MODULAR STURUCTURED MULTILEVEL INVERTER AS A THREE-PHASE SHUNT ACTIVE POWER FILTER WITH UNIFIED CONSTANT FREQUENCY INTEGRATION CONTROL

ALI IBRAHIM ISMAAIL

A project report submitted in partial fulfillment of the requirements for the award of the degree of Master of Engineering (Electrical Mechatronics & Automatic Control)

Faculty of Electrical Engineering Universiti Teknologi Malaysia

MAY 2007

MODULAR STURUCTURED MULTILEVEL INVERTER AS A THREE-PHASE SHUNT ACTIVE POWER FILTER WITH UNIFIED CONSTANT FREQUENCY INTEGRATION CONTROL

2006/2007-II ALI IBRAHIM ISMAAIL

Ezdoo Aljanobeia Zliten Libya. DR. NAZIHA BT. AHMAD AZLI

MAY 2007

MAY 2007

I hereby declare that I have read this project report and in my opinion this project report is sufficient in terms of scope and quality for the award of the degree of Master of Engineering (ElectricalMechatronics & Automatic Control)

Signature Name of Supervisor Date

ii

I declare that this project report entitled Modular Structured Multilevel Inverter as a Three-phase shunt Active Power Filter with Unified Constant Frequency Integration Control is the result of my own research except as cited in the references. The project report has not been accepted for any degree and is not concurrently submitted in candidature of any other degree.

Signature Name Date

iii

Specially Dedicated To My Beloved Mother, Father, Brothers and Sisters

iv

ACKNOWLEDGMENT

In the name of Allah, Most Gracious, and Most Merciful

Praise be to Almighty Allah (Subhanahu Wa Taala) who gave me the courage and patience to carry out this work. Pease and blessing of Allah be upon his last prophet Mohammed (Sallulaho-Alaihe Wassalam) and all his companions (Sahaba), (Razi-Allaho-Anhum) who devoted their lives towards the prosperity and spread of Islam.

My deep appreciation and heartfelt gratitude goes to my supervisor, Dr. Naziha Bte Ahmad Azli, for her kindness, constant endeavor, and guidance and the numerous moments of attention she devoted through out this work.

Also, thanks to the members of my family, especially my wife, for being very supportive throughout the development of this project.

Finally, I would like to ask my colleagues and friends whom I have been associated to accept my sincere thanks within the process of completing the project.

ABSTRACT

In recent years, the usage of power electronics equipments continues to increase, due to the increased usage of nonlinear loads and distributed power sources. These nonlinear loads generate harmonics and reactive currents, which lead to low power factor, low energy efficiency, low power capacity, and harmful disturbance to other appliances. These reactive currents will distort the voltage at the point of common coupling, reducing the quality of power delivered to other consumers on the network. Nowadays shunt active power filters (APFs), due to their flexibility and reliability are one of the most versatile and efficient solutions in the compensation of the load power factor and current harmonics. APFs provide only the harmonic and reactive power to cancel the one generated by the nonlinear loads or sources. This project presents a Modular Structured Multilevel Inverter (MSMI) as a three-phase shunt active power filter with Unified Constant Frequency Integration (UCI) control. Using MSMI APF with a unified constant-frequency integration controller, a unity power factor and low total harmonic distortion can be realized in all three phases. The proposed control approach employs one integrator with reset, along with several logic and linear components such as flip-flops, comparators, and clock. There are several important features of this implementation, it does not require three-phase load current and phase voltage sensing, also the nontrivial task of calculating harmonics and reactive current component is not required, and finally, it does not use any multipliers. These features make the proposed control approach simple, robust and reliable. The proposed three-phase MSMI APF with UCI control was simulated using MATLAB/Simulink. Simulation results have demonstrated a good suppression in harmonic distortion and improvement in the power factor of the power system.

vi

ABSTRAK

Dalam beberapa tahun kebelakangan ini, penggunaan peralatan elektronik kuasa semakin meninggkat disebabkan oleh peningkatan penggunaan beban tidak lurus dan pengagihan sumber kuasa. Beban tidak lurus mengeluarkan harmonik dan arus re-aktif yang akan mengurangkan faktor kuasa, kecekapan kuasa, kapasiti kuasa dan gangguan berbahaya kepada alatan yang lain. Arus re-aktif akan mengganggu voltan pada titik penyambungan biasa yang mana akan mengurangkan kualiti kuasa yang dihantar kepada pengguna di talian. Sekarang ini, shunt active power filter (APFs) banyak digunakan kerana fleksibiliti dan keboleharapan yang sungguh serba boleh dan penyelesain yang cekap dalam menimbal-balik faktor kuasa beban dan harmonik arus. APFs menyediakan harmonik dan kuasa re-aktif untuk membatalkan harmonik dan kuasa re-aktif yang dihasilkan oleh beban tidak lurus atau sumber. Projek ini mempersembahkan Modular Structured Multilevel Inverter (MSMI) sebagai tiga fasa shunt active power filter (APFs) bersama dengan Unified Constant Frequency Integration (UCI) control. Dengan menggunakan MSMI APF bersama Unified Control Frequency Integration Control, faktor kuasa sepadu dan jumlah gangguan harmonik yang rendah boleh direalisasikan pada semua sistem tiga fasa. Kawalan yang telah dicadangkan menggunakan satu pengamilan bersama reset, beberapa logik serta komponen lurus seperti flip-flop, pembanding dan jam. Ada beberapa keutamaan dalam perlaksanaan projek ini, di mana ia tidak menggunakan arus beban tiga fasa dan pengesan voltan fasa. Ia juga tidak menggunakan tugas yang tidak remeh untuk mengira harmonik dan arus re-aktif. Akhir sekali ia juga tidak menggunakan pendarab. Keutamaan ini menghasilkan cadangan kawalan yang mudah, tahan lasak dan boleh diharap. Cadangan menggunakan tiga fasa MSMI APF bersama kawalan UCI telah disimulasi menggunakan MATLAB/Simulink. Keputusan simulasi telah menunjukkan penumpasan gangguan harmonik yang baik dan membaikkan faktor kuasa dalam sistem kuasa.

vii

TABLE OF CONTENTS

CHAPTER DECLARATION DEDICATION

TITLE

PAGE ii iii iv v vi vii ix x xiii 1 4 7 7 8 9 9 9 12 13 14 16 19

ACKNOWLEDGEMENT ABSTRACT ABSTRAK TABLE OF CONTENT LIST OF TABLES LIST OF FIGURES LIST OF APPENDIX
1

INTRODUCTION 1.1 1.2 1.3 1.4 Project overview Objective Scope of Project Thesis outline

THREE-PHASE ACTIVE POWER FILTER AND THE CONTROL SCHEME 2.1 2.2 2.3 vvvv 2.4 2.5 Introduction Full bridge inverter Three-phase MSMI circuit topology and operation A five-level Three-phase MSMI Proposed control for three-phase MSMI 2.5.1 One cycle control theory

2.5.2 Proposed UCI APF control aaaaaaaaaaaaa method

viii

DESIGN THE SIMULATION BLOCKS 3.1 3.2 3.3 Introduction Setting simulation parameters

22 22 24 25 25 26 27 29 29 30 31 34 34 34 39 39 40 42 42 44 48 49 51 51 52 53 56-78

Single-phase MSMI system 3.3.1 Single-phase nonlinear load 3.3.2 Schematics of single-phase aaaaaaaaaaaaaaaMSMI APF 3.3.3 Schematics of the controller of sssssssssssssssss single-phase MSMI 3.4 Three-phase MSMI system 3.4.1 Three-phase nonlinear load 3.4.2 Schematics of three-phase MSMI aaaaaaaaaaaaa.aAPF 3.4.3 Schematics of the controller for aaaaaaaaaaaaa three-phase MSMI
4

SIMULATION RESULTS AND ANALYSIS 4.1 4.2 4.3 Introduction Generation of switching signal Single-phase MSMI system

4.3.1 The single-phase nonlinear load 4.3.2 Compensation with single-phase aaaaaaaaaaaaaaMSMI APF 4.4 Three-phase MSMI system 4.4.1 The three-phase nonlinear load 4.4.2 Compensation with three-phase aaaaaaaaaaaaaa MSMI APF 4.5 Load changes 4.6 Discussion
5

CONCLUSION 5.1 5.2 Conclusion Future work

REFERENCES Appendices A - B

ix

LIST OF TABLES

TABLE NO. 2.1 2.2 3.1

TITLE Operation of the switches Functions of R-S flip flop Value of the simulation parameters

PAGE 11 15 24

LIST OF FIGURES

FIGURE NO. 1.1 1.2 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 4.1 4.2 4.3 4.4 4.5 4.6 4.7

TITLE Shunt APF connected to the nonlinear load Three-phase wye connection of n level cascade inverter Full bridge inverter Bipolar mode Unipolar mode Output phase voltage 5-level three-phase wye connected MSMI Block diagram of control 5-level three-phase MSMI One cycle control The switch function Project sequence Non linear load full bridge diode rectifier with R-C load Single-phase MSMI APF UCI controller for single-phase MSMI Single-phase MSMI APF system Three-phase nonlinear load Three-phase MSMI APF UCI controller for three-phase MSMI system Three-phase MSMI APF system

PAGE 3 6 10 10 11 13 14 15 16 16 23 25 26 27 28 29 30 32 33

A small section of the carrier signal and 35 reference signals Input signal to R port of the flip-flop for leg A 35 Input signal to S port of the flip-flop for leg A 36 Control signal for switch S1 Control signal for switch S2 36 36

Input signal to R port of the flip-flop for leg B 37 Input signal to S port of the flip-flop for leg B 37

xi 4.8 4.9 4.10 4.11 4.12 4.13 4.14-a 4.14-b 4.15-a 4.15-b 4.16-a 4.16-b 4.17-a 4.17-b 4.17-c 4.18-a 4.18-b 4.19-a 4.19-b 4.20-a 4.20-b 4.21-a Control signal for switch S3 Control signal for switch S4 Wave form of source current caused by diode rectifier with RC load Source current harmonic component Source current waveform after compensation Harmonic spectrum of source current after compensation Source current wave form before compensation for Phase A Harmonic spectrum of source current before compensation for phase A Source current wave form before compensation for Phase B Harmonic spectrum of source current before compensation for phase B Source current wave form before compensation for Phase C Harmonic spectrum of source current before compensation for phase C Compensation current produced by three phase MSMI APF for phase A Compensation current produced by three phase MSMI APF for phase B Compensation current produced by three phase MSMI APF for phase C Waveform of source current after compensation for phase A Harmonic spectrum of source current after compensation for phase A Waveform of source current after compensation for phase B Harmonic spectrum of source current after compensation for phase B Waveform of source current after compensation for phase C Harmonic spectrum of source current after compensation for phase C Input supply current in phase with input supply voltage at AC main after compensation of MSMI APF for phase A 38 38 39 40 40 41 42 42 43 43 43 44 44 45 45 45 46 46 46 47 47 47

xii Input supply current in phase with input supply voltage at AC main after compensation of MSMI APF for phase B Input supply current in phase with input supply voltage at AC main after compensation of MSMI APF for phase C Compensation current to the load changing Source current drawn from the AC input with change in load

4.21-b

48

4.21-c 4.22 4.23

48 49 49

xiii

LIST OF APPENDICES

APENDIX A B

TITLE Table of Current Distortion Limits In IEEE Std 519 MATLAB Documentations for Simulation Model

PAGE 56 57

CHAPTER 1

INTRODUCTION

The increasing use of power electronic devices to provide more precise control of electrical power has brought about an increase in the distortion of voltage and current waveforms. Modern electrical distribution systems typically supply a high percentage of nonlinear loads. Due to the increased use of nonlinear industrial loads and power electronics, the currents and voltages present on the system can no longer be deemed as pure sinusoidal. These nonlinear loads generate poor power quality. However, the power quality problem has become a great concern due to the rapidly increasing use of nonlinear loads and power electronic equipment. Harmonic distortion is a key phrase used today when talking about power quality. Harmonic distortion is the production of harmonic frequencies by an electronic system when a signal is applied at the input, and it is measured in terms of percent total harmonic distortion of the fundamental frequency [24]. Additional losses in the electrical distribution systems are caused by the harmonic currents. The losses lead to low power factor which yields as overheating in apparatus, higher air-conditioning costs and higher power costs. Furthermore, harmonic will lead to lower reliability.

In the present era of utility deregulation and competition, many utility and industrial customers are concerned about reliability of electrical supply and quality of power. They are also anxious over the truth that harmonic can lead to computer network failure, humming in telecommunication lines and transformer overheating. The effects of harmonic distortion are hard to measure while the end results are easy to understand in terms of higher operating costs and lower reliability.

2 The total harmonic distortion problem are well understood and directly related to the proliferation of loads consuming non-sinusoidal current, referred to as "nonlinear loads". These types of loads are used for the conversion, variation and regulation of electric power in commercial, industrial and residential installations. There are many equipment (loads) with feed power from AC power supply such as computers, printers, power equipment, television sets, microwave ovens, fluorescent lightings and motors, as well as heating and air-conditioning equipment. These represent a mixture of linear and non-linear loads, all powered from the same AC source. If the content of non-linear loads becomes too large, it could reason significant distortion to the AC voltage. When this distortion is taken to extremes, it can result in malfunction or damage to other equipment sharing that source.

Nowadays, a variety of approaches are used to minimize and control harmonic distortion, but all present disadvantages. All solutions demonstrate higher utility costs because of continued poor power factors. However, to reduce harmonic contamination in the power lines, active power filters (APF) are viable solutions to eliminate the harmonics and improve the power factor. There are many configurations of active filters, such as the series active filter, shunt active filter, and combination of shunt and series active filter. Shunt APF is considered to be the most basic configuration for active power filter. An APF is a device that is connected in parallel with the AC line as shown in Figure 1.1. It needs to be sized only for the harmonic current drawn by the non-linear loads and function as a current source to cancel the reactive and harmonic currents generated from a group of nonlinear loads, so that the resulting total current drawn from the AC main is sinusoidal [8]. The performance of an APF largely depends on the inverter topologies and the pulse width modulation (PWM) control method.

Source Current

Load Current

IS

IL

Filter Current Power Distribution Equivalent Circuit IF Nonlinear Load

Shunt Active Power Filter

Figure 1.1: Shunt APF connected to the nonlinear load.

Active power filters are becoming a viable alternative to passive filters and are gaining market share speedily as their cost becomes competitive with the passive variety [8]. Also APF has some advantages such as the size of APF depend on the harmonic current drawn by the nonlinear loads and that need to be compensated, simplicity, reliability, efficiency, respond to changing load and harmonic conditions. However, passive power filter have many disadvantages, such as large size, resonance, and fixed in their harmonic response.

Numerous types of shunt active power filters have been proposed in many papers. Most of these papers discuss the standard and function for controlling different topologies of APFs. Meanwhile, little of them talk about the voltage range application of APFs. This project is concerned on a new topology of three-phase APF based on Modular Structure Multilevel Inverter (MSMI), which is generally for high voltage/high power applications. The MSMI has many distinct features in terms of its structure, which is simple, modular and also requires the least number of components. These features provide the flexibility in extending the MSMI to higher number of levels without undue increase in circuit complexity as well as facilitate packaging [7].

4 1.1 Project overview

The issue of active filters started in 1971. Shunt APF has been explored by many researchers. The shunt APF is considered to be the most basic configuration for APF [12]. In order to control the produced current that is equal in amplitude and opposite in direction of the reactive current of the nonlinear load, different control strategies have been presented to improve the dynamic and steady-state performance of the APF (such as proportional-integral (PI), variable-structure control, fuzzy logic, and neural nets) [1]. Most of these control approaches need to sense the three-phase line voltage, three-phase load current and then calculate its harmonics and reactive components in order to generate the reference for controlling the current of a bridge converter. Those control methods require fast and real-time calculation; therefore, a high-speed digital microprocessor and high-performance A/D converters are necessary, which yields complexity, high cost and low stability [3].

Another simple method of control scheme for three-phase APF is known as Unified Constant-Frequency Integration Control (UCI) based on one cycle control was introduced by Dr. Smedly from California Institute of Technology in 1991 [9]. The controller is designed to vary the duty cycle of the inverter switches such that compensation of the harmonics can be done in cycle. This control method eliminates the need of calculating the current reference as well as the use of multipliers and voltage sensors in the control loop [3].

UCI control becomes a focus control strategy and the development of the control techniques applied to APFs meet a new high tide in the last years [5]. UCI control method employs an integrator to control the pulse width of an AC-DC converter so its current draw is precisely opposite to the reactive and harmonic current draw of the nonlinear loads. The control method features are carrier free, constant switching frequency operation, minimum reactive and harmonic current generation and simple analog circuitry. It provides a low cost and high performance

5 solution for power quality control. This control method is generalized to control a family of converters that are suitable for APF applications.

Due to the widespread use of modern electronic equipment and the natural limitation to the appliance of active filters at high power levels, it is difficult to realize high power rated filters with the required bandwidth for compensating the typical harmonic currents. The inverter topology that seems to be gaining interest lately is the multilevel inverter. Multilevel inverter was initiated by A. Nabae in 1981 who introduced a basic three level inverter, also known as the Neutral Point Clamped (NPC) inverter [15]. The main feature of a multilevel inverter is its ability to reduce the voltage stress on each power device due to the utilization of multiple levels on the DC bus.

This project suggests a three-phase MSMI APF for high power application that utilizes the UCI control scheme. Three-phase MSMI APF consists of cascade of full-bridge inverters with separate DC sources (SDCS) and this cascade full-bridge inverter can be connected in star connection as shown in Figure 1.2. The output phase voltage is the sum of inverter units output [10]. A UCI control method is based on one-cycle control that employs an integrator with reset as its core component along with a few logic and linear components to control the pulse width of a three-phase rectifier APF, so that all three phase currents drawn form or the current output to the utility line is sinusoidal. With one-cycle control, the multipliers and three-phase load current sensors in the control loop are eliminated and the control circuitry is simple and robust. The overall circuitry is reduced. Active power filters with UCI controller provide a cost effective and flexible solution for power quality control.

n -1

Figure 1.2: Three-phase Wye connection of n level cascade inverter

The proposed configuration of a three-phase MSMI APF with UCI control obtains low total harmonic distortion (THD) and enforces the three-phase load current to follow the three-phase line voltage, which results in a three-phase unity power factor. The MSMI APF is suitable for high power application and has the ability to reduce the voltage stress on the semiconductor components.

This project is an extension to a previous project which has been completed for a single-phase MSMI APF with UCI. A three-phase simulation of an MSMI APF system is presented for the purpose of demonstration in this project and acceptable result has been obtained from the simulation.

7 1.2 Objective

The objectives of this project can be summarized as follows:

- To extend the use of a single-phase MSMI in an APF system with UCI control, to three-phase application.

- To achieve low supply current total harmonic distortion (THD) in the power system.

- To achieve three-phase unity power factor on the supply side.

1.3 Scope of project

This project introduces three phase MSMI shunt APFs with UCI control. The scope of the project can be summarized as follows:

- Represent the nonlinear load with a diode rectifier with RC load, and analysis as the distorted source current waveform drawn by the nonlinear load.

- A simulation study on the operation and performance of a three-phase MSMI with UCI control as an active power filter.

- Using MATLAB Simulink to simulate both single-phase and three-phase MSMI APFs.

- Testing the simulation to evaluate the performance of the three-phase APF.

8 - Comparing the performance of the APF systems (both single phase and threephase).

1.4 Thesis Outline

This thesis is organized into five chapters, which are summarized as follows:

Chapter 1 gives an introduction and short peep on the fundamental aspects of the project, such as: overview, project background, objectives and scope of the project.

Chapter 2 describes the full bridge inverter topology and its control scheme, the schematic of three-phase MSMI APF as well as the control diagram.

Chapter 3 demonstrates the development of the simulation blocks of the proposed three-phase MSMI APF configuration with selected control scheme.

Chapter 4 displays the simulation results and discusses the compensation performance of the single phase and three-phase MSMI APF subject to a typical nonlinear load.

Chapter 5 presents conclusions and recommendations for future researchers.

CHAPTER 2

THREE-PHASE ACTIVE POWER FILTER AND THE CONTROL SCHEME

2.1 Introduction

This chapter describes in detail the installation and operation of the proposed three-phase MSMI APF and the control architecture used in this project. Also, this chapter presents the control method in the form of mathematical equations.

2.2 Full bridge inverter

The full-bridge inverter as shown in Figure 2.1 used to convert DC to AC can be considered as a typical shunt APF. Shunt APF produces harmonic current that has the same magnitude and different phase of harmonic that is generated by a nonlinear load. The output is obtained from the DC input by opening and closing switches in an appropriate sequence. The operation of the switches can be controlled by PWM techniques. Control of the switches for sinusoidal PWM output requires two carrier signals and modulating signal (reference), which are sinusoidal waveform and

10 triangular waveform respectively. The frequency of the carrier signal is much higher than the modulated signal. There are two methods to control the operation of the switching; bipolar and unipolar scheme. [6]

S1

S3

+ vdc
-

+ VAB A Load

S4

S2

Figure 2.1: Full bridge inverter

In bipolar switch mode only one reference signal is required and compared with carrier signal and the result of the comparison will produce PWM waveform as in Figure 2.2, which control the operation of the switches. The switches S1 and S4 are operated to form complementary, i.e. when switch S1 is on, then the switch S4 is off, the same condition for S2 and S3. When Vtri>Vc then switches S3 and S4 will turn on, the other two switches are turned off, when Vtri<Vc then switches S1 and S2 will turn on, the other two switches are turned off.

2vtri

vc

Vdc vAB -Vdc


Figure 2.2: Bipolar mode

11 In unipolar mode two reference signals are required to compare with the triangular signal to obtain pulses that are required to operate the switches as shown in Figure 2.3. Table 2.1 shows the operation of the switches, where 1 indicates the switch is ON and 0 indicates the switch is OFF.

Table 2.1: Operation of the switches

Comparing Signal Vtri<Vc Vtri>Vc Vtri>-Vc Vtri<-Vc

S1 1 0 0 0

S2 0 1 0 0

S3 0 0 1 0

S4 0 0 0 1

vc Vtri -vc

vA vB vAB
Figure 2.3: Unipolar mode

12 2.3 Three-phase MSMI circuit topology and operation

Figure 1.2 has shown a general configuration of the MSMI. Each module of the MSMI has the same structure where it consists of cascaded single-phase fullbridge inverter. The total output phase voltage is equal to the summation of the output voltage of the respective modules that are connected in series, which is close in form to a sinusoidal waveform as shown in Figure 2.4. The number of DC input voltages required in this topology depends on the number of levels and the type of system. The number of modules (m) that is equal to the number of DC sources required depends on the number of levels (n) of the MSMI. For each phase, the number of modules m= (n-1)/2. [13]

There are many advantages of using multilevel inverter such as the following:

1. It is structure is simple and consists of fewer components.

2. Multilevel inverters can reach high voltage and reduce harmonics by their own structures without transformers.

3. It has the ability to reduce the voltage stress on each power device due to the utilization of multiple levels on the DC bus.

4. It is more suitable for high-voltage and high-power applications than the conventional inverters.

5. It switches each device only once per line cycle, which generates a multi step staircase voltage waveform similar to a pure sinusoidal output voltage by increasing the number of levels.

6. Packaging layout is much easier, because of the simplicity of structure and lower component count [7].

13

Figure 2.4: Output phase voltage

2.4 A five-level three-phase MSMI

The structure of a wye connected five-level three-phase MSMI is as shown in Figure 2.5 which consists of two cascaded inverter per phase where each inverter has two legs, also, each leg has two switches. MSMI APF in each phase produces current that has the same magnitude with that generated by the nonlinear load, but different in phase, so that the net resultant current is pure sinusoidal. The capacitor is charged from the source during the operation of the inverter switching. Voltage divider is also installed at the APF which sends the divided voltage to the controller.

As the name indicates the output phase voltage has five levels, which include +2VDC, +VDC, 0, -VDC and -2VDC, based on the Kirchoff's Voltage Law, the voltage for each phase can be calculated. This output depends on the topology of the

14 operation of the switching. The number of modules required is two, based on the equation that gives the relationship between n and m.

Figure 2.5: 5-level three-phase wye connected MSMI

2.5 Proposed control for three-phase MSMI

Figure 2.6 shows the proposed block diagram of the five-level three phase MSMI controller, where VA1, VA2, VB1, VB2, VC1, VC2 are the DC voltages of the inverter capacitors for the phases A, B and C respectively. For each module in each phase, the DC voltage and the source current are sensed and sent to the controller. The DC capacitor voltage is integrated and compared with the source current then the

15 output of the comparator is entered to an R-S flip flop to generate the pulses, which turn OFF and turn ON the switches, based on the function of the R-S flip flop, which is exposed in Table 2.1. This operation of integration starts when it gets pulse from the clock pulse. The ports Q and Q are generated based on the condition that is required for compensation.

VA1 VA2

VB1 VB2

VC1 VC2

Phase A

Phase B

Phase C

Figure 2.6: Block diagram for control of a 5-level three phase MSMI

Table 2.2: Functions of R-S flip flop R 0 0 1 1 S 0 1 0 1 Q(t+1) Q(t) 1 0 X

Q(t+1) = Present output of flip flop Q(t) = Previous output of flip flop Activated output = 1 Deactivated output =0 Do not care output = x

The R-S flip flop will receive two signals; one from the comparator through R input port while the other signal from the clock through S input port. The period of the clock pulses determines the constant switching frequency operation of the MSMI while the integrator will reset when the next clock pulse triggers it [11].

16 2.5.1 One Cycle Control Theory

The scheme of the one-cycle control employs an integrator with reset as its core component to generate triangular carrier waveform, also some logical devices such as flip flop, clock and comparators are used to produce switching signals to the multilevel inverter as shown in Figure 2.7.

Figure 2.7: The One-Cycle Control

The switch S is operated according to the switching function k(t) at constant frequency fs = 1/Ts, as shown in Figure 2.8.

1 k (t ) = 0

0<t<TON TON<t<T s

(2.1)

Figure 2.8: The switch function

17 From Figure 2.8, the switching cycle Ts= Ton+ Toff , where Ton is the time duration when the switch is on and Toff is the time duration when the switch is off. The duty-ratio d = Ton/Ts is modulated by an analog control reference vref (t). The input signal x(t) is chopped by the switch and transferred to the output node of the switch to form a switched variable y(t). The envelope of the switched variable y(t) is the same as the input signal x(t), while the frequency and the pulse width of the switched variable y(t) is the same as that of the switch function k(t), as can be clear by seen in Figure 2.8.

Y(t) = k(t) x(t)

(2.2)

The switch frequency fs is much higher than the frequency bandwidth of the input signal x(t); then the effective signal carried in the switch output, i.e. the average of the switched variable is,[9]

y (t ) =

1 Ts

Ton

x(t )dt
0

(2.3)

y (t ) x(t )d (t )

It is clear from the previous equation that the switched variable y(t) at the output of the switch is the product of the input signal x(t) and the duty-ratio d(t); therefore, the switch is nonlinear. If the duty-ratio of the switch is modulated, such that the integration of the switched variable at the switch output is exactly equal to the integration of the control reference in each cycle,

Ton

x(t )dt = vref dt


0 0

Ts

(2.4)

Then the average value of the switched variable at the switch output is exactly equal to the control reference in each cycle, since the switching period is constant. Thus, the average of the switched variable is instantaneously controlled within one cycle,

18

1 y (t ) = Ts

Ton

1 s x(t )dt = vref dt = vref Ts 0 0

(2.5)

This concept is defined as the one-cycle control technique. With one-cycle control, the effective output signal of the switch is y(t)=vref(t). The one-cycle control technique turns a non-linear switch into a linear path.

The implementation circuit for one-cycle controlled constant-frequency switch is shown in Figure 2.7. The core component of the one-cycle control technique is the integrator and the reset. The integration starts at the moment when the switch is turned on by the fixed frequency clock pulse. The integration value vin(t) is compared with the control reference vref(t) instantaneously as follows, where c is a constant.

vin = c x(t )dt


0

(2.6)

At the instant when vin is equal to vref(t), the controller sends a command to the switch to change it's condition from on to off state, also the controller will reset the integrator to zero. The duty ratio d= Ton/Ts is determined by:
dTs

c x(t )dt = vref (t )


0

(2.7)

Since the switch period Ts is constant and K= l/cTs is a constant, the average value of the switched variable at the switch output y(t) is [9]:

y (t ) =

1 Ts

dTs

x(t )dt = Kv
0

ref

(t )

(2.8)

19

2.5.2 Proposed UCI APF control method

The control objective of the full-bridge inverter is to provide the reactive and harmonic current required by the nonlinear load, so that the net current draws from the AC main is the fundamental active power used at the nonlinear load.

The control key equations for the UCI controller are derived for the threephase MSMI based on the work presented in [14] and [2]. During the positive half cycle Vga, Vgb, Vgc > 0, S1 is always ON in each phase. The inductor voltages will be as follows,

VLA(ON)=Vga VLB(ON)=Vgb VLC(ON)=Vgc and

for for for

0<t<dATs 0<t<dBTs 0<t<dCTs (2.9)

V ga Vdc , d A = d1 VLA (OFF)=Vga-Vo = V ga 2Vdc , d A = d 2

for

dATs<t<Ts

V gb Vdc , d B = d1 VLB (OFF)=Vgb-Vo = V gb 2Vdc , d B = d 2 V gb Vdc , d B = d1 VLC (OFF)=Vgc-Vo = V gb 2Vdc , d B = d 2

for

dBTs<t<Ts

(2.10)

for

dCTs<t<Ts

For constant frequency operation, the average inductor in voltage-second of each phase is approximately balanced during each switching cycle, that is,

20 VLA(ON). dATs + VLA (OFF).(1- dA)Ts= 0 VLB(ON).dBTs +VLB (OFF).(1- dB)Ts = 0 VLC(ON).dCTs + VLC(OFF).(1- dC)Ts = 0 By substituting (2.9) and (2.10) into (2.11) (2.11)

Vga. dATs + (Vga- V0).(1- dA)Ts = 0 Vgb.dBTs + (Vgb- V0).(1- dB)Ts = 0 Vgc.dCTs + (Vgc- V0).(1- dC)Ts = 0 Similarly for the negative half cycle,

when Vga>0 when Vgb>0 when Vgc>0 (2.12)

Vga. dATs + (Vga+ V0).(1- dA)Ts = 0 Vgb.dBTs + (Vgb+ V0).(1- dB)Ts = 0 Vgc.dCTs + (Vgc+ V0).(1- dC)Ts = 0 Suppose,

when Vga<0 when Vgb<0 when Vgc<0 (2.12)

V g V ge = V g

i g and i ge = i g

for

Vg>0 Vg<0

(2.13)

The combination of (2.11), (2.12) and (2.13) yields the relationship between duty ratios of the switches, input AC voltage for each phase and DC bus voltage of the APF.

Vgea=V0 (1-dA) Vgeb=V0 (1-dB) Vgec=V0 (1-dC) In order to achieve three phase unity power factor, the control goal of the APF is therefore to force the AC current to follow the AC input voltage. For each phase, with Rs as the equivalent sensing resistance, (2.14)

21 Vge=Rs.ige (2.15)

Equations (2.14) and (2.15), yield the control key equations as follows,

Rsa.igea= V0 (1-dA) Rsb.igeb= V0 (1-dB) Rsc.igec= V0 (1-dC) (2.16)

CHAPTER 3

DESIGN OF THE SIMULATION BLOCKS

3.1 Introduction

Figure 3.1 shows a flow chart which briefly offers simple steps that are followed in completing this project. MATLAB/Simulation was utilized in this project to simulate the nonlinear load and the proposed single-phase and three-phase MSMI APF with UCI control. Finally, the results obtained from the simulation study are analyzed.

This chapter shows in detail the simulation blocks of the proposed MSMI APF as a single-phase shunt APF with UCI control and expands the proposed system to a three-phase MSMI APF. Also, the controller for the proposed three-phase MSMI APF is shown in detail. Data type conversion blocks were implemented as an interface to convert data between the connection of Simulink blocks and Simpowersystem blocks from Boolean data to Double data type or vice versa.

23

Start Study the supply current Literature review Simulate the nonlinear load and analyze the generated harmonic Design single phase MSMI with UCI controller Expand single phase MSMI with UCI to 3-phase Analyze the results

Troubleshoot

Verification

No

Is the desired result achieved? Yas Testing and enhancement

Analyze and discussion

End
Figure 3.1: project sequence

24 3.2 Setting Simulation parameters

The APF that has been mentioned in the previous two chapters was simulated using MATLAB/Simulink. To achieve the project goal in an efficient manner, simulation parameters were placed. By changing the stop time to 0.4second, maximum simulation step size was selected to be 1e-6, and finally, the solver option was set at ode 15s (stiff/NDF) solver. The parameters that are used in the proposed simulation system are listed in Table 3.1.

Table 3.1: Value of the simulation parameters

Parameter Line Voltage Phase voltage Line Frequency Resistance Capacitance APF inductor APF DC-bus capacitor Switching frequency

Symbol Vg Vga,b,c, F Rl Cl Lf Cf Fs

Value 240 Vrms 415 V 50 Hz 250 1000 F 5mH 500F 10kHz

25 3.3 Single-phase MSMI system

3.3.1 Single-phase nonlinear load

Figure 3.2 shows a single-phase nonlinear load, which is represented by a full-bridge uncontrolled diode rectifier parallel with an R-C load.

Nonlinear full bridge diode rectifier with R-C load

T1

T4

is

Scope i pcur T o Workspace R-L


a

Diode
a

Diode1 C

R1

i -

is

CM

T2 AC
m

T3

R2

Diode2
a a

Diode3

Figure 3.2: Nonlinear load full bridge diode rectifier with R-C load

26 3.3.2 Schematics of single-phase MSMI APF

The structure of a single-phase MSMI APF is shown in Figure 3.3. It consists of eight switching devices with two DC-link capacitors. An MSMI consists of cascaded full bridge inverters with separate DC sources (SDCS). Two modules of a full-bridge inverter are required to get a five-level MSMI.

Figure 3.3: Single-phase MSMI APF

27 3.3.3 Schematics of the controller of single-phase MSMI

Figure 3.4 illustrates the schematic diagram of the controller for a singlephase MSMI. The controller for module 1 is similar to that of module 2, whereby each controller will obtain input from its corresponding module. Each flip-flop has the duty to control each leg of the MSMI.

Unified Constant Frequency Integration (UCFI) Controller

DT5 1 Out1 DT4 double

S-R Flip-Flop
Q S

Scope Gain2 DTC1 boolean DTC RO <= 1.5 Const2 Ts2 -K-

Integrator 1 s

Gain1 -1 Ts1 1 In1

!Q

2 Out2 2 In2 0.1 Gain4 3 Out3

double

boolean

controller for module 1

DT1 double

S-R Flip-Flop1
Q S

DT2 boolean

Ts3

DT6
!Q R

DT3 boolean

RO1 Gain3 <= -1

4 Out4

double

DT11 7 Out7 DT10 double

S-R Flip-Flop2
Q S

Scope1 Gain6 DTC3 boolean DTC2 RO2 <= 1.25 Const1 Ts5 -K-

Integrator1 1 s

Gain5 -1 Ts4 3 In3

!Q

8 Out8

double

boolean

controller for module 2

DT7 5 Out5 DT12 double

S-R Flip-Flop3
Q S

DT8 boolean

Ts6

DT9
!Q R

RO3 Gain7 <= -1

6 Out6

double

boolean

Figure 3.4: UCI controller for single-phase MSMI

28 The entire single-phase MSMI with UCI controller is shown in Figure 3.5. It can be noticed that, the MSMI is connected in parallel with a point between the source and nonlinear load, where the filter current will be generated to compensate the distortion accrued from the nonlinear load, so that the source current remain sinusoidal.

Figure 3.5: Single-phase MSMI APF system

29 3.4 Three-phase MSMI system

3.4.1 Three-phase nonlinear load

Figure 3.6 shows a three-phase nonlinear load that is used in this project. The load is represented by a full bridge uncontrolled diode rectifier parallel with R-C load in each phase. In1, In2, In3 are connected to the supply terminals Va, Vb and Vc respectively.

Figure 3.6: Three-phase nonlinear load

30 3.4.2 Schematics of three-phase MSMI APF

Three-phase structure of the MSMI APF is connected in Wye connection as shown in Figure 3.7 which consists of twenty-four switching devices with six DClink capacitors. The three-phase MSMI consists of cascaded full-bridge inverters with separate DC sources (SDCS). Two modules of the full-bridge inverter in each phase are required to get a five-level MSMI. The number of modules per phase for an M level MSMI is equal to (m-1)/2. In25, In26 and In27 are connected to a point between the source and the three-phase nonlinear load.

Figure 3.7: Three-phase MSMI APF

31 3.4.3 Schematics of the controller for a three-phase MSMI

The UCI controller for a three-phase MSMI is similar to that used in singlephase, where each phase of the three-phase system has its own controller as depicted in Figure 3.8. From Figure 3.8, In1 and In3 are connected to the capacitor voltage of module 1 and module 2 for phase A while In2 is connected to the main current for phase A. Similar connections are also made for the other two phases.

32

Figure 3.8: UCI controller for three-phase MSMI system

33 The overall APF system of the three phase MSMI with UCI controller is shown in Figure 3.9.

Figure 3.9: Three-phase MSMI APF system

CHAPTER 4

SIMULATION RESULTS AND ANALYSIS

4.1 Introduction

This chapter presents the results obtained from the simulation to support the theoretical and the equations in chapters II. The simulation results are shown and analyzed in this chapter in two main sections which are single-phase MSMI system and three-phase MSMI system.

4.2 Generation of switching signal

The switching signals of leg A and leg B are controlled by comparing the carrier signal with two reference signals. Carrier signals can be obtained from the integrated output voltage of the integrator. The integrator is enhanced with a reset to repeat the process after each cycle of integration. The signal that is produced from the comparison is fitted to a flip-flop. The output signal from the flip-flop is used to change the switching status (ON or OFF).

35 Figure 4.1 shows a small section of the carrier signal and reference signals for controlling module 1 of phase A in the three-phase MSMI. The previous explanation and following figures are valid for module 2 of phase A. The other two phases B and C of the three-phase MSMI give similar results as that of phase A.

Figure 4.1: A small section of the carrier signal and reference signals

Figure 4.2 shows the input signal to R port of the flip-flop that is generated by the comparison between the carrier signal and the reference signal for leg A. However, the S port receives its signal from a clock with constant frequency pulses; in this case the constant frequency is equal to 10 kHz, as in Figure 4.3.

Figure 4.2: Input signal to R port of the flip-flop for leg A

36

Figure 4.3: Input signal to S port of the flip-flop for leg A

The output signals from the R-S flip-flop is shown in figure 4.4 and 4.5, the

Q port signal of the flip-flop will control switch S1 while the complement signal
Q will control switch S2.

Figure 4.4: Control signal for switch S1

Figure 4.5: Control signal for switch S2

37 Controlling leg B is the same as leg A, where the input signal to the R port of the flip-flop is obtained from the comparison of the carrier signal with the reference signal for leg B as shown in Figure 4.6. Figure 4.7 shows the input signal to the S port of the flip-flop when controlling leg B.

Figure 4.6: Input signal to R port of the flip-flop for leg B

Figure 4.7: Input signal to S port of the flip-flop for leg B

Figures 4.8 and 4.9 show the control switching signals for switch S3 and S4 respectively, obtained in a similar fashion as mention previously.

38

Figure 4.8: Control signal for switch S3

Figure 4.9: Control signal for switch S4

39 4.3 Single-phase MSMI system

4.3.1 The single-phase nonlinear load

The single-phase nonlinear load is represented by a full-bridge diode rectifier in parallel with an R-C load. The load is connected to an AC supply as in Figure 3.2. The AC input current drawn by the nonlinear load is shown in Figure 4.10. It is clear that the current waveform encounters high distortion and its harmonic component is very high. The harmonic spectrum is shown in Figure 4.11 with the value of the total harmonic distortion at 146.73%.

Figure 4.10: Waveform of source current caused by diode rectifier with RC load

40

Figure 4.11: Source current harmonic components

4.3.2 Compensation with single-phase MSMI APF

The nonlinear current is compensated using a single-phase MSMI APF associated with UCI control. The simulation result was taken during steady state condition. Figure 4.12 shows the supply current to the nonlinear load after compensation by the MSMI. The current wave form is close to sinusoidal form compared with the original input current to the nonlinear load. The THD is reduced from 146.73% to 6.32%. Figure 4.13 shows the current harmonic component.

Figure 4.12: Source current waveform after compensation.

41

Figure 4.13: Harmonic spectrum of source current after compensation.

42 4.4 Three-phase MSMI system

4.4.1 The three-phase nonlinear load

As mentioned in the previous chapter, the three-phase nonlinear load is represented by a full-bridge uncontrolled diode rectifier parallel with an R-C load in each phase. Figures 4.14, 4.15 and 4.16 show the three-phase AC input currents drawn by the nonlinear load and their harmonic current components for phases A, B and C.

F F T w in d ow : 5 o f 2 0 c y c le s o f s e lec t e d s ig n al 15 10 5 0 -5 -1 0 -1 5 0.3

0.3 1

0. 3 2

0.3 3

0 .3 4

0.35 Tim e (s )

0 .3 6

0 .3 7

0.38

0 .3 9

0.4

Figure 4.14-a: Source current waveform before compensation for phase A

F u n d a m e n t a l (5 0 H z ) = 2 . 4 , T H D = 1 4 6 . 7 3 % 100 90 80 Mag (% of Fundamental) 70 60 50 40 30 20 10 0 0 10 20 30 40 50 H a rm o n i c o rd e r 60 70 80 90 100

Figure 4.14-b: Harmonic spectrum of source current before compensation for Phase A

43

Figure 4.15-a: Source current waveforms before compensation for Phase B

Figure 4.15-b: Harmonic spectrum of source current before compensation for Phase B

Figure 4.16-a: Source current waveforms before compensation for Phase C

44

Figure 4.16-b: Harmonic spectrum of source current before compensation for Phase C

4.4.2 Compensation with three-phase MSMI APF

The nonlinear current is compensated using a three-phase MSMI APF associated with UCI control. Figure 4.17 shows the three-phase current of the threephase MSMI. This current will compensate the nonlinear current to become sinusoidal waveform.

Figure 4.17-a: Compensation current produced by three-phase MSMI APF for phase A

45

Figure 4.17-b: Compensation current produced by three-phase MSMI APF for phase B

Figure 4.17-c: Compensation current produced by three-phase MSMI APF for phase C

The wave shape of the three phase AC source current waveform after compensation by the proposed configuration of the three phase MSMI APF, is shown in Figures 4.18a, 4.19a and 4.20a for phases A, B, C, respectively, which are nearly similar to sinusoidal with slight distortion. The THD of the three-phase AC main current as shown in Figures 4.18b, 4.19b and 4.20b for phases A, B, C, respectively, is greatly reduced to about 5%, which exhibit superior results.

Figure 4.18-a: Waveform of source current after compensation for phase A

46

Figure 4.18-b: Harmonic spectrum of source current after compensation for phase A

Figure 4.19-a: waveform of source current after compensation for phase B

Figure 4.19-b: Harmonic spectrum of source current after compensation for phase B

47

Figure 4.20-a: waveform source current after compensation for phase C

Figure 4.20b: Harmonic spectrum of source current after compensation for phase C

Figure 21 shows that the supply current is forced to be in phase with the voltage at the AC main which indicates that unity power factor of the three-phase system is achieved.

400 300 200 100 0 -100 -200 -300

Figure 4.21-a: Input supply current in phase with input phase voltage at AC mains after compensation of MSMI APF for Phase A

48
400 300 200 100 0 -100 -200 -300

Figure 4.21-b: Input supply current in phase with input phase voltage at AC mains after compensation of MSMI APF for Phase B

400 300 200 100 0 -100 -200 -300

Figure 4.21-c: Input supply current in phase with input phase voltage at AC mains after compensation of MSMI APF for Phase C

4.5 Load changes

A load change has also been conducted to test the ability and flexibility of the proposed three-phase MSMI APF configuration in compensating the current harmonics. The load is changed from 250 to 200 . Figure 22 shows the compensation current generated by the proposed three-phase MSMI. The instantaneous compensation from the MSMI APF has proven its flexibility in handling load change. From Figure 23 it can be noticed that the current drawn from

49 the AC supply remains a sinusoidal waveform without being affected by the changes that occurs at the load.

Figure 4.22: Compensation current to the changing load

Figure 4.23: Source current drawn from the AC input with change in load

4.6 Discussion

The overall results of the designed three-phase MSMI APF with UCI control have shown that the MSMI APF has managed to compensate the distortion in the line current caused by nonlinear load which in this case is represented by a full-bridge diode rectifier connected in parallel with an R-C load. Based on the results, the proposed system is capable of responding effectively to the harmonics caused by the three-phase diode rectifier. The total harmonic distortion of the source current

50 obtained from the nonlinear load without compensation is too high; about 146.73% in each phase. For the single-phase case when compensation is made with the proposed MSMI APF, the total harmonic distortion is reduced to 6.32%, which is fairly good. For the three-phase when compensation on the harmonic distortion is made with the proposed three-phase MSMI APF with UCI control, more reduction in total harmonic distortion percentage was obtained, where it can be measured as 5.8% in phase A, 5% in phase B and 4.59% in phase C. In a nutshell, the performance of the MSMI APF using the UCI control is better in three-phase than in the single-phase system.

CHAPTER 5

CONCLUSION

5.1 Conclusion

The increasing use of nonlinear loads in distribution systems has resulted in excessive harmonic injection and reactive power burden in the utility. The nonlinear load draws voltage and current waveforms pollution of power system more than before. To overcome this problem a three-phase MSMI active power filter system is proposed for high voltage/high power applications. The implemented three-phase MSMI with UCI control has successfully given a better impact on harmonics mitigation in the power system.

A five-level three-phase MSMI APF with UCI controller is employed in this project to reduce voltage stress on the inverter switches at high power application. A superior impact on harmonics mitigation in the power system was achieved by using the proposed system. By using a three-phase MSMI APF with UCI control about twenty nine times of THD reduction can be gained. The current compensation is performed in the manner of cycle by cycle using the three-phase MSMI APF with UCI controller, so that the compensated net current matches the input voltage closely, thus achieving a three-phase unity power factor.

52 The capability of the three-phase MSMI APF with UCI controller provides a flexible solution for power quality control. In a nutshell, the proposed three-phase MSMI APF system is simple, robust and possesses reliable characteristic that has shown satisfactory performance in the lessening of harmonic current problems in power system.

5.2 Future work

The future works that can be considered are as follows:

Hardware implementation of the three-phase MSMI APF system is recommended as an extension to the simulation project for verification purpose.

Higher levels of the MSMI can be considered to obtain better results in terms of harmonic current compensation and further reduce the voltage stress on the switching devices.

The proposed three-phase MSMI APF system can be considered for small load and heavy load.

53

REFERENCES

1. Bhim Singh, Kamal Al-Haddad, and Ambrish Chandra, "A Review of Active Filters for Power Quality Improvement", IEEE TRANSACTIONS ON INDUSTRIAL
ELECTRONICS, VOL. 46, NO. 5, OCTOBER 1999.

2. Chongming Qiao , Keyue M. Smedley, Franco Maddaleno, "A Comprehensive Analysis and Design of a Single Phase Active Power Filter with Unified Constantfrequency Integration Control.", 2001 IEEE, pp 1619-1625.

3. Chongming Qiao, Taotao Jin, and Keyue Ma Smedley, "One-Cycle Control of Three-Phase Active Power Filter with Vector Operation", IEEE TRANSACTIONS ON
INDUSTRIAL ELECTRONICS, VOL. 51, NO. 2, APRIL 2004.

4. Chongming Qiao and Keyue M. Smedley, "Three-phase Active Power Filters with Unified Constant-frequency Integration Control" pp 689-705.

5. Donghua Chen, Shaojun Xie, "Review of the control strategies applied to active power filters", IEEE International Conference on Electric Utility Deregulation, Restructuring and Power Technologies (DRPT2004) April 2004 Hong Kong.

6. D. W. Hart, Introduction to Power Electronics New Jersey: Prentice Hall, 1997.

7. Fang Zheng Peng, Jih-Sheng Lai, John McKeever and James VanCOevering "A Multilevel Voltage-Source Inverter with Separate DC Sources for Static Var Generation", 1995 IEEE 2541.

54 8. Hugh Rudnick, Juan Dixon and Luis Morn, "Active power filters as a solution to power quality problems in distribution networks", IEEE September / October 2003.

9. Keyue M. Smedley, and Slobodan Cuk, One-Cycle Control of Switching Converters", IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 10, NO. 6,
NOVEMBER 1995.

10. Leon M. Tolbert, Fang Z. Peng, Multilevel converter as a Utility Interface for Renewable Energy Systems.

11. L. P. YI. Modular Structured Multilevel Inverter as Active Power Filter with Unified Constant-Frequency Integration control. Master of Engineering (ElectricalPower), UTM 2005

12. Luowei Zhou and Keyue M. Smedley, "Unified Constant-frequency Integration Control of Active Power Filters", 2000 IEEE, pp 406-412.

13. N. A. Azli and A.H. Mohd Yatim, Modular Structured Multilevel Inverter for High Power AC Power Supply Applications, Industrial Electronics, ISIE 2001. IEEE International Symposium on Volume: 2, 12-16 June 2001 Pages: 728-733.

14. N. A. Azli, P. Y. Lim, "Modular Structured Multilevel Inverter with Unified Constant-Frequency Integration Control for Active Power Filters", IEEE PEDS 2005

15. Nabae, A., Takahashi,I. And Akagi, H. (1981). A Neutral Point Clamped PWM Inverter. IEEE Transactions on Industry Applications, Vol. 17, No. 5, pp. 518-523.

16. Taotao Jin, Jun Wen, and Keyue Smedley, "Control and Topologies for Threephase Three-level Active Power Filters" pp 450-455.

17. Taotao Jin and Keyue M. Smedley, "Operation of Unified Constant-frequency Integration Controlled Three-phase Active Power Filter with Unbalanced Load", 2003 IEEE.

55 18. IEEE PES Harmonic Working Group. Characteristics and Modeling of Harmonic SourcesPower Electronic Devices. IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 16, NO. 4, OCTOBER 2001.

19. Leow, Pei Ling "SVM based hysteresis current controller for a three phase active power filter".

20. F.Z. Peng, J. W. McKeever, D. J. Adams, Cascade Multilevel Inverters for Utility Applications. Industrial Electronics, Control and Instrumentation, 1997, IECON 97, 23rd International Conference on, volume: 2, 9-14 Nov. 1997, pg 437442.

21. Mark McGranaghan "Active power filter design and specification for control of harmonics in industrial and commercial facilities" Electrotek Concept, Inc. Knoxville TN, USA.

22. Haque, M. T. Single Phase PQ Theory for Active Filters. 2002 IEEE Region Conference on Computers, Communications, Control and Power Engineering. Oct 28-31. TENCON 02 Proceedings. 2002. vol. 3: 1941-1944.

23. S. Buso, L. Malesani, Comparison of Current Control Techniques for Active Filter Applications, IEEE Trans on Industrial Electronics. vol. 45. No.5, October 1998.

24. Integrated Publishing, Electrical Engineering Training Series, http://www.tpub.com/neets/book23/101a.htm

56

APPENDIX A

Table of Current Distortion Limits in IEEE Std 519

Harmonic current limits for nonlinear loads at the point-of-common coupling with other loads at voltages of 2.4 to 69 kV Maximum harmonic current distortion in % of fundamental ISC/IL <11
<20* 20-50 50-100 100-1000 >1000 4.0 7.0 10.0 12.0 15.0

Harmonic Order (Odd Harmonics) 11 h<17


2.0 3.5 4.5 5.5 7.0

TDD 35 h
0.3 0.5 0.7 1.0 1.4 5.0 8.0 12.0 15.0 20.0

17 h<23
1.5 2.5 4.0 5.0 6.0

23 h<35
0.6 1.0 1.5 2.0 2.5

Where ISC = Maximum short circuit current at PCC. IL = Maximum load current (fundamental frequency) at PCC.

57

APPENDIX B

MATLAB Documentations for Simulation Model


MSMI_UCI Details for MSMI_UCI Ali Ibrahim Ismaail

25-April-2007

58 Model MSMI_UCI Full Model system


MSMI_UCI

1. MSMI with UCI controller for phase A 2. MSMI with UCI controller for phase B 3. MSMI with UCI controller for phase C 4. Three-phase nonlinear load

Simulation Parameter
Start time Stop time Solver Max step size Min step size Initial step size Relative tolerance Absolute tolerance Maximum order Refine factor Zero cross

Value
0.0 0.4 Variable-step, ode 15s (stiff/NDF) 1e-6 Auto Auto 1e-3 Auto 5 1 On

59 MSMI-UCI system

Table 1- Three-phase AC Voltage Source Block Properties Name


AC AC1 AC2

A
415 415 415

P
0 120 240

F
50 50 50

Stime
0 0 0

Measure
None None None

PSBOutput type
1 1 1

Table 2- Bus Bar Block Properties Name


T connector T connector1

PSBoutput type
1 1

Table 3- Current Measurement Block Properties Name Phasor Simulation


CM CM1 CM2 off off off

Output Type
Magnitude Magnitude Magnitude

PSBOutput Type
01 01 01

PSBequivalent
0 0 0

60 Table 4- From Block Properties Name


FromipcurA FromipcurB FromipcurC

GotoTag
ipcurA ipcurB ipcurC

Defined In
Selector Selector Selector

Table 5- Goto Block Properties Name


GotoipcurA GotoipcurB GotoipcurC

Goto Tag
ipcurA ipcurB ipcurC

Tag Visibility
Local Local Local

Used By
Scope, Gain4, To Workspace, Scope1 Scope2, Gain4, To Workspace1, Scope3 Scope4, Gain4, To Workspace2, Scope5

Table 6- PSB option menu block Block Properties


Name
Powergui

Frange
[0:2:500]

Ylog

Xlog

Save

off

on

Off

Variable ZData

Structure Source

Zoom FFT On

Start time 0.3

cycles
1

DisplayStyle
4

fundamental
50

FreqAxis MaxFrequency
on 5000

frequencyindice
1

Rms Steady
1

display
off

Ts
0

methode
off

frequency
60

Echo messages
off

Table 7- Series RLC Branch Block Properties Name


5 mH 5 mH1 5 mH2

a
10 10 10

b
5e-3 5e-3 5e-3

c
Inf Inf Inf

Measure
None None None

PSBOutput Type
1 1 1

61 Table 8- To Workspace Block Properties


Name
To Workspace1 To Workspace2 To Workspace3

VariableName ipcurA ipcurB ipcurC

MaxDataPoints Inf Inf Inf

Decimation 1 1 1

SampleTime -1 -1 -1

SaveFormat array array array

Table 9- Ground Block Properties Name


Ground (output) Ground (input)1

PSBOutput
1 0

62 Appendix Table 1- Block Type Count BlockType


Goto From

Count
3 3

Block Names
GotoipcurA, GotoipcurB, GotoipcurC FromipcurA, FromipcurB, FromipcurC MSMI with UCI controller for Phase A, MSMI with UCI controller for Phase B, MSMI with UCI controller for Phase C, 3-phaseNon Linear Load, multilevel1for Phase A, multilevel2for Phase A, multilevel1for Phase B, multilevel2for Phase B, multilevel1for Phase C, multilevel2for Phase C, UCI controller for phase A, UCI controller for phase B, UCI controller for phase C Scope, Scope1, Scope2 To Workspace1, To Workspace2, To Workspace3 5 mH, 5 mH1, 5 mH2 powergui CM,CM1.CM2 T connector, T connector1 AC, AC1 AC2 Ground (output), ground (input1)

SubSystem

13

Scope To Workspace Series RLC Branch PSB option menu block (m) Current measurement (m) Bus Bar (m) AC Voltage Source (m) Ground

3 3 3 1 3 2 3 2

Table 2- Model Variables Name


ipcurA ipcurB ipcurC Source

Parent Blocks
FromipcurA FromipcurB FromipcurC Gotoipcur powergui

Calling string
ipcurA ipcurA ipcurB ipcurB ipcurC ipcurC source

63 MSMI-UCI System /Three-phase diode Rect. RC load

64 Table 1- Bus Bar Block Properties Name


Bus Bar (thin horiz) Bus Bar (thin horiz)2 Bus Bar (thin horiz) 1 Bus Bar (thin horiz)3 Bus Bar (thin horiz) 4 Bus Bar (thin horiz) 5 L connector T connector T connector 1 T connector 2 T connector 3

input output
4 0 4 0 4 0 N/A N/A N/A N/A N/A 0 4 0 4 0 4 N/A N/A N/A N/A N/A

PSBOutputType 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111
111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 1 1 1 1 0

Table 2- Current Measurement Block Properties Name


CM1 CM2 CM3

Phaser simulation
off off off

Output type
Magnitude Magnitude Magnitude

PSBOutputType
01 01 01

PSBequivalent
0 0 0

Table 3- Diode Block Properties Name


Diode Diode 1 Diode 2 Diode 3 Diode 4 Diode 5 Diode 6 Diode 7 Diode 8 Diode 9 Diode 10 Diode 11

Ron
0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01

Lon
0 0 0 0 0 0 0 0 0 0 0 0

Vf
0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8

IC
0 0 0 0 0 0 0 0 0 0 0 0

Rs
10 10 10 10 10 10 10 10 10 10 10 10

Cs
0.01e-6 0.01e-6 0.01e-6 0.01e-6 0.01e-6 0.01e-6 0.01e-6 0.01e-6 0.01e-6 0.01e-6 0.01e-6 0.01e-6

PSBOutputType
10 10 10 10 10 10 10 10 10 10 10 10

65 Table 4- In port Block Properties Name


In1 In2 In3

Port
1 2 3

PortDimensions SampleTime
-1 -1 -1 -1 -1 -1

Defined In
constant constant constant

Table 5- Ground Block Properties Name


Ground (input)

PSBOutput
0

Table 6- Series RLC Branch Block Properties Name


R1 R2 R3 R4 R5 R6 1mH 1mH 1 1mH 2 RC1 RC2 RC3

R
125 125 125 125 125 125 1e-3 1e-3 1e-3 0 0 0

L
0 0 0 0 0 0 1e-3 1e-3 1e-3 0 0 0

C
inf inf inf inf inf inf inf inf inf 1000e-06 1000e-06 1000e-06

Measure
None None None None None None None None None None None None

PSBOutputType 1 1 1 1 1 1 1 1 1 1 1 1

Table 7- Terminator Block Properties Name


T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12

66 Table 8- To Workspace Block Properties


Name
To
Workspace

VariableName
loadcurA loadcurB loadcurC

MaxDataPoints
inf inf inf

Decimation
1 1 1

SampleTime
-1 -1 -1

SaveFormat
Array Array Array

To
Workspace1

To
Workspace 2

Table 9- Voltage Measurement Block Properties Name


VM VM 1 VM 2 VM 3 VM 4 VM 5 VM 6 VM 7 VM 8

PhasorSimulation OutputType
off off off off off off off off off Magnitude Magnitude Magnitude Magnitude Magnitude Magnitude Magnitude Magnitude Magnitude

PSBOutputType PSBequivalent
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

67 Appendix Table 1- Block Type Count Block Type


Terminator Series RLC Branch (m) Scope Diode (m)
Voltage Measurement (m)

Count
12 12 12 12 9

Block Names
T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 R1, R2, R3, R4, R5, R6, 1mH, 1mH1, 1mH2, RC1, RC2, RC3 Scope1, Scope2, Scope3, Scope4, Scope5, Scope6, Scope7, Scope8, Scope9, Scope10, Scope11, Scope12 Diode, Diode1, Diode2, Diode3, Diode4, Diode5, Diode6, Diode7, Diode8, Diode9, Diode10, Diode11 VM, VM1, VM2, VM3, VM4, VM5, VM6, VM7, VM8 Bus Bar (thin horiz), Bus Bar (thin horiz)1, Bus Bar (thin horiz)2, Bus Bar (thin horiz)3, Bus Bar (thin horiz)4, Bus Bar (thin horiz)5, T connector, T connector1, T connector2, T connector3, L connector To Workspace, To Workspace1, To Workspace2 Three-phase nonlinear load Ground (input) In1, In2, In3 CM1, CM2, CM3

Bus Bar (m)

To Workspace SubSystem Ground Inport


Current Measurement (m)

3 1 1 3 3

68 MSMI-UCI System / MSMI Level1for phase A

Table 1- Bus Bar Block Properties Name


Bus Bar (thin horiz) Bus Bar (thin horiz)1 T connector

Input Output PSBOutput Type


4 0 N/A 0 4 N/A 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 1

Table 2- Current Measurement Block Properties Name


CM2

Phasor Simulation
off

Output Type
Magnitude

PSBOutput Type
01

PSBequivalent
0

Table 3- Ideal Switch Block Properties Name


S1 S2 S3 S4

Ron
0.01 0.01 0.01 0.01

Initial state
Open Open Open Open

Rs
0.1 0.1 0.1 0.1

Cs
0.01e-6 0.01e-6 0.01e-6 0.01e-6

PSBOutputType
10 10 10 10

69 Table 4- Inport Block Properties Name


In1 In2 In3 In4 In5

Port
1 2 3 4 5

Port dimension
-1 -1 -1 -1 -1

Sample Time
-1 -1 -1 -1 -1

Defined In
Constant DT1 DT6 DT4 DT5

Table 5- Outport Block Properties Name


Out1 Out2

Port
1 2

Output When Disabled


held held

Initial Output
[] []

Used By
Gain1, Scope1 Terminator, Terminator1, T connector

Table 6- Series RLC Branch Block Properties Name


Rf1 Rf2 Cf1

R(Ohms)
100 100 0

L(H)
0 0 0

C(F)
inf inf 500e-6

Measure
None None None

PSBOutput Type
1 1 1

Table 7- Terminator Block Properties Name


T1 T2 T3 T4

Table 8- To Workspace Block Properties


Name To Workspace1 VariablName MaxDtaPoints Decimation IapfA inf 1 SampleTime SaveFormat -1 Array

Table 9- Voltage Measurement Block Properties Name


VM VM 1 VM 2

Phasor Simulation
off off off

Output Type
Magnitude Magnitude Magnitude

PSBOutput Type
0 0 0

PSBequivalent
0 0 0

70 Appendix Table 1- Block Type Count Block Type


Inport Terminator Ideal Switch (m) Series RLC Branch (m) Scope Bus Bar (m) Voltage Measurement (m) Outport To Workspace SubSystem Current Measurement (m)

Count
5 4 4 3 4 3 3 2 1 3 1

Block Names
In1, In2, In3, In4, In5 T1, T2, T3, T4 S1, S2, S3, S4 Rf1, Rf2, Cf1 Scope1, Scope2, Scope3, Scope4 Bus Bar (thin horiz), Bus Bar (thin oriz)1, T connector VM, VM1, VM2 Out1, Out2 To Workspace1 MSMILevel1 for phase A, MSMILevel1 for phase B, MSMILevel1 for phase C CM2

71 MSMI-UCI System / MSMI Level2for phase A

Table 1- Bus Bar Block Properties Name


Bus Bar (thin horiz) Bus Bar (thin horiz)1 T connector

Input Output PSBOutput Type


4 0 N/A 0 4 N/A 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 111111111111111111111111111111111111111111 1

Table 2- Ideal Switch Block Properties Name


S5 S6 S7 S8

Ron
0.01 0.01 0.01 0.01

Initial state
Open Open Open Open

Rs
0.1 0.1 0.1 0.1

Cs
0.01e-6 0.01e-6 0.01e-6 0.01e-6

PSBOutputType
10 10 10 10

72 Table 3- Inport Block Properties Name


In1 In2 In3 In4 In5

Port
1 2 3 4 5

Port dimension
-1 -1 -1 -1 -1

Sample Time
-1 -1 -1 -1 -1

Defined In
Constant DT11 DT10 DT12 DT7

Table 4- Outport Block Properties Name


Out1 Out2

Port
1 2

Output When Disabled


held held

Initial Output
[] []

Used By
Gain5 T connector

Table 5- Series RLC Branch Block Properties Name


Rf1 Rf2 Cf1

R(Ohms)
100 100 0

L(H)
0 0 0

C(F)
inf inf 500e-6

Measure
None None None

PSBOutput Type
1 1 1

Table 6- Terminator Block Properties Name


T1 T2 T3 T4

Table 7- Voltage Measurement Block Properties Name


VM VM 1

Phasor Simulation
off off

Output Type
Magnitude Magnitude

PSBOutput Type
0 0

PSBequivalent
0 0

73 Appendix Table 1- Block Type Count Block Type


Inport Terminator Ideal Switch (m) Series RLC Branch (m) Scope Bus Bar (m) Voltage Measurement (m) Outport SubSystem

Count
5 4 4 3 2 3 3 2 3

Block Names
In1, In2, In3, In4, In5 T1, T2, T3, T4 S5, S6, S7, S8 Rf1, Rf2, Cf1 Scope1, Scope2 Bus Bar (thin horiz), Bus Bar (thin oriz)1, T connector VM, VM1 Out1, Out2 MSMILevel2 for phase A, MSMILevel2 for phase B, MSMILevel2 for phase C

74 MSMI-UCI System / UCI controller

Table 1- Constant Block Properties Name


Const1 Const2

Value VectorParams1D OutDataType Mode


1.250 1.500 on on Inherit from 'Constant value' Inherit from 'Constant value'

ConRadix Group
Use specified scaling Use specified scaling

75 Table 2- DataTypeConversion Block Properties Name


DT5 DT4 DT1 DT6 DT11 DT10 DT7 DT12 DTC1 DTC DT2 DT3 DTC3 DTC2 DT8 DT9

Data type
double double double double double double double double boolean boolean boolean boolean boolean boolean boolean boolean

Table 3- DiscretePulseGenerator Block Properties Name


Ts1 Ts2 Ts3 Ts4 Ts5 Ts6

Pulse Type
Time based Time based Time based Time based Time based Time Based

Amplitude Period
1 1 1 1 1 1 1e-4 1e-4 1e-4 5e-5 1e-4 1e-4

Pulse Width
1 1 1 1 1 1

Phase Delay
0 0 0 0 0 0

Sample Time
1 1 1 1 1 1

VectParas1D
on on on on on on

Table 4- Gain Block Properties Name


Gain1 Gain2 Gain3 Gain4 Gain5 Gain6 Gain7

Gain
-1 250 -1 0.1 -1 600 -1

Multiplication
Element-wise(K.*u) Element-wise(K.*u) Element-wise(K.*u) Element-wise(K.*u) Element-wise(K.*u) Element-wise(K.*u) Element-wise(K.*u)

Out Data Type Mode


Same as input Same as input Same as input Same as input Same as input Same as input Same as input

76 Table 5- Inport Block Properties Name


In1 In2 In3

Port
1 2 3

Port Dimensions
-1 -1 -1

Sample Time
-1 -1 -1

Defined In
Selector Selector Selector

Table 6- Integrator Block Properties Name


Integrator Integrator1

External Reset
rising rising

Initial Condition Source


internal internal

Initial Condition
0 0

Limit Output
off off

Zero Cross
on on

Upper Saturation Limit


inf inf

Lower Saturation Limit


-inf -inf

Show Saturation Port


off off

Show State Port


off off

Absolute Tolerance
auto auto

Table 7- Outport Block Properties Name


Out1 Out2 Out3 Out4 Out5 Out6 Out7 Out8

Port
1 2 3 4 5 6 7 8

Output When Disabled


held held held held held held held held

Initial Output
[] [] [] [] [] [] [] []

Used By
Data Type Conversion, Switch Data Type Conversion, Switch Data Type Conversion, Switch Data Type Conversion, Switch Data Type Conversion, Switch Data Type Conversion, Switch Data Type Conversion, Switch Data Type Conversion, Switch

Table 8- RelationalOperator Block Properties Name


RO RO1 RO2 RO3

Operator
<= <= <= <=

Input Same DT
off off off off

Logic Out Data Type Mode


Logical (see Advanced Sim. Parameters) Logical (see Advanced Sim. Parameters) Logical (see Advanced Sim. Parameters) Logical (see Advanced Sim. Parameters)

Logic Data Type


uint(8) uint(8) uint(8) uint(8)

Zero Cross
on on on on

77 Table 9- SR-FlipFlop Block Properties Name


S-R Flip-Flop S-R Flip-Flop1 S-R Flip-Flop2 S-R Flip-Flop3

Initial condition
0 0 0 0

Table 10- Sum Block Properties Name


Sum1 Sum2

Icon Shape
round round

List of signs
++ ++

Input Same DT
off off

Out Data Type Mode


Inherit via internal rule Inherit via internal rule

Table 11- To Workspace Block Properties Name


To Workspace1 To Workspace2 To Workspace3 To Workspace4 To Workspace5 To Workspace6 To Workspace8 To Workspace9 To Workspace10 To Workspace11

Variable Name
contrl ref S1 S2 S3 S4 S5 S6 S7 S8

Max Data Points


inf inf inf inf inf inf inf inf inf inf

Decimation
1 1 1 1 1 1 1 1 1 1

Sample Time
-1 -1 -1 -1 -1 -1 -1 -1 -1 -1

Save Format
Array Array Array Array Array Array Array Array Array Array

78 Appendix Table 1- Block Type Count Block Type


To Workspace DataTypeConversion Outport Gain DiscretePulseGenerator SRFlipFlop (m) RelationalOperator Inport Sum Scope Integrator Constant SubSystem

Count
10 16 8 7 6 4 4 3 2 2 2 2 3

Block Names
ToWorkspace1, ToWorkspace2, ToWorkspace3, ToWorkspace4, ToWorkspace5, ToWorkspace6, ToWorkspace8, ToWorkspace9, ToWorkspace10, ToWorkspace11 DT5, DT4, DT1, DT6, DT11, DT10, DT7, DT12, DTC1, DTC, DT2, DT3, DTC3, DTC2, DT8, DT9 Out1, Out2, Out3, Out4, Out5, Out6, Out7, Out8 Gain1, Gain2, Gain3, Gain4, Gain5, Gain6, Gain7 Ts1, Ts2, Ts3, Ts4, Ts5, Ts6 S-R Flip-Flop, S-R Flip-Flop1, S-R Flip-Flop2, S-R Flip-Flop3 RO, RO1, RO2, RO3 In1, In2, In3 Sum1, Sum2 Scope, Scope1 Integrator, Integrator1 Const1, Const2 UCI Controller for phase A, UCI Controller for phase B, UCI Controller for phase C