Anda di halaman 1dari 15

TYPICAL LIQUID LEVEL INSTALLATIONS

Transmitter Connected to Open Tank


Calibrated Range =
160 to 800 mmH2O

Input Data Entry


Span 640 MAXIMUM LEVEL HW, MIN 160
X =

Calculation Result
= (X) 800 = (Y) 200 = (X) 800 + x x (GL) 0.8 (GL) 0.8 (Y) 200 x (GL) 0.8

800

mm

HW, MAX 800

CALIBRATION DATA MINIMUM LEVEL


Y = % Input Simulation mm H2O Output Result mA

200
GL =

mm 0.8 g/cm3

0 25 50 75 100

160.00 320.00 480.00 640.00 800.00

4.00 8.00 12.00 16.00 20.00

Notes
HW = Equivalent Head of Water HW,MIN = HW at minimum liquid level HW,MAX = HW at maximum liquid level GL = Specific gravity of tank liquid

TYPICAL LIQUID LEVEL INSTALLATIONS


Transmitter Connected to Closed Tank with Dry Leg
Calibrated Range =
262.5 to 5512.5 mmH2O

Input Data Entry


Span 5250 MAXIMUM LEVEL HW, MIN 262.5
X =
Dry Leg

Calculation Result
= (X) 5000 = (Y) 250 = (X) 5000 + x x (GL) 1.05 (GL) 1.05 (Y) 250 x (GL) 1.05

5000

mm

HW, MAX 5512.5

CALIBRATION DATA MINIMUM LEVEL


Y = % Input Simulation mm H2O Output Result mA

250
GL =

mm 1.05 g/cm3

0 25 50 75 100

262.50 1575.00 2887.50 4200.00 5512.50

4.00 8.00 12.00 16.00 20.00

Notes
HW = Equivalent Head of Water HW,MIN = HW at minimum liquid level HW,MAX = HW at maximum liquid level GL = Specific gravity of tank liquid

TYPICAL LIQUID LEVEL INSTALLATIONS


Transmitter Connected to Closed Tank with Wet Leg
Calibrated Range =
-4137.5 to 1112.5 mmH2O

Input Data Entry


Span 5250 MAXIMUM LEVEL HW, MIN -4137.5
GS D

Calculation Result
= (X) 5000 = Y 250 = ( X 5000

(GL) 1.05

x (GL)
1.05

D 0.8 (GL) 1.05

(GS) 5500

5500
Wet Leg

X =

5000

mm

HW, MAX 1112.5

Y ) 250

###

D 0.8

(GS) 5500

0.8

### CALIBRATION DATA MINIMUM LEVEL


Y = % Input Simulation mm H2O Output Result mA

250
GL =

mm 1.05 g/cm3

0 25 50 75 100

-4137.50 -2825.00 -1512.50 -200.00 1112.50

4.00 8.00 12.00 16.00 20.00

Notes
HW = Equivalent Head of Water HW,MIN = HW at minimum liquid level HW,MAX = HW at maximum liquid level D = Height of wet leg GL = Specific gravity of tank liquid GS = Specific gravity of wet leg liquid

TYPICAL LIQUID DENSITY INSTALLATIONS


Transmitter Connected to Open Tank With Constant Level
Calibrated Range =
4000.0 to 5400.0 mmH2O

Input Data Entry


INPUT

Calculation Result
Span 1400 HW, MIN 4000 HW, MAX = = = (X) 5000 X 5000 X 5000 x x x ( GMAX 1.08 GMIN 0.8 GMAX 1.08

GMIN ) 0.8

OVER FLOW

X =

5000 0.8 1.08

mm g/cm3 g/cm
3

5400

GMIN = GMAX =

CALIBRATION DATA
% Input Simulation mm H2O Output Result mA

0 25 50 75 100

4000.00 4350.00 4700.00 5050.00 5400.00

4.00 8.00 12.00 16.00 20.00

Notes
HW = Equivalent Head of Water HW,MIN = HW at minimum density HW,MAX = HW at maximum density GMIN = Minimum Specific gravity of tank liquid GMAX = Maximum Specific gravity of tank liquid GS = Specific gravity of wet leg liquid

TYPICAL LIQUID DENSITY INSTALLATIONS


Transmitter Connected to Open Tank With Varying Level
Calibrated Range =
4.0 to 6.0 mmH2O

Input Data
Span 2 MINIMUM LEVEL HW, MIN 4
GS

Calculation Result
= (X) 2 = X 2 = X 2 x x x ( GMAX 4 ( GMIN 3 ( GMAX 4

GMIN ) 3

GS) 1

1
Wet Leg

HW, MAX
X = GMIN = GMAX =

GS ) 1

2 3 4

mm g/cm3 g/cm
3

6 CALIBRATION DATA
%

Input Simulation mm H2O

Output Result mA

0 25 50 75 100

4.00 4.50 5.00 5.50 6.00

4.00 8.00 12.00 16.00 20.00

Notes
HW = Equivalent Head of Water HW,MIN = HW at minimum density HW,MAX = HW at maximum density GMIN = Minimum Specific gravity of tank liquid GMAX = Maximum Specific gravity of tank liquid GS = Specific gravity of wet leg liquid

TYPICAL LIQUID INTERFACE LEVEL INSTALLATIONS


Transmitter Connected to Open Tank With Constan Overflow
Calibrated Range = 590.0
to 690.0 mmH2O

Input Data Entry


Span
OVER FLOW

Calculation Result
= X 500 = ( Y 50 = ( Y 50 x x ( GMAX 1.2 GMAX ) 1.2

GMIN ) 1

A =

30

mm

100 HW, MIN 590 HW, MAX 690

MAXIMUM INTERFACE

( A 30

X ) 500

GMIN 1

GMIN =

g/cm3

X ) 500

GMAX 1.2

( A 30

GMIN ) 1

500 X

mm

CALIBRATION DATA
GMAX = Y =

1.2 50

g/cm mm

Input Simulation mm H2O

Output Result mA

MINIMUM INTERFACE

0 25 50 75 100

590.00 615.00 640.00 665.00 690.00

4.00 8.00 12.00 16.00 20.00

Notes
HW = Equivalent Head of Water HW,MIN = HW at minimum interface HW,MAX = HW at maximum interface GMIN = Minimum Specific gravity of upper (lighter) liquid GMAX = Maximum Specific gravity of lower (heavier) liquid GS = Specific gravity of wet leg liquid

A = Distance constan overflow and desired maximum interface

TYPICAL LIQUID INTERFACE LEVEL INSTALLATIONS


Transmitter Connected to Closed Tank With Wet Leg
Calibrated Range =
105.9 to 183.9 mmH2O

Input Data Entry


Span
MINIMUM LEVEL

Calculation Result
= X 600 = ( Y 30 = ( Y 30 x x ( GMAX 1.08 GMAX ) 1.08

GMIN ) 0.95

78 A = 50 mm HW, MIN 105.9 HW, MAX X = 600 mm 183.9

MAXIMUM INTERFACE GS

( A 50

X ) 600

GMIN 0.95

( A 50

X 600

Y ) 30

GS 0.8

0.8

g/cm3
GMIN =

0.95

g/cm3

X ) 600

GMAX 1.08

( A 50

GMIN ) 0.95

( A 50

X 600

Y ) 30

GS 0.8

CALIBRATION DATA
GMAX =

1.08

g/cm

% Y =

Input Simulation mm H2O

Output Result mA

MINIMUM INTERFACE

30

mm

0 25 50 75 100

105.90 125.40 144.90 164.40 183.90

4.00 8.00 12.00 16.00 20.00

Notes
HW = Equivalent Head of Water HW,MIN = HW at minimum interface HW,MAX = HW at maximum interface GMIN = Minimum Specific gravity of upper (lighter) liquid GMAX = Maximum Specific gravity of lower (heavier) liquid GS = Specific gravity of wet leg liquid

A = Distance minimum level and desired maximum interface

Anda mungkin juga menyukai