08180018.2
03/2001
CONTENTS
PAGE
UNIT SPECIFICATIONS MAJOR COMPONENTS SPECIFICATION ROOM TEMPERATURE CONTROL UNIT DIMENSIONS PERFORMANCE CHART ELECTRIC WIRING DIAGRAM THE UNIT DOES NOT WORK ELECTRIC CIRCUIT INTERRUPTED WHEN "ON" BUTTON IS PRESSED
ELECTRICAL CIRCUIT INTERRUPTED AFTER "ON" PRESSED
(WAIT 3 MINUTES ONLY FOR MODELS WITH "TT5" ELECTRONIC CONTROL)
3 4-5 6 6 7 8-9 10 10 11 11 12 12 12 13 13
FAN MOTOR DOES NOT WORK WHILE "ON" BUTTON IS PRESSED. (FMI) INDOOR FAN MOTOR WORKS AT ONE SPEED ONLY POOR COOLING POOR HEATING FAN MOTOR WORKS NORMALLY BUT THE COMPRESSOR DOES NOT OPERATE (FMO) OUTDOOR FAN MOTOR DOES NOT OPERATE THE FLASHING LED IS ON, AND THE UNIT DOES NOT OPERATE COMPRESSOR DOES NOT WORK BUT FAN MOTOR OPERATES NORMALLY
14
14
2 di 14
SAP-P91G5/P92Q5HK/P93GS5/P93G5A
SAP-P92Q5/P93G5 COOLING HEATING
230V BTU/h W (Kcal/h) High/low m/h High/low m/h l/h 9000 2640 (2270) 500/400 1150 0,92 230V 198264 4,7/5,2* 9,7 1050 2170 2,7 20 (SAP-P91G5/P92Q5/P92Q5HK) 21-23 (SAP-P93G5/P93GS5)* Electronic/ I.C. thermostat switches on the unit two Rotary (hermetic) 690 (SAP-P91G5/P92Q5/P92Q5HK) 640 (SAP-P93G5/P93GS5) Capillary tube 53/48 48 2 900 415 330 440 375 230 42 9 Data can be changed without notice 6880 2000(1720)
-
V A W A A
Refrigerant control Noise level Lp (NOTE 3) Flexible tube lenght DIMENSIONS & WEIGHT Internal unit
External unit
Net weight
Height Width Depth Height Width Depth Internal unit External unit
NOTE 1: Rating conditions (ISO 5151): Internal temperature: 27C D.B. , 19C W.B. External temperature: 32C D.B. , 24C W.B. NOTE 2: Operating limits: MINIMUM Internal temperature: 19C D.B.,14C W.B. External temperature: NOTE 3: Refering data : 18C D.B.
Internal unit: room size 100m3 ; reverberation time 0,5sec.; distance 2m. External unit: hemispheric radiance; distance 4m.
3 di 14
COMPRESSOR Rotary (hermetic) Model Nominal input (230V) Compressor oil Coil resistance ( 20C) RUN CAPACITOR Capacity Tension SAFETY DEVICES Type Operating temperature Operating amperes (ambient temperature 25C) COMPRESSOR Rotary (hermetic) Model Nominal input (230V) Compressor oil Coil resistance ( 20C) RUN CAPACITOR Capacity Tension SAFETY DEVICES Operating temperature Operating amperes (ambient temperature 25C) AIR TEMPERATURE SENSOR Resistance FAN MOTOR Centrifugal blower Power supply Number of poles High/low speed Nominal input (230V) Coil resistance ( 20C)
(CM) W cc C-R C-S (C3) F V~ (OLR) open C close C Opens with (CM) W cc C-R C-S (C3) F V~ (OLR) open C close C Opens with (TH1) k (FMI) dimensions mm
TT6 Electronic 18,5 1,5C 31 2C 0,9 0,2C 2 +1/-0 min. ON/OFF button COOLING button HIGH/LOW speed ALARM lamp SAP-P91G5/P92Q5/P92Q5HK 806 835 45 890 500 3,263,387% 7,498367% Compressor 20 450 External type MRA38074-3229 / MRA 99003-6V 1405C 6911C 16 A in 616 sec. SAP-P93G5/P93GS5 RH165VHAT 910/930 300 3,337% 6,017% Compressor 25 450 Internal type 1505C 9010C 28 A in 310 sec. NTC 5,8 ( a 22C) MO1395 RR170Z9443,01 170 x 156 230V~50Hz 4
Rpm W 90
4 di 14
FAN CAPACITOR Capacity Tension FLOAT MICROSWITCH Contacts rating POWER RELAY (compressor) Coil supply Coil resistance ( 20C) Contacts rating ELECTRIC HEATER RELAY Coil supply Coil resistance Contacts rating SAFETY THERMOSTAT(HEATER) SAFETY THERMOFUSE(HEATER) DRAIN PUMP Power supply Nominal input (220V) Coil resistance (20C) PUMP RELAY Coil supply Coil resistance ( 20C) Contacts rating HEAT EXCHANGER COIL Coils Rows Fin pitch Face area FAN MOTOR Axial blower Power supply Number of poles Rpm Nominal input (220V) Coil resistance ( 20C)
mm m (FMO) mm
Safety devices Setting: open RUN CAPACITOR Capacity Tension HEAT EXCHANGER Coils Rows Fin pitch Face area mm m open close (C2) F V~ C
Internal fan 1,5 450 CROUZET F83161.3.161L 12(3)A - 250VAC FINDER 65.31 230V~50Hz 725010% 30A - 250V FINDER 65.22 230 VAC - 50 Hz 7250 10% 16A - 250 VAC A70 - 172 71C 6% with PTC MD4204A 98C+0C-4C MES-PC-30.95643.02 230V~50Hz 1210% 94010% FINDER 60.61 230V~50Hz 725010% 10A - 250V Evaporator coil Alluminium fin / Copper tube 2 1,8 0,08 MO1515 280 230V~50Hz 4 1230 61 BLUE - BROWN 2637% BLUE - BLACK 2857% Internal thermostat 15010 Automatic External fan motor 2 450 Condenser coil Alluminium fin / Copper tube 2 1,6 0,23
5 di 14
ON/OFF SWITCH COMPRESSORE SWITCH COMPRESSOR SET TEMPERATURE +1C SET TEMPERATURE FAN SET SPEED
NOTES:
1. If the compressor is turned off, the control circuit sets an automatic minimum 2 minutes delay to protect the compressor from stalling out when trying to start against the high side refrigerant pressure. 2. If the room temperature is 1C above the set temperature, the compressor starts working if this has been OFF for at least 3 minutes. 3. If the room temperature is the same or under the set temperature the compressor stops working.
4) UNIT DIMENSION mm
W mm
415 375
D mm
330 230
5,5
32 C
27C
4,5
21C
3,5
3 20 22 24 26 28 30 32 34 36 38 40 42 44 46
EXTERNAL TEMPERATURE (C) OPERATING CHARACTERISTICS WITH RELATIVE HUMIDITY AROUND 50%
7 di 14
Legend of colors
N/BLK B/BLU M/BRN G/V-GRN/YEL A/ORG R/RED W/WHT YEL GRN PNK G/GRY BLACK BLUE BROWN GREEN/YELLOW ORANGE RED WHITE YELLOW GREEN PINK GREY
SAP-P91G5
Temperatura Corrente
8 di 14
NOTA:
9 di 14
NO
NO
NO
NO
NO
electric heater
Is it short circuited?
10 di 14
SERVICE MANUAL
(WAIT 3 MINUTES ONLY FOR MODELS WITH "TT5" ELECTRONIC CONTROL)
COOLING OPERATION
NO
connections are
insulated. YES Check if compressor relay YES
NO
Check insulation on heater relay connections (RR) YES Check if the heater relay
YES
works
Is it in short circuit ? YES YES Check the heater(RE)
NO
NO
Replace (FMO)
outdoor fan motor
11 di 14
NO
6. POOR COOLING
Is the unit cooling capacity suitable for the room thermal loads ? YES Are both air filters and heat exchanger cleaned ? YES Check if Difference between room air temperature and outlet air delivered is up to 10 C NO Suggest a more powerful unit
NO
YES
NO
Low R22 gas charge Proceed with normal operations foreseen for the above points
NO
12 di 14
SERVICE MANUAL
8. FAN MOTOR WORKS NORMALLY BUT THE COMPRESSOR DOES NOT OPERATE(FMI)
Check hardness and continuity. Is the relay compressor coil (PR white cable) power supplied ? Replace the relay (PR) NO
YES Check if relay contects are closed YES YES Is the thermostat in the right posi tion ? YES Is room tempera ture over 19 C ? YES Check the sensor continuity (TH1) through 7-8 electronic control (CE) terminal blocks YES Check electronic control (CE) NO Replace the sensor (TH1) NO Adjust thermostat position
YES
Check compressor klixon contacts(ORL) Are they open ? NO Check the capaci tor capacity (C)
NO
NO
YES
NO
NO
YES
Disconnect the unit from line and manually rotate the propeller
NO
YES
Check electrical connections and winding continuity on outdoor fan(FMO).
NO
YES
Is the voltage in coil relay (RC)
YES
NO
Replace relay(RC)
NO
Check electronic control (CE)
NO
Replace electronic control (CE)
13 di 14
SERVICE MANUAL
10.THE FLASHING LED IS ON, AND THE UNIT DOES NOT OPERATE
Check electrical connections and cable continuity. YES Check micro floating pump (MP) (ONLY SAP-P91G5) YES Check safety micro floating (MS)
NO
NO
YES Check condensate pump motor (PC) YES Check pump relay (RP)
NO
NO
Replace relay(RC)
NO
YES Check if relay contact is closed YES Check if compressor klixon is open YES Check compressor capacitor(C) YES Check compressor winding continuity
NO
Replace klixon(K)
NO
NO
Fit it properly,
NO
NO
Replace compressor.
NO
NO
14 di 14