Panel 2 Best of Reversible DC Substation

Railenergy Final Conference Brussels 25th November, 2010

Daniel CORNIC - Sbastien LECHELLE ALSTOM TRANSPORT - ENOTRAC

Brussels 25th November 2010

Railenergy Final Conference NRG-ALS-P-3.2-039

Best of reversible DC substation Context


Transport Authorities and their suppliers today seek Energy Efficiencies as a contribution to both: Their overall business performance Their identity as modern & responsible public service organisations This presentation is about the original design and validation of a reversible DC substation conceived by ALSTOM and shared with Railenergy Trackside works: - It is one of several ALSTOM solutions developed to address customer demand for superior energy management capability in public transport. - It is also the fruit of initiatives and research work that go back to a time before Sustainable Development became fashionable.
Brussels 25th November 2010 Railenergy Final Conference NRG-ALS-P-3.2-039 2

Best of reversible DC substation New technology

Grid

Transformer

USST REGENERATION Umax2 Umax1 TRACTION

Controlled Rectifier
-Controller

Inverter + Active Filter

RECOVERY Control range

U0 Un

DC Railway Network Umin1 ; Umax2 TU Umin1 ; Umax2 TU

3 Iinv

1,5 Iinv Iinv

Irect

1,5 Irect

3 Irect

ISST

Brussels 25th November 2010

Railenergy Final Conference NRG-ALS-P-3.2-039

Best of reversible DC substation Simulation and evaluation


+7% energy saving on Utrech-Zwolle regional line, Netherlands Improved line receptivity (from 77% to 99%) Simplified model has been used for simulation purposes In reality, line receptivity likely to be 100% Rheostatic braking not used anymore (lower tare mass/equip. volume)

1.5 kV DC 87 km long 15 stations 15 min headway 6-to-12 car EMU

Brussels 25th November 2010

Railenergy Final Conference NRG-ALS-P-3.2-039

Best of reversible DC substation Sensitivity analysis Amount of Energy saving is dependent upon:

Operational headways Frequency of the stop points System voltage Line gradients Rolling stock auxiliaries power consumption

Brussels 25th November 2010

Railenergy Final Conference NRG-ALS-P-3.2-039

Best of reversible DC substation Sensitivity analysis Operational headways:


LINEAR NET and GROSS BRAKING POWER (absolute) Regional #1 (3kV - 4km) & Regional #2 (1.5kV - 4km)
100,0 95,0 90,0 85,0 80,0 75,0 70,0

Grid

SS i

Grid SS j

Reg. #1 - Linear Gross Braking Power (kW / line km) Reg. #1 - Linear Net Braking Power (kW / line km) Reg. #2 - Linear Gross Braking Power (kW / line km) Reg. #2 - Linear Net Braking Power (kW / line km)

TU

Hi

TU

kWh/h per line kilometer

65,0 60,0 55,0 50,0 45,0 40,0 35,0 30,0 25,0 20,0 15,0 10,0 5,0 0,0 0 5 10 15 20 25 30 35 40 45 50 55 60

Headway (mn)

Brussels 25th November 2010

Railenergy Final Conference NRG-ALS-P-3.2-039

Best of reversible DC substation Sensitivity analysis Frequency of the stop points:


LRT
20% Daily average recovered (% of traction energy) 18% 16% 14% 12% 10% 8% 6% 4% 2% 0% 0 1000 2000 3000 4000 Di (m) 5000 6000 7000 8000

Grid

SS i

Grid SS j
=

TU METRO It is the absolute value of energy saving that matters for the business case ! PS

TU Di PS

REGIONAL Baseline

Brussels 25th November 2010

Railenergy Final Conference NRG-ALS-P-3.2-039

Best of reversible DC substation Sensitivity analysis System voltage:


8% Daily average recovered (% of traction energy)

Grid

SS i

Grid SS j
=

Ref Railenergy UC3.3

1500 v / 3000 v TU

TU
7% 6% 5% 4% 3% 2% 1% 0% 0 750 1500 2250 DC Voltage (V) 3000 3750

Regional Baseline

Brussels 25th November 2010

Railenergy Final Conference NRG-ALS-P-3.2-039

Best of reversible DC substation Sensitivity analysis Line gradients:


100 80 60 40 20 0 0 -20 Track distance [km] 10 20 30 40 50 60 70 80 90

Grid SS i

Grid SS j

Altitude [m]

1500 v :Base / 1% / 2% =

100 90 80 70 60 50 40 30 20 10 0 0 10 20 30 40 50 60 70 80 90

Regional Baseline gradient +7% savings

Altitude [m]

1% hills +8.5% savings

Track distance [km]

100 90 80 70 60 50 40 30 20 10 0 0

Altitude [m]

2% hills +9% savings

Brussels 20 30 40 25th10 November 2010

50

60

70

80

Railenergy Final Conference 90 NRG-ALS-P-3.2-039

Track distance [km]

Best of reversible DC substation Sensitivity analysis Train auxiliary power:


=

SSi

SSj

1500 v
TU TU
100%

Average train auxiliary power [% of rated power] 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 16% 14% 12% 10% 8% 6% 4% 2% 0% 0 100 200 300 Average train auxiliary power [kW] 400 500

TU

TU

Daily average energy savings (% of traction energy)

Regional Baseline

600

Brussels 25th November 2010

Railenergy Final Conference NRG-ALS-P-3.2-039

10

Best of reversible DC substation Conclusion & outlook


Energy saving targets were reached, and sensitivity analysis was carried out confirming the great potential of reversible substations for energy savings, Validation by LCC analysis and Technical Assessment Report were done, A TecRec (UIC-UNIFE Technical Recommendation) on reversible substation is under progress for future integration into CENELEC standards, An industrial plan is being built on ALSTOM side for 1500V and 3000V DC substation, to be Free for tender after validation of a full scale substation on a railway network. Clip of HESOP project presentation