Anda di halaman 1dari 2

_______________________________________________________________ ____

Phoenix Inverter

Phoenix Inverter

SinusMax - Superior engineering Developed for professional duty, the Phoenix range of inverters is suitable for the widest range of applications. The design criteria have been to produce a true sine wave inverter with optimised efficiency but without compromise in performance. Employing hybrid HF technology, the result is a top quality product with compact dimensions, light in weight and capable of supplying power, problem-free, to any load. Extra start-up power A unique feature of the SinusMax technology is very high start-up power. Conventional high frequency technology does not offer such extreme performance. Phoenix inverters, however, are well suited to power up difficult loads such as refrigeration compressors, electric motors and similar appliances. Virtually unlimited power thanks to parallel and 3-phase operation capability Up to 6 units Phoenix 24/3000 can operate in parallel to achieve higher power output. Six 24/3000 units, for example, will provide 15 kW / 18 kVA output power. Operation in 3-phase configuration is also possible. (Please request VE.Bus enabled units for best 3 phase performance) To transfer the load to another AC source: the automatic transfer switch If an automatic transfer switch is required on models rated at 800 VA or more, we recommend to using the Phoenix Multi instead. The switch is included in these products and the charger function of the Multi can be disabled. For our lower power models we recommend the use of our Filax Automatic Transfer Switch. Computers and other electronic equipment will continue to operate without disruption because both the Filax and the Phoenix Multi feature a very short switchover time (less than 20 milliseconds). Computer interface All models rated at 1200 VA or more have a RS-485 computer interface. All you need to connect to your PC is our data link MK2 (see under accessories). This data link takes care of galvanic isolation between the inverter and the computer, and converts from RS-485 to RS-232. Together with the VEConfigure software, which can be downloaded free of charge from our website www.victronenergy.com, all parameters of the inverters can be customised. This includes output voltage and frequency, over and under voltage settings and programming the relay. This relay can for example be used to signal several alarm conditions, or to start a generator. The inverters can also be connected to VENet, the new power control network of Victron Energy, or to other computerised monitoring and control systems. New applications of high power inverters The possibilities of paralleled high power inverters are truly amazing. For ideas, examples and battery capacity calculations please refer to our book Electricity on board (available free of charge from Victron Energy and downloadable from www.victronenergy.com).

Application example

Victron Energy B.V. / De Paal 35 / 1351 JG ALMERE / The Netherlands Phone: (+31) (0)36 535 97 00 / Fax: (+31) (0)36 535 97 40 / www.victronenergy.com / e-mail: sales@victronenergy.com

Specifications
Phoenix inverter 12 Volt 24 Volt 48 Volt 12/180 24/180 48/180
10,5 - 15,5 21,0 - 31,0 42,0 - 62,0 180 180 180 175 / 150 175 / 150 175 / 150 200 200 200 91 / 92 / 92 2,2 / 3,0 / 4,0 n. a. a,b,d,h

12/350 24/350 48/350


10,5 - 15,5 21,0 - 31,0 42,0 - 62,0 350 350 350 300 / 250 300 / 250 300 / 250 500 500 500 90 / 91/ 92 3,0 / 3,5 / 4,0 n. a. a,b,d,h

12/750 24/750 48/750


10,5 - 15,5 21,0 - 31,0 41,0 - 62,0 750 750 750 700 / 650 700 / 650 700 / 650 1400 1400 1400 91 / 93 / 94 12 / 12 / 12 3/4/5 a,b,d,h

C 12/1200 C 24/1200
9,5 - 16,0 19,5 - 32,2 1200 1200 1000 / 900 1000 / 900 2200 2200 93 / 94 8 / 11 5/8
relay driver (7)

C 12/1600 C 24/1600
9,5 - 16,0 19,5 - 33,0 1600 1600 1300 / 1200 1300 / 1200 2300 3000 93 / 94 8 / 11 5/8
relay driver (7)

C 12/2000 C 24/2000
9,5 - 16,0 19,5 - 33,0 2000 2000 1600 / 1450 1600 / 1450 4000 4000 93 / 94 10 / 13 8 / 10
relay driver (7)

12/3000 24/3000 48/3000

(4) (4) (4)

Input voltage range (V DC) Cont. output power at 25 C (VA)


(5)

Cont. power at 25 / 40 (W) C C

Phoenix Inverter

Peak power (W) Max. efficiency 12 / 24 / 48 V (%) Zero-load power 12 / 24 / 48 V (W) Zero-load power in AES mode Multi purpose relay driver or relay
(6)

9,5 - 16,0 19,5 - 33,0 38,0 - 66,0 3000 3000 3000 2500 / 2000 2500 / 2000 2500 / 2000 6000 6000 6000 93 / 94 / 95 15 / 15 / 16 10 / 10 / 12 relay a-h

Protection (3) Common Characteristics (2,3) ENCLOSURE Material & Colour Battery-connection 230 V AC-connection Protection category Weight (kg) Dimensions (hxwxd in mm) ACCESSORIES Remote panel (RS 485 port) Remote on-off switch Automatic transfer switch STANDARDS Safety Emission / Immunity Automotive Directive

a,b,c,d,f,g,h

a,b,c,d,f,g,h

a,b,c,d,f,g,h

Output: 230 V 2% / 50/60 Hz 0,2% (switch selectable) Operating temperature range: -20 to +50 (fan assisted cooling) C Humidity (non condensing) : max 95% aluminium (blue Ral 5012) 1) IP 20 2,7 72x132x200 1) IP 20 3,5 72x155x237 Screw conn. IP 20 2,7 72x180x295 1) G-ST18i IP 21 10 375x214x110 (PIV) Filax EN 60950 Filax EN 60950 Filax EN 60950 Phoenix Multi EN 60335-1 1) G-ST18i IP 21 10 375x214x110 (PIV) Phoenix Multi EN 60335-1 M8 studs
Spring-clamp

M8 studs
Screw-clamp

IEC-320 (IEC-320 plug included) or Schuko

IP 21 12 520x255x125 (PIV) Phoenix Multi EN 60335-1

IP 21 18 362x258x218 (PIV) Phoenix Multi EN 60335-1

EN55014-1 / EN 55014-2 95/54/EC and 2004/104/EC 5) Non linear load, crest factor 3:1 6) Multipurpose relay which can be set for general alarm, DC undervoltage or genset start signal function 7) Relay driver: open collector 66V 40mA

1) Battery cables of 1.5 meter (12/180 with cigarette plug) 2) 115 V AC on request 3) Protection a. Output short circuit b. Overload c. Battery voltage too high d. Battery voltage too low e. Battery reverse polarity detection f. 230 V AC on inverter output g. Input voltage ripple too high h. Temperature too high 4) Suitable for parallel and 3-phase operation

Five parallel units: output power 12,5 kW

Accessories

Battery Alarm
An excessively high or low battery voltage is indicated by an audible and visual alarm, and a relay for remote signalling. .

Phoenix Inverter Control (PIV)


This panel is intended for the models equipped with a RS-485 data port. It can also be used on a Phoenix Multi when an automatic transfer switch but no charger function is desired. The brightness of the LEDs is automatically reduced during night time.

Computer controlled operation and monitoring (Victron Interface MK2)


All models rated at 1200 VA or more are ready to communicate with a computer through a RS-485 data port. All you need to link to your PC and be able to set and read out all parameters is the data link as shown and software available on our website. (see also A guide to VEConfigure) Moreover, all Victron Energy products equipped with an RS-485 data port can easily be integrated in VE.Net, the new power control network of Victron Energy, or in other computerised monitoring and control systems.

BMV-501 Battery Monitor


The BMV 501 Battery Monitor features an advanced microprocessor control system combined with high resolution measuring systems for battery voltage and charge/discharge current. Besides this, the software includes complex calculation algorithms, like Peukerts formula, to exactly determine the state of charge of the battery. The BMV 501 selectively displays battery voltage, current, consumed Ah or time to go. The monitor also stores a host of data regarding performance and use of the battery.

Victron Energy B.V. / De Paal 35 / 1351 JG ALMERE / The Netherlands Phone: (+31) (0)36 535 97 00 / Fax: (+31) (0)36 535 97 40 / www.victronenergy.com / e-mail: sales@victronenergy.com

Anda mungkin juga menyukai