Concentrator Lightning Protectors Installation Instruction Prejob Preparation You need one set (red and green) of protectors

to protect each bus cable. Read the other pages in this file and understand how you will wire them. You will need to turn off power to the concentrator for about 1 - 2 hours. Before turning off concentrator, shut down gNA (that is good time to defrag gNA computer). Ensure the red and green modules are fully seated in their base elements (transport may have loosen them). The protectors will snap onto the DIN rail in your concentrator. First hook the top on then push the bottom until it snaps on. The metal feet that snap on the DIN rail are connected directly to the grounding connectors 2 and 4. The feet are grounding points. Tools needed: Wire Cutters, Knife, Screwdriver, Cable Ties. Punch out 3 holes in the bottom and 3 holes on the side of the concentrator (punch from inside to outside). Normal cable glands are too small to support the cables. Plan to support with cable ties. Ensure the DIN rail will hold all your lightning protector sets. You may have to shift other things like SlimPaks. Label both sides (where you will cut) of the bus cables with the bus number Installation Shut down gNA. Turn off concentrator power and remove plug. You can leave the bus cables connected to the concentrator. Cut the bus cables about 2 1/2 feet from the end (ensure the short end will reach into the concentrator far enough). Strip the bus cables insulation about 8 inches or so. Connect the wires correctly to the lightning protectors. It is easier to connect the wires first then attach the protector to the DIN rail. Turn on concentrator. Start gNA and resend calibrations to concentrator. Label the protectors with the bus number.

Lightning Protector for Concentrator Paris Color Code


One Set (Red and Green) for each Bus cable. Snaps on to concentrator DIN rail.

Refer to the 4 page Geoservices bulletin I.OPS.GEO.0046 "Lightning Protectors for Geonext Hardware" There is a mistake on page 3. Brown (24V +Ve Supply ) and Orange (-Ve Supply) are reversed on the diagram because Brown should connect to Base Element 5/L and 6/L (Line) and Orange should connect to 1/N and N/2 (Neutral)

BUS CABLE PLUGS INTO CONCENTRATOR BUS CABLE (PARIS COLOR CODE) BROWN 24V (+Ve) SUPPLY RED DATABUS (-Ve) ORANGE -Ve SUPPLY YELLOW DATABUS (+Ve) GREY

1 2 3 4 SHIELD

If your bus wire colors are different, make a new sheet copy of this page and change it to your colors. Just do not mix up 1, 2, 3, 4.

To Ground OUT BASE ELEMENT PT-BE/FM or PT-BE


N/2 Gnd/4 11 12 L/6 2 8 4 10 6 12

BASE ELEMENT PT 2X2+F-BE or PT 2X2-BE

PROTECTIVE PLUG

PHOENIX CONTACT PLUGTRAB PT 2-PE/S 24AC-ST 28 39 31 8

PHOENIX CONTACT PLUGTRAB PT 5-HF 12DC-ST 28 38 77 5


7 9 3 11 5

PROTECTIVE PLUG

PROTECTS 24VDC POWER SUPPLY


1/N 3/Gnd 5/L

PROTECTS RS COMMUNICATION (DATA SIGNAL)

IN
3 1 4 2

BUS CABLE FROM FIELD BOX

Lightning Protector for Concentrator T201 Color Code


One Set (Red and Green) for each Bus cable. Snaps on to concentrator DIN rail.

Refer to the 4 page Geoservices bulletin I.OPS.GEO.0046 "Lightning Protectors for Geonext Hardware" There is a mistake on page 3. Brown (24V +Ve Supply ) and Orange (-Ve Supply) are reversed on the diagram because Brown should connect to Base Element 5/L and 6/L (Line) and Orange should connect to 1/N and N/2 (Neutral)

BUS CABLE PLUGS INTO CONCENTRATOR BUS CABLE (T201 COLOR CODE) BLACK 24V (+Ve) SUPPLY BROWN DATABUS (-Ve) GRAY -Ve SUPPLY GRN/YEL DATABUS (+Ve)

1 2 3 4

If your bus wire colors are different, make a new sheet copy of this page and change it to your colors. Just do not mix up 1, 2, 3, 4.

OUT BASE ELEMENT PT-BE/FM or PT-BE


N/2 Gnd/4 11 12 L/6 2 8 4 10 6 12

BASE ELEMENT PT 2X2+F-BE or PT 2X2-BE

PROTECTIVE PLUG

PHOENIX CONTACT PLUGTRAB PT 2-PE/S 24AC-ST 28 39 31 8

PHOENIX CONTACT PLUGTRAB PT 5-HF 12DC-ST 28 38 77 5


7 9 3 11 5

PROTECTIVE PLUG

PROTECTS 24VDC POWER SUPPLY


1/N 3/Gnd 5/L

PROTECTS RS COMMUNICATION (DATA SIGNAL)

IN
3 1 4 2 2

BUS CABLE FROM FIELD BOX (Degasser cable)

Lightning Protector for Concentrator West Pelaut Pit Bus Color Code
One Set (Red and Green) for each Bus cable. Snaps on to concentrator DIN rail.

Refer to the 4 page Geoservices bulletin I.OPS.GEO.0046 "Lightning Protectors for Geonext Hardware" There is a mistake on page 3. Brown (24V +Ve Supply ) and Orange (-Ve Supply) are reversed on the diagram because Brown should connect to Base Element 5/L and 6/L (Line) and Orange should connect to 1/N and N/2 (Neutral)

BUS CABLE PLUGS INTO CONCENTRATOR BUS CABLE (WEST PELAUT PIT BUS COLOR CODE) 1 BLACK 24V (+Ve) SUPPLY 2 BROWN DATABUS (-Ve) 3 BLUE -Ve SUPPLY 4 GRN/YEL DATABUS (+Ve)

If your bus wire colors are different, make a new sheet copy of this page and change it to your colors. Just do not mix up 1, 2, 3, 4.

OUT BASE ELEMENT PT-BE/FM or PT-BE


N/2 Gnd/4 11 12 L/6 2 8 4 10 6 12

BASE ELEMENT PT 2X2+F-BE or PT 2X2-BE

PROTECTIVE PLUG

PHOENIX CONTACT PLUGTRAB PT 2-PE/S 24AC-ST 28 39 31 8

PHOENIX CONTACT PLUGTRAB PT 5-HF 12DC-ST 28 38 77 5


7 9 3 11 5

PROTECTIVE PLUG

PROTECTS 24VDC POWER SUPPLY


1/N 3/Gnd 5/L

PROTECTS RS COMMUNICATION (DATA SIGNAL)

IN
3 1 4 2 2

BUS CABLE FROM FIELD BOX (Degasser cable)

Lightning Protector for Concentrator Bima Rig Floor Code Code


One Set (Red and Green) for each Bus cable. Snaps on to concentrator DIN rail.

Refer to the 4 page Geoservices bulletin I.OPS.GEO.0046 "Lightning Protectors for Geonext Hardware" There is a mistake on page 3. Brown (24V +Ve Supply ) and Orange (-Ve Supply) are reversed on the diagram because Brown should connect to Base Element 5/L and 6/L (Line) and Orange should connect to 1/N and N/2 (Neutral)

BUS CABLE PLUGS INTO CONCENTRATOR BUS CABLE (BIMA RIG FLOOR BUS COLOR CODE) 1 RED 24V (+Ve) SUPPLY 2 BLACK DATABUS (-Ve) 3 BLUE -Ve SUPPLY 4 GRN/YEL DATABUS (+Ve)

If your bus wire colors are different, make a new sheet copy of this page and change it to your colors. Just do not mix up 1, 2, 3, 4.

OUT BASE ELEMENT PT-BE/FM or PT-BE


N/2 Gnd/4 11 12 L/6 2 8 4 10 6 12

BASE ELEMENT PT 2X2+F-BE or PT 2X2-BE

PROTECTIVE PLUG

PHOENIX CONTACT PLUGTRAB PT 2-PE/S 24AC-ST 28 39 31 8

PHOENIX CONTACT PLUGTRAB PT 5-HF 12DC-ST 28 38 77 5


7 9 3 11 5

PROTECTIVE PLUG

PROTECTS 24VDC POWER SUPPLY


1/N 3/Gnd 5/L

PROTECTS RS COMMUNICATION (DATA SIGNAL)

IN
3 1 4 2 2

BUS CABLE FROM FIELD BOX (Degasser cable)

Lightning Protector for Concentrator Bima Pit Room Bus Color Code
One Set (Red and Green) for each Bus cable. Snaps on to concentrator DIN rail.

Refer to the 4 page Geoservices bulletin I.OPS.GEO.0046 "Lightning Protectors for Geonext Hardware" There is a mistake on page 3. Brown (24V +Ve Supply ) and Orange (-Ve Supply) are reversed on the diagram because Brown should connect to Base Element 5/L and 6/L (Line) and Orange should connect to 1/N and N/2 (Neutral)

BUS CABLE PLUGS INTO CONCENTRATOR BUS CABLE (BIMA PIT ROOM BUS COLOR CODE) 1 RED 24V (+Ve) SUPPLY 2 YELLOW DATABUS (-Ve) 3 GREEN -Ve SUPPLY 4 BLUE DATABUS (+Ve) SHIELD GREY

If your bus wire colors are different, make a new sheet copy of this page and change it to your colors. Just do not mix up 1, 2, 3, 4.

To Ground OUT BASE ELEMENT PT-BE/FM or PT-BE


N/2 Gnd/4 11 12 L/6 2 8 4 10 6 12

BASE ELEMENT PT 2X2+F-BE or PT 2X2-BE

PROTECTIVE PLUG

PHOENIX CONTACT PLUGTRAB PT 2-PE/S 24AC-ST 28 39 31 8

PHOENIX CONTACT PLUGTRAB PT 5-HF 12DC-ST 28 38 77 5


7 9 3 11 5

PROTECTIVE PLUG

PROTECTS 24VDC POWER SUPPLY


1/N 3/Gnd 5/L

PROTECTS RS COMMUNICATION (DATA SIGNAL)

IN
3 1 4 2

BUS CABLE FROM FIELD BOX

Lightning Protector Set with bus cable without shield (degasser cable). If bus cable has a shield, connect shield at bottom connector 3 on both red and green modules. Then connect a grounding wire at the top connector 4 on both modules and ground in concentrator (Top connection not critical since module snap-on feet will ground connectors 3 and 4 to DIN rail).

6 - Line 4 - Ground 2 - Neutral

Out to Concentrator
2 11 12 Red LED will come on if hit by lightning (after LED bypass fuse blows 4 6

8 10 12

Protects Power

Protects Data Signal

7 9 11 1 3 1 - Neutral 3 - Ground Databus -Ve 5 - Line Databus +Ve +24 VDC Supply - Ve Supply Field Box Connections 1. Black (24VDC +Ve Supply) 2. Brown (Databus -Ve) 3. Gray (-Ve Supply) 4. Yellow/Green (Databus + Ve) 5

In from Field Box

Three sets of lightning protectors installed for three bus cables

Note lightning protector diagram placed next to concentrator

Degasser cables used for bus cables

Left View of Red PT 2-PE/S Module

Left View of Green PT 5-HF Module