Anda di halaman 1dari 8

2006 Seattle Nonresidential Energy Code Compliance Form Instructions for 2006 Seattle Energy Code Electronic Forms

Revised Dec 2007

Start-up Overvie w Save Files Getting Around Filling Fields

This file, 2006sec-MECH.XLS, has electronic versions of the 2006 compliance forms for mechanical systems. Open a working copy of this file and be sure to use Save As to save it to a new file name. Alternatively, you can save the file as a template in the XLSTART subdirectory in the EXCEL directory, and open new copies with the "File New" menu command. Look for "2006secMECH". This workbook file contains multiple worksheets. Each worksheet is indicated by a tab at the bottom of the screen. (If you don't see the tabs, visit menu option "Tools-Options-View-Sheet Tabs".) You may visit each form by clicking on its tab. Most calculations are automated. The spaces which display the results of calculations are not editable. Some adjustments to formatting have been made to facilitate electronic filling and calculation of the forms. Each time you open this file and start filling forms, you must save it under a new filename of your choosing using File Save As. The original template file cannot be altered. You may also save your own versions of the forms this way. Each form has two pages (front and back). Both pages are available on screen when you click the tab for a form. Use the scroll bars to find the second page. It is either to the right, below, or sometimes to the right and below the first page. All project info and the date for all forms is entered once on "MECH-SUM" and automatically reproduced on the other forms. Always fill in the heading of MECH-SUM, even if you will not be using that form. The other forms have a reminder to do this. Only fillable fields are accessible. If you try to edit any other field, you'll get an error message. You may use the TAB key to move to the next fillable field. If the TAB doesn't take you where you want to go, use the mouse. Avoid excessively long text strings when entering information. In some cases, text that extends beyond the available space will simply not be seen. In most cases, the text will wrap within the cell. This may force part of the form onto a new page To enter the date, use this format: mm/dd/yyyy. For example, you would enter 7/2/2006 or 12/15/2007. On MECH-MOT, horsepower (HP) is displayed in fractions, but may be entered any way. For example, 1-1/2 may be entered as "1.5" or as "1 1/2". Check boxes can be either blank, or checked-off with an "x" shown in the box. To toggle between cases, click the box with your mouse. Radio buttons (circles) are either filled or unfilled. Only one in a set may be filled. Drop-down lists have an arrow at the right side of the space. Click the arrow with your mouse and select the appropriate option. One of the options is a blank. When a form has a space for notes or explanation, click anywhere in the space to edit. Your cursor will become a text editing insertion bar and you can edit as with a word processor.

You can address, phone, Personal footer using personalize the forms with your company name,save the file underor any other information. This is done by editing the File Page Setup Header/Footer. You can then a new template name and re-use it again. izing Many tables, such as for listing equipment types, have a certain number of lines for entering data. There may not always be Adding enough lines for all the entries you need to make. With this electronic version, you can add additional lines to the table.

Lines To add additional lines where this feature is available, click on the "+" button with your mouse. This button is located to the right and of the sheet. If you can't see it, scroll right (or change the View Zoom setting to 83%). Removin To remove lines that you have added, click on the "-" button with your mouse. You cannot remove lines that were not added; an error appears if you try. g
If you add additional lines with this method, the pagination will usually be affected. The forms will be forced to carry additional lines over to other pages. Be sure to submit all pages to the plans examiner.

Printing

The forms should print on any printer supported by Windows. You will need to have the following TrueType fonts installed under Windows: Arial, Times New Roman, Courrier New and Wingdings. These are all standard Windows fonts. If you are losing form or flowchart details when printing, you may have a shortage of printer memory. Try printing problem pages individually. By default, only selected forms are printed. To select one or more forms, hold down the Ctrl key and click the tabs of the worksheets you need. Issue the File Print Selected Sheets command. To print the entire set, use File Print Entire Workbook.

Clean Forms Partial Form Sets MECHSUM

It is possible to print clean, blank versions of these forms for hand filling. To do so, delete all of the heading information at the beginning of MECH-SUM, and make sure that all fillable cells in the forms are empty. Then print the clean forms. For each radio button group, there is a button labeled "Clear". Clicking this button will clear the other buttons so that they will print as empty circles. The "Clear" button will not print. There are two companion templates to this file: 2006sec-ENV.XLS (chapter 13 envelope requirements); 2006sec-LGT.XLS (Chapter 15 lighting requirements). Forms in a set may not be deleted, because the file is locked, but you need not print all the forms, as explained in "Printing" above. If your building has both Simple Systems and Complex Systems, you must use separate copies of MECH-SUM for each type. Two copies of the form are provided for this purpose.

As this respond slowly to changes Re-Calcu calculation is a large file, it may"Tools-Options-Calculation" if it is set to automatically re-calculate after every action. To set to manual, visit the menu item. Then manually recalculate using the F9 key. lation

2006 Seattle Nonresidential Energy Code Compliance Form Mechanical Summary MECH-SUM
2006 Seattle Nonresidential Energy Code Compliance Forms
Revised Dec 2007

Project Info

Project Address

1 - Always fill out this line on MECH-SUM1 2 - Fill out this line on MECH-SUM1 3 - Fill out this line on MECH-SUM1

Date

7/29/2011

For Building Dept. Use

Applicant Name: Applicant Address: Applicant Phone:

4 - Fill out this line on MECH-SUM1 5 - Fill out this line on MECH-SUM1 6 - Fill out this line on MECH-SUM1

#REF! #REF!

Project Description
Briefly describe mechanical system type and features. Includes Plans FALSE

Include documentation requiring compliance with commissioning requirements, Section 1416. Prescriptive Path Clear buttons See reverse for economizer flowchart. Systems Analysis

Compliance OptionSeattle no longer has a separate simple system path.

The following information is required to be incorporated with the mechanical equipment schedules on the Equipment Schedules plans. For projects without plans, fill in the required information below.

Cooling Equipment Schedule


Equip. ID Brand Name1 Model No.1 Capacity2 Btu/h Total CFM OSA CFM or Econo? SEER or EER IPLV3 Location

Heating Equipment Schedule


Equip. ID Brand Name1 Model No.1 Capacity2 Btu/h Total CFM OSA cfm or Econo? Input Btuh Output Btuh Efficiency4

Fan Equipment Schedule


Equip. ID Brand Name1 Model No.1 CFM SP1 HP/BHP Flow Control5 Location of Service

2 3 4 If available. As tested according to Table 14-1A through 14-1G. If required. COP, HSPF, Combustion Efficiency, or AFUE, as applicable. 5 Flow control types: variable air volume(VAV), constant volume (CV), or variable speed (VS). 1

E E c x o E n c 4 o E . m n c 2006 Seattle Nonresidential Energy Code Compliance Forms 0 ? Revised Dec 2007 _ i? o _ z? m n Economizer Summary Full Air Econo ____________________________________________________________________ _ e? i o Check box(es) for exceptions being _ z m Ex 4: ___________________ claimed. List the system/equipment Ex 1: ___________________ Ex 2: ___________________ r _ i e that qualifies for each exception. See _ r z Section 1433 for full description of Ex 5: ___________________ Ex 6: ___________________ n Ex 7: ___________________ _ c i e Economizer requirements. _ n r Ex 8: ___________________ Ex 9a: __________________ l Ex 9b: __________________ ? _ u c i ? d l n Ex 9c: __________________ Ex 9d: __________________ ? e u c ? d l Decision Flowchart Use this flowchart to determine if project complies with Economizer requirements. If not, ? e u the Systems Analysis Option must be used. d ? e START d Reference ?

2006 Seattle Nonresidential Energy Code Compliance Form Economizer Summary MECH-SUM

Section 1433

100% Air Economizer No Exception 1: DX/AC Unit NOT Outdoors or Adj to Outdoors No Exception 2: Chilled Water System No

Yes

Full Air Economizer -Complies

Yes

Unit Cap <33,000 Btuh & EER 15% Over Code No Chiller Eff 10% Over Code No

Yes

Bldg. Cap. w/o economizer <72,000 Btuh or 5%? No

Yes

Yes

Yes

Exception 4: Cooling 75% Site HR or Solar No

Yes

Exception 5: Special OA Filtration Needs No

Yes

Exception 6: Dehumidification with supporting energy analysis No

Yes

Exception 7: Heat Pump Loop Yes Meeting All Criteria No

Exception 9: Dedicated Server or Eq Rm

Yes

Served by 14-1A or 14-1B Equipment No

Yes

Exception 9a: EER 15% Over Code No Waterside Economizer No

Yes

No

Exception 9c: Served by 14-1C, K,L M Chiller Yes Air Cooled No

Yes

Exception 9b: EER 5% Over Code

Yes

No Yes Exception 9d: ASHRAE 127 Equipment Passing 14-1A/14-1B EER Yes No 2 stage or better part load Yes for cap >85,000 Btuh? No

Yes

IPLV 10% Over Code No

Yes

IPLV 5% Over Code No

2006 Seattle Nonresidential Energy Code Compliance Form Mechanical - Complex Systems Checklist MECH-COMP
2006 Seattle Nonresidential Energy Code Compliance Forms Project Address 1 - Always fill out this line on MECH-SUM1 The following additional information is necessary to check a mechanical permit application for a complex mechanical system for compliance with the mechanical requirements in the Seattle Nonresidential Energy Code. Use the checklist as a reference for notes added to the mechanical drawings (see the MECH-CHK checklist for additional system requirements). This information must be on the plans since this is the official record of the permit. Having this information in separate specifications alone is NOT an acceptable alternative. Applicability (yes, no, n.a.) 4.0 4.0 4.0 Code Section Date Revised Dec 2007 7/29/2011 For Building Department Use

Component

Information Required

Location on Plans

Building Department Notes

ADDITIONAL CHECKLIST ITEMS FOR COMPLEX SYSTEMS ONLY


1431.1 1431.2 1432.1 Field assem. sys. System Sizing Setback & shut-off Provide calculations Provide design heating and cooling load calculations Indicate separate systems or show isolation devices on plans Indicate automatic reset Indicate automatic reset, cooling tower, & heat pump loop valves Indicate economizer on equipment schedule or specify exception claimed and provide calculations to justify qualification Indicate separate systems on plans Indicate that simultaneous heating and cooling is prohibited, unless use of exception is justified Indicate heat recovery on plans; complete and attach heat recovery calculations MECH-MOT or Equip. Schedule with hp, rpm, efficiency Indicate variable speed drive on fan and pump schedules Indicate uncooled and unheated make-up air Indicate VAV, unheated/uncooled or heat rec. makeup

4.0 1432.2.1 Air system reset 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 1432.2.2 Hydronic System 1433 1434 1435 1436 1437 1438 1439.1 1439.2 Air Economizer Separate air sys. Simul. htg. & clg. Heat recovery Elec. motor effic. All fans and pumps Kitchen Hoods Fume Hoods

If "no" is circled for any question, provide explanation:

Decision Flowchart

Use this flowchart to determine how the requirements of the Complex Systems Option apply to the project. Refer to the indicated Code sections for more complete information on the requirements.

Start Here

Section 1411 .1 Equipment Efficiency Shall Meet Tables 14-1A through 14-1G

Gas/Oil Furnace input 225,000 Btuh or Gas /Oil Unit Heater?

No

Any Fuel Furnace input 225,000 Btuh?

No

Field-Assembled Equipment ?

No

Air System Serving Multiple Zones?

No

Capacity of HW Heating System > 300 ,000 Btuh ?

Yes

Yes

Yes
Section 1431 .1 Calculations of Total On -Site Energy Input & Ouput Required

Yes

Yes
Section 1432 .2.2 Hot Water Supply Temperature Reset Required

No

yes no n.a.

1411 .1 Intermittent Ignition Device & Power Venting or Damper. If input 225 ,000 Btuh then 1412.6 Modulating or Staged Combustion Controls Required

1411.1 0.75 % Maximum Jacket Loss

Section 1432.2.1 Supply Air Reset Controls Required

(continued on back)

2006 Seattle Nonresidential Energy Code Compliance Form Mechanical - Complex Systems (back) MECH-COMP
2006 Seattle Nonresidential Energy Code Compliance Forms 12/30/99
Revised Dec 2007

Economizer Complies Section 1433 Yes

Supply Air and OSA SA >5,000 cfm & OSA>70% SA>10,000 cfm & OSA>50 % SA>20,000 cfm & OSA>30 %

Yes

Section 1436 50% Effective Heat Recovery Required

Motor Incl. in Eqpmt. Covr'd by Tbl 14-1A -141G? Yes

No

Multi-speed Motor in Multi speed system?

No

Section 1437 Motors Must Meet Efficiencies in Table 14-4 Yes

Yes

System or Zones w/ Simultaneous Htg. & Clg.? No

Yes

Section 1435 Zone Controls Must Reduce Supply Air Quantity Before Reheating/Recooling

Yes

Fans or Pumps > 7.5 HP?

Yes

Section 1438 Variable Flow Devices Required Yes

No

Section 1439.2 Total Bldg. Fume Exhaust > 15 ,000 cfm? One Required: Yes a. 50% VAV Exhaust & Make-up b. 75% Direct Makeup w / Tempering Only c. Heat Recovery per 1436 d. Constant Volume w / < 50fpm Face Velocity Yes

No Section 1439.1 No Heating or Cooling for at Least 50% of Make-up Air Yes

Kitchen Exhaust Hood > 5,000 cfm?

Yes

No DONE

2006 Seattle Nonresidential Energy Code Compliance Form Electric Motors MECH-MOT
2006 Seattle Nonresidential Energy Code Compliance Forms Project Address 1 - Always fill out this line on MECH-SUM1 Complete the following for all design A & B squirrel-cage, T-frame induction permanently wired polyphase motors from 1 hp to 200 hp having synchronous speeds of 3600, 1800 or 1200 rpm (unless one of the exceptions below applies). Date Revised Dec 2007 7/29/2011 For Building Department Use

Motor No. or Location

HP

Type (open/closed)

Description of Application or Use

Synch. Speed

Min.Nom. Full load Efficiency

Minimum Nominal Full-Load Efficiency


Open Motors Synchronous Speed (RPM) HP 1.0 1.5 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 3,600 82.5 84.0 84.0 85.5 87.5 88.5 89.5 90.2 91.0 91.0 91.7 92.4 93.0 93.0 93.0 93.6 93.6 94.5 1,800 1,200 Efficiency (%) 82.5 80.0 84.0 84.0 84.0 85.5 86.5 86.5 87.5 87.5 88.5 88.5 89.5 90.2 91.0 90.2 91.0 91.0 91.7 91.7 92.4 92.4 93.0 93.0 93.0 93.0 93.6 93.6 94.1 93.6 94.1 94.1 94.5 94.1 95.0 94.5 95.0 94.5 3,600 75.5 82.5 84.0 85.5 87.5 88.5 89.5 90.2 90.2 91.0 91.0 91.7 92.4 93.0 93.0 93.6 94.5 94.5 95.0 Closed Motors 1,800 1,200 Efficiency (%) 82.5 80.0 84.0 85.5 84.0 86.5 87.5 87.5 87.5 87.5 89.5 89.5 89.5 89.5 91.0 90.2 91.0 90.2 92.4 91.7 92.4 91.7 93.0 93.0 93.0 93.0 93.6 93.6 94.1 93.6 94.5 94.1 94.5 94.1 95.0 95.0 95.0 95.0

Exceptions: 1. Motors in systems designed to use more than one speed of a multi-speed motor. 2. Motors already included in the efficiency requirements for HVAC equipment (Tables 141A or 14-1B) . 3. Motors that are an integral part (i.e. not easily removed and replaced) of specialized process equipment (i.e. equipment which requires a special motor, such as an explosionproof motor). 4. Motors integral to a listed piece of equipment for which no qualifying motor has been approved (i.e. if the only U.L. listing for the equipment is with a less-efficient motor and there is no energy-efficient motor option). For motors claiming an exception, list motor and note which exception applies.

2006 Seattle Nonresidential Energy Code Compliance Form Mechanical Permit Plans Checklist MECH-CHK
2006 Seattle Nonresidential Energy Code Compliance Forms Project Address 1 - Always fill out this line on MECH-SUM1 Date Revised Dec 2007 7/29/2011 The following information is necessary to check a mechanical permit application for compliance with the mechanical requirements in the 2006 Seattle Nonresidential Energy Code. Applicability (yes, no, n.a.) Code Section 1411 1411.4 1411.1 1411.1 1412 1412.1 1412.2 1412.3 1412.4 Component Information Required Location Building Department on Plans Notes

HVAC REQUIREMENTS (Sections 1401-1424)


4.0 4.0 4.0 4.0 4.0 4.0 4.0 Equipment performance Pkg. elec. htg.& clg. List heat pumps on schedule Minimum efficiency Combustion htg. HVAC controls Temperature zones Deadband control Humidity control Automatic setback Equipment schedule with type, capacity, efficiency Indicate intermittent ignition, flue/draft damper & jacket loss Indicate locations on plans Indicate 5 degree deadband minimum Indicate humidistat Indicate thermostat with night setback and 7 diff. day types Indicate damper location and auto. controls & max. leakage Indicate optimum start controls Indicate microprocessor on thermostat schedule Indicate modulating or staged control Indicate balancing features on plans Indicate demand control ventilation for high-occupancy areas

4.0 1412.4.1 Dampers 4.0 1412.4.2 Optimum Start 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 1412.5 1412.6 1412.7 1412.8 1413 1413.1 1413.1 1413.2 1413.3 1413.4 1414 1414.1 1414.2 1415.1 Heat pump control Combustion htg. Balancing Ventilation Control

Economizers Air Econo Operation Indicate 100% capability on schedule Wtr Econo Operation Indicate 100% capacity at 45 degF db & 40 deg F wb Water Econo Doc Humidification Ducting systems Duct sealing Duct insulation Piping insulation Indicate clg load & water econo & clg tower performance Indicate direct evap or fog atomization w/ air economizer Indicate sealing necessary Indicate R-value of insulation on duct Indicate R-value of insulation on piping Integrated operation Indicate capability for partial cooling

1416 Completion Requirements 4.0 1416.2.1 Commissioning Provide commissioning plan 4.0 1416.2.2-3 Sys.Bal & Func.Test Indicate air and water system balancing & functional testing 4.0 1416.2.4 Commissioning 4.0 1416.2.5 Comm. Report 4.0 4 1434 Separate air sys. Mechanical Summary Form 1440 1441 1442 1443 1452 1452 1453 1454 1454 Service water htg. Elec. water heater Shut-off controls Pipe Insulation Heat Pump COP Heater Efficiency Pool covers Pools 90+ degrees Indicate O&M manuals, record drawings, staff training Indicate requirements for prelim. & final commissioning report Indicate separate systems on plans Completed and attached. Equipment schedule with types, input/output, efficiency, cfm, hp, economizer

SERVICE WATER HEATING AND HEATED POOLS (Sections 1440-1454)


4.0 4.0 4 4 4 4.0 4.0 4.0 Indicate R-10 insulation under tank Indicate automatic shut-off Indicate R-value of insulation on piping Indicate minimum COP of 4.0 Indicate pool heater efficiency Indicate vapor retardant cover Indicate R-12 pool cover, and R-12 sides and bottom

Pool heater controls Indicate switch and 65 degree control

If "no" is circled for any question, provide explanation:

klist

2006 Seattle Nonresidential Energy Code Compliance Form MECH-CHK Mechanical Permit Plans Checklist
Revised Dec 2007

2006 Seattle Nonresidential Energy Code Compliance Forms

alarm

uire

in aust hree

n ow the

pers rate

w.g.

inch n 24 0 inch

t shall lowest

NOTE THAT SINGLE-FAN/DUAL-DUCT SYSTEMS AND min outs MULTIZONE SYSTEMS DO NOT COMPLY WITH THIS REQUIREMENT. THIS IS BECAUSE ECONOMIZER OPERATION LOWERS THE TEMPERATURE OF THE AIR ENTERING THE HOT DECK HEATING COIL, INCREASING ITS ENERGY USE. IN ORDER TO USE THIS TYPE OF SYSTEM, THE SYSTEM MUST MEET ONE OF THE ECONOMIZER EXCEPTIONS AND HAVE NEITHER TYPE OF ECONOMIZER. (ANOTHER RESOLUTION IS TO USE A DUAL-FAN/DUAL-DUCT SYSTEM WHERE THE HOT DECK FAN SUPPLIES ONLY RETURN AIR OR RETURN AIR PLUS MINIMUM VENTILATION AIR.) THIS REQUIREMENT WILL NOT AFFECT THREEDECK MULTIZONE SINCE THEY CANNOT WORK WITH AN AIR ECONOMIZER IN ANY CASE (IT WOULD MAKE THE NEUTRAL DECK A COLD DECK). AN EXCEPTION TO THE HEATING IMPACT IS PROVIDED FOR ECONOMIZERS ON VAV SYSTEMS THAT CAUSE ZONE LEVEL HEATING TO INCREASE DUE TO A REDUCTION IN SUPPLY AIR TEMPERATURE. REDUCING SUPPLY AIR TEMPERATURES ON A COOLING-VAV SYSTEM WILL REDUCE FAN ENERGY (PARTICULARLY IF THE SYSTEM HAS A VARIABLE SPEED DRIVE), OFFSETTING THE ENERGY LOST DUE TO INCREASED REHEAT ENERGY. SEE THE DISCUSSION AND DIAGRAMS OF SECTION 6.5.1.4 OF ASHRAE/IESNA STANDARD 90.1 IN THE USERS MANUAL.

1414 Ducting Systems 1414.1 Sealing: Duct work which is designed to operate at pressures above inch water column static pressure shall be sealedin (( accordance with Standard RS-7. Extent of sealing required isas )) follows: 1. ((Static pressure: inch to 2 inches; seal transverse joints. )) (Reserved.) 2. Static pressure: (( )) inches to 3 inches; seal all transverse joints 2 and longitudinal seams. Spiral lock seams in round and flat oval ductwork do not require sealing, however, other seams shall be sealed. 3. Static pressure: above 3 inches; seal all transverse joints, longitudinal seams and duct wall penetrations. ((Duct tape and other pressure sensitive tape shall not be used as the primary sealant where ducts are designed to operate at static pressures of 1 inch W.C. or greater. )) All low-pressure supply and return air systems not located entirely within the conditioned space, including the unconditioned side of enclosed stud bays or joist cavities/spaces used to transport air, shall be securely fastened and sealed. Ductwork shall be sealed using welds, gaskets, mastic, or mastic-plus-embedded-fabric tape. Enclosed stud bays or joist cavities/spaces used to transport air shall be sealed using mastic-plus-embedded-fabric tape or, when drywall is used to enclose the air system, drywall mud and tape. Duct tape is not permitted as a sealant on any ducts. EXCEPTION:Fibrous glass duct systems installed in accordance with standard UL 181A and flexible duct systems installed in accordance with standard UL 181B may use tapes listed for these systems.

ems have gned to day to iately a perature led

shall heat ontrols the first ting is

on ave shall l to

tially-

432.2.

inal mited to,

Anda mungkin juga menyukai