Abstract-This paper proposes a modified deadbeat control scheme modified deadbeat control algorithm is proposed. The modified
of 3-phase PWM inverter with LC filter for uninterruptible power deadbeat algorithm produces a first-order exponential response
supply(UPS). The deadbeat current and voltage controller are during one input step, which has an effect to separate the pole
used to obtain the fast transient response of UPS system in general. of voltage control loop from that of current control loop. The
However, conventional deadbeat controller has a defect to become
unstable. In this paper, to remove the defect which makes a system separate pole placement of voltage and current controller can
unstable due to the same pole placement of conventional deadbeat guarantee the robustness of control loop. In addition,
current and voltage controller, modified deadbeat algorithm, conventional method requires the information of load current
which produces a first-order exponential response during one for compensation of disturbances, which is generated by abrupt
input step, is proposed. Because the overall controller is change of load currents. Hence, this control system needs the
constructed by deadbeat control, the response of the proposed load current sensors. In this paper, to estimate the load current
control system is fast and the structure of controller is simple. In with other states, full order disturbance observer algorithm is
addition, the full-order state and disturbance observer is used. The presented disturbance observer estimates the load
constructed to compensate the disturbances generated by a current without the current sensor and cancels the disturbance
sudden change of load currents. The proposed disturbance
observer estimates state values of load currents within a finite time, by adding feedforward compensating loop in voltage control
and cancels the disturbances by adding feedforward compensation loop. By the proposed control algorithm, the THD of output
loop in the control system. The validity of the modified deadbeat voltage of the UPS system is reduced and the transient response
control scheme is proved by the results of simulation and of the controller is improved. Through the results of simulation
experiment and experiment, the proposed scheme was verified
0-7803-5769-8/99/$10.0001999IEEE
1003
Equations (1)-(3) can be transformed into state equation on k l l = k22 k12 = 4 2 1
the synchronous reference frame. Choosing the capacitor
111 = I 2 2 I12 = -121
voltage and inductor current as the state variables, the state
mll = m22 m12 = -m21
equation can tle represented like Eq. (4),(5). And which are the
d-q variables of voltage and current on the synchronous
Equation (10) is the state equation of the inverter current and
reference frame. ( 1 1 ) represents the state equation of the capacitor voltage loop.
A reference voltage fo; the output on the synchronous
reference frame will be given as Eq. (1 3).
111. MODIFEID
DEADBEAT
CONTROL
v,
0
Equation (4) 2nd ( 5 ) can be put into the following matrix form:
'Aqd = Aqd -4- vAqd - vcqd (7) Fig.2. shows the proposed deadbeat control system with the
disturbance observer. The controller consists of the current
'Cqd = 'Cqd Aqd - (8) controller, the voltage controller and disturbance observer. The
structures of control block have double control loops, and
Assuming that V, and I , are constant during sampling especially the voltage controller is modified by using proposed
interval T s , Eq.(7) and (8) of the inverter current and the scheme, which is explained in followings.
capacitor voltage can be converted into the discrete-time state
equations of (10) , ( 1 1) and ZOH(Zero Order Hold) conversion
method is adopted for discretization A. Current Controller
1004
(Assuming I , , >> I,, , in case of low sampling time)
vcqdk-El
I I
of the voltage control loop. Then the output y ( t ) is transformed
into z domain like Eq. (22).
tkqd
control loop. If current minor loop is assumed to be an ideal
Fig. 4 Simple block diagram of voltage control loop
current source, the feedforward loop of Fig. 4 will compensate
the disturbance caused by load current. In conventional case, From Fig. 4, a simple open loop transfer function of the voltage
the deadbeat controller has the proportional function (like P control loop is derived as follows:
controller).
1005
If the unit feadback loop transfer function is expressed like
G c ( z )of Eq. 1(24),the voltage controller D ( z ) in Fig. 4 can be
-
represented like (25) (26).
rbll b121
C. Disturbance Observer
1006
Iv. SIMULATION AND EXPERIMENT
RESULTS Fig.l7(a) shows the A-phase load current of diode rectifier
measured by sensor and Fig. 17@) represents the load current
The system parameters for simulation and experiment are estimated by using disturbance observer. Here, it is shown that
shown in Table 1. The sampling period for real time processing disturbance observer exactly can estimate the load currents.
is 100[usec] and the LC filter are designed in the view of the
performance of the controller and the THD value of the output
voltage. To prove the validity of the proposed algorithm,
e e- e
simulation and experiment was executed for R-L linear and
rectifier nonlinear load, respectively. The results the proposed 'I.
'
1 v*
L
: Reference Peak Voltage I 179 [VI I 1
Vdc : Dc-link Voltage 360 [VI
(Change of the rated load power: from 0% to 100%)
T. : Sampling Period 100 [psecl
Dc Capacitor of Rectifier Load 4700 [yF]
Inductance of Load 2 [mHI
Rated Load 5 rkVAl
-
Fig. 5 7 shows the simulation results for R-L linear load and
represents the effect of disturbance observer. Fig. 5 shows the _-
2 %-
(4 (b)
Fig. 13 represents that proposed scheme compensates the Fig.7. Output voltage(in
voltage@ case that the disturbance compensation by proposed
disturbance caused by load current and guarantee the fast scheme is included in the control loop)
(a)Line-to-line output voltage waveforms.
transient response of output voltage. And THD of capacitor
(b)d-q representation of the output voltage.
voltage is less than 1%. Fig. 14-16 shows the experiment
results for nonlinear rectifier load. Fig.15 is the case that
disturbance is compensated by current sensor and Fig.16
represents that proposed observer compensates the disturbance.
The THD in nonlinear load is less than 2.5%
1007
40 0 s !
001.
!
6103
!
0112
!O l i l l
011
(4
Fig.9. Output v,oltage(incase that the disturbance compensation by using (a) (b)
current sensors is included in the control loop) Fig. 12.0utput voltage(in case that the disturbance compensation is not
(a) Line-to-line output voltage waveforms. included in the control loop)
(b)d-q representation of the output voltage. (a) Line-to-line output voltage waveforms. [90V I DIV.]
(b)d-q representation of the output voltage. [60V I DIV.]
s
_._ o -
%
g E
y
..
,. * .
_ .
12 7- '$.OX &,E5 0.0s E.IS Q.ll5 I.!1
1008
(b
V. CONCLUSION
REFERENCES
1009