1. Head: The term head refers to energy generated by fluid by either static (no
flow) or dynamic (flow) means. It can be given in terms of pressure (Pa) or metres (m)
of fluid, however the meaning remains the same.
2. Pressure: The SI (Standard International) unit for pressure is the Pascal (Pa), with
one kiloPascal (kPa) equal to 1,000Pa and one megaPascal (MPa) equal to
1,000,000Pa. One Pascal is described as one Newton (N) of force applied over an
area of one square metre:
p = F/A
For example, weight is a force. A person having a mass of 90kg has a weight of:
Say that persons combined footprint (both feet) occupied an area of 0.06 square
metres, then the total pressure exerted by that person standing on two feet is:
P = 882/0.06
P = 14,700Pa (14.7kPa)
Since standing on one foot occupies only half the area, the pressure would double if
the person was standing on one foot i.e. 29.4kPa.
3. Static Head: Static head is potential energy a fluid possesses. It is in essence the
pressure created by the weight of the fluid. The magnitude of static head a volume
of fluid holds is a function of the vertical height of the fluid and the density of the
fluid.
Hs = U.g.h
Figure 1 shows 2 different tanks, filled with the same liquid to heights h1 and h2
with pressure gauges installed in each tank at the same level.
Hs(1)= U.g.h1
Hs(2)= U.g.h2
Since the properties U and g are constant for each tank, the difference between p1
and p2 is:
Hs(2)-Hs(1)= U.g.(h2-h1)
Note that the volume of fluid is not considered, only the height of fluid. Thus despite
tank 1 containing considerably more liquid than tank 2, the static head produced by
tank 2 is more than that generated by tank 1. The ratio of this difference is simply:
Hs(1):Hs(2) = h1:h2
Figure 2 shows a U shaped device containing a volume of liquid, with one end of the
device open to atmosphere (at p1) and the other end closed (at p2) and pressurised
by air. By knowing the density of the fluid and by measuring the height h1, we can
calculate the difference in pressure between p2 and p1. Since the open end is open
to atmosphere and hence atmospheric pressure, gauge p1 will be zero and the
pressure registered by gauge p2 will be some quantity above atmospheric pressure.
p2-p1 = U.g.h
Where the static head produced by the height h of the liquid is:
Hs = U.g.h
Hence:
Hs = p2-p1
For example, if the liquid was water (U=1000kg/m3) and the height h the water was
displaced was 0.1m, then:
Hs = p2-p1 = 1000*9.8*0.1
p2-p1 = 980Pa (0.98kPa)
Therefore p2 = 980Pa (gauge pressure), since p1 = 0Pa (gauge pressure)
If the fluid was now changed to diesoline (U=860kg/m3) and the pressure p2 was
maintained at 980Pa, the height h would be:
Since Hs = U.g.h
Therefore: h = Hs/(U.g)
h = 980/(860*9.8)
h = 0.116m
The increase in height has occurred due to the fact that per unit volume, diesoline
weighs less than water, i.e. the density of diesoline is less than the density of water.
For a liquid denser than water, say liquid mercury (U=13,600kg/m3), the height
would be less than that achieved by water (h=0.00735m for the mercury).
Hd = 0.5*U*v2
Fluid flowing through a pipe possesses dynamic head supplied by either a pump or
the static head stored within the liquid. For example, if a valve were opened at the
base of a tank filled with liquid, the liquid would flow from the valve thus converting
the static head (potential energy) of the liquid into dynamic head (kinetic energy).
The pressure and velocity at which the liquid exits will decrease as the height of
liquid in the tank decreases due to the corresponding decrease in static head.
5. Head Loss: One of the laws of physics states that no process is 100% reversible
i.e. additional energy is required to reverse or repeat a process due to some energy
always being lost (destroyed) during each cycle usually in the form of heat. The
same applies to fluid mechanics. Whenever fluid flows through a pipe, valve, pump,
even an open drain, there is some loss of energy. This loss of energy is classed as
head loss. It is a loss due to the fact that it requires energy input to overcome the
necessity to transfer the fluid. Whenever fluid moves, some of the energy the fluid
possessed prior to it moving is lost. The magnitude of this loss is dependent mainly
upon 4 factors:
x viscosity of the liquid (i.e. its ability to flow) a property of the fluid
x speed at which the liquid is travelling indication of whether flow is
laminar or turbulent
x rate at which the fluid is required to change direction i.e. bends, valves
etc.
x roughness of surfaces in contact with the fluid i.e. rusty pipes Vs new
pipes
1. Dynamic loss due to the nature i.e. physical make-up, of the fluid itself
i.e. its viscosity and density
2. Dynamic loss due to the interaction of the fluid with other surfaces i.e.
pipe walls, valves, pumps, etc.
3. Static loss as fluid is lifted to a different height. NOTE: If fluid falls to a
different level, this is a negative static loss, or a static head gain.
Each type of head loss can be determined separately, however for most applications
the combined loss (total loss) of a system is referred to.
Height h determines the amount of static head driving the fluid from tank 1 through
the pipework into tank 2. The greater the height h, the greater the driving force
behind the fluid.
The dynamic head loss of the liquid through the pipework is equal to the static head
between the tanks. The dynamic head loss through the pipework is a function of the
internal diameter of the pipe and the number and type of fittings i.e. valves etc. The
magnitude of this loss is dependent upon the characteristics of the fluid and the
speed at which it flows through the pipework being proportional to the amount of
static head.
6. Pump Head: A pump is a device, which adds energy (head) to fluid. There are
many types of pump, each with their own method of transferring mechanical energy
into fluid head. Some pumps are designed to handle various types of fluid e.g. either
water, fuel, molasses etc., whilst certain pumps are designed to perform certain
specific tasks e.g. metering pumps, submerged spear-point pumps, superchargers,
etc. Regardless of their design, they each transfer fluid from one location to another
by adding energy to the fluid.
Pump design also determines the type of energy supplied to a fluid. Some pumps
create little static head yet can develop high dynamic head e.g. axial flow fans,
whilst others such as vane pumps develop high static head with the amount of
dynamic head proportional to the rotational speed of the pump. Such positive
displacement pumps as the vane pump, incorporate a bypass valve which limits the
pump head generated in order to protect the pump, motor, and delivery system
from pressure overload.
Pump head can be measured by observing the static pressure within the delivery
line under no-flow conditions i.e. turning the pump on with the nozzle locked off.
Under this condition, the dynamic head and thus dynamic head loss is zero,
therefore the pump head registered by the gauge on the delivery line of the pump
refers to the total pump head available. Note however that any difference in height
between the pump and the level at which you observe the head measurement, will
Technical Bulletin Fluid Theory 04/00 The Refuelling Specialists
be affected by the static head between those points. Indeed the pump head could
also be determined by installing a large vertical length of pipe onto the pump outlet
and observing the height at which the fluid reaches with the pump on. The static
head existing between the pump and the surface of the liquid is equal to the pump
head.
Figure 4 shows a typical refuelling system. The system incorporates both dynamic
and static head loss, due to the need for the pump to supply energy to force fuel
through pipework and upwards to a higher level.
Bernoullis equation was devised as an energy balance that can be applied between
2 points in an incompressible (liquid) fluid system. For example, between points 2
and 3 in Figure 4:
Total fluid head consists of three parts; pressure head, velocity (dynamic) head, and
potential (static) head. Basically, the total head at point 2 is equal to the total head
at point 3 plus the total head loss between the two points.
Analysing Figure 4, there exists dynamic head loss between; p1 to p2, p2 to p3,
and p3 to p4, whilst static head loss occurs between; p2 to p3, and p3 to p4. The
total loss of the system is the sum of all dynamic losses and all static losses. The
pump must supply sufficient head to account for the total loss of the system, thus
delivering the required rate of fuel through the nozzle into the tank. Increasing the
head loss between p1 and p2 by partially closing the valve, would increase the
Technical Bulletin Fluid Theory 04/00 The Refuelling Specialists
pressure at p1 and reduce the pressure available at p2, p3, and inevitably p4.
Alternatively, reducing the loss between say p1 and p3 by installing fewer bends or
larger diameter pipe would increase the head available at p3 and thus p4. The total
loss of the nozzle and receiver has been determined from flow testing on the Banlaw
test tank. In most applications, this loss is the major cause of head loss between
points p3 and p4.
The pressure at p4 is zero until such time as the vent closes. Immediately prior to
nozzle shut-off once the vent has closed the pressure at p4 will be the difference
between the pressure observed at p3 before the vent had closed, and the pressure
p3 that initiates nozzle shut-off. For every rate of fuel delivery through the nozzle,
there is a pressure p3 which will initiate nozzle shut-off. These values have been
determined by flow tests conducted on the Banlaw test tank.
Banlaw offers different back spring settings to cater for varying head loss between
p3 and p4. High static head loss, remote receiver location, and drop tubes all
increase the total loss between the nozzle and the top of the tank. High loss
between p3 and p4 increase the pressure at p3, thus requiring a heavier spring
setting to maintain the nozzle on until the vent has closed. To minimise the pressure
p4 i.e. the level of tank pressurisation, it is imperative to match the correct spring
setting with the pressure observed at p3.
Taken close to the pump discharge, the stagnation pressure will represent the total
pump head available. Note that in a no-flow situation with the pump running, the
stagnation pressure is equal to the static pressure, as the dynamic pressure is equal
to zero. As flow is initiated, the static pressure is reduced and accounted for by the
increase in dynamic pressure i.e. pressure head is converted to velocity head. If the
location of the measurements was now moved further away from the pump i.e.
downstream, both the static pressure and stagnation pressure are reduced by the
total head loss present between the two points.
NOTE: Most references to line pressure refer to the static pressure. There is
different terminology used to describe the same property. Whichever term you use,
be sure to note the flowrate and distinguish between values obtained during flow
and no-flow conditions.
NOTE: Please ensure that any technical information or advice given out is factual
and accurate. Confirm with me should you have any doubts.
Adam Peattie
Product & Design Engineer
BANLAW PIPELINE PTY LTD
adam@banlaw.com.au