
of
over
over
over
diameter
conductor resistance insulation screen extruded approx
at 20 C approx
approx
inner
covering

Weight
of
cable
approx

Phase
Min
Phase Conductor
Max
Max
bending reactance capacity
short
current current
radius at 50 Hz approx
circuit carrying carrying
approx
current capacity capacity
in air
in
30 C
ground
(single (T 20 C,
core in depth 1
trefoil
m, gtr
format)
Km/W)
(/km) (F/km) (kA/sec)
(mm)
(A)
(A)

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(mm)

(mm)

(kg/km)

6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10

3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300
3x400

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,00754
0,0601
0,0470

14,0
16,2
17,7
19,4
20,9
22,3
23,8
26,4
29,0
31,4

16,2
17,4
18,9
20,6
22,1
23,5
25,0
27,6
30,1
32,5

36,6
39,0
42,4
46,0
49,2
52,6
55,8
61,4
66,9
72,5

46,0
48,7
52,7
56,7
60,4
63,7
67,5
73,2
80,1
86,4

5439
6264
7534
9018
10421
11873
13694
16503
19821
23839

737
779
844
908
966
1019
1080
1172
1282
1382

0,11
0,11
0,10
0,10
0,09
0,09
0,09
0,09
0,08
0,08

0,20
0,25
0,28
0,31
0,34
0,37
0,40
0,45
0,50
0,55

5,0
7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0

184
218
271
327
374
423
482
563
635
717

181
212
259
308
348
389
439
501
557
620

RE4H1OLR 12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20

3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300
3x400

7,0
8,2
9,7
11,4
12,9
14,3
15,8
18,4
20,6
23,0

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,00754
0,0601
0,0470

19,2
20,4
21,9
23,6
25,1
26,5
28,0
30,6
33,2
35,6

20,4
21,6
23,1
24,8
26,2
27,6
29,2
31,8
34,3
36,7

45,6
48,1
51,4
55,4
58,5
61,5
64,9
70,5
76,4
81,5

55,9
58,6
62,6
66,5
69,9
73,2
77,8
83,7
90,4
96,5

7472
8409
9823
11418
12703
14267
16452
19722
23202
27420

895
937
1002
1064
1118
1171
1244
1340
1447
1544

0,13
0,12
0,11
0,11
0,10
0,10
0,10
0,09
0,09
0,09

0,16
0,17
0,19
0,22
0,24
0,25
0,27
0,30
0,34
0,37

5,0
7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0

187
222
275
331
379
426
485
564
635
717

180
212
258
307
347
386
436
498
557
620

RE4H1OLR

151

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA M - D
(XLPE/DRYLAM/PVC)

single core

from 3,6/6 (7,2) kV to 18/30 (36) kV

Construction

>
>
>
>
>

>
>

Applicable
standards

IEC 60502-2 Design and tests guidelines


IEC 60228
Conductors
IEC 60332-1 Flame retardant
Prysmian document GPD-003 for chemical moisture barrier

IEC 60332-1

152

EXCELLENT

STANDARD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Semiconducting layer
extruded compound
Insulation
XLPE compound
Semiconducting layer
extruded compound
Chemical moisture barrier
longitudinally applied Al tape bonded with extruded chemical resistant
polymeric layer
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa ,6/6 kV

14 D

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA M - D from 3,6/6 (7,2) to 18/30 (36) kV (XLPE/DRYLAM/PVC) - single core

Type*

Diameter Maximum Diameter Diameter


DC
of
over
over
conductor resistance insulation screen
at 20 C
approx
approx

Max
Phase Conductor
current
capacity
short
carrying
approx
circuit
current capacity in
air 30 C
(single
core in
trefoil
format)
(F/km)
(kA/sec)
(A)

Outer
diameter
approx

Weight
of
cable
approx

Min
bending
radius

Phase
reactance
at 50 Hz
approx (*)

(mm)

(mm)

(kg/km)

(mm)

(/km)

14,0
16,2
17,7
19,4
20,9
22,3
23,8
26,4
29,0
31,4
34,6
38,9

16,2
17,4
18,9
20,6
22,1
23,5
25,0
27,6
30,1
32,5
35,7
40,1

21,5
22,5
24,4
26,0
27,7
29,0
30,8
33,4
36,2
39,1
42,5
47,0

691
829
1059
1334
1601
1875
2254
2842
3479
4322
5415
6915

0,13
0,12
0,12
0,11
0,11
0,10
0,10
0,10
0,09
0,09
0,09
0,09

0,20
0,25
0,28
0,31
0,34
0,37
0,40
0,45
0,50
0,55
0,61
0,70

5,0
7,2
10
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

189
226
284
347
401
457
524
623
714
824
951
1091

186
219
269
321
366
410
462
532
600
679
766
855

19,2
20,4
21,9
23,6
25,1
26,5
28,0
30,6
33,2
35,6
38,8
43,1

20,4
21,6
23,1
24,8
26,2
27,6
29,2
31,8
34,3
36,7
39,9
44,3

25,6
26,9
28,6
30,3
31,8
33,4
35,0
37,7
40,6
43,2
46,7
51,2

857
1014
1245
1543
1806
2105
2479
3096
3758
4600
5718
7248

0,14
0,13
0,13
0,12
0,12
0,11
0,11
0,10
0,10
0,10
0,09
0,09

0,16
0,17
0,19
0,22
0,24
0,25
0,27
0,30
0,34
0,37
0,41
0,46

5,0
7,2
10
13,6
17,2
21,5
26,5
34,4
43,0
>50,0
>50,0
>50,0

196
234
292
356
411
467
535
633
725
835
963
1104

186
219
269
322
366
409
463
533
601
681
768
860

Voltage

Cross
section

(kV)

(mm2)

(mm)

(/km)

(mm)

RE4H5R4R

6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10

1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

RE4H5R4R

12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20

1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9
26,2
29,9

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470
0,0366
0,0283

Max
current
carrying
capacity
in ground
(T 20 C,
depth 1 m,
gtr Km/W)
(A)

( )

* trefoil formation

153

Power
cables

TEPLA
Plant & Petrochem Cables

TEPLA M - SD
(XLPE/CuT/DRYLAM/PVC)

multi-core

from 3,6/6 (7,2) kV to 18/30 (36) kV

Construction

>
>
>
>
>
>
>

>
>

Applicable
standards

IEC 60502-2 Design and tests guidelines


IEC 60228
Conductors
IEC 60332-1 Flame retardant
Prysmian document GPD-003 for chemical moisture barrier

IEC 60332-1

154

EXCELLENT

STANDARD

0 C

Conductor
bare copper circular stranded, according to class 2 of IEC 60228
Semiconducting layer
extruded compound
Insulation
XLPE compound
Semiconducting layer
extruded compound
Metallic screen
copper tapes
Fillers
penetrating non hygroscopic compound
Chemical moisture barrier
longitudinally applied Al tape bonded with extruded chemical resistant
polymeric layer
Sheath
PVC compound ST2 quality
Marking
e. g. : PRYSMIAN year - n x csa 3,6/6 kV

14 D

Pb

90C

250C

NORMAL
OPERATION
TEMPERATURE

SHORT
CIRCUIT
TEMPERATURE

technergy

TM

INTEGRATED CABLING SOLUTIONS

> Power cables according to IEC 60502-2


> Flame retardant cables according to IEC 60332-1

TEPLA M - SD from 3,6/6 (7,2) to18/30 (36) kV (XLPE/CuT/DRYLAM/PVC) - multi-core

(kV)

(mm2)

(mm)

(/km)

(mm)

(mm)

(mm)

(mm)

Phase
Min
Phase Conductor
Max
Max
bending reactance capacity short
current current
radius at 50 Hz approx
circuit carrying carrying
approx
current capacity capacity
in air
in
30 C
ground
(single (T 20 C,
core in depth 1
trefoil
m, gtr
format)
Km/W)
(/km) (F/km) (kA/sec)
(kg/km)
(mm)
(A)
(A)

RE4H1OH5R4R

6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10
6/10

3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300
3x400

7,0
8,1
9,8
11,4
12,9
14,3
15,7
18,4
20,5
22,9

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470

14,0
16,2
17,7
19,4
20,9
22,3
23,8
26,4
29,0
31,4

16,2
17,4
18,9
20,6
22,1
23,5
25
27,6
30,1
32,5

36,6
39,0
42,4
46,0
49,2
52,6
55,8
61,4
66,9
72,5

43,4
45,8
49,6
53,3
57,3
60,4
64,0
69,4
75,6
81,3

2796
3304
4133
5137
6157
7156
8449
10500
12838
15692

610
640
700
750
800
850
900
970
1060
1140

0,11
0,11
0,10
0,10
0,09
0,09
0,09
0,09
0,08
0,08

0,20
0,25
0,28
0,31
0,34
0,37
0,40
0,45
0,50
0,55

5,0
7,2
10,0
13,6
17,2
21,5
26,5
34,4
43,0
>50,0

190
213
265
320
366
414
473
552
630
717

181
212
259
308
348
389
435
501
560
628

RE4H1OH5R4R

12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20
12/20

3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300
3x400

7,0
8,2
9,7
11,4
12,9
14,3
15,8
18,4
20,6
23,0

0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,0470

19,2
20,4
21,9
23,6
25,1
26,5
28,0
30,6
33,2
35,6

20,4
21,6
23,1
24,8
26,2
27,6
29,2
31,8
34,3
36,7

45,6
48,1
51,4
55,4
58,5
61,5
64,9
70,5
76,4
81,5

52,5
55,3
59,2
63,0
66,4
69,5
73,3
78,8
84,7
90,5

3660
4268
5166
6263
7250
8304
9710
11882
14252
17229

720
750
800
860
910
950
1000
1090
1170
1250

0,13
0,12
0,11
0,11
0,10
0,10
0,10
0,09
0,09
0,09

0,16
0,17
0,19
0,22
0,24
0,25
0,27
0,30
0,34
0,37

5,0
7,2
10
13,6
17,2
21,5
26,5
34,4
43,0
>50,0

183
217
269
324
371
417
476
553
630
717

180
212
258
307
347
386
432
498
560
628

Type

Voltage

Cross Diameter Maximum Diameter Diameter Diameter Outer


Weight
DC
section
of
over
over
over diameter
of
conductor resistance insulation screen extruded approx
cable
at 20 C approx approx
inner
approx
covering

155

Notes

156

TEPLA
Plant & Petrochem Cables

technergy

TM

INTEGRATED CABLING SOLUTIONS

157

Notes

158

TEPLA
Plant & Petrochem Cables

technergy

TM

INTEGRATED CABLING SOLUTIONS

159

TEPLA
Plant & Petrochem Cables
Prysmian TechnergyTM Plant & Petrochem Cables General
Catalogue, April 2007.
Prysmian reserves the right to modify at any time the technical,
dimensional and weight characteristics shown in this catalogue
anyhow always in accordance to the mentioned Standards in
case it improves the features of its products.
There is no responsibility of the manufacturer for damages to
persons and property in case of improper use and/or neglecting
the recommendations for using cables and norms, contained
in this catalogue, relevant to installation and operation in
plant and petrochem applications.

160

technergy
INTEGRATED CABLING SOLUTIONS

TM

HONG KONG
Prysmian Cable Systems Pte. Ltd.
Unit A, 18/F, China Overseas Building
139 Hennessy Road
Wanchai, Hong Kong
tel. +85 2 2827 8308
fax +85 2 2827 7212

AUSTRALIA
Prysmian Power Cables & Systems
Australia PTY LTD
1 Heathcote Road
Locked Bag 7042, Liverpool Business Centre 1871
NSW
tel. +61 2 96000 777
fax +61 2 96000 747

HUNGARY
Prysmian MKM Magyar Hungarian Cable
Works Co. Ltd.
Barzda u. 38
H-1116 Budapest
tel. +36 1 3822222
fax +36 1 3822202

AUSTRIA
Prysmian OEKW GmbH
Lembockgasse 47A, 1230 Wien
tel. +43 1 866770
fax +43 1 86677109
BRAZIL
Prysmian Energia Cabos e Sistemas do Brasil S. A.
Av. Alexandre de Gusmao 145
09110-900 Santo Andr - SP
tel. +55 11 49984000
fax +55 11 49984811
CHINA
Prysmian Tianjin Cables Co. Ltd.
513, Huang He Road, Nankai District
Tianjin, 300112
tel. +86 22 2753 9679
fax +86 22 2753 3485
EGYPT
Prysmian Cables & Systems
8 Abd El Azim Aoudallah st. Hegaz sq.
Heliopolis - Cairo
tel. +20 2 2418557
fax +20 2 6381327
FINLAND
Prysmian Cables & Systems Oy
P.O. Box 13
FIN-02401 Kirkkonummi
tel. +358 10 77551
fax +358 9 2982204
FRANCE
Prysmian Energie Cables et Systmes France s.a.
19, Avenue de la Paix - BP 712
Paron - 89100, Sens Cedex
tel. +33 3 86957769
fax +33 3 86957781
GERMANY
Prysmian Kabel und Systeme GmbH
Austrasse 99
96465 Neustadt bei Coburg
tel. +49 9568 895 1000
fax +49 30 3675 6000

INDONESIA
PT. Prysmian Cables Indonesia
Gedung BRI II, Suite 1502
Jln. Jend Sudirman No 44-46
Jakarta 10210
tel. +62 264 351222
fax +62 264 351780
ITALY
Prysmian Cavi e Sistemi Energia Italia Srl
Viale Sarca 222, 20126 Milano
tel. +39 02 6449 8108
fax +39 02 6440 8108
MALAYSIA
Prysmian Cable Systems Pte. Ltd.
Power Cable Malaysia Sdn Bhdn
Lot 2 Jalan Kawat 15/18
40702 Shah Alam, Selangor Darul Ehsan
tel. +60 3 5518 4528
fax +60 3 5511 9590
NETHERLANDS
Prysmian Cables and Systems B.V.
Schieweg 9, 2627 AN Delft
P.O. Box 495, 2600 AL Delft
The Netherlands
tel. +31 15 260 5260
fax +31 15 261 3808
NORTH AMERICA
Prysmian Cables & Systems North America
700 Industrial Drive
Lexington, SC 29072 - USA
tel. +1 803 9511130
fax +1 803 9511092
NORWAY
Prysmian Kabler og Systmer AS
P.O.Box 1384, N - 1401 Ski
tel. +47 64 915713
fax +47 64 915714
ROMANIA
Prysmian Cabluri si Sisteme SA
Soseaua Draganesti, Km. 4 - 0500 Slatina
tel. +40 49 435699
fax +40 49 433484

RUSSIA
Prysmian Cables and Systems
6th street 8 Marta, 6a, bldg 1
Moscow 125167
tel. +7 095 9337036
fax +7 095 9337035
SINGAPORE
Prysmian Cable Systems Pte. Ltd.
No 4 Tuas Avenue 12. 3rd Storey
639047 Singapore
tel. +65 6862 9866
fax +65 6862 9877
SLOVAKIA
Prysmian Kablo s.r.o.
Trnavska cesta 50
821 02 Bratislava
tel. +421 2 4949 1215
fax +421 2 4949 1248
SPAIN
Prysmian Cables y Sistemas S.L.
Carretera C-15, Km. 2
08800 Vilanova i la Geltr (Barcelona)
tel. +34 93 811 6181
fax +34 93 811 6011
SWEDEN
Prysmian Kablar och System AB
Turebergs All 2
SE-19162 Sollentuna
tel. +46 8 260416
fax +46 8 260413
THAILAND
Prysmian Cable Systems Pte Ltd.
555 RASA Tower 11th Floor
Phaholyothin Road, Lardyao
Chatuchak - Bangkok 10900
tel. +66 2 937 0316
fax +66 2 937 0318
TURKEY
Turk Prysmian Kablo ve Sistemleri A.S.
Buyukdere Caddesi No 117
34394 Gayrettepe
Istanbul
tel. +90 212 3551500
fax +90 212 2175810
U.A.E. (Dubai)
Prysmian Cabels and Systems Middle East
P.O. Box 72125, Dubai
tel. +971 4 345 7870
fax +971 4 345 7101
UK
Prysmian Cables and Systems Ltd.
Chickenhall Lane
Eastleigh
Hampshire, SO50 6YU
tel. +44 2380 295555
fax +44 2380 295111

World Wide Excellence Center


4

tel. +39 02 6449 8108, fax +39 02 6440 8108

Head Office
Prysmian Cables and Systems - Viale Sarca 222, 20126 Milano, Italy - tel. +39 02 6449 1, fax +39 02 6449 2931 - www.prysmian.com

dega design group

ARGENTINA
Prysmian Energa Cables y Sistemas
de Argentina S. A.
Fbrica La Rosa, Av. da Argentina 6784
1439 Capital Federal
tel. +54 11 46302000
fax +54 11 46302100

Anda mungkin juga menyukai