NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

NCCI: Design of portal frame eaves connections


This NCCI provides information on the design method for a bolted eaves moment connection. It includes several simplifications which are explained throughout the document, to obtain simpler but conservative calculations.

Contents
1. 2. 3. 4. 5.
Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

Design model Parameters Weld design Potential resistances of bolt rows in the tension zone Assessment of the compression zone Column web panel in shear Rafter web in compression Force distribution in bolt rows Assessment of the shear resistance Limits of application Background.

2 4 6 7 12 14 15 15 19 20 21

6. 7. 8. 9. 10. 11.

Page 1

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

1.
1.1

Design model
Stiffness

According to 5.2.2.1(1) of EN 1993-1-8, a joint can be classified as rigid, nominally pinned or semi-rigid according to its rotational stiffness by comparing its initial stiffness, Sj,ini with the classification boundaries given in 5.2.2.5 of EN 1993-1-8. The initial stiffness of a joint connecting H or I sections may be calculated according to the rules given in 6.3.1 of EN 1993-1-8. A joint may be classified on the basis of experimental evidence, experience of previous satisfactory performance in similar cases or by calculations based on test evidence.

1.2

Strength

1.2.1 General model


The moment resistance, Mj,Rd, and the shear resistance, Vj,Rd, of the joint depend on the connected members and the basic components of the joint that make a contribution to the joint resistance: bolts, column web and flanges, haunch and rafter web and flanges and welds, see Figure 1.1. 6.1.3 and Table 6.1 of EN 1993-1-8 provide the information to identify the basic joint components.
9 9 4 6 VEd 3 M j,Ed 4 6 VEd 3 M j,Ed

Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

1 B 2 B

1 2

5 8 C 10 7 C 10 7

5 8

(a) Flush end plate Key: 1. Column 2. Eaves haunch A. Tension zone 3. Rafter 4. Flange Weld 5. Web weld 6. Bolts B. Shear zone

(b) Extended end plate 7. End plate 8. Shear bolts 9. Optional tension stiffeners 10. Compression stiffener C. Compression zone

Figure 1.1

Portal frame eaves connections with bolted end plate

Page 2

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

Some countries treat the bolts in the tension zone and in the shear zone as one group of bolts, therefore, extra bolts (noted * in Figure 1.1) may be required to satisfy the spacing requirements in Table 3.3 of EN 1993-1-8. Other countries treat them as two separate bolt groups, and no additional bolts are necessary. According to EN 1993-1-8 6.2.7.2, once the basic components have been identified, the design moment resistance of the eaves bolted end-plate joints may be determined from:
M j, Rd = hr Ftr, Rd
r

where:

Ftr, Rd

is the effective design tension resistance of bolt-row r, is the distance from bolt-row r to the centre of compression; this can be taken as the middle of the compression flange of the haunch. is the bolt-row number.

hr

The joint must satisfy:

M j, Ed
Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

M j, Rd

1,0

The procedure to determine the joint resistance is presented in Table 1.1.


Table 1.1 Procedure to determine Ftr,Rd and the joint resistance
Step 1. Calculate potential tension resistance of each bolt row in the tension zone 2. Calculate the design compression resistance in the compression zone 3. Calculate the design shear resistance of the column web panel 4. Calculate the effective design tension resistance of each bolt row 5. Calculate the moment resistance of the joint 6. Assessment for vertical shear forces

Ft, Rd(row) Fc, Rd Vwp, Rd Ftr, Rd

M j, Rd = hr Ftr, Rd
r

VEd VRd

1.2.2 Simplifications
Several simplifications have been done in this NCCI in order to make the calculation of the eaves moment connections easier, leading to a conservative approach. These are described below: In the full calculation the tying resistance of bolt rows should be calculated by considering bolt rows individually and bolt rows as part of groups of bolt rows, and taking the minimum resistance obtained. In this simple approach, only the individual bolt rows are considered. This leads to conservative results but saves a lot of time and effort in the process. Page 3

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

The effective length of each T-stub to calculate the tying resistance of the bolt row is taken as the minimum possible effective length to avoid the superposition of the effective lengths of the different bolt rows. This is shown in section 4.1 in this document. Based on 6.2.2(2) of EN 1993-1-8 the tension zone and the shear zone are treated separately. It is assumed that bolts in the tension zone support only tension and no shear. Similarly the bolts in the shear zone only support shear and no tension. 4 of EN 1993-1-8 gives rules for weld design. Weld design is usually carried out after the calculation of the design resistance of the connection. However, this NCCI gives simple rules for the initial sizing of the welds. It specifies full strength welds, which leads to a simple calculation procedure. Further methods for weld design are given in Annex A of this NCCI.

2.
e1
Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

Parameters
bc ex b ep w ec ep d1 hc IPE 500 ex d2 p p p t ep IPE 450

d2 p p p h ep p2 p3 d3 epl

a p3 d3 e pl 3000

IPE 450

Figure 2.1

Portal frame eave: Parameter definition

a Afb bp d1 d2 d3 e1 ec ep

effective throat thickness of the weld; cross section of the rafter flange width of the end plate distance from the top of the tension flange of the rafter to the edge of the end plate pitch between the bolt row in the extended zone of the end plate and the first bolt row below the tension flange of the rafter distance from the last shear bolt row to the bottom of the compression flange of the haunch vertical distance from the edge of the column flange to the first bolt row horizontal distance from the edge of the column flange to the bolt line horizontal distance from the edge of the end plate to the bolt line Page 4

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

epl ex fub fu,b fu,c fu,h fu,p fy,b fy,c fy,h fy,p hc hp
Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

distance between the bottom of the compression flange of the haunch and the edge of the end plate vertical distance from the edge of the end plate to the first bolt row ultimate strength of the bolt ultimate strength of the rafter ultimate strength of the column ultimate strength of the haunch ultimate strength of the end plate yield strength of the rafter yield strength of the column yield strength of the haunch yield strength of the end plate depth of the column depth of the end plate distance from the centre of a bolt to 20% distance into the adjacent haunched rafter weld to the end-plate or distance from the centre of a bolt to 20% distance into the column web root (as indicated in Figure 6.2 of EN1993-1-8). number of bolts in shear number of horizontal bolt rows in tension pitch between bolt rows in the tension zone pitch between the last tension bolt and the first shear bolt pitch between bolt rows in the shear zone is the bolt row number, the bolt-rows are numbered starting from the bolt-row furthest from the centre of compression; gauge (i.e. distance between cross centres) thickness of the rafter flange thickness of the column flange thickness of the end plate thickness of the rafter web thickness of the column web

ns nt p p2 p3 r w tfb tfc tp twb twc

Page 5

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

3.
3.1

Weld design
Tension flange to end-plate weld

Conservatively a full strength weld is appropriate. This requirement will be satisfied provided the weld throat thickness is such that:

f y w M2 a tfb f M0 u 2 where: fy fu is yield strength of rafter section is nominal ultimate strength of the weaker part joined (i.e. end plate or rafter section) is the correlation factor from Table 4.1 of EN 1993-1-8

When M0 = 1,0 and M2 = 1,25:


Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

a 0,46 t fb for a S235 beam a 0,48 t fb for a S275 beam


a 0,55 t fb for a S355 beam

Additional calculation methods are given in Annex A of this NCCI.

3.2

Web to end-plate weld

Rafter web welds in the tension zone should conservatively be full strength. It is sensible to use this full strength weld for the full web depth as well. This requirement will be satisfied provided the weld throat thickness is such that: f y w M2 a t wb f M0 u 2 where: fy fu is yield strength of rafter section is nominal ultimate strength of the weaker part joined (i.e. end plate or rafter section)

w is the correlation factor from Table 4.1 of EN 1993-1-8


When M0 = 1,0 and M2 = 1,25
a 0,46 t wb for a S235 beam

Page 6

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

a 0,48 t wb for a S275 beam a 0,55 t wb for a S355 beam

3.3

Compression flange welds

If the compression flange has a properly sawn end, a nominal weld is sufficient and the following throat thicknesses are recommended: 5 mm fillet welds or 4 mm fillet welds, for beams with flange thickness of 12 mm or less In other cases, the weld must be designed to carry the full compressive force expected in the haunch flange.

4. Potential resistances of bolt rows in the tension zone


Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

NOTE: EN 1993-1-8 uses the symbol Ft,Rd to refer to both the tension resistance of an individual bolt row and the tension resistance of one bolt. In this document Ft,Rd(row) has been used to refer to the tension resistance of the row.

For each bolt row, the potential design tension resistance is given in EN 1993-1-8 6.2.7.2(6):
Ft, Rd(row)
Table 4.1
Component Column flange in bending Column web in transverse tension End-plate in bending Rafter web in tension

= min Ft, fc, Rd ;

Ft, wc, Rd ; Ft, ep, Rd ; Ft, wb, Rd

)
Section number

Components of the joint to determine the potential design resistance of a bolt row

Ft, fc, Rd Ft, wc, Rd Ft, ep, Rd Ft, wb, Rd

4.1 4.2 4.3 4.4

The potential design tension resistance Ft,Rd(row) for each bolt-row should be determined in sequence, starting from the furthest bolt row from the centre of compression (bolt row 1) and then progressing to the next one (bolt-row 2) until the last one, the closest one to the centre of compression, is calculated (see Figure 4.1). Assume the centre of compression is in line with the centre of the compression flange of the haunch.

Page 7

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

r =1

r =1 r =2 r =3

r =2 r =3 r =4

(a) Flush end plate

(b) Extended end plate

Figure 4.1

Order to determine the potential design tension resistance of bolt rows in eaves connections.

Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

For simplicity and ease of calculations, the potential design tension resistance of each boltrow assumes that there is no overlap with other bolt-rows. This simplified approach leads to conservative results assuming that T-stub effective length eff is determined accordingly, see worked example SX031. The effective design tension resistance Ftr,Rd for each bolt row may be less than the potential design tension resistance Ft,Rd(row)

4.1

Column flange in bending

The design resistance and failure mode of an unstiffened column flange in transverse bending, together with the associated bolts in tension, should be taken as similar to those of an equivalent T-stub flange. Ft,fc,Rd = min (FT,1,Rd, FT,2,Rd, FT,3,Rd); accounting for prying forces and the three failure modes (see table 4.2 below). This is the same as Table 6.2 of EN 1993-1-8 6.2.4:
Table 4.2
Failure mode Mode 1 Complete flange yielding

Failure modes and design resistance


Design resistance

FT,1, Rd =
FT,2, Rd =

4 M pl,1, Rd m
2 M pl,2, Rd + n Ft, Rd m+n

Mode 2

Bolt failure with flange yielding

Mode 3

Bolt failure

FT,3,Rd = Ft,Rd

Page 8

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

where:
Ft, Rd = 0,9 f ub As

M2

is the tension resistance of non countersunk bolts. i.e. two bolts per row

Ft,Rd = 2Ft,Rd
M pl,1, Rd M pl,2, Rd
n

= 0,25 l eff,1t fc 2 f y / M0 = 0,25 l eff,2 tfc 2 f y / M0


= emin

but

n 1,25m , see Figure 6.2 in EN 1993-1-8

leff

can be determined according to Figure 6.2, Figure 6.9 and Table 6.4 (for unstiffened

columns) or Table 6.5 (for stiffened columns) of EN 1993-1-8. Alternatively a simple conservative approach as given below can be used.
Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

For an individual bolt row the following simplification can be made:

leff,1 = leff,2 = Leff


leff,1 is leff,2 is
the value of the value of

as shown in figure 4.2 below

leff leff

for mode 1 for mode 2

This method is based on the assumption that the effective length is always limited to a maximum distance of the pitch between bolt centres. Figure 4.2 and table 4.3 illustrate this approach.

Page 9

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

L eff

Row 1 Row 2 Row 3

Leff

Leff =p

L eff =p

(a)
L eff Row 1 Row 2 Row 3 Row 4

Leff

Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

Leff =p

L eff =p

(b)

Figure 4.2

Effective lengths of the T-stub in (a) extended end plate and (b) flush end plate connections.

Page 10

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

Table 4.3

Effective length for each bolt row


End bolt row adjacent to a stiffener (stiffened column flange) or outside the tension flange of the rafter (end plate) Inner bolt row adjacent to a stiffener (stiffened column flange) or below the tension flange of the rafter (end plate)

End bolt row

Inner bolt row

2m m + 2e1 2m m + 2e1
4m + 1,25e 2m + 0,625e + 0,5 p
e1+ 0,5 p
2m x

e1 + m (2m + 0,625e )

2m m m + p
0,5 + m (2m + 0,625e )

2m 4m + 1,25e p

mx + 2 w mx + 2e
4mx + 1,25ex e + 2mx + 0,625ex
0,5bp

0,5w + 2mx + 0,625ex


Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

4.2

Column web in transverse tension

The transverse tension resistance for an unstiffened column web is given in EN 1993-1-8 6.2.6.3 as:

Ft, wc,Rd
where:

beff,t, wc t wc f y,wc M0

1 1 + 1,3(beff,c, wc twc / Avc )


2

is the reduction factor to allow for the interaction with

shear in the column web panel. Avc is the shear area of the column, see EN 1993-1-1 6.2.6(3). For rolled I and H sections it can be conservatively taken as hw t w .

beff,t, wc = l eff , see section 4.1

4.3

End-plate in bending

The design resistance and failure mode of an end-plate in bending, together with the associated bolts in tension, can be determined following the methodology given in section 4.1 of this document for column flange in bending and using Table 6.6 instead of Table 6.4 of EN 1993-1-8.
Ft,ep,Rd = min( FT,1, Rd ; FT,2, Rd ; FT,3, Rd )

Page 11

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

4.4

Rafter web in tension

The resistance of the rafter web in tension for an unstiffened web can be calculated according to EN 1993-1-8 6.2.6.8 as follows:

Ft,wb,Rd
where:

beff,t,wb t wb f y,wb

M0

beff,t, wc = l eff , see section 4.1

5.

Assessment of the compression zone


Fc, fh, Rd )

The design compression resistance of the compression zone may be calculated as follows:
Fc, Rd = min (Fc, wc, Rd ;
Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

For Fc, wc, Rd and Fc,fh, Rd see sections 5.1 and 5.2 below. In addition, it is necessary to assess that:
Fc, Ed Fc, Rd

Due to the fact that haunches in portal frames are typically long enough, the component of the compression force in the direction of the haunch can be considered as the horizontal component acting in the column web, which is the sum of the tensile resistances of the bolts:

Fc, Ed = Ft, Rd(row)


Table 5.1
Component Column web in compression Haunch flange and web in compression

Components of the joint involved in the assessment of the compression zone


Section number

Fc, wc, Rd Fc, fh, Rd

5.1 5.2

5.1

Column web in transverse compression

5.1.1 Requirement of a compression stiffener


A stiffener is needed when the column web in compression is not strong enough to take all the compression force. The stiffener also guards against the buckling of column web. The stiffener also improves the stability of the column, especially if there is a plastic hinge forming at this position. In most practical cases a compression stiffener will be required. Page 12

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

5.1.2 Column web with a compression stiffener


The design resistance of a stiffened column subject to transverse compression may be done in accordance with 9.1(3) of EN 1993-1-5.

5.1.3 Column web without a compression stiffener


The design resistance of an unstiffened column web subject to transverse compression is given in EN 1993-1-8, 6.2.6.2:

Fc, wc, Rd
where:

k wcbeff,c, wct wc f y, wc k wc beff,c, wc t wc f y, wc ; = min M0 M1

is a reduction factor, see section 4.2

beff,c,wc
ap
Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

= t fb + 2 2 a p + 5(t fc + s) + s p ; is the effective width of column web in compression for bolted end-plate connections.
is the weld throat. is the length obtained by dispersion at 45 through the end-plate (at least t p and, provided that the length of end-plate below the flange is sufficient, up to 2t p ). is the reduction factor for plate buckling:

sp

if p 0,72

then

= 1,0

if p > 0,72 then

( p 0,2)

p2

where

p = 0,932

beff,c,wc d wc f y,wc E t wc 2

it the plate slenderness.


d wc = hc 2(t fc + rc )

for a rolled I or H section column: for a welded I or H section column:


k wc

d wc

= hc 2(t fc + 2ac )

is a reduction factor accounting the maximum longitudinal compressive stress com,Ed due to axial force and bending moment in the column web (adjacent to the root radius for a rolled section or the toe of the weld for a welded section) when com,Ed 0,7 f y,wc when com,Ed > 0,7 f y,wc then then
k wc = 1,0
k wc = 1,7 com,Ed f y,wc

Page 13

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

In preliminary calculations, a value of k wc = 1,0 is recommended, as well as checking the value later, once the longitudinal stress is known. However, the value of k wc = 0,7 can conservatively be used.

5.2

Haunch flange and web in compression

The compression resistance of the haunch flange is given by the following expression in 6.2.6.7 of EN 1993-1-8.

Fc,fh,Rd,
h Mc,Rd

(h t fh )

M c,Rd

is the depth of the beam including rafter and haunch is the design moment resistance of the beam (rafter + haunch) cross-section, reduced if necessary to allow for shear, see EN 1993-1-1 6.2.5. Mc,Rd may be calculated neglecting the intermediate flange. is the flange thickness of the connected haunch.

tfh
Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

If the height of the beam (rafter + haunch) exceeds 600 mm the contribution of the rafter web to the design compression resistance should be limited to 20%. This means that if the resistance of the flange is t fb bfb f y,fb then:
Fc,fh, Rd tfbbfb f y,fb 0,8

6.

Column web panel in shear

d 69 , the tw resistance of the column web panel in shear for an unstiffened column, according to 6.2.6.1 of EN 1993-1-8, is:

Provided the column web slenderness satisfies the following condition:

Vwp, Rd
where
Avc

0,9 f y, wc Avc 3 M0

is the shear area of the column, see EN 1993-1-1 6.2.6(3) and section 4.2 in this document.

Page 14

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

7.

Rafter web in compression

The design resistance and failure mode of the rafter web in compression, due to the reinforcement of the haunch, can be determined following the methodology given in section 5.1 for column web in transverse compression:

Figure 7.1
Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

Failure of the rafter web in compression

Fc, wb, Rd

k wc beff,c, wb t wb f y, wb k wc beff, c, wbt wb f y, wb = min ; M0 M1

If this resistance is not enough to support the acting compression force in the rafter web, a compression stiffener should be provided.

8.

Force distribution in bolt rows

The potential resistance in each bolt row Ft,Rd (see section 4) is calculated one row at a time, starting at the top and working down. The force permitted in any bolt row is based on its potential resistance, and not on its lever arm. Bolts rows near a point of stiffness, such as the beam flange or a stiffener, will be therefore attract more load and have higher potential resistance.
Plastic distribution

A plastic distribution of forces in bolt rows is permitted, but this is only possible if the deformation of the column flange or end plate can take place. There are two conditions that the effective tension resistance of the bolts must satisfy (see Figures 8.1(a) and 8.2(a): According to EN 1993-1-8 6.2.7.2(7) compression resistance or the shear resistance of the column web panel must be greater than the sum of the tension resistance of all the bolts: 1. Compression: Ft,Rd(row) min(Fc,wc,Rd ; Fc,fh,Rd ; Fc,wb,Rd )

Page 15

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

2.

Column web panel in shear:

Ft,Rd(row)

Vwp,Rd

See sections 5 and 6 for the calculation of the compression resistance and the shear resistance of the web panel.

=1

is the transformation parameter according to EN 1993-1-8 5.3(8)

If the conditions mentioned above are not satisfied then modifications are required (see Figures 8.1(b) and 8.2(b)).
Triangular limit

According to 6.2.7.2(9) of EN 1993-1-8, no bolt row should have a potential tension resistance greater than 1,9 times the effective tension resistance of any of the bolt rows below:
Ftx, Rd 1,9 Ft, Rd

where
Ftx, Rd
Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

is the effective design tension resistance of bolt row x is the furthest bolt row from the centre of compression that has an effective tension resistance greater than 1,9 times the effective tension resistance of any of the bolts below.

If the potential resistance of a bolt row is governed by mode 3 failure (i.e. bolt failure) (given as Ft, Rd(row) 1,9 Ft, Rd ) then plastic distribution is not possible. Therefore modification to the potential resistance is made to ensure that they do not exceed the triangular distribution for rows below the rafter flange (see Figures 8.1 and 8.2).

Page 16

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

F tx,Rd 1.9 F t,Rd F t,Rd,1 F t,Rd,2 F t,Rd,3

F tx,Rd 1.9 F t,Rd Ftr,Rd,1 = F t,Rd,1 Ftr,Rd,2 = F t,Rd,2 Ftr,Rd,3< F t,Rd,3

F c,Rd F t,Rd,i
(a) Plastic distribution Because Fc,Rd and Vwp,Rd Ft,Rd,i therefore the effective tension resistance (Ftr,Rd) is equal to the potential design resistance (Ft,Rd,i)

F c,Rd < F t,Rd,i F c,Rd = tr,Rd,i F

(b) Modified plastic distribution Because Fc,Rd and/or Vwp,Rd < Ft,Rd,i therefore the effective tension resistances (Ftr,Rd) have to be reduced starting from the closest bolt to the compression centre:
F tx,Rd > 1.9 F t,Rd F t,Rd,1 = F tr,Rd,1 Ftr,Rd,2 Ftr,Rd,3

Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

F tx,Rd > 1.9 F t,Rd F t,Rd,1 = F tr,Rd,1 Ftr,Rd,2 Ftr,Rd,3

F c,Rd F t,Rd,i
(c) Triangular limit Because Ftx,Rd > 1,9 Ft,Rd the effective tension resistance has to be reduced:

F c,Rd < F t,Rd,i F c,Rd = F tr,Rd,i

(d) Triangular limit Because Ftx,Rd > 1,9 Ft,Rd the effective tension resistance has to be reduced:

Ftr,Rd = Ftx,Rd

hr hx

Ftr,Rd = Ftx,Rd

hr hx

Because Fc,Rd and/or Vwp,Rd < Ft,Rd,i the effective tension resistances (Ftr,Rd) have to be reduced, starting from the closest bolt to the compression centre

Figure 8.1

Flush end plate force distribution in bolt rows.

Page 17

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

F t,Rd,1

F tx1,Rd 1.9 F t,Rd F t,Rd,2

Ftr,Rd,1 = F t,Rd,1 F tx1,Rd 1.9 F t,Rd Ftr,Rd,2 = F t,Rd,2 Ftr,Rd,3 = F t,Rd,3 Ftr,Rd,4< F t,Rd,4

F t,Rd,3 F t,Rd,4

F c,Rd F t,Rd,i

F c,Rd < F t,Rd,i F c,Rd = tr,Rd,i F

(a) Plastic distribution Because Fc,Rd and Vwp,Rd Ft,Rd,i therefore the effective tension resistance (Ftr,Rd) is equal to the potential design resistance (Ft,Rd,i)
F t,Rd,1 = F tr,Rd,1 F tx1,Rd > 1.9 F t,Rd F t,Rd,2 = F tr,Rd,2 Ftr,Rd,3 Ftr,Rd,4

(b) Modified plastic distribution Because Fc,Rd and/or Vwp,Rd < Ft,Rd,i therefore the effective tension resistances (Ftr,Rd) have to be reduced starting from the closest bolt to the compression centre
F t,Rd,1 = F tr,Rd,1 F tx1,Rd > 1.9 F t,Rd F t,Rd,2 = F tr,Rd,2 Ftr,Rd,3 Ftr,Rd,4

Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

F c,Rd F t,Rd,i

F c,Rd < F t,Rd,i F c,Rd = tr,Rd,i F

(c) Triangular limit Because Ftx,Rd > 1,9 Ft,Rd therefore the effective tension resistance has to be reduced:

(d) Triangular limit Because Ftx,Rd > 1,9 Ft,Rd therefore the effective tension resistance has to be reduced:

Ftr,Rd = Ftx,Rd

hr hx

Ftr,Rd = Ftx,Rd

hr hx

Because Fc,Rd and/or Vwp,Rd < Ft,Rd,i therefore the effective tension resistances (Ftr,Rd) have to be reduced starting from the closest bolt to the compression centre

Figure 8.2

Extended end plate force distribution in bolt rows.

Page 18

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

9.

Assessment of the shear resistance

The design shear resistance to vertical shear forces of the joint must be determined by accounting the contributions of the relevant basic components:
VRd = ns min Fv, i, Rd ;

Fb, i, fc, Rd ;

Fb, i, ep, Rd ; see Table 9.1

where
ns
Table 9.1
Component Bolts in shear Bolts in bearing on column flange Bolts in bearing on end-plate
Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

is the number of bolts that are required to resist shear, see EN 1993-1-8 6.2.2(2)
Components of the joint involved in the assessment of the shear resistance
Section number

Fv, Rd
Fb, c, Rd Fb, ep, Rd

9.1 9.2 9.3

9.1
Fv,Rd

Bolts in shear
=

The design resistance of bolts in shear is given in EN 1993-1-8 3.6 as:

v f ub As M2
is the tensile stress area of the bolt for bolt classes 4.6, 5.6 and 8.8 for classes 4.8, 5.8, 6.8 and 10.9

where:
As

v = 0,6 v = 0,5

9.2

Bolts in bearing on column flange

The design resistance of bolts in bearing on the column flange is given by the following expression according to Table 3.4 of EN 1993-1-8.

Fb,c,Rd =
where:

k1 b f u d t fc M2
f ub ; 1,0 fu
p1 1 3d 0 4

= min d ;
e1 3d 0

in the direction of load transfer:

for end bolts; d

for inner bolts

Page 19

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

perpendicular to the direction of load transfer:

k1 k1

e = min 2,8 2 1,7; 2,5 d 0 p = min1,4 2 1,7; 2,5 d0

for edge bolts

for inner bolts

9.3

Bolts in bearing on end-plate

The design resistance for bolts subjected to shear on the end-plate, can be determined following the methodology given in the section 9.2 for bolts in bearing in the column flange:

Fb,ep,Rd =

k1 a b f u d t p M2

10. Limits of application


Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

The application of this document must be in accordance with the rules and relevant limits of application set out in EN 1993-1-8. A summary of these is presented below: Haunches should be arranged according to EN 1993-1-8 6.2.6.7(2): the steel grade of the haunch should match that of the member; the flange size and the web thickness of the haunch should not be less than that of the member; the angle of the haunch flange to the flange of the member should not be greater than 45; the length of stiff bearing ss should be taken as equal to the thickness of the haunch flange parallel to the beam. According to EN 1993-1-8 6.2.6.7(2), the method given in this document for determining the design moment resistance of a joint Mj,Rd should not be used if the axial force in the connected member exceeds 5% of the design plastic resistance Np,Rd of its cross-section According to EN 1993-1-8 6.2.6.7(3) the following conservative method may be used, if the axial force NEd in the connected beam exceeds 5% of the design resistance, Npl,Rd: M j,Ed M j,Rd where: Mj.Rd Nj.Rd is the design moment resistance of the joint, assuming no axial force; is the axial design resistance of the joint, assuming no applied moment. + N j,Ed N j,Rd 1,0

Bolts in the tension zone are assumed to provide their full design resistance in tension and the total shear resistance is assumed to be provided by the bolts in the shear zone. Page 20

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

11. Background.
The rules in this NCCI are based on: (1) EN 1993-1-8:2005 Eurocode 3: Design of Steel Structures Part 1-8: Design of Joints. CEN. (2) EN 1993-1-1:2005 Eurocode 3: Design of Steel Structures Part 1-1:General rules and rules for buildings. CEN. (3) ENV 1993-1-1:1992 and ENV 1993-1-1 AC:1992, Eurocode 3: Design of Steel Structures Part 1-1: General rules and rules for Buildings. CEN. (4) Joints in Steel Construction Moment Connections (P207). The Steel Construction Institute and The British Constructional Steelwork Association Ltd., 1995.

Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

Page 21

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

Annex A
Tension flange to end plate weld
1. Design a weld to carry the tension capacity of the flange

N pl, Rd =
2.

Afb f y

M0

Design a weld to carry the total tension force in the top three bolt rows for an extended end plate:

Ftr,Rd = Ft1,Rd + Ft2,Rd + Ft3,Rd


or the total tension force in the top two bolt rows for a flush end plate:

Ftr,Rd = Ft1,Rd + Ft2,Rd


Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

According to the simplified method in 4.5.3 of EN 1993-1-8, the design resistance of the weld per unit length, Fw, Rd is:
Fw, Rd = f vw, d a

where:
Fw, Ed Fw, Rd Fw, Ed f vw, d

is the design value of the weld force per unit length; is the design shear resistance of the weld: f vw,d =

w M2

fu / 3

fu

is the nominal ultimate tensile strength of the weaker part joined is the correlation factor, see Table 4.1 in EN 1993-1-8.

The length of the weld to multiply with the design resistance per unit length to obtain the total design resistance of the weld is:
beff = b 2a

where b a is the total length of the weld is the throat of the weld

If the size of the weld is too big ( a 12mm ) then the use of partial depth penetration butt welds reinforced by superimposed fillet welds is recommended. The design resistance of butt welds is given in EN 1993-1-8 4.7. Page 22

NCCI: Design of portal frame eaves connections

NCCI: Design of portal frame eaves connections SN041a-EN-EU

Quality Record
RESOURCE TITLE Reference(s) ORIGINAL DOCUMENT Name Created by Technical content checked by Editorial content checked by Technical content endorsed by the following STEEL Partners: 1. UK 2. France 3. Sweden
Created on Monday, January 03, 2011 This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement

NCCI: Design of portal frame eaves connections

Company LABEIN LABEIN

Date

Jaime Grijalvo Jose Antonio Chica

G W Owens A Bureau B Uppfeldt C Mller J Chica G W Owens

SCI CTICM SBI RWTH Labein SCI

23/5/06 23/5/06 23/5/06 23/5/06 23/5/06 12/7/06

4. Germany 5. Spain Resource approved by Technical Coordinator TRANSLATED DOCUMENT This Translation made and checked by: Translated resource approved by:

Page 23