Anda di halaman 1dari 2

Unitor Marine Systems

Mail: Bldg 60, Lane 369 Chuang Ye Road, Pudong Kang Qiao
Industrial Zone, Shanghai 201319, P.R. China For Service and Spares contact: Barwil Unitor Ships Service
Tel: +86 21 6118 3000, Fax: +86 21 6118 3001
Internet: www.wilhelmsen.com
Mail: PO Box 33, NO-1324 Lysaker, Norway
Tel: +47 67 584000, Fax: +47 67 584319 UNITOR FIRE SUPPRESSION SYSTEMS

CO2 Fire Extinguishing System

What is U n i t o r M a r i n e S y s t e m s • Machinery Spaces


• Pump Rooms
Unitor Marine Systems delivers safety and environmental
systems for New-builds and Retrofits in the Marine and
Offshore markets. It is present in all major shipbuilding
• Cargo Holds
countries and delivers after sales service through its sister
company Barwil Unitor Ships Service with local expertise from
390 sites serving 2200 ports in 116 countries.
Unitor Marine Systems delivered over 1000 systems per annum
from sales locations in South Korea, Japan, China, Singapore,
Vietnam, Norway, Finland, The Netherlands, Great Britain,
Germany, Poland, Russia, France, Italy, Spain, Croatia,
Greece, Turkey, UAE, Iran, India and Brazil.

Products
• CO2 Fire Extinguishing System
• High Expansion Foam Fire Extinguishing System
• Deck Foam Fire Extinguishing System
• Dry Chemical Powder Fire Extinguishing System
• Local Application Fire Fighting System
• Deep Fat Extinguishing System
• Water Based Fire Extinguishing System
• Clean Agent Fire Extinguishing System
• Sample Extraction Smoke Detection System
• Fire Detection and Fire Alarm System
• Nitrogen Membrane Inert Gas System
• Nitrogen Membrane Controlled and Modified Atmosphere System
• Nitrogen Cylinder System
• Oxygen/Acetylene Fixed System
• Fire and Safety Equipment
(All systems conform to the relevant SOLAS and IMO requirements and hold approvals required by class)

Trust us to protect you, your people and


the environment
Trust us to protect you, your people and
the environment

Part of Wilhelmsen Maritime Services,


a Wilh. Wilhelmsen group company

ID.No PBco2rev.00
Technical Design

The system consists of a high pressure cylinder bank with either manual or pressure operated cylinder top valves. The
cylinder bank and a unique manifold are stored in their own insulated room. Valves are connected to the manifold using
flexible high pressure hoses.

From main distribution valves, a piping system is used to distribute the gas to the discharge nozzles which are placed
CO2 Fire Extinguishing System uniformly throughout the protected spaces. The system is operated manually from a release cabinet located centrally,
or from release cabinets placed close to the protected space.
Machinery Spaces, Pump Rooms and Cargo Holds
When releasing the system, the main distribution valve opens while simultaneously the pilot gas to the pressure oper-
ated CO2 cylinder top valves is delayed for a specified time. After the delay, the cylinder top valves open and the gas is
discharged through the piping and nozzles into the protected space.

The cylinders with manifolds and discharge hoses can be delivered assembled in rack modules. The system can also
The Unitor CO2 (carbon-dioxide) fire extinguishing system is a total flooding be complemented by the Unitor Local Application Fire Fighting System for providing total fire protection for engine
system designed to comply with SOLAS Chapter II-2 and FSS Code room.
Chapter 5, for use in engine rooms, pump rooms and cargo holds.

It extinguishes fires using CO2 by reducing the oxygen content in the space.
The CO2 gas has proven to be a fast acting fire extinguishing agent and is
effective on deep seated fires in cargo holds. Local systems for paint lockers
and galley ducting are available and smoke sampling systems for cargo
holds can also be incorporated in the CO2 system package.

Features and benefits

• Fast fire extinguishing system


• Effective on deep-seated fires in engine rooms, Technical Data
pump rooms and cargo holds Distribution valves
Cylinders Sizes : DN20 to DN150
• Type approved extinguishing system Volume [ltr] : 67.5 / 80 Nominal pressure : PN100 and PN160
• Safety release delay designed for crew security Weight of CO2 gas [kg] : 45 / 55 Material of construction
Weight of filled cylinder [kg] : 125 / 140 body : steel
• Can utilise CO2 gas distribution piping to cargo Storage pressure@20oC [bar] : 60 Stem and ball : stainless steel
holds for smoke sampling Test pressure [bar] : 250 Certificates : DNV or according to
Certificates : All major specifications
• CO2 has an Ozone Depletion Potential (ODP) of
classes
zero and a Global Warming Potential (GWP) of 1
Standard : EN 1964/Pi- Manifold
• Unitor uses CO2 gas recovered from an industrial mark. US DOT Size : DN40 – DN100
process – kinder to the environment 3AA Nominal pressure : PN100
Release cabinet Certificates : all major class
• Rack modules (cylinders, manifolds and discharge Cylinders : 2.68 ltr with certificates or
hoses) can be supplied as option. 1.78 kg CO2 according to
Degree of protection : IP55 specification