Anda di halaman 1dari 8

SA5/18/EN/1

Heater Banks
Type TV-HB For connection to VAV Terminal Boxes

TROX South Africa (Pty) Ltd. 10 Wigford Road Masons Mill Pietermaritzburg

Tel. +27 (0)33 398 1006 Fax. +27 (0)33 398 1100 email : pmb@troxsa.co.za Website: www.troxsa.co.za

Introduction Manufacturing Details


Introduction Manufacturing Details Selection Data Selection Data Electrical Specications Heater Capacities Wiring Diagram Overheat Thermostat Order Codes Order Example Introduction 2 2 3 4 5 5 6 6 7

The TROX TV-HB heater banks provide electrical heating in order to condition supply air in commercial and industrial applications. The heater banks have been designed for easy installation on the rectangular ends of TROX VAV Terminal Boxes TVA-TVB. The heater banks are available with a range of heating capacities in order to suite the desired heating requirements with option of thermal insulation (mill board or breglass) and thermal cut-off device (auto or manual reset).

Manufacturing Details

Galvanised housing with 30mm frame Galvanised removable cover to heater terminals Black heat elements Silicon wire to elements IP55 Terminal box Optional insulation o 12mm Mill board internally lined o 25mm breglass externally lined Optional thermal cut-off device (auto or manual)

Selection Data
Selection Data
Size (TVZ) . V max (l/s) Max Heater Capacity (kW) Heater Bank Size (mm) B 198 308 458 598 798 898 H 152 152 210 500 250 315 400 615 1025 1680 9 12 15 201 252 354 235 286 388 632 832 932 L E 186 186 244 F 232 342 492

125 160 200

150 250 405

1.5 2.5 6

30

30

30

30

Terminal box

Selection Data

Cover

Heater element Mounting bracket [removable}

Heater element

Heater bank casing

Terminal box xed to the side

Electrical Specication
Heater Capacities In order to meet the desired requirements the range of TROX TV-HB heater banks is available with a range of different wiring schemes, each of which presented in the table below. Along with every heater bank, a full wiring diagram is supplied. Each heater bank is designed to be balanced across the phases All wiring terminates in an IP55 terminal box on the side (left or right) of the heater bank. Each terminal box has additional terminals for an overheat thermostat to be connected.

Standard Heater Capacity [W]


500

Single Phase (230V)

Three Phase (400V) Step 1 Step 2 Step 3

750

1000

1500

2000

2500

3000

4500

6000

9000

12000

15000

Electrical Specication
Overheat Thermostat For safety purposes the TROX TV-HB may be supplied with either an auto or manual overheat thermostat. Capillary thermostat with adjustable cut out (0-120C) either manual or automatic reset (240V, 20A) Surface mount thermostat with set cut out (65C) either manual or automatic reset ( 230V,16A)

Three Phase - 1 Step

Blue White Red (Neutral) Black MCB MCB MCB

To control

K1

K1 Supply & Switch gear by others Heater bank complete with terminal box by TROX + Black Blue White Red

Legend .................................. = Terminal box

OHS 10A Step 1

Single Phase

(230Vac) Live Neutral MCB

K1 Supply & Switch gear by others Heater bank complete with terminal box by TROX Live

Neutral

OHS

Order Details

T V- H B

250

500 W Watts : 500 W 750 W 1000 W 1500 W 2000 W 2500 W 3000 W 4500 W 6000 W 9000 W 12000 W 15000 W

Size: 125 160 200 250 315 400

Step: 1 2 3

Insulation: 0 = None 1 = Fibreglass 2 = Mill board

Terminal Box: L = Left R = Right Phase: 1 = Single Phase 3 = 3 Phase 0= 1= 2= 3= 4= 5= (In direction of Air Flow) Accessories None Manual overheat stat Auto overheat stat Pressure switch Pressure switch with manual overheat stat Pressure switch with auto overheat stat

Order Example: Make : TROX Order Details: TV-HB/250/500/3/3/1/0/L

Design changes reserved All rights reserved TROX South Africa (Pty) Ltd October 2005