PT PLN (PERSERO)
PT PLN (PERSERO)
JALAN TRUNOJOYO BLOK M-I/135 KEBAYORAN BARU JAKARTA SELATAN 12160
Disusun oleh: Kelompok Bidang SCADA dengan Surat Keputusan Direksi PT PLN (Persero) No.094.K/DIR/2006
Kelompok Kerja Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik dengan Surat Keputusan General Manager PT PLN (Persero) Penelitian dan Pengembangan Ketenagalistrikan No. 006.K/LITBANG/2007
Diterbitkan oleh: PT PLN (PERSERO) Jalan Trunojoyo Blok M-I /135, Kebayoran Baru Jakarta Selatan
10. Ir. Yarid Pabisa 11. Ir. Ruly Chaerul 12. Ir. Herry Santoso 13. Ir. Yanuar I. Prakoso 14. Ir. Hesti Sayoga 15. Ir. Deany EA Rumengan
Susunan Kelompok Kerja Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik
Surat Keputusan General Manager PT PLN (Persero) Litbang Ketenagalistrikan No: 004.K/LITBANG/2007
1. 2. 3. 4. 5. 6. 7. 8. Ir. Solida Novrizal Erdiansyah, ST Ir. A. Sugeng Sugarjito Ir. Ruly Chaerul Tri Hardimasyar, ST Ir. Yarid Pabisa Ir. Joko Pramono Ir. Denden Ruhdani : Sebagai Ketua merangkap Anggota : Sebagai Sekretaris merangkap Anggota : Sebagai Anggota : Sebagai Anggota : Sebagai Anggota : Sebagai Anggota : Sebagai Anggota : Sebagai Anggota
Daftar Isi Daftar Isi .................................................................................................................................i Daftar Tabel .........................................................................................................................iii Daftar Gambar.....................................................................................................................iv Daftar Gambar.....................................................................................................................iv Daftar Lampiran ...................................................................................................................v Prakata ................................................................................................................................vii 1. 2. 3. 4.
4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 4.13 4.14 4.15 4.16 4.17 4.18 4.19
Ruang Lingkup ............................................................................................. 1 Tujuan........................................................................................................... 1 Acuan Normatif............................................................................................. 1 Istilah dan Definisi ........................................................................................ 1
Alarm ................................................................................................................................. 1 Control center .................................................................................................................... 2 Distribution control center (DCC) ....................................................................................... 2 Feeder colouring ................................................................................................................ 2 Gardu hubung .................................................................................................................... 2 Gardu induk ....................................................................................................................... 2 Gardu tengah ..................................................................................................................... 2 Inter distribution control center (IDCC) ............................................................................... 2 Inter regional control center (IRCC) ................................................................................... 2 Keypoint ............................................................................................................................. 2 Maintenance center............................................................................................................ 2 National control center (NCC) ............................................................................................ 3 Operator............................................................................................................................. 3 Regional control center (RCC) ........................................................................................... 3 Regu pemeliharaan............................................................................................................ 3 Supervisory control and data acquisition (SCADA) ............................................................ 3 Telecontrol ......................................................................................................................... 3 Telesignal........................................................................................................................... 3 Telemetering ...................................................................................................................... 3
5.
5.1 5.2
Umum ........................................................................................................... 3
Fasilitas SCADA ................................................................................................................ 3 Teleinformasi data.............................................................................................................. 4 i
5.3 5.4
6.
6.1 6.2
Lampiran A Daftar Teleinformasi (Transmisi)............................................................. 7 Lampiran B Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk)................................................................................................................................... 17 Lampiran C Daftar Teleinformasi (Distribusi) ......................................................... 131 Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi) .......................................................................................................................... 139 Lampiran E Struktur Informasi .................................................................................. 172 Lampiran F Simbol dan Warna ................................................................................. 180
ii
Daftar Tabel
Tabel 1. Struktur informasi ............................................................................................ 173 Tabel 2. Level tegangan ................................................................................................ 175 Tabel 3. Nama bay atau feeder .................................................................................... 176 Tabel 4. Kode tegangan dari primer dan sekunder trafo.......................................... 176 Tabel 5. Kode nama peralatan/alarm/elemen ............................................................ 177 Tabel 6. Warna tampilan................................................................................................ 183
iii
Daftar Gambar
Gambar 1. Batas wewenang antara IRCC dengan RCC (Tipe-a).............................. 5 Gambar 2. Batas wewenang antara IRCC dengan RCC (Tipe-b).............................. 5 Gambar 3. Batas wewenang antara RCC dengan DCC .............................................. 6 Gambar 4. Struktur informasi khusus (bay diameter)............................................... 178 Gambar 5. Struktur informasi khusus (gardu induk 1 breaker)............................ 179 Gambar 6. Simbol gambar ............................................................................................ 181 Gambar 7. Tampilan status........................................................................................... 182
iv
Lampiran B Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk) ...................................................................................................................................17
TA-01: Konfigurasi Umum Pada 1 Breaker ................................................................................. 18 TA-02: Konfigurasi Umum Pada Double Busbar ............................................................................ 28 TA-03: Konfigurasi Umum Pada Single Busbar ............................................................................. 39 TB-01: Generator Combined Cycle Pada Konfigurasi 1 Breaker................................................. 50 TB-02: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi 1 Breaker .......................... 52 TB-03: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Double Busbar ..................... 54 TB-04: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Single Busbar ...................... 56 TB-05: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1 Breaker .......................... 58 TB-06: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar ..................... 60 TB-07: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar ...................... 62 TB-08: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1 Breaker .......................... 64 TB-09: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar ..................... 66 TB-10: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar ...................... 68 TB-11: Interbus Transformer (Secondary Side Connected to 1 Breaker).................................................................................. 70 TB-12: Interbus Transformer73 (Secondary Side Connected to Double Busbar)............................................................................. 73 TB-13: Interbus Transformer (Secondary Side Connected to Single Busbar) .............................................................................. 76 TB-14: Interbus Transformer (Secondary Side Connected to 1 Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier) .. 79 TB-15: Interbus Transformer (Secondary Side Connected to Double Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)............................................................................................................................... 82 TB-16: Interbus Transformer (Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)............................................................................................................................... 85 TB-17: Bay Trafo Tenaga Pada Konfigurasi 1 Breaker ............................................................... 88 TB-18: Bay Trafo Tenaga Pada Konfigurasi Double Busbar .......................................................... 91 TB-19: Bay Trafo Tenaga Pada Konfigurasi Single Busbar ........................................................... 94 TB-20: Bay Reaktor Pada Konfigurasi 1 Breaker ....................................................................... 97 TB-21: Bay Reaktor Pada Konfigurasi Double Busbar ................................................................... 98 TB-22: Bay Reaktor Pada Konfigurasi Single Busbar .................................................................. 100 TB-23: Bay Capasitor Pada Konfigurasi Double Busbar .............................................................. 102 TB-24: Bay Capasitor Pada Konfigurasi Single Busbar................................................................ 104 TB-25: Bay Penghantar Pada Konfigurasi 1 Breaker ............................................................... 106 TB-26: Bay Penghantar Pada Konfigurasi Double Busbar ........................................................... 109 TB-27: Bay Penghantar Pada Konfigurasi Single Busbar ............................................................ 112 TB-28: Bay Penghantar Paralel Dengan Reaktor Pada Konfigurasi Double Busbar .................... 115 TB-29: Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1 Breaker ...................... 118 TB-30: Bay Penghantar Paralel Dengan 2 Reaktor Seri Pada Konfigurasi 1 Breaker ............... 121 TB-31: Bay Kopel Pada Konfigurasi Double Busbar .................................................................... 124 TB-32: Bus Section ...................................................................................................................... 126 TB-33: Bay Diameter Pada Konfigurasi 1 Breaker .................................................................... 128 TB-34: Bus Bar ............................................................................................................................ 130
Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi) .......................................................................................................................... 139
DA-01: Konfigurasi Umum Pada Double Busbar.......................................................................... 140 DA-02: Konfigurasi Umum Pada Single Busbar ........................................................................... 143 DB-01: Trafo 150/20 kV dan 70/20 kV Tipe 1............................................................................... 146 DB-02: Trafo 150/20 kV dan 70/20 kV Tipe 2............................................................................... 148 DB-03: Trafo 150/20 kV dan 70/20 kV Tipe 3............................................................................... 150 DB-04: Generator Pada Konfigurasi Double Busbar .................................................................... 152 DB-05: Generator Pada Konfigurasi Single Busbar...................................................................... 154 DB-06: Feeder 20 kV Tipe 1 ........................................................................................................ 156 DB-07: Feeder 20 kV Tipe 2 ........................................................................................................ 158 DB-08: Feeder 20 kV Tipe 3 ........................................................................................................ 160 DB-09: Bus Section 20 kV Tipe 1................................................................................................. 162 DB-10: Bus section 20 kV Tipe 2 ................................................................................................. 163 DB-11: Kopel................................................................................................................................ 164 DB-12: Capacitor Bay .................................................................................................................. 165 DB-13: SUTM radial dengan keypoint dan PBO .......................................................................... 166 DB-14: SUTM radial dengan keypoint tanpa PBO........................................................................ 168 DB-15: SUTM loop dengan beberapa keypoint ............................................................................ 169 DB-16: Spindle 20 kV................................................................................................................... 170
vi
Prakata
Standar SCADA ini merupakan pengganti dari Pola SCADA SPLN No. 109 Tahun 1996, dalam rangka mengikuti perkembangan teknologi SCADA. Standar ini menjelaskan mengenai master station, komunikasi dan remote station yang terdiri dari enam bagian, yaitu: 1. 2. 3. 4. 5. 6. S3.001 S5.001 S5.002 S4.001 S6.001 S7.001 Peralatan SCADA sistem tenaga listrik Teleinformasi data untuk operasi jaringan tenaga listrik Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik Pengujian sistem SCADA Perencanaan dan pembangunan sistem SCADA Operasi dan pemeliharaan sistem SCADA
Keenam standar di atas adalah yang telah diselesaikan dalam tahun 2007 dan direncanakan akan ditambah dengan beberapa standar lainnya mengenai SCADA. Standar ini mencakup definisi, perangkat keras, perangkat lunak, kebutuhan teleinformasi data, pengujian, kinerja, kajian kelayakan dalam pembangunan, operasi dan pemeliharaan yang memiliki hubungan dengan sistem SCADA. Standar ini dapat menjadi acuan dalam setiap perencanaan, pembangunan, operasi dan pemeliharaan sistem SCADA di PT PLN (Persero) secara nasional.
vii
1.
Ruang Lingkup
Teleinformasi data terdiri dari telecontrol, telesignal dan telemetering. Sesuai dengan penggunaannya, teleinformasi data dibedakan untuk kepentingan operasi dan kebutuhan pemeliharaan. Standar ini dimaksudkan untuk menetapkan standar teleinformasi data yang diaplikasikan untuk kebutuhan pemeliharaan sistem tenaga listrik dan mencakup sistem transmisi dan sistem distribusi. Standar ini, berlaku untuk sistem SCADA: a. National Control Center, disingkat NCC; b. Inter Regional Control Center, disingkat IRCC; c. Regional Control Center, disingkat RCC; d. Inter Distribution Control Center, disingkat IDCC; e. Distribution Control Center, disingkat DCC.
2.
Tujuan
Standar ini ditujukan untuk memberikan pedoman yang terarah dan seragam dalam penerapan teleinformasi data bagi kebutuhan pemeliharaan sistem transmisi dan sistem distribusi tenaga listrik yang mengutamakan mutu, keandalan dan ekonomi. Standar ini merupakan acuan dalam pembangunan sistem SCADA baru dan pengembangan sistem SCADA yang telah ada.
3.
Acuan Normatif
Dokumen normatif berikut berisi persyaratan-persyaratan yang menjadi referensi dalam pembuatan standar SCADA: Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik. a. SNI 04-7021.1.1-2004: 2004, Peralatan dan Sistem Telekontrol Bagian 1: Pertimbangan Umum Seksi 1: Prinsip Umum; b. Keputusan Menteri Energi dan Sumberdaya Mineral Nomor: 150K/30/MEM/2004, Aturan Jaringan Sistem Tenaga Listrik Jawa-Madura-Bali;
4. 4.1
Perubahan kondisi dari peralatan atau sistem yang telah terdeteksi sebelumnya karena fungsi yang tidak dilakukan oleh operator/dispatcher, atau kegagalan peralatan untuk merespon secara benar. Indikasi alarm berupa audible atau visual, atau keduanya.
4.2
Control center
Pusat kendali pengoperasian sistem tenaga listrik dimana master station ditempatkan.
4.3
4.4
Feeder colouring
4.5
Gardu hubung
4.6
Gardu induk
4.7
Gardu tengah
Gardu yang merupakan titik tengah beban atau titik tengah feeder.
4.8
4.9
4.10
Keypoint
Peralatan switching dimana bisa dilakukan manuver antara dua feeder atau lebih.
4.11
Maintenance center
4.12
Pusat kendali yang terhubung dengan beberapa inter regional control center.
4.13
Operator
Petugas yang mengawasi dan mengeksekusi secara lokal peralatan di gardu induk.
4.14
4.15
Regu pemeliharaan
4.16
Sistem yang mengawasi dan mengendalikan peralatan proses yang tersebar secara geografis. [ IEC 870-1-3 ]
4.17
Telecontrol
Kendali peralatan operasional jarak jauh menggunakan transmisi informasi dengan teknik telekomunikasi. [IEV 371-01-01] Catatan Telekontrol dapat berisi kombinasi perintah, alarm, indikasi, metering/pengukuran, proteksi dan fasilitas tripping, tidak menggunakan pesan suara.
4.18
Telesignal
Pengawasan status dari peralatan operasional dalam jarak tertentu dengan menggunakan teknik telekomunikasi seperti kondisi alarm, posisi switch atau posisi katup. [IEV 371-0104]
4.19
Telemetering
Transmisi nilai variabel yang diukur dengan menggunakan teknik telekomunikasi. [IEV 371-01-03]
5. 5.1
Setiap pembangunan pembangkit, gardu induk, gardu hubung, gardu tengah, key point dan fasilitas sistem tenaga listrik yang baru harus dapat dipantau dari control center dan
dilakukan pengujian sebelum diintegrasikan ke sistem transmisi atau sistem distribusi tenaga listrik.
5.2
Teleinformasi data
Standar ini membedakan teleinformasi data untuk transmisi dan distribusi. Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik dapat dilihat pada pada Lampiran A Daftar Teleinformasi (Transmisi) sampai dengan Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi). Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi maka master station dapat digunakan untuk fungsi RCC dan DCC. Dalam hal ini teleinformasi yang digunakan mengacu pada teleinformasi data transmisi dan distribusi. Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik ditampilkan pada Maintenance Center dan Local HMI (Human Machine Interface). Konfigurasi workstation di luar control center yang difungsikan untuk Maintenance Center, menampilkan kebutuhan teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik, dapat dilihat pada SPLN S3.001 Butir 5.2 dan untuk Local HMI (Human Machine Interface) dapat dilihat pada SPLN S3.001 Butir 7.2. Setiap pembangunan SCADA untuk fasilitas sistem tenaga listrik, kebutuhan teleinformasi datanya harus mengacu pada SPLN S5.001 (Teleinformasi data untuk operasi jaringan tenaga listrik) dan SPLN S5.002 (Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik).
5.3
Struktur informasi
Event dan alarm pemeliharaan merupakan informasi kepada regu pemeliharaan dan operator tentang kejadian pada peralatan sistem tenaga listrik yang tampil di monitor dan disimpan di data historikal. Struktur informasi event dan alarm SCADA dapat dilihat pada Lampiran E Struktur Informasi.
5.4
Simbol dan warna diperlukan untuk penyajian diagram sistem tenaga listrik pada monitor dan layar tayang. Simbol dan warna untuk tiap jenis dan kondisi peralatan bersifat informatif dan dipilih sedemikian rupa sehingga jenis dan kondisi peralatan tersebut mudah dikenali oleh regu pemeliharaan dan operator. Simbol dan warna dapat dilihat pada Lampiran F Simbol dan Warna.
6.
Teleinformasi data yang dikirim ke/dari suatu control center ditentukan oleh kewenangannya dalam operasi sistem, sehingga dibutuhkan adanya batas yang jelas antara kewenangan IRCC dan RCC serta RCC dan DCC. Berikut ini dijelaskan perbatasan kebutuhan teleinformasi data antara IRCC dan RCC serta antara RCC dan DCC.
6.1
Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC adalah di titik pelayanan tegangan ekstra tinggi atau tegangan tinggi yang ditentukan, dan atau seperti Gambar 1 dan Gambar 2 berikut: a. Bila sisi sekunder IBT terhubung dengan konfigurasi double busbar
BUSBAR TET/TT
IRCC
RCC BUSBAR TT
BUSBAR TT
IRCC
RCC
BUSBAR TT
6.2
Perbatasan kebutuhan teleinformasi data antara RCC dan DCC di gardu induk ditunjukan pada Gambar 3.
BUSBAR TT
L /R P Q V I RCC
DCC
BUSBAR TM
Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi (belum dipisahkan antara fungsi RCC dan DCC) maka perbatasan kebutuhan teleinformasi data dapat mengacu pada perbatasan fungsi RCC dan DCC atau disesuaikan dengan SOP yang berlaku di daerah tersebut.
A-1: Telesignal
Single (S) or Double (D) Indication D Alarm (A) or Event/ Indication (I) I
No
Kode
Fungsi
Implementasi Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Capasitor Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor RTU Gardu induk, Kopel, Feeder, Diameter Gardu induk Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Generator Generator Generator Generator Feeder, Trafo Gardu induk, Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Trafo Generator Distribution Transformer Gardu induk Gardu induk, Kopel, Feeder, Trafo, Diameter Trafo Trafo Transformer Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu Induk Generator
BI
CAM
Capasitor Auto/Manual
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
CB CD CSO DCBC ES GUC LFA LFC LFR LI LR LRT PSO RACK RMT SAM TC TCC TFAM 110RF 110SF 220F 220RF 220SF 24RF 24SF 380F 48RF 48SF AIRCF AQR
Circuit breaker closed/opened Control disable switch Check synchronizing override Dummy breaker closed/opened Earth Switch Closed/Opened Generator unit run/stop Load frequency available/not available Load frequency control on/off switch Load frequency request on/off Line isolator switch closed/opened Local remote Local remote switch for tapchanger Power station operated Circuit Breaker Rack-In/Rack-Out Reset Master Trip Synchronization Auto/Manual Tap changer raise/lower Tap changer auto/manual Transformer Fan Auto/Manual 110 VDC Rectifier failure 110 VDC Supply failure 220 VAC Failure 220 VDC Rectifier failure 220 VDC Supply failure 24 VDC Rectifier failure 24 VDC Supply failure 380 VAC Failure 48 VDC Rectifier failure 48 VDC Supply failure Air conditioning failure Automatic power factor regulator
D D D D D D D D D D D D D D D D D D D S S S S S S S S S S S S
I I I I I I I I I I I I I I I I I I I A A A A A A A A A A A I
No
Kode active
Fungsi
Implementasi
34 35 36 37 38 39 40 41 42 43 44
AR ARO AVR BPA BPAF BPB BPBF CBDF CBFA CBFB CBM
Circuit breaker auto reclose Auto reclose off Automatic voltage regulator on/off Busbar protection (a) Busbar protection (a) failure Busbar protection (b) Busbar protection (b) failure Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance
Feeder Feeder Generator Busbar Busbar Busbar Busbar Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor, Generator Diameter Diameter Diameter Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Gardu induk Remote station Kopel, Feeder, Trafo, Capasitor, Reaktor Gardu Induk Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder
45
CBTR
Circuit breaker trip Circulating current protection (a) operate Circulating current protection (b) operate Circulating current protection failure Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress Cabinet temperatur DC supply failure DC ground Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase r Directional earth fault (a) phase s Directional earth fault (a) phase t
46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69
CCPA CCPB CCPF CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT CF CSP CTE DCF DCG DEARX DEATX DEBRX DEBTX DEFAF DEFAR DEFAS DEFAT
S S S S S S S S S S S S S S S S S S S S S S S S
A A A A A A A A A A A A I I A A A A A A A A A A
No 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112
Kode DEFBF DEFBR DEFBS DEFBT DFRF DIFF DOOR DSDF DTARX DTATX DTBRX DTBTX DZ1AR DZ1AS DZ1AT DZ1BR DZ1BS DZ1BT DZ2AR DZ2AS DZ2AT DZ2BR DZ2BS DZ2BT DZ3AR DZ3AS DZ3AT DZ3BR DZ3BS DZ3BT DZAF DZARX DZATX DZBF DZBRX DZBTX ERF FOTF FPO FRA FRSF GFRF GOV
Fungsi Directional earth fault (b) failure Directional earth fault (b) phase r Directional earth fault (b) phase s Directional earth fault (b) phase t Disturbance fault recorder faulty Differential failure Door activated Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure FO terminal faulty Fire protection operated Fire alarm Fire alarm system failure Ground fault relay failure Free acting governor active
Implementasi Feeder Feeder Feeder Feeder Gardu Induk Trafo Gardu Induk Busbar, Kopel, Feeder, Trafo, Capasitor Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Feeder Busbar, Kopel, Bus Section, Feeder, Trafo, Reaktor, Diameter Gardu Induk Trafo Gardu Induk Gardu Induk Gardu Induk, Kopel, Bus Section, Feeder, Trafo, Capasitor Generator
10
Fungsi Genset ready Generator transformer trip Internal remote station Load frequency control unit failure Low oil pressure cable trip
Implementasi Gardu Induk Trafo Generator Remote Station Generator Cable Feeder Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter, Generator Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter, Generator Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter, Generator Gardu Induk Cable Feeder Kopel, Bus Section, Feeder, Trafo, Capasitor Trafo Trafo Busbar, Feeder, Trafo, Capasitor Busbar, Feeder, Trafo, Capasitor Trafo, Capasitor, Reaktor Trafo Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor Kopel, Feeder, Bus Section, Trafo, Reaktor, Capasitor Gardu Induk Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Gardu Induk
118
LPA
119
LPB
120
LPT
121 122 123 124 125 126 127 128 129 130 131 132 133
MTO OCPA OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR P2OCR PBXF PD
Master trip operate Oil cable pressure alarm Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay PABX faulty Pole discrepancy
S S S S S S S S S S S S S
A A A A A A A A A A A A A
134
PHR
Trip phase R
135
PHS
Trip phase S
136 137
PHT PLCF
S S
A A
11
No
Kode
Fungsi
Implementasi Busbar, Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Trafo, Reaktor Gardu induk Feeder Gardu Induk Reaktor Reaktor Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Reaktor Trafo Reaktor Reaktor Reaktor Reaktor Reaktor Gardu Induk Gardu Induk Gardu Induk Gardu Induk Gardu induk Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Trafo Trafo Trafo Trafo Trafo Trafo Trafo Trafo Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter
138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158
POT PRDT PTF PWF RADF RBUC2 RBUCA RCBF RCFF REFF RF RFDP ROLA RSPA RSPT RSTA RTN RTUA SIA SYNF SZPA
Protection on test Pressure relay device trip Protection faulty Pilot wire failure Radio link faulty Reaktor bucholz trip Reaktor bucholz alarm Relay circuit breaker fail failure Reaktor cooling fan failure Restrcited earth fault failure Reactor failure Reaktor fire detection & protection Reaktor oil level alarm Reaktor sudden pressure alarm Reaktor sudden pressure trip Reset alarm Relay tegangan nol Remote Station Alarm Station intruder alarm Synchronizing failure Short zone protection (a) operate
S S S S S S S S S S S S S S S S S S S
A A A A A A A A A A A A A I I A A A A
159
SZPB
160 161 162 163 164 165 166 167 168 169
SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1
Short zone protection failure Tranformer AVR failure Transformer Bucholz trip Transformer Bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1
S S S S S S S S S S
A A A A A A A A A A
170
TCS2
12
No 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189
Kode TFDP TJANT TOLA TOOS TPAF TPBF TPIF TSPA TSPT UFR UT UVR UVRF VS VTF WTHVA WTHVT WTLVA WTLVT
Fungsi Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Teleprotection (a) failure Teleprotection (b) failure Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Unit trip Under voltage relay Under voltage relay failure Voltage status Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip
Implementasi Trafo Trafo Trafo Trafo Feeder Feeder Trafo Trafo Trafo Feeder, Trafo Generator Busbar Busbar, Feeder, Trafo Busbar Busbar, Feeder, Trafo, Capasitor Trafo Trafo Trafo Trafo
S S S S S S S S S S S S S S
A A A A A A A A I A A A A A
Keterangan: A = I =
Announciation of abnormal condition (audible alarm, flashing display, etc) Event/Indication (normal condition)
13
A-2: Telemeasurement
No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Kode AMF CCB CNTA CTPI F I KVARH KWH P POAQ PRAQ PRES Q RH TEMP V
Fungsi Amperes fault ( per phase ) Counter of circuit breaker Counter arester Counter tap position indication Frekuensi Arus Kilovar hour Kilowatt hour Daya Aktif Real power setting Maksimum power variation setting Pressure Daya Reaktif Relative humidity Temperature Tegangan
Implementasi Feeder, Trafo, Capasitor Reaktor Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor Feeder, Trafo Trafo Gardu induk Feeder, Trafo, Kopel Feeder, Trafo Feeder, Trafo Feeder, Trafo, Generator Generator Generator Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor Feeder, Trafo, Generator, Capasitor, Reaktor Gardu Induk Trafo, Reaktor Feeder, Trafo, Generator, Busbar
14
15
16
17
L/R
L/R
L/R
L/R
L/R
L/R BUSBAR -B V
L/R P Q V I
BAY TRANSMISI
P Q V I
L/R
P Q V I
BAY TRAFO TENAGA
BAY IBT
18
Teleinformasi Data Untuk Konfigurasi Umum Pada 1 Breaker Group Bay Data TM No 1 14 22 23 24 25 26 27 28 29 30 31 32 61 76 107 109 110 111 113 121 132 137 142 153 154 155 157 5 13 17 18 3 7 9 10 7 37 38 39 40 77 106 126 127 138 182 183 184 Kode F RH 110RF 110SF 220F 220RF 220SF 24RF 24SF 380F 48RF 48SF AIRCF DCG DOOR FOTF FRA FRSF GFRF GRE MTO PBXF PLCF RADF RSTA RTN RTUA SIA CSO LR RMT SAM CSO LR RMT SAM V BPA BPAF BPB BPBF DSDF ERF OVR OVRF POT UVR UVRF VS Fungsi Frekuensi Relative humidity 110 VDC rectifier failure 110 VDC supply failure 220 VAC failure 220 VDC rectifier failure 220 VDC supply failure 24 VDC rectifier failure 24 VDC supply failure 380 VAC failure 48 VDC rectifier failure 48 VDC supply failure Air conditioning failure DC ground Door activated FO terminal faulty Fire alarm Fire alarm system failure Ground fault relay failure Genset ready Master trip operate Pabx faulty PLC terminal faulty Radio link faulty Reset alarm Relay tegangan nol Remote station alarm Station intruder alarm Check synchronizing override Local remote Reset master trip Synchronization auto/manual Check synchronizing override Local remote Reset master trip Synchronization auto/manual Tegangan Busbar protection (a) Busbar protection (a) failure Busbar protection (b) Busbar protection (b) failure Disconnecting switch driving fault Event recorder failure Over voltage relay operate Over voltage relay failure Protection on test Under voltage relay operate Under voltage relay failure Voltage status 19 Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2
TSS
GARDU INDUK
TSD
A A A A A A A A A A A A A A A A A I A A A A A A A A I I I I
RCD BUSBAR TM
TSS
A A A A A A A A I A A I
Group Bay
No 7 59 115 4 3 5 2 12 41 42 43 44 46 47 48 58 106 118 119 120 133 134 135 136 138 145 157 158 159 160 169 170 1
Kode ES CTE IR CD CD DCBC CCB PRES CBDF CBFA CBFB CBM CCPA CCPB CCPF CSP ERF LPA LPB LPT PD PHR PHS PHT POT RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 BI CB CSO LR SAM BI CB CSO LR SAM AMF *) CNTA I
Fungsi Earth switch closed/opened Cabinet temperatur Internal remote station Control disable switch Control disable switch Dummy circuit breaker closed/opened Counter of circuit breaker Pressure Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Circulating current protection (a) operate Circulating current protection (b) operate Circulating current protection failure Check synchronizing in progress Event recorder failure Low pressure alarm Low pressure block Low pressure trip Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual Amperes fault ( per phase ) Counter arester Arus
Tipe I A A I
Jmh 2 1 1 1 1 1 3 3 3 3 3 3 1 1 3 3 3 3 3 3 3 3 3 3 1 3 3 3 3 3 3 3 6 3 3 3 3 6 3 3 3 3 1 1 1
REMOTE STATION
TSD RCD TM
A A A I A A A I A A A A A A A A I A A A A A A A I I I I I
TSS
DIAMETER
TSD
3 5 13 18 1
RCD
BAY TRANSMISI
TM
2 4 7 10 1 3 6
20
Group Bay
Data
No 7 8 9 12 13 16
Kode KVARH KWH P PRES Q V CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT CF *) CSP DCF DEARX
*)
Fungsi Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tegangan Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2
Tipe
Jmh 1 1 1 1 1 1
TSS
49 50 51 52 53 54 55 56 57 58 60 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91
A A A A A A A A A I A A A A A A A A A A A A A A A I I I I A A A A A A A A A A
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
DEATX *) DEBRX *) DEBTX *) DEFAF DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) *) DZ2AS *) DZ2AT DZ2BR *)
*)
21
Group Bay
Data
No 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) *) DZ3BS *) DZ3BT DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF
LOWCT**) OCPA**)
Fungsi Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip Oil cable pressure alarm
Tipe A A A A A A A A A I I A I I A A A A A A A A A I A A A A A A A A A A A A I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
106 111 117 122 123 126 127 130 131 138 141 145 157 158 159 160 175 176 180 182 183 185 7 TSD RCD TC TM 12 6 1 1 3 4 6 7 8 9 12 13
OCRF OVR *) OVRF *) P2GFR P2OCR POT PWF RCBF SYNF SZPA SZPB SZPF TPAF *) TPBF *) UFR UVR *) UVRF *) VTF ES LI
LI
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Earth switch closed/opened Line isolator switch closed/opened
Line isolator switch closed/opened
BAY IBT
TPI
AMF CNTA CTPI I KVARH KWH P PRES Q
22
Group Bay
Data
No 15 16 41 42 43 44 58 60 74 75 77 106 108 111 118 119 120 123 124 125 128 129 130 131 133 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173
Kode
TEMP V
Fungsi
Temperature Tegangan
Tipe
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSS
CBDF CBFA CBFB CBM CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT OCRF OTA OTT P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA
Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm
A A A I I A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A
23
Group Bay
Data
No 174 177 178 179 180 185 186 187 188 189 3 5 7 12
Kode TOOS TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT CB CSO ES LI LR LRT SAM TCC TFAM CB CSO LI LR LRT SAM TC TCC TFAM TPI AMF CNTA CTPI I KVARH KWH P PRES Q TEMP V DCF DFRF DIFF DSDF ERF FPO
Fungsi Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual Tap position indication Amperes fault ( per phase ) Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated
Tipe A A A A A A A A A A I I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
13 14 18 20 21 2 4 6 7
RCD
8 10 11 12 13 1 1 3 4 6 7 8 9 12 13 15 16 60 74 75 77 106 108
TC
TM
TSS
A A A A A A
24
Group Bay
Data
No 111 123 124 125 126 127 128 129 130 131 138 139 145 147 158 159 160 161 162 163 164 165 166 167 168 171 172 173 174 177 178 179 180 182 183 185 186 187 188 189 7 12
Kode GFRF OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR P2OCR POT PRDT RCBF REFF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR UVR UVRF VTF WTHVA WTHVT WTLVA WTLVT ES LI LRT TCC TFAM LI
Fungsi Ground fault relay failure Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer avr failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Earth switch closed/opened Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer auto/manual Transformer fan auto/manual Line isolator switch closed/opened 25
Tipe A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A A I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
14 20 21
RCD
Group Bay
Data
No 8 11 12 13 1 12 13 15 60 74 106 128 130 131 138 139 145 148 158 159 160 7 12 21
Kode LRT TC TCC TFAM AMF PRES Q TEMP DCF DFRF ERF P1DIF P2GFR P2OCR POT PRDT RCBF RF SZPA SZPB SZPF ES LI TFAM LI TFAM I KVARH KWH P Q V DFRF DIFF ERF GTT P1REF P2GFR P2OCR POT REFF ES LI LI
Fungsi Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual Amperes fault ( per phase ) Pressure Daya reaktif Temperature DC supply failure Disturbance fault recorder faulty Event recorder failure Differential Ground fault relay Over current relay Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Earth switch closed/opened Line isolator switch closed/opened Transformer fan auto/manual Line isolator switch closed/opened Transformer fan auto/manual Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Restricted earth fault Ground fault relay Over current relay Protection on test Restricted earth fault failure Earth switch closed/opened Line isolator switch closed/opened Line isolator switch closed/opened
Tipe
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
BAY REAKTOR
TSS
A A A A A A A A A A A A A I I I
TSD
RCD
TM
BAY GENERATOR
TSS
A A A A A A A A A I I
TSD RCD
KETERANGAN:
26
= Khusus untuk OHL Feeder = Khusus untuk Cable Feeder A = Alarm I = Indikasi Rincian Teleinformasi diatas adalah rincian per bay
**)
*)
27
P Q V
P Q I
BAY KOPEL
L/R
L/R I
L/R
BUSBAR - A V
BUSBAR - B V
L/R
L/R
L/R
L/R P Q V I
BAY TRANSMISI
P Q V I
BAY TRAFO TENAGA
P Q V I
BAY IBT
28
Teleinformasi Data Untuk Konfigurasi Umum Pada Double Busbar Group Bay Data TM No 1 14 22 23 24 25 26 27 28 29 30 31 32 61 76 107 109 110 111 113 121 132 137 142 153 154 155 157 5 13 17 18 3 7 9 10 7 37 38 39 40 77 106 126 127 138 182 183 184 Kode F RH 110RF 110SF 220F 220RF 220SF 24RF 24SF 380F 48RF 48SF AIRCF DCG DOOR FOTF FRA FRSF GFRF GRE MTO PBXF PLCF RADF RSTA RTN RTUA SIA CSO LR RMT SAM CSO LR RMT SAM V BPA BPAF BPB BPBF DSDF ERF OVR OVRF POT UVR UVRF VS Fungsi Frekuensi Relative humidity 110 VDC rectifier failure 110 VDC supply failure 220 VAC failure 220 VDC rectifier failure 220 VDC supply failure 24 VDC rectifier failure 24 VDC supply failure 380 VAC failure 48 VDC rectifier failure 48 VDC supply failure Air conditioning failure DC ground Door activated FO terminal faulty Fire alarm Fire alarm system failure Ground fault relay failure Genset ready Master trip operate Pabx faulty PLC terminal faulty Radio link faulty Reset alarm Relay tegangan nol Remote station alarm Station intruder alarm Check synchronizing override Local remote Reset master trip Synchronization auto/manual Check synchronizing override Local remote Reset master trip Synchronization auto/manual Tegangan Busbar protection (a) Busbar protection (a) failure Busbar protection (b) Busbar protection (b) failure Disconnecting switch driving fault Event recorder failure Over voltage relay operate Over voltage relay failure Protection on test Under voltage relay operate Under voltage relay failure Voltage status 29 Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2
TSS
GARDU INDUK
TSD
A A A A A A A A A A A A A A A A A I A A A A A A A A I I I I
RCD BUSBAR TM
TSS
A A A A A A A A I A A I
Group Bay
No 7 59 115 4 3 5 2 6 12 41 42 43 44 58 60 77 106 111 118 119 120 123 130 131 133 134 135 136 138 145 157 158 159 160 169 170 1 3 5 13 18 1 2 4 7 10 1 2 3
Kode ES CTE IR CD CD DCBC CCB I PRES CBDF CBFA CBFB CBM CSP DCF DSDF ERF GFRF LPA LPB LPT OCRF P2GFR P2OCR PD PHR PHS PHT POT RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 BI CB CSO LR SAM BI
CB CSO
Fungsi
Tipe
Jmh 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 2 1 1 1 1 1 1 1
REMOTE STATION
TSD RCD TM
TSS
KOPEL
TSD
Earth switch closed/opened I Cabinet temperatur A Internal remote station A Control disable switch I Control disable switch Dummy circuit breaker closed/opened Counter of circuit breaker Arus Pressure A Circuit breaker drive failure A Circuit breaker failure (a) operate A Circuit breaker failure (b) operate I Circuit breaker maintenance I Check synchronizing in progress A DC supply failure A Disconnecting switch driving fault A Event recorder failure A Ground fault relay failure A Low pressure alarm A Low pressure block A Low pressure trip A Over current relay failure A Ground fault relay A Over current relay A Pole discrepancy A Trip phase R A Trip phase S A Trip phase T I Protection on test A Relay circuit breaker fail failure A Synchronizing failure A Short zone protection (a) operate A Short zone protection (b) operate A Short zone protection failure A Trip coil supervisory 1 A Trip coil supervisory 2 Bus isolator switch closed/opened I Circuit breaker closed/opened I Check synchronizing override I Local remote I Synchronization auto/manual I Bus isolator switch closed/opened
Circuit breaker closed/opened Check synchronizing override
RCD
BAY TRANSMISI
TM
Local remote Synchronization auto/manual Amperes fault ( per phase ) Counter of circuit breaker Counter arester
30
Group Bay
Data
No 6 7 8 9 12 13 16 34 35 41 42 43 44 49 50 51 52 53 54 55 56 57 58 60 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85
Kode I KVARH KWH P PRES Q V *) AR ARO *) CBDF CBFA CBFB CBM CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT *) CF CSP DCF DEARX *) DEATX *) DEBRX *) DEBTX *) DEFAF DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) *) DZ1BR
*)
Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tegangan Circuit breaker auto reclose Auto reclose off Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1
Tipe
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSS
I I A A A I A A A A A A A A A I A A A A A A A A A A A A A A A I I I I A A A A
31
Group Bay
Data
No 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) *) DZ2BS *) DZ2BT DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF
LOWCT**)
Fungsi Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip
Tipe A A A A A A A A A A A A A A A I I A I I A A A A A A A A A A A A A A A A I A A A A A A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
106 111 117 118 119 120 122 123 126 127 130 131 133 134 135 136 138 141 145 157 158 159 160 169 170 175 176 180 182
OCRF OVR *) OVRF *) P2GFR P2OCR PD PHR PHS PHT POT PWF RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 TPAF *) TPBF *) UFR UVR *)
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate
32
Group Bay
Data
No 183 185 1 3 5 7 12 13 18 1 2 4 6 7 10 1 1 2 3 4 6 7 8 9 12 13 15 16 41 42 43 44 58 60 74 75 77 106 108 111 118 119 120 123 124 125 128 129 130
Fungsi Under voltage relay failure Voltage transformer failure Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Synchronization auto/manual Bus isolator switch closed/opened
Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened
Tipe A A I I I I I I I
Jmh 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
BAY IBT
TC
Local remote Synchronization auto/manual Tap position indication Amperes fault ( per phase ) Counter of circuit breaker
Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan
TM
TSS
CBDF CBFA CBFB CBM CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT OCRF OTA OTT P1DIF P1REF P2GFR
Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay
A A A I I A A A A A A A A A A A A A A A A
33
Group Bay
Data
No 131 133 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 185 186 187 188 189 1 3 5 7 13 14 18 20 21 1 2 4 7
Kode P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT BI CB CSO ES LR LRT SAM TCC TFAM BI CB CSO LR
Fungsi Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote
Tipe A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A I I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 2 1 1 1 1 1 2 1 1 1
TSD
RCD
34
Group Bay
Data
No 8 10 11 12 13 1 1 2 3 4 6 7 8 9 12 13 15 16 41 42 43 44 60 74 75 77 106 108 111 118 119 120 123 124 125 126 127 128 129 130 131 133 134 135 136 138 139 145 147
Kode LRT SAM TC TCC TFAM TPI AMF CCB CNTA CTPI I KVARH KWH P PRES Q TEMP V CBDF CBFA CBFB CBM DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF
Fungsi Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual Tap position indication Amperes fault ( per phase ) Counter of circuit breaker Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure
Tipe
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TC
TM
TSS
A A A I A A A A A A A A A A A A A A A A A A A A A A A I A A A
35
Group Bay
Data
No 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 182 183 185 186 187 188 189 1 3 7 13 14 16 20 21 1 2 7 8 11 12 13 1 2 12 13 15 41
Kode SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR UVR UVRF VTF WTHVA WTHVT WTLVA WTLVT BI CB ES LR LRT RACK TCC TFAM BI CB LR LRT TC TCC TFAM AMF CCB PRES Q TEMP CBDF
Fungsi Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer avr failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Local/remote switch for tapchanger Circuit breaker rackin/rackout Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Local remote Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual Amperes fault ( per phase ) Counter of circuit breaker Pressure Daya reaktif Temperature Circuit breaker drive failure
Tipe A A A A A A A A A A A A A A A A A A A A A A A A A A A A I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
BAY REAKTOR TM
TSS
36
Group Bay
Data
No 42 43 44 60 74 106 118 119 120 128 130 131 133 134 135 136 138 139 145 148 158 159 160 169 170 1 3 7 12 13 21 1 2 6 7 13 6 7 8 9 13 16 41 44 58 74 75 106 114
Kode CBFA CBFB CBM DCF DFRF ERF LPA LPB LPT P1DIF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF RF SZPA SZPB SZPF TCS1 TCS2 BI CB ES LI LR TFAM BI CB LI LR TFAM I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT
Fungsi Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Event recorder failure Low pressure alarm Low pressure block Low pressure trip Differential Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip
Tipe A A A A A A A A A A A A A A A A A A A A A A A A A I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 2 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 1
TSD
RCD
BAY GENERATOR TM
TSS
A A A A A A A
37
Group Bay
Data
No 118 119 120 129 130 131 133 134 135 136 138 147 157 169 170 1 3 7 12 13 1 2 6 7
Kode LPA LPB LPT P1REF P2GFR P2OCR PD PHR PHS PHT POT REFF SYNF TCS1 TCS2 BI CB ES LI LR BI CB LI LR
Fungsi Low pressure alarm Low pressure block Low pressure trip Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote
Tipe A A A A A A A A A A A A A A A I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 2 1 1 1
TSD
RCD
KETERANGAN:
= Khusus untuk OHL Feeder = Khusus untuk Cable Feeder A = Alarm I = Indikasi Rincian Teleinformasi diatas adalah rincian per bay
**) *)
38
P Q V P Q I L/R L/R
BUSBAR V
L/R
L/R
L/R
L/R P Q V I
BAY TRANSMISI
P Q V I
BAY TRAFO TENAGA
P Q V I
BAY IBT
39
Teleinformasi Data Untuk Konfigurasi Umum Pada Single Busbar Group Bay Data TM No 1 14 22 23 24 25 26 27 28 29 30 31 32 61 76 107 109 110 111 113 121 132 137 142 153 154 155 157 5 13 17 18 3 7 9 10 7 37 38 39 40 77 106 126 127 138 182 183 184 Kode F RH 110RF 110SF 220F 220RF 220SF 24RF 24SF 380F 48RF 48SF AIRCF DCG DOOR FOTF FRA FRSF GFRF GRE MTO PBXF PLCF RADF RSTA RTN RTUA SIA CSO LR RMT SAM CSO LR RMT SAM V BPA BPAF BPB BPBF DSDF ERF OVR OVRF POT UVR UVRF VS Fungsi Frekuensi Relative humidity 110 VDC rectifier failure 110 VDC supply failure 220 VAC failure 220 VDC rectifier failure 220 VDC supply failure 24 VDC rectifier failure 24 VDC supply failure 380 VAC failure 48 VDC rectifier failure 48 VDC supply failure Air conditioning failure DC ground Door activated FO terminal faulty Fire alarm Fire alarm system failure Ground fault relay failure Genset ready Master trip operate Pabx faulty PLC terminal faulty Radio link faulty Reset alarm Relay tegangan nol Remote station alarm Station intruder alarm Check synchronizing override Local remote Reset master trip Synchronization auto/manual Check synchronizing override Local remote Reset master trip Synchronization auto/manual Tegangan Busbar protection (a) Busbar protection (a) failure Busbar protection (b) Busbar protection (b) failure Disconnecting switch driving fault Event recorder failure Over voltage relay operate Over voltage relay failure Protection on test Under voltage relay operate Under voltage relay failure Voltage status 40 Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSS
GARDU INDUK
TSD
A A A A A A A A A A A A A A A A A I A A A A A A A A I I I I
RCD BUSBAR TM
TSS
A A A A A A A A I A A I
Group Bay
No 7 59 115 4 3 5 1 2 3 6 7 8 9 12 13 16 34 35 41 42 43 44 49 50 51 52 53 54 55 56 57 58 60 62 63 64 65 66 67 68 69 70 71 72
Kode ES CTE IR CD CD DCBC AMF CCB CNTA *) I KVARH KWH P PRES Q V AR *) ARO *) CBDF CBFA CBFB CBM CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT CF *) CSP DCF DEARX *) DEATX *) DEBRX *) DEBTX *) DEFAF DEFAR DEFAS DEFAT *) DEFBF DEFBR DEFBS
*)
Fungsi Earth switch closed/opened Cabinet temperatur Internal remote station Control disable switch Control disable switch Dummy circuit breaker closed/opened Amperes fault ( per phase ) Counter of circuit breaker Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tegangan Circuit breaker auto reclose Auto reclose off Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S
Tipe I A A I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
REMOTE STATION
TSD RCD
BAY TRANSMISI
TM
TSS
I I A A A I A A A A A A A A A I A A A A A A A A A A A A
41
Group Bay
Data
No 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) *) DTBTX *) DZ1AR *) DZ1AS DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) *) DZ3AT *) DZ3BR *) DZ3BS DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF
LOWCT**)
Fungsi Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip
Tipe A A A I I I I A A A A A A A A A A A A A A A A A A A I I A I I A A A A A A A A A A A A A A A A I A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
106 111 117 118 119 120 122 123 126 127 130 131 133 134 135 136 138 141
OCRF OVR *) OVRF *) P2GFR P2OCR PD PHR PHS PHT POT PWF
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pilot wire failure
42
Group Bay
Data
No 145 157 158 159 160 169 170 175 176 180 182 183 185 1 3 5 7 12 13 18 1
Kode RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 *) TPAF TPBF *) UFR UVR *) UVRF *) VTF BI CB CSO ES LI LR SAM BI
CB CSO LI
Fungsi Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Synchronization auto/manual Bus isolator switch closed/opened
Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened
Tipe A A A A A A A A A A A A A I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
BAY IBT
TC
TM
TSS
2 4 6 7 10 1 1 2 3 4 6 7 8 9 12 13 15 16 41 42 43 44 58 60 74 75
Local remote Synchronization auto/manual Tap position indication Amperes fault ( per phase ) Counter of circuit breaker
Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan
Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure
A A A I I A A A
43
Group Bay
Data
No 77 106 108 111 118 119 120 123 124 125 128 129 130 131 133 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 185 186 187 188
Kode DSDF ERF FPO GFRF LPA LPB LPT OCRF OTA OTT P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA
Fungsi Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm
Tipe A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
44
Group Bay
Data
No 189 1 3 5 7 13 14 18 20 21 1 2 4 7
Kode WTLVT BI CB CSO ES LR LRT SAM TCC TFAM BI CB CSO LR LRT SAM TC TCC TFAM TPI AMF CCB CNTA CTPI I KVARH KWH P PRES Q TEMP V CBDF CBFA CBFB CBM DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT
Fungsi LV winding temperatur trip Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual Tap position indication Amperes fault ( per phase ) Counter of circuit breaker Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip
Tipe A I I I I I I I I I
Jmh 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
TC
TM
TSS
A A A I A A A A A A A A A A
45
Group Bay
Data
No 123 124 125 126 127 128 129 130 131 133 134 135 136 138 139 145 147 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 182 183 185 186 187 188 189
Kode OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR UVR UVRF VTF WTHVA WTHVT WTLVA WTLVT BI CB
Fungsi Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer avr failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Bus isolator switch closed/opened Circuit breaker closed/opened
Tipe A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
1 3
46
Group Bay
Data
No 7 13 14 16 20 21 1 2 7
Kode ES LR LRT RACK TCC TFAM BI CB LR LRT TC TCC TFAM AMF CCB PRES Q TEMP CBDF CBFA CBFB CBM DCF DFRF ERF LPA LPB LPT P1DIF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF RF SZPA SZPB SZPF TCS1 TCS2 BI CB
Fungsi Earth switch closed/opened Local remote Local/remote switch for tapchanger Circuit breaker rackin/rackout Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Local remote Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual Amperes fault ( per phase ) Counter of circuit breaker Pressure Daya reaktif Temperature Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Event recorder failure Low pressure alarm Low pressure block Low pressure trip Differential Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened
Tipe I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
RCD
8 11 12 13 1 2 12 13 15 41 42 43 44 60 74 106 118 119 120 128 130 131 133 134 135 136 138 139 145 148 158 159 160 169 170 1 3
BAY REAKTOR TM
TSS
A A A A A A A A A A A A A A A A A A A A A A A A A A I I
TSD
47
Group Bay
Data
No 7 12 13 21 1 2
Kode ES LI LR TFAM BI CB LI LR TFAM I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT P1REF P2GFR P2OCR PD PHR PHS PHT POT REFF SYNF TCS1 TCS2 BI CB ES LI LR BI CB LI
Fungsi Earth switch closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch 48
Tipe I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
RCD
6 7 13 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 129 130 131 133 134 135 136 138 147 157 169 170 1
BAY GENERATOR TM
TSS
A A A A A A A A A A A A A A A A A A A A A A I I I I I
TSD
3 7 12 13
RCD
1 2 6
Group Bay
Data
No 7
Kode LR
Tipe
Jmh 1
KETERANGAN:
= Khusus untuk OHL Feeder = Khusus untuk Cable Feeder A = Alarm I = Indikasi Rincian Teleinformasi diatas adalah rincian per bay
**) *)
49
Joint Control
P Q V
P Q V
P Q V
P Q V
P Q I
P Q I
P Q I
BUSBAR- A
BUSBAR- B
Teleinformasi Data Untuk Generator Combined Cycle Pada Konfigurasi 1 Breaker Data No 6 7 8 9 13 16 74 75 106 114 129 Kode I KVARH KWH P Q V DFRF DIFF ERF GTT P1REF Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Restricted earth fault Tipe Jmh 3 4 4 7 7 4 3 3 3 3 3
TM
TSS
A A A A A
50
Data
Fungsi Ground fault relay Over current relay Protection on test Restricted earth fault failure Circuit breaker closed/opened Line isolator switch closed/opened Line isolator switch closed/opened
Tipe A A A A I I
Jmh 3 3 3 3 2 3 3
TSD RCD
51
TB-02
P Q V
P Q V
P Q I
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi 1 Breaker Data No 6 7 8 9 13 16 74 Kode I KVARH KWH P Q V DFRF Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Disturbance fault recorder faulty Tipe Jmh 1 2 2 3 3 2 1
TM
TSS
52
Data
Fungsi Differential failure Event recorder failure Generator transformer trip Restricted earth fault Ground fault relay Over current relay Protection on test Restricted earth fault failure Circuit breaker closed/opened Line isolator switch closed/opened Line isolator switch closed/opened
Tipe A A A A A A A A I I
Jmh 1 1 1 1 1 1 1 1 2 1 1
TSD RCD
53
TB-03
P Q V
P Q V
P Q I L/R
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Double Busbar Data No 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 129 Kode I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT P1REF Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Restricted earth fault Tipe Jmh 1 2 2 3 3 2 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A
54
Data
No 130 131 133 134 135 136 138 147 157 169 170 1 3 7 13 1 2 7
Kode P2GFR P2OCR PD PHR PHS PHT POT REFF SYNF TCS1 TCS2 BI CB ES LR BI CB LR
Fungsi Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Local remote
Tipe A A A A A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 2 3 1 1 2 1 1
TSD
RCD
55
TB-04
P Q V
P Q V
P Q I L/R
BUSBAR
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Single Busbar Data No 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 129 130 131 133 Kode I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT P1REF P2GFR P2OCR PD Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Restricted earth fault Ground fault relay Over current relay Pole discrepancy Tipe Jmh 1 2 2 3 3 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A
56
Data
Fungsi Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Local remote
Tipe A A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1
TSD
RCD
57
TB-05
P Q V
P Q I
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1 Breaker Data No 6 7 8 9 13 16 74 75 106 114 129 Kode I KVARH KWH P Q V DFRF DIFF ERF GTT P1REF Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Restricted earth fault Tipe Jmh 1 1 1 2 2 1 1 1 1 1 1
TM
TSS
A A A A A
58
Data
Fungsi Ground fault relay Over current relay Protection on test Restricted earth fault failure Earth switch closed/opened Line isolator switch closed/opened Line isolator switch closed/opened
Tipe A A A A I I
Jmh 1 1 1 1 1 1 1
TSD RCD
59
TB-06
P Q V P Q I L/R
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar Data No 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 129 130 131 Kode I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT P1REF P2GFR P2OCR Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Restricted earth fault Ground fault relay Over current relay Tipe Jmh 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A
60
Data
Fungsi Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Local remote
Tipe A A A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 2 1 1 1 2 1 1
TSD
RCD
61
TB-07
P Q V P Q I L/R
BUSBAR
Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar Data No 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 129 130 131 133 134 135 136 Kode I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT P1REF P2GFR P2OCR PD PHR PHS PHT Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Tipe Jmh 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A A A A
62
Data
Fungsi Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Local remote
Tipe A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
63
TB-08
P Q V P Q I
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1 Breaker Data No 6 7 8 9 13 16 74 75 106 Kode I KVARH KWH P Q V DFRF DIFF ERF Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Disturbance fault recorder faulty Differential failure Event recorder failure Tipe Jmh 1 1 1 2 2 1 1 1 1
TM
TSS
A A A
64
Data
Fungsi Generator transformer trip Restricted earth fault Ground fault relay Over current relay Protection on test Restricted earth fault failure Circuit breaker closed/opened Line isolator switch closed/opened Line isolator switch closed/opened
Tipe A A A A A A I I
Jmh 1 1 1 1 1 1 2 1 1
TSD RCD
65
TB-09
P Q V
P Q I L/R
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar Data No 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 129 Kode I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT P1REF Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Restricted earth fault Tipe Jmh 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A
66
Data
No 130 131 133 134 135 136 138 147 157 169 170 1 3 7 13 1 2 7
Kode P2GFR P2OCR PD PHR PHS PHT POT REFF SYNF TCS1 TCS2 BI CB ES LR BI CB LR
Fungsi Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Local remote
Tipe A A A A A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 2 3 1 1 2 1 1
TSD
RCD
67
TB-10
P Q V P Q I
L/R
BUSBAR
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar Data No 6 7 8 9 13 16 41 44 58 74 75 106 114 118 119 120 129 130 131 133 Kode I KVARH KWH P Q V CBDF CBM CSP DFRF DIFF ERF GTT LPA LPB LPT P1REF P2GFR P2OCR PD Fungsi Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Circuit breaker drive failure Circuit breaker maintenance Check synchronizing in progress Disturbance fault recorder faulty Differential failure Event recorder failure Generator transformer trip Low pressure alarm Low pressure block Low pressure trip Restricted earth fault Ground fault relay Over current relay Pole discrepancy Tipe Jmh 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A
68
Data
Fungsi Trip phase R Trip phase S Trip phase T Protection on test Restricted earth fault failure Synchronizing failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Bus isolator switch closed/opened Circuit breaker closed/opened Local remote
Tipe A A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1
TSD
RCD
69
TB-11
L/R
BUSBAR - A
P Q V I
Download to RCC
BUSBAR - B
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to 1 Breaker) Data TC TM No 1 1 3 4 6 7 8 9 13 Kode TPI
AMF CNTA CTPI I KVARH KWH P Q
Tipe I
Jmh 1 1 1 1 1 1 1 1 1
70
Data
No 15 16 58 60 74 75 77 106 108 111 123 124 125 128 129 130 131 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 171 172 173 174 177 178 179 180 185 186 187 188 189 7 12 14
Kode
TEMP V
Fungsi
Temperature Tegangan
Tipe
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1
TSS
TSD
CSP DCF DFRF DIFF DSDF ERF FPO GFRF OCRF OTA OTT P1DIF P1REF P2GFR P2OCR POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT ES LI LRT
Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Earth switch closed/opened Line isolator switch closed/opened Local/remote switch for tapchanger
I A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A I I I
71
Data
No 20 21 6 8 11 12 13
Fungsi Tap changer auto/manual Transformer fan auto/manual Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe I I
Jmh 1 1 2 1 1 1 1
RCD
72
TB-12
L/R P Q V I
L/R
BUSBAR - A
Download to RCC
BUSBAR - B
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Double Busbar) Data TC No 1 1 3 4 6 7 8 9 12 13 15 16 Kode TPI
AMF CNTA CTPI I KVARH KWH P PRES Q TEMP V
Tipe I
Jmh 1 1 1 1 1 1 1 1 1-2 *) 1 1 1
TM
73
Data TSS
No 41 42 43 44 58 60 74 75 77 106 108 111 118 119 120 123 124 125 128 129 130 131 133 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177
Kode CBDF CBFA CBFB CBM CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT OCRF OTA OTT P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF
Fungsi Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure
Tipe A A A I I A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A
Jmh 1-2 *) 1-2 *) 1-2 *) 1-2 *) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1-2 *) 1-2 *) 1-2 *) 1-2 *) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1-2 *) 1-2 *) 1 1 1 1 1
74
Data
Kode TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT BI CB CSO ES LI LR LRT SAM TCC TFAM BI CB CSO LI LR LRT SAM TC TCC TFAM
Fungsi Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A A A A A I I I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 2-4 *) 1-2 *) 1-2 *) 2 1-0 *) 1-2 *) 1 1-2 *) 1 1 2-4 *) 1-2 *) 1-2 *) 1-0 *) 1-2 *) 1 1-2 *) 1 1 1
TSD
RCD
75
TB-13
L/R
P Q V I
Operation Responsibility by IRCC or RCC
L/R
BUSBAR
Download to RCC
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Single Busbar) Data TC No 1 1 3 4 6 7 8 9 12 13 15 16 41 42 43 44 Kode TPI
AMF CNTA CTPI I KVARH KWH P PRES Q TEMP V
Tipe I
TM
TSS
Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance
A A A I
76
Data
No 58 60 74 75 77 106 108 111 118 119 120 123 124 125 128 129 130 131 133 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 185
Kode CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT OCRF OTA OTT P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR VTF
Fungsi Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure
Tipe I A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A
77
Data
Kode WTHVA WTHVT WTLVA WTLVT BI CB CSO ES LI LR LRT SAM TCC TFAM BI CB CSO LI LR LRT SAM TC TCC TFAM
Fungsi HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A I I I I I I I I I I
Jmh 1 1 1 1 1-2 *) 1-2 *) 2 1-0 *) 1-2 *) 1 1-2 *) 1 1 1-3 *) 1-2 *) 1-2 *) 1-0 *) 1-2 *) 1 1-2 *) 1 1 1
TSD
RCD
78
TB-14: Interbus Transformer (Secondary Side Connected to 1 Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier)
INTERBUS TRANSFORMER Secondary Side Connected to 1 Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier
BUSBAR (IRCC)
TB-14
L/R Q P Q V I
BUSBAR - A
Download to RCC
BUSBAR - B
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to 1 Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier) Data TC TM No 1 1 3 4 6 7 8 9 Kode TPI
AMF CNTA CTPI I KVARH KWH P
Tipe I
Jmh 1 1 1 1 1 1 1 1
79
Data
No 13 15 16 58 60 74 75 77 106 108 111 123 124 125 128 129 130 131 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 171 172 173 174 177 178 179 180 185 186 187 188 189 7 12 14
Kode
Q TEMP V
Fungsi
Daya reaktif Temperature Tegangan
Tipe
Jmh 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 3 1
TSS
TSD
CSP DCF DFRF DIFF DSDF ERF FPO GFRF OCRF OTA OTT P1DIF P1REF P2GFR P2OCR POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT ES LI LRT
Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Earth switch closed/opened Line isolator switch closed/opened Local/remote switch for tapchanger
I A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A I I I
80
Data
No 20 21 6 8 11 12 13
Fungsi Tap changer auto/manual Transformer fan auto/manual Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe I I
Jmh 1 1 3 1 1 1 1
RCD
81
TB-15: Interbus Transformer (Secondary Side Connected to Double Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Double Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier) Data TC TM No 1 1 3 4 6 7 8 9 12 Kode TPI
AMF CNTA CTPI I KVARH KWH P PRES
Tipe I
Jmh 1 1 1 1 1 1 1 1 1-2 *)
82
Data
No 13 15 16 41 42 43 44 58 60 74 75 77 106 108 111 118 119 120 123 124 125 128 129 130 131 133 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172
Kode
Q TEMP V
Fungsi
Daya reaktif Temperature Tegangan
Tipe
Jmh 2 1 1 1-2 *) 1-2 *) 1-2 *) 1-2 *) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1-2 *) 1-2 *) 1-2 *) 1-2 *) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1-2 *) 1-2 *) 1 1
TSS
CBDF CBFA CBFB CBM CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT OCRF OTA OTT P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT
Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip
A A A I I A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A
83
Data
No 173 174 177 178 179 180 185 186 187 188 189 1 3 5 7 12 13 14 18 20 21 1 2 4 6 7 8 10 11 12 13
Kode TOLA TOOS TPIF TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT BI CB CSO ES LI LR LRT SAM TCC TFAM BI CB CSO LI LR LRT SAM TC TCC TFAM
Fungsi Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A A A A A A A A I I I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 2-4 *) 1-2 *) 1-2 *) 2 2-1 *) 1-2 *) 1 1-2 *) 1 1 2-4 *) 1-2 *) 1-2 *) 2-1 *) 1-2 *) 1 1-2 *) 1 1 1
TSD
RCD
84
TB-16: Interbus Transformer (Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)
INTERBUS TRANSFORMER Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier
BUSBAR (IRCC or RCC)
TB-16
L/R
P Q V I
Operation Responsibility by IRCC or RCC
L/R
Download to RCC
BUSBAR
Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier) Data TC No 1 1 3 4 6 7 8 9 12 13 15 16 Kode TPI
AMF CNTA CTPI I KVARH KWH P PRES Q TEMP V
Tipe I
Jmh 1 1 1 1 1 1 1 1 1-2 *) 2 1 1
TM
85
Data TSS
No 41 42 43 44 58 60 74 75 77 106 108 111 118 119 120 123 124 125 128 129 130 131 133 134 135 136 138 139 145 147 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177
Kode CBDF CBFA CBFB CBM CSP DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT OCRF OTA OTT P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SYNF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF
Fungsi Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Over current relay failure Oil temperature alarm Oil temperatur trip Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer AVR failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure
Tipe A A A I I A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A
Jmh 1-2 *) 1-2 *) 1-2 *) 1-2 *) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1-2 *) 1-2 *) 1-2 *) 1-2 *) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1-2 *) 1-2 *) 1 1 1 1 1
86
Data
Kode TSPA TSPT UFR VTF WTHVA WTHVT WTLVA WTLVT BI CB CSO ES LI LR LRT SAM TCC TFAM BI CB CSO LI LR LRT SAM TC TCC TFAM
Fungsi Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened Local remote Local/remote switch for tapchanger Synchronization auto/manual Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A A A A A I I I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1-2 *) 1-2 *) 2 2-1 *) 1-2 *) 1 1-2 *) 1 1 1-3 *) 1-2 *) 1-2 *) 2-1 *) 1-2 *) 1 1-2 *) 1 1 1
TSD
RCD
87
Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi 1 Breaker Data TC TM No 1 1 3 4 6 7 8 9 12 13 Kode TPI AMF CNTA CTPI I KVARH KWH P PRES Q Fungsi Tap position indication Amperes fault ( per phase ) Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tipe I Jmh 1 1 1 1 1 1 1 1 1 1
88
Data
No 15 16 60 74 75 77 106 108 111 123 124 125 126 127 128 129 130 131 138 139 145 147 158 159 160 161 162 163 164 165 166 167 168 171 172 173 174 177 178 179 180 182 183 185 186 187 188 189 7
Kode TEMP V DCF DFRF DIFF DSDF ERF FPO GFRF OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR P2OCR POT PRDT RCBF REFF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR UVR UVRF VTF WTHVA WTHVT WTLVA WTLVT ES
Fungsi Temperature Tegangan DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer avr failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Earth switch closed/opened
Tipe
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSS
TSD
A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A A A I
89
Data
No 12 14 20 21 6 8 11 12 13
Fungsi Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer auto/manual Transformer fan auto/manual Line isolator switch closed/opened Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe I I I I
Jmh 1 1 1 1 1 1 1 1 1
RCD
90
TB-18: Bay Trafo Tenaga Pada Konfigurasi Double Busbar BAY TRAFO TENAGA PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A TB-18
BUSBAR - B
L/R P Q V I
TEGANGAN TINGGI
Batas wewenang
TEGANGAN MENENGAH
DOUBLE BUSBAR
Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi Double Busbar Data TC No 1 1 2 3 4 6 7 8 9 12 13 15 16 41 42 43 44 Kode TPI AMF CCB CNTA CTPI I KVARH KWH P PRES Q TEMP V CBDF CBFA CBFB CBM Fungsi Tap position indication Amperes fault ( per phase ) Counter of circuit breaker Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Tipe I Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A I
91
Data
No 60 74 75 77 106 108 111 118 119 120 123 124 125 126 127 128 129 130 131 133 134 135 136 138 139 145 147 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 182
Kode DCF DFRF DIFF DSDF ERF FPO GFRF LPA LPB LPT OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR UVR
Fungsi DC supply failure Disturbance fault recorder faulty Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer avr failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Under voltage relay operate
Tipe A A A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
92
Data
Kode UVRF VTF WTHVA WTHVT WTLVA WTLVT BI CB ES LR LRT RACK TCC TFAM BI CB LR LRT TC TCC TFAM
Fungsi Under voltage relay failure Voltage transformer failure HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Local/remote switch for tapchanger Circuit breaker rackin/rackout Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Local remote Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A A A I I I I I I I I
Jmh 1 1 1 1 1 1 2 1 1 1 1 1 1 1 2 1 1 1 1 1 1
TSD
RCD
93
TB-19: Bay Trafo Tenaga Pada Konfigurasi Single Busbar BAY TRAFO TENAGA PADA KONFIGURASI SINGLE BUSBAR
BUSBAR TB-19
L/R P Q V I
TEGANGAN TINGGI
Batas wewenang
TEGANGAN MENENGAH
DOUBLE BUSBAR
Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi Single Busbar Data TC No 1 1 2 3 4 6 7 8 9 12 13 15 16 41 42 43 44 60 74 Kode TPI AMF CCB CNTA CTPI I KVARH KWH P PRES Q TEMP V CBDF CBFA CBFB CBM DCF DFRF Fungsi Tap position indication Amperes fault ( per phase ) Counter of circuit breaker Counter arester Counter tap position indication Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Temperature Tegangan Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Tipe I Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A I A A
94
Data
No 75 77 106 108 111 118 119 120 123 124 125 126 127 128 129 130 131 133 134 135 136 138 139 145 147 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 177 178 179 180 182 183 185
Kode DIFF DSDF ERF FPO GFRF LPA LPB LPT OCRF OTA OTT OVR OVRF P1DIF P1REF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF REFF SZPA SZPB SZPF TAF TBUC2 TBUCA TCA TCFF TCH TCL TCPF TCS1 TCS2 TFDP TJANT TOLA TOOS TPIF TSPA TSPT UFR UVR UVRF VTF
Fungsi Differential failure Disconnecting switch driving fault Event recorder failure Fire protection operated Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Over current relay failure Oil temperature alarm Oil temperatur trip Over voltage relay operate Over voltage relay failure Differential Restricted earth fault Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Restricted earth fault failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Tranformer avr failure Transformer bucholz trip Transformer bucholz alarm Tap changer alarm Transformer cooling fan failure Tap changer high limit Tap changer low limit Transformer cooling pump failure Trip coil supervisory 1 Trip coil supervisory 2 Transformer fire detection & protection Transformer jansen trip Transformer oil level alarm Transformer out of step alarm Tap position indication failure Transformer sudden pressure alarm Transformer sudden pressure trip Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure
Tipe A A A A A A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A A A A A A A A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
95
Data
Kode WTHVA WTHVT WTLVA WTLVT BI CB ES LR LRT RACK TCC TFAM BI CB LR LRT TC TCC TFAM
Fungsi HV winding temperatur alarm HV winding temperatur trip LV winding temperatur alarm LV winding temperatur trip Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Local remote Local/remote switch for tapchanger Circuit breaker rackin/rackout Tap changer auto/manual Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Local remote Local/remote switch for tapchanger Tap changer raise/lower Tap changer auto/manual Transformer fan auto/manual
Tipe A A A A I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
96
BUSBAR - B
Reaktor
Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi 1 Breaker Data No Kode Fungsi 1 AMF Amperes fault ( per phase ) 12 PRES Pressure TM 13 Q Daya reaktif 15 TEMP Temperature 60 DCF DC supply failure 74 DFRF Disturbance fault recorder faulty 106 ERF Event recorder failure 128 P1DIF Differential 130 P2GFR Ground fault relay 131 P2OCR Over current relay TSS 138 POT Protection on test 139 PRDT Pressure relay device trip 145 RCBF Relay circuit breaker fail failure 148 RF Reaktor failure 158 SZPA Short zone protection (a) operate 159 SZPB Short zone protection (b) operate 160 SZPF Short zone protection failure 7 ES Earth switch closed/opened TSD 12 LI Line isolator switch closed/opened 21 TFAM Transformer fan auto/manual 6 LI Line isolator switch closed/opened RCD 13 TFAM Transformer fan auto/manual
Tipe
A A A A A A A A A A A A A I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
97
TB-21
BUSBAR - A
BUSBAR - B
L/R Q
Reaktor
Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi Double Busbar Data No 1 2 12 13 15 41 42 43 44 60 74 106 118 119 120 128 130 131 133 134 135 136 138 Kode AMF CCB PRES Q TEMP CBDF CBFA CBFB CBM DCF DFRF ERF LPA LPB LPT P1DIF P2GFR P2OCR PD PHR PHS PHT POT Fungsi Amperes fault ( per phase ) Counter of circuit breaker Pressure Daya reaktif Temperature Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Event recorder failure Low pressure alarm Low pressure block Low pressure trip Differential Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A A A A A
98
Data
Kode PRDT RCBF RF SZPA SZPB SZPF TCS1 TCS2 BI CB ES LI LR TFAM BI CB LI LR TFAM
Fungsi Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual
Tipe A A A A A A A A I I I I I I
Jmh 1 1 1 1 1 1 1 1 2 1 1 1 1 1 2 1 1 1 1
TSD
RCD
99
TB-22
L/R Q
Reaktor
Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi Single Busbar Data No 1 2 12 13 15 41 42 43 44 60 74 106 118 119 120 128 130 131 133 134 135 136 138 139 145 148 158 Kode AMF CCB PRES Q TEMP CBDF CBFA CBFB CBM DCF DFRF ERF LPA LPB LPT P1DIF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF RF SZPA Fungsi Amperes fault ( per phase ) Counter of circuit breaker Pressure Daya reaktif Temperature Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Event recorder failure Low pressure alarm Low pressure block Low pressure trip Differential Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Short zone protection (a) operate 100 Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A A A A A A A A A
Data
Fungsi Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual
Tipe A A A A I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
101
TB-23
BUSBAR - A
BUSBAR - B
L/R Q
Capasitor
Teleinformasi Data Untuk Bay Capasitor Pada Konfigurasi Double Busbar Data No 1 2 12 13 15 41 42 43 44 60 74 106 118 119 120 128 130 131 133 134 135 Kode AMF CCB PRES Q TEMP CBDF CBFA CBFB CBM DCF DFRF ERF LPA LPB LPT P1DIF P2GFR P2OCR PD PHR PHS Fungsi Amperes fault ( per phase ) Counter of circuit breaker Pressure Daya reaktif Temperature Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Event recorder failure Low pressure alarm Low pressure block Low pressure trip Differential Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A A A
102
Data
No 136 138 139 145 148 158 159 160 169 170 1 3 7 12 13 21 1 2 6 7 13
Kode PHT POT PRDT RCBF RF SZPA SZPB SZPF TCS1 TCS2 BI CB ES LI LR TFAM BI CB LI LR TFAM
Fungsi Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual
Tipe A A A A A A A A A A I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 2 1 1 1 1
TSD
RCD
103
TB-24
L/R Q
Capasitor
Teleinformasi Data Untuk Bay Capasitor Pada Konfigurasi Single Busbar Data No 1 2 12 13 15 41 42 43 44 60 74 106 118 119 120 128 130 131 133 134 135 136 138 139 145 148 158 Kode AMF CCB PRES Q TEMP CBDF CBFA CBFB CBM DCF DFRF ERF LPA LPB LPT P1DIF P2GFR P2OCR PD PHR PHS PHT POT PRDT RCBF RF SZPA Fungsi Amperes fault ( per phase ) Counter of circuit breaker Pressure Daya reaktif Temperature Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance DC supply failure Disturbance fault recorder faulty Event recorder failure Low pressure alarm Low pressure block Low pressure trip Differential Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pressure relay device trip Relay circuit breaker fail failure Reaktor failure Short zone protection (a) operate 104 Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A A A A A A A A A A A A A A A
Data
Fungsi Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Line isolator switch closed/opened Local remote Transformer fan auto/manual
Tipe A A A A I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
105
TB-25: Bay Penghantar Pada Konfigurasi 1 Breaker BAY PENGHANTAR PADA KONFIGURASI 1 BREAKER
BUSBAR - A TB-25
BUSBAR - B
P Q V I
Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi 1 Breaker Data No 1 3 6 7 8 9 13 16 49 50 51 52 53 54 55 56 Kode AMF CNTA *) I KVARH KWH P Q V CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT Fungsi Amperes fault ( per phase ) Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A A
106
Data
No 57 58 60 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode CF *) CSP DCF DEARX *) DEATX *) DEBRX *) *) DEBTX *) DEFAF DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) *) DZ1AR *) DZ1AS DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) DZAF *) *) DZARX *) DZATX DZBF *) DZBRX *) DZBTX *) ERF GFRF
LOWCT**) OCPA**)
Fungsi Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip Oil cable pressure alarm
Tipe A I A A A A A A A A A A A A A A A I I I I A A A A A A A A A A A A A A A A A A A I I A I I A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
107
Data
No 123 126 127 130 131 138 141 145 157 158 159 160 175 176 180 182 183 185 7 12 6
*)
Kode OCRF OVR *) OVRF *) P2GFR P2OCR POT PWF RCBF SYNF SZPA SZPB SZPF TPAF *) TPBF *) UFR UVR *) UVRF *) VTF ES LI
LI
Fungsi Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Earth switch closed/opened Line isolator switch closed/opened
Line isolator switch closed/opened
Tipe A A A A A I A A A A A A A A A A A A I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD RCD
KETERANGAN:
**)
108
TB-26: Bay Penghantar Pada Konfigurasi Double Busbar BAY PENGHANTAR PADA KONFIGURASI DOUBLE BUSBAR
TB-26
BUSBAR - A
BUSBAR - B
L/R P Q V I
Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi Double Busbar Data No 1 2 3 6 7 8 9 12 13 16 34 35 41 42 43 44 49 50 51 52 53 54 55 Kode AMF CCB CNTA *) I KVARH KWH P PRES Q V AR *) ARO *) CBDF CBFA CBFB CBM CDAF CDAR CDAS CDAT CDBF CDBR CDBS Fungsi Amperes fault ( per phase ) Counter of circuit breaker Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tegangan Circuit breaker auto reclose Auto reclose off Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
I I A A A I A A A A A A A
109
Data
No 56 57 58 60 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode CDBT CF *) CSP DCF DEARX *) DEATX *) *) DEBRX *) DEBTX DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) *) DTBTX *) DZ1AR *) DZ1AS DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) *) DZ3AT *) DZ3BR *) DZ3BS DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF
LOWCT**)
Fungsi Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip
Tipe A A I A A A A A A A A A A A A A A A I I I I A A A A A A A A A A A A A A A A A A A I I A I I A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
110
Data
No 118 119 120 122 123 126 127 130 131 133 134 135 136 138 141 145 157 158 159 160 169 170 175 176 180 182 183 185 1 3 5 7 12 13 18 1 2 4 6 7 10
*)
Fungsi Low pressure alarm Low pressure block Low pressure trip
Oil cable pressure alarm
Tipe A A A A A A A A A A A A A I A A A A A A A A A A A A A A I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1
TSD
OCRF OVR *) *) OVRF P2GFR P2OCR PD PHR PHS PHT POT PWF RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 *) TPAF TPBF *) UFR UVR *) UVRF *) VTF BI CB CSO ES LI LR SAM BI
CB CSO LI
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Synchronization auto/manual Bus isolator switch closed/opened
Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened
RCD
LR SAM
KETERANGAN:
**)
111
Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi Single Busbar Data No 1 2 3 6 7 8 9 12 13 16 34 35 41 42 43 44 49 50 51 52 53 54 55 56 57 58 60 Kode AMF CCB CNTA *) I KVARH KWH P PRES Q V AR *) ARO *) CBDF CBFA CBFB CBM CDAF CDAR CDAS CDAT CDBF CDBR CDBS CDBT CF *) CSP DCF Fungsi Amperes fault ( per phase ) Counter of circuit breaker Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tegangan Circuit breaker auto reclose Auto reclose off Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
I I A A A I A A A A A A A A A I A
112
Data
No 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode DEARX *) DEATX *) DEBRX *) DEBTX *) DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) *) DZ1BR *) DZ1BS DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) *) DZAF *) DZARX *) DZATX DZBF *) DZBRX *) DZBTX *) ERF GFRF
LOWCT**)
Fungsi Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip
Tipe A A A A A A A A A A A A A A I I I I A A A A A A A A A A A A A A A A A A A I I A I I A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
113
Data
No 123 126 127 130 131 133 134 135 136 138 141 145 157 158 159 160 169 170 175 176 180 182 183 185 1 3 5 7 12 13 18 1 2 4 6 7 10
*)
Kode OCRF OVR *) OVRF *) P2GFR P2OCR PD PHR PHS PHT POT PWF RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 TPAF *) TPBF *) UFR *) UVR *) UVRF VTF BI CB CSO ES LI LR SAM BI
CB CSO LI
Fungsi Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Synchronization auto/manual Bus isolator switch closed/opened
Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened
Tipe A A A A A A A A A I A A A A A A A A A A A A A A I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
LR SAM
KETERANGAN:
**)
114
TB-28: Bay Penghantar Paralel Dengan Reaktor Pada Konfigurasi Double Busbar BAY PENGHANTAR PARALEL DENGAN REAKTOR PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A TB-28
BUSBAR - B
L/R P Q V I
Teleinformasi Data Untuk Bay Penghantar Serial Dengan Reaktor Pada Konfigurasi Double Busbar Data No 1 2 3 6 7 8 9 12 13 16 34 35 41 42 43 44 49 Kode AMF CCB CNTA *) I KVARH KWH P PRES Q V AR *) ARO *) CBDF CBFA CBFB CBM CDAF Fungsi Amperes fault ( per phase ) Counter of circuit breaker Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Pressure Daya reaktif Tegangan Circuit breaker auto reclose Auto reclose off Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Current differential relay (a) failure Tipe Jmh 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1
TM
TSS
I I A A A I A
115
Data
No 50 51 52 53 54 55 56 57 58 60 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103
Kode CDAR CDAS CDAT CDBF CDBR CDBS CDBT CF *) CSP DCF DEARX *) DEATX *) DEBRX *) DEBTX *) DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) DTBTX *) DZ1AR *) DZ1AS *) DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) DZ2AT *) DZ2BR *) *) DZ2BS *) DZ2BT DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) DZAF *) DZARX *) DZATX *) DZBF *)
Fungsi Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure
Tipe A A A A A A A A I A A A A A A A A A A A A A A A I I I I A A A A A A A A A A A A A A A A A A A I I A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
116
Data
No
104 105
Fungsi Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip
Tipe I I A A A A A A A A A A A A A A A A I A A A A A A A A A A A A A A I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 2 2 1 1 2 1 1 2 1 1
TSD
RCD
106 111 117 118 119 120 122 123 126 127 130 131 133 134 135 136 138 141 145 157 158 159 160 169 170 175 176 180 182 183 185 1 3 5 7 12 13 18 1 2 4 6 7 10
*)
LOWCT**)
OCRF OVR *) OVRF *) P2GFR P2OCR PD PHR PHS PHT POT PWF RCBF SYNF SZPA SZPB SZPF TCS1 TCS2 TPAF *) TPBF *) UFR UVR *) UVRF *) VTF BI CB CSO ES LI LR SAM BI
CB CSO LI
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Earth switch closed/opened Line isolator switch closed/opened Local remote Synchronization auto/manual Bus isolator switch closed/opened
Circuit breaker closed/opened Check synchronizing override Line isolator switch closed/opened
LR SAM
KETERANGAN:
**)
117
TB-29: Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1 Breaker BAY PENGHANTAR PARALEL DENGAN 1 REAKTOR PADA KONFIGURASI 1 BREAKER
BUSBAR - A TB-29
BUSBAR - B
Q L/R
P Q V I
Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1 Breaker Data No 1 3 6 7 8 9 13 16 49 50 51 52 53 54 55 Kode AMF CNTA *) I KVARH KWH P Q V CDAF CDAR CDAS CDAT CDBF CDBR CDBS Fungsi Amperes fault ( per phase ) Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Current differential (b) phase S Tipe Jmh 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1
TM
TSS
A A A A A A A
118
Data
No 56 57 58 60 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode CDBT CF *) CSP DCF DEARX *) DEATX *) *) DEBRX *) DEBTX DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) DTBRX *) *) DTBTX *) DZ1AR *) DZ1AS DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) *) DZ2AT DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) DZ3BT *) *) DZAF DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF
LOWCT**)
Fungsi Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Low oil pressure cable trip
Tipe A A I A A A A A A A A A A A A A A A I I I I A A A A A A A A A A A A A A A A A A A I I A I I A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
119
Data
No 122 123 126 127 130 131 138 141 145 157 158 159 160 175 176 180 182 183 185 3 7 12 2 6
*)
Kode
OCPA**)
Fungsi
Oil cable pressure alarm
Tipe A A A A A A I A A A A A A A A A A A A I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 2
TSD RCD
OCRF OVR *) OVRF *) P2GFR P2OCR POT PWF RCBF SYNF SZPA SZPB SZPF TPAF *) TPBF *) UFR UVR *) UVRF *) VTF CB ES LI CB
LI
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Circuit breaker closed/opened Earth switch closed/opened Line isolator switch closed/opened Circuit breaker closed/opened
Line isolator switch closed/opened
KETERANGAN:
**)
120
TB-30: Bay Penghantar Paralel Dengan 2 Reaktor Seri Pada Konfigurasi 1 Breaker BAY PENGHANTAR PARALEL DENGAN 2 REAKTOR SERI PADA KONFIGURASI 1 BREAKER
BUSBAR- A TB-30
BUSBAR- B Q Q P Q V I
Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 2 Reaktor seri Pada Konfigurasi 1 Breaker Data No 1 3 6 7 8 9 13 16 49 50 51 52 53 54 Kode AMF CNTA *) I KVARH KWH P Q V CDAF CDAR CDAS CDAT CDBF CDBR Fungsi Amperes fault ( per phase ) Counter arester Arus Kilovar hour Kilowatt hour Daya aktif Daya reaktif Tegangan Current differential relay (a) failure Current differential (a) phase R Current differential (a) phase S Current differential (a) phase T Current differential relay (b) failure Current differential (b) phase R Tipe Jmh 1 1 1 1 1 1 3 1 1 1 1 1 1 1
TM
TSS
A A A A A A
121
Data
No 55 56 57 58 60 62 63 64 65 66 67 68 69 70 71 72 73 74 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105
Kode CDBS CDBT CF *) CSP DCF DEARX *) *) DEATX *) DEBRX *) DEBTX DEFAF *) DEFAR DEFAS DEFAT DEFBF *) DEFBR DEFBS DEFBT DFRF DSDF DTARX *) DTATX *) *) DTBRX *) DTBTX DZ1AR *) DZ1AS *) DZ1AT *) DZ1BR *) DZ1BS *) DZ1BT *) DZ2AR *) DZ2AS *) *) DZ2AT DZ2BR *) DZ2BS *) DZ2BT *) DZ3AR *) DZ3AS *) DZ3AT *) DZ3BR *) DZ3BS *) *) DZ3BT *) DZAF DZARX *) DZATX *) DZBF *) DZBRX *) DZBTX *) ERF GFRF
Fungsi Current differential (b) phase S Current differential (b) phase T Carrier faulty Check synchronizing in progress DC supply failure Directional earth fault (a) relay receive Directional earth fault (a) relay transmit Directional earth fault (b) relay receive Directional earth fault (b) relay transmit Directional earth fault (a) failure Directional earth fault (a) phase R Directional earth fault (a) phase S Directional earth fault (a) phase T Directional earth fault (b) failure Directional earth fault (b) phase R Directional earth fault (b) phase S Directional earth fault (b) phase T Disturbance fault recorder faulty Disconnecting switch driving fault Direct transfer trip (a) receive Direct transfer trip (a) transmit Direct transfer trip (b) receive Direct transfer trip (b) transmit Distance (a) phase R zone 1 Distance (a) phase S zone 1 Distance (a) phase T zone 1 Distance (b) phase R zone 1 Distance (b) phase S zone 1 Distance (b) phase T zone 1 Distance (a) phase R zone 2 Distance (a) phase S zone 2 Distance (a) phase T zone 2 Distance (b) phase R zone 2 Distance (b) phase S zone 2 Distance (b) phase T zone 2 Distance (a) phase R zone 3 Distance (a) phase S zone 3 Distance (a) phase T zone 3 Distance (b) phase R zone 3 Distance (b) phase S zone 3 Distance (b) phase T zone 3 Distance relay (a) failure Distance (a) relay receive Distance (a) relay transmit Distance relay (b) failure Distance (b) relay receive Distance (b) relay transmit Event recorder failure Ground fault relay failure
Tipe A A A I A A A A A A A A A A A A A A A I I I I A A A A A A A A A A A A A A A A A A A I I A I I A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
106 111
122
Data
No 117 122 123 126 127 130 131 138 141 145 157 158 159 160 175 176 180 182 183 185 7 12 6
Kode
LOWCT**) OCPA**)
Fungsi
Low oil pressure cable trip Oil cable pressure alarm
Tipe A A A A A A A I A A A A A A A A A A A A I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 3 2
TSD RCD
OCRF OVR *) OVRF *) P2GFR P2OCR POT PWF RCBF SYNF SZPA SZPB SZPF TPAF *) TPBF *) UFR UVR *) UVRF *) VTF ES LI
LI
Over current relay failure Over voltage relay operate Over voltage relay failure Ground fault relay Over current relay Protection on test Pilot wire failure Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Short zone protection failure Teleprotection (a) failure Teleprotection (b) failure Under frequency relay operate Under voltage relay operate Under voltage relay failure Voltage transformer failure Earth switch closed/opened Line isolator switch closed/opened
Line isolator switch closed/opened
KETERANGAN:
*)
**)
123
TB-31: Bay Kopel Pada Konfigurasi Double Busbar BAY KOPEL PADA KONFIGURASI DOUBLE BUSBAR
TB-31
L/R
I
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk Bay Kopel Pada Konfigurasi Double Busbar Data TM TSS No 2 6 12 41 42 43 44 58 60 77 106 111 118 119 120 123 130 131 133 134 135 136 138 145 157 158 159 Kode CCB I PRES CBDF CBFA CBFB CBM CSP DCF DSDF ERF GFRF LPA LPB LPT OCRF P2GFR P2OCR PD PHR PHS PHT POT RCBF SYNF SZPA SZPB Fungsi Counter of circuit breaker Arus Pressure Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress DC supply failure Disconnecting switch driving fault Event recorder failure Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Over current relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A I I A A A A A A A A A A A A A A I A A A A
124
Data
Fungsi Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual Bus isolator switch closed/opened
Circuit breaker closed/opened Check synchronizing override
Tipe A A A I I I I I
Jmh 1 1 1 2 1 1 1 1 2 1 1 1 1
TSD
RCD
LR SAM
125
BUS SECTION
Tipe-1
L/R
Tipe-2 L/R
Teleinformasi Data Untuk Bus Section Data TM TSS No 2 12 41 42 43 44 58 106 111 118 119 120 123 130 131 133 134 135 136 138 145 157 158 159 Kode CCB PRES CBDF CBFA CBFB CBM CSP ERF GFRF LPA LPB LPT OCRF P2GFR P2OCR PD PHR PHS PHT POT RCBF SYNF SZPA SZPB Fungsi Counter of circuit breaker Pressure Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Check synchronizing in progress Event recorder failure Ground fault relay failure Low pressure alarm Low pressure block Low pressure trip Over current relay failure Ground fault relay Over current relay Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Short zone protection (b) operate Tipe Jmh Tipe-1 Tipe-2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A I I A A A A A A A A A A A A I A A A A
126
TSD
Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual Bus isolator switch closed/opened
Circuit breaker closed/opened Check synchronizing override
A A A I I I I I
RCD
LR SAM
1 1 1 2 1 1 1 1 2 1 1 1 1
127
TB-33
L/R
L/R
L/R
BUSBAR - B
Teleinformasi Data Untuk Diameter Data TM TSS No 2 12 41 42 43 44 46 47 48 58 106 118 119 120 133 134 135 136 138 145 157 158 Kode CCB PRES CBDF CBFA CBFB CBM CCPA CCPB CCPF CSP ERF LPA LPB LPT PD PHR PHS PHT POT RCBF SYNF SZPA Fungsi Counter of circuit breaker Pressure Circuit breaker drive failure Circuit breaker failure (a) operate Circuit breaker failure (b) operate Circuit breaker maintenance Circulating current protection (a) operate Circulating current protection (b) operate Circulating current protection failure Check synchronizing in progress Event recorder failure Low pressure alarm Low pressure block Low pressure trip Pole discrepancy Trip phase R Trip phase S Trip phase T Protection on test Relay circuit breaker fail failure Synchronizing failure Short zone protection (a) operate Tipe Jmh 3 3 3 3 3 3 1 1 3 3 3 3 3 3 3 3 3 3 1 3 3 3
A A A I A A A I A A A A A A A A I A A A
128
Data
Fungsi Short zone protection (b) operate Short zone protection failure Trip coil supervisory 1 Trip coil supervisory 2 Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual Bus isolator switch closed/opened Circuit breaker closed/opened Check synchronizing override Local remote Synchronization auto/manual
Tipe A A A A I I I I I
Jmh 3 3 3 3 6 3 3 3 3 6 3 3 3 3
TSD
RCD
129
Teleinformasi Data Untuk Bus Bar Data TM No 7 37 38 39 40 77 106 126 127 138 182 183 184 7 Kode V BPA BPAF BPB BPBF DSDF ERF OVR OVRF POT UVR UVRF VS ES Fungsi Tegangan Busbar protection (a) Busbar protection (a) failure Busbar protection (b) Busbar protection (b) failure Disconnecting switch driving fault Event recorder failure Over voltage relay operate Over voltage relay failure Protection on test Under voltage relay operate Under voltage relay failure Voltage status Earth switch closed/opened Tipe A A A A A A A A I A A I I Jumlah 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSS
TSD
130
131
C-1: Telesignal
No Kode Fungsi Implementasi Single (S) or Double (D) Indication Suggested Alarm (A) or Event/Indication (I)
ARU
BI
Feeder PBO Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf Capacitor Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf Generator PBO RTU RTU Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf Keypoint Gardu Tengah Gardu Hubung Generator Key Point Gardu Tengah Gardu Hubung Bus Coupler Bus Section Feeder Capacitor Reactor Gen Transf Generator Keypoint PBO Gardu Tengah Gardu Hubung Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf
CAM
Capacitor Auto/Manual
CB
5 6
CD DCBC
D D
I I
ES
8 9
GUC LBS
D D
I I
10
LR
Local Remote
11
RACK
132
No
Kode
Fungsi
Implementasi
Generator 12 13 14 RR 110RF 110SF Recloser Reset 110VDC Rectifier Failure 110VDC Supply Failure Feeder PBO Gardu Induk Gardu Induk Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung Gardu Induk Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung k RTU Feeder PBO Feeder PBO Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf PBO Bus Coupler Bus Section Feeder Incoming Capacitor Reactor PBO RTU IED Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung D S S I A A
15
220F
16
380F
17
48RF
18
48SF
19 20 21
AIRCF AR ARO
Air Conditioning Failure Circuit Breaker Auto Reclose Auto Reclose Off
S S S
A A A
22
CBDF
23
CBTR
CB Trip
24
CTE
Cabinet Temperatur
25
DCG
DC Ground
26
DOOR
Door Activated
133
No
Kode
Fungsi
Implementasi
27
FOTF
FO Terminal Faulty
Gardu Induk IED PBO Gardu Tengah Gardu Hubung Gardu Induk Gardu Induk Gardu Induk PBO Gen Transf Keypoint Gardu Hubung Gardu Tengah RTU IED Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf PBO PBO Feeder Bus Coupler Bus Section Feeder Capacitor Reactor Bus Coupler Bus Section Feeder Capacitor Reactor Gardu Induk Bus Coupler Bus Section Feeder Capacitor Reactor Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung Gen Transf Gen Transf
28 29 30 31 32 33 34
Fire Protection Operated Fire Alarm Fire Alarm System Failure Ground Fault Relay Failure Generator Transformer Trip Homopolar Fault Detector Internal Remote Station
S S S S S S S
A A A A A A A
35
LPA
36 37
OCRF P1DEF
S S
A A
38
P2GFR
39
P2OCR
40
PBXF
PABX Faulty
41
PTF
Protection Faulty
42
RADF
43 44
RBUCA RBUCZ
S S
A A
134
No
Kode
Fungsi
Implementasi
45 46 47 48 49 50 51 52
Reaktor Fire Detection & Protection Reaktor Oil Level Alarm Reaktor Sudden Pressure Alarm Reaktor Bucholz Sudden Pressure Trip Reset Alarm Station Intruder Alarm Tap Changer High Limit Tap Changer Low Limit
Gen Transf Gen Transf Gen Transf Gen Transf Gardu Induk Gardu Induk Incoming Incoming Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf PBO Incoming Feeder Generator
S S S S S S S S
A A A A A A A A
53
TCS1
54 55 56
TPIF UFR UT
Tap Position Indication Failure Under Frequency Relay Operate Unit Trip
S S S
A A A
135
C-2: Telemeasurement
No Kode Fungsi Implementasi
AMF
CCB
Feeder Incoming Gen Transf PBO Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf PBO Busbar Feeder Incoming Capacitor Reactor Generator Keypoint PBO Feeder Incoming Capacitor Reactor Gen Transf Feeder Incoming Capacitor Reactor Gen Transf Feeder Incoming Capacitor Reactor Generator Keypoint Incoming Incoming Capacitor Reactor Generator Busbar Generator Keypoint PBO
Frekuensi
Arus
KVARH
Kilovar Hour
KWH
Kilowatt Hour
Daya Aktif
PF
Power Factor
Daya Reaktif
10
Tegangan
136
TPI
Incoming
137
ARU
Feeder PBO Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf RTU RTU Keypoint Gardu Tengah Gardu Hubung Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf Keypoint PBO Gardu Tengah Gardu Hubung Gardu Induk Feeder PBO
CB
3 4 5
CD DCBC LBS
Control Disable Switch Dummy Circuit Breaker Closed/Opened Load Break Switch Close/Open
LR
Local Remote
7 8
RMT RR
138
139
P Q V
P Q I L/ R L/R
KOPEL
BUSBARA -
BUSBARB -
L/R
I P Q PF
L/R
FEEDER
INCOMING 20KV
140
Teleinformasi Data Untuk Konfigurasi Umum Pada Double Busbar Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan 1 AMF Ampere Fault 2 CCB Counter of Circuit Breaker 4 I Arus TM 5 KVARH Kilovar Hour 6 KWH Kilowatt Hour 7 P Daya Aktif 20 AR Circuit Breaker Auto Reclose 21 ARO Auto Reclose Off 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 37 P1DEF Directional Earth Fault TSS 38 P2GFR Ground Fault Relay Feeder 39 P2OCR Over Current Relay 41 PTF Protection Faulty 53 TCS1 Trip Coil Supervisory 1 55 UFR Under Frequency Relay Operate 1 ARU Auto Reclose Use/Unuse 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened TSD 7 ES Earth Switch Closed/Opened 10 LR Local Remote 12 RR Recloser Reset 1 ARU Auto Recloser Use/Unuse 2 CB Circuit Breaker Closed/Opened RCD 6 LR Local Remote 8 RR Recloser Reset Incoming 1 AMF Amperes Fault 20 kV 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure TSD 2 BI Bus Isolator Switch Closed/Opened
Tipe
Jmh 1 6 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2
A A A A A A A A A A A I I I I I I
A A A A A A A A A A I
141
Group Bay
Data
No 4 7 2 6 2 4 5 6 7 9 22 23 35 37 38 39 41 53 2 3 4 7 10 2 6 4 7 9 10 56 4 8 2 22 23 35 38 39 41 53 2 4 7 10 2 6
Kode CB ES CB LR CCB I KVARH KWH P Q CBDF CBTR LPA P1DEF P2GFR P2OCR PTF TCS1 BI CAM CB ES LR CB LR I P Q V UT CB GUC CCB CBDF CBTR LPA P2GFR P2OCR PTF TCS1 BI CB ES LR CB LR
Fungsi Circuit Breaker Closed/Opened Earth Switch Closed/Opened Circuit Breaker Closed/Opened Local Remote Counter of Circuit Breaker Arus Kilovar Hour Kilowatt Hour Daya Aktif Daya Reaktif Circuit Breaker Drive Failure CB Trip Low Pressure Alarm Directional Earth Fault Ground Fault Relay Over Current Relay Protection Faulty Trip Coil Supervisory 1 Bus Isolator Switch Closed/Opened Capacitor Auto/Manual Circuit Breaker Closed/Opened Earth Switch Closed/Opened Local Remote Circuit Breaker Closed/Opened Local Remote Arus Daya aktif Daya reaktif Tegangan Unit Trip Circuit breaker closed/opened Generator unit run/stop Counter of Circuit Breaker Circuit Breaker Drive Failure CB Trip Low Pressure Alarm Ground Fault Relay Over Current Relay Protection Faulty Trip Coil Supervisory 1 Bus Isolator Switch Closed/Opened Circuit Breaker Closed/Opened Earth Switch Closed/Opened Local Remote Circuit Breaker Closed/Opened Local Remote
Tipe I I I I
Jmh 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1
RCD
TM
Capasitor
TSS
TSD
A A A A A A A A I I I I I
RCD
A I I A A A A A A A I I I I
TSS Kopel
TSD
RCD
142
P Q V
BUSBAR A -
L/R
I P Q PF
L/R
FEEDER
INCOMING 20 KV
143
Teleinformasi Data Untuk Konfigurasi Umum Pada Single Busbar Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan 1 AMF Ampere Fault 2 CCB Counter of Circuit Breaker 4 I Arus TM 5 KVARH Kilovar Hour 6 KWH Kilowatt Hour 7 P Daya Aktif 20 AR Circuit Breaker Auto Reclose 21 ARO Auto Reclose Off 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 37 P1DEF Directional Earth Fault TSS 38 P2GFR Ground Fault Relay Feeder 39 P2OCR Over Current Relay 41 PTF Protection Faulty 53 TCS1 Trip Coil Supervisory 1 55 UFR Under Frequency Relay Operate 1 ARU Auto Reclose Use/Unuse 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened TSD 7 ES Earth Switch Closed/Opened 10 LR Local Remote 12 RR Recloser Reset 1 ARU Auto Recloser Use/Unuse 2 CB Circuit Breaker Closed/Opened RCD 6 LR Local Remote 8 RR Recloser Reset Incoming 1 AMF Amperes Fault 20 kV 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure TSD 2 BI Bus Isolator Switch Closed/Opened
Tipe
Jmh 1 3 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A A A A A A A A A I I I I I I
A A A A A A A A A A I
144
Group Bay
Data
No 4 7 2 6 2 4 5 6 7 9 22 23 35 37 38 39 41 53 2 3 4 7 10 2 6 4 7 9 10 56 4 8
Kode CB ES CB LR CCB I KVARH KWH P Q CBDF CBTR LPA P1DEF P2GFR P2OCR PTF TCS1 BI CAM CB ES LR CB LR I P Q V UT CB GUC
Fungsi Circuit Breaker Closed/Opened Earth Switch Closed/Opened Circuit Breaker Closed/Opened Local Remote Counter of Circuit Breaker Arus Kilovar Hour Kilowatt Hour Daya Aktif Daya Reaktif Circuit Breaker Drive Failure CB Trip Low Pressure Alarm Directional Earth Fault Ground Fault Relay Over Current Relay Protection Faulty Trip Coil Supervisory 1 Bus Isolator Switch Closed/Opened Capacitor Auto/Manual Circuit Breaker Closed/Opened Earth Switch Closed/Opened Local Remote Circuit Breaker Closed/Opened Local Remote Arus Daya aktif Daya reaktif Tegangan Unit Trip Circuit breaker closed/opened Generator unit run/stop
Tipe I I I I
Jmh 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1 1
RCD
TM
Capasitor
TSS
TSD
A A A A A A A A I I I I I
RCD
A I I
145
DB - 01
RCC
I P Q PF
DCC
L/R
Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 1 Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan Incoming 1 AMF Amperes Fault 20 kV 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure TSD 2 BI Bus Isolator Switch Closed/Opened
Tipe
Jmh 1 6 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2
A A A A A A A A A A I
146
Group Bay
Data
No 4 7 2 6
Kode CB ES CB LR
Fungsi Circuit Breaker Closed/Opened Earth Switch Closed/Opened Circuit Breaker Closed/Opened Local Remote
Tipe I I I I
Jmh 1 1 1 1
RCD
147
DB -02
RCC DCC
I P Q PF
L/R
Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 2 Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan Incoming 1 AMF Amperes Fault 20 kV 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure TSD 4 CB Circuit Breaker Closed/Opened
Tipe
Jmh 1 6 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A A A A A A A A I
148
Group Bay
Data
No 7 11 2 6
Kode ES RACK CB LR
Fungsi Earth Switch Closed/Opened Circuit Breaker Rackin/Rackout Circuit Breaker Closed/Opened Local Remote
Tipe I I I I
Jmh 1 1 1 1
RCD
149
DB-03: Trafo 150/20 kV dan 70/20 kV Tipe 3 TRAFO 150/20 KV DAN 70/20 KV TYPE 3
DB -03
RCC DCC
I P Q PF L/R
Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 3 Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan Incoming 1 AMF Amperes Fault 20 kV 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure TSD 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened
Tipe
Jmh 1 3 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A A A A A A A A I I
150
Group Bay
Data
No 7 2 6
Kode ES CB LR
Tipe I I I
Jmh 1 1 1
RCD
151
DB-04
P Q V P Q I L/R
BUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk Generator Pada Konfigurasi Double Busbar Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan Incoming 1 AMF Amperes Fault 20 kV 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure
Tipe
Jmh 1 6 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A A A A A A A A
152
Group Bay
Data TSD
No 2 4 7 2 6 4 7 9 10 56 4 8
Kode BI CB ES CB LR I P Q V UT CB GUC
Fungsi Bus Isolator Switch Closed/Opened Circuit Breaker Closed/Opened Earth Switch Closed/Opened Circuit Breaker Closed/Opened Local Remote Arus Daya aktif Daya reaktif Tegangan Unit Trip Circuit breaker closed/opened Generator unit run/stop
Tipe I I I I I
Jmh 2 1 1 1 1 3 1 1 1 1 1 1
A I I
153
DB-05
P Q V P Q I L/R
BUSBAR
Teleinformasi Data Untuk Generator Pada Konfigurasi Single Busbar Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan Incoming 1 AMF Amperes Fault 20 kV 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 8 PF Power Factor 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay TSS 41 PTF Protection Faulty 51 TCH Tap Changer High Limit 52 TCL Tap Changer Low Limit 53 TCS1 Trip Coil Supervisory 54 TPIF Tap Position Indication Failure 2 BI Bus Isolator Switch Closed/Opened TSD 4 CB Circuit Breaker Closed/Opened 7 ES Earth Switch Closed/Opened 2 CB Circuit Breaker Closed/Opened
Tipe
Jmh 1 3 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A A A A A A A A I I I I
154
Group Bay
Data RCD
No 6 6 4 7 9 10 56 4 8
Kode LR LR I P Q V UT CB GUC
Fungsi Local Remote Local Remote Arus Daya aktif Daya reaktif Tegangan Unit Trip Circuit breaker closed/opened Generator unit run/stop
Tipe I
Jmh 1 1 3 1 1 1 1 1 1
A I I
155
I ( R) I ( S) I ( T) P
L/R
Teleinformasi Data Untuk Feeder 20 kV Tipe 1 Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan Feeder 1 AMF Ampere Fault 2 CCB Counter of Circuit Breaker 4 I Arus TM 5 KVARH Kilovar Hour 6 KWH Kilowatt Hour 7 P Daya Aktif 20 AR Circuit Breaker Auto Reclose 21 ARO Auto Reclose Off 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 37 P1DEF Directional Earth Fault TSS 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay 41 PTF Protection Faulty 53 TCS1 Trip Coil Supervisory 1 55 UFR Under Frequency Relay Operate TSD 1 ARU Auto Reclose Use/Unuse 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened
Tipe
Jmh 1 6 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1
A A A A A A A A A A A I I I
156
Group Bay
Data
No 7 10 12 1 2 6 8
Kode ES LR RR ARU CB LR RR
Fungsi Earth Switch Closed/Opened Local Remote Recloser Reset Auto Recloser Use/Unuse Circuit Breaker Closed/Opened Local Remote Recloser Reset
Tipe I I I
Jmh 1 1 1 1 1 1 1
RCD
157
L/R
I ( R) I ( S) I ( T) P
Teleinformasi Data Untuk Feeder 20 kV Tipe 2 Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan Feeder 1 AMF Ampere Fault 2 CCB Counter of Circuit Breaker 4 I Arus TM 5 KVARH Kilovar Hour 6 KWH Kilowatt Hour 7 P Daya Aktif 20 AR Circuit Breaker Auto Reclose 21 ARO Auto Reclose Off 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 37 P1DEF Directional Earth Fault TSS 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay 41 PTF Protection Faulty 53 TCS1 Trip Coil Supervisory 1 55 UFR Under Frequency Relay Operate TSD 1 ARU Auto Reclose Use/Unuse 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened
Tipe
Jmh 1 3 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1
A A A A A A A A A A A I I I
158
Group Bay
Data
No 7 10 11 12 1 2 6 8
Fungsi Earth Switch Closed/Opened Local Remote Circuit Breaker Rackin/Rackout Recloser Reset Auto Recloser Use/Unuse Circuit Breaker Closed/Opened Local Remote Recloser Reset
Tipe I I I I
Jmh 1 1 1 1 1 1 1 1
RCD
159
I ( R) I ( S) I ( T) P
L/R
Teleinformasi Data Untuk Feeder 20 kV Tipe 3 Group Data No Kode Fungsi Bay 3 F Frekuensi Busbar TM 10 V Tegangan Feeder 1 AMF Ampere Fault 2 CCB Counter of Circuit Breaker 4 I Arus TM 5 KVARH Kilovar Hour 6 KWH Kilowatt Hour 7 P Daya Aktif 20 AR Circuit Breaker Auto Reclose 21 ARO Auto Reclose Off 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 37 P1DEF Directional Earth Fault TSS 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay 41 PTF Protection Faulty 53 TCS1 Trip Coil Supervisory 1 55 UFR Under Frequency Relay Operate TSD 1 ARU Auto Reclose Use/Unuse 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened
Tipe
Jmh 1 3 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A A A A A A A A A A A I I I
160
Group Bay
Data
No 7 10 12 1 2 6 8
Kode ES LR RR ARU CB LR RR
Fungsi Earth Switch Closed/Opened Local Remote Recloser Reset Auto Recloser Use/Unuse Circuit Breaker Closed/Opened Local Remote Recloser Reset
Tipe I I I
Jmh 1 1 1 1 1 1 1
RCD
161
DB - 09
L/R
Teleinformasi Data Untuk Bus Section 20 kV Tipe 1 Group Data No Kode Fungsi Bay TM 2 CCB Counter of Circuit Breaker 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm TSS 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay 41 PTF Protection Faulty Bus Section 53 TCS1 Trip Coil Supervisory 1 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened TSD 7 ES Earth Switch Closed/Opened 10 LR Local Remote 2 CB Circuit Breaker Closed/Opened RCD 6 LR Local Remote
Tipe A A A A A A A I I I I
Jmh 1 1 1 1 1 1 1 1 2 1 1 1 1 1
162
DB -10
L/R
Teleinformasi Data Untuk Bus Section 20 kV Tipe 2 Group Data No Kode Fungsi Bay TM 2 CCB Counter of Circuit Breaker 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm TSS 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay 41 PTF Protection Faulty Bus 53 TCS1 Trip Coil Supervisory 1 Section 2 BI Bus Isolator Switch Closed/Opened 4 CB Circuit Breaker Closed/Opened TSD 7 ES Earth Switch Closed/Opened 10 LR Local Remote 11 RACK Circuit Breaker Rackin/Rackout 2 CB Circuit Breaker Closed/Opened RCD 6 LR Local Remote
Tipe A A A A A A A I I I I I
Jmh 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1
163
DB-11: Kopel
KOPEL
DB -11
L/R
Teleinformasi Data Untuk Kopel Group Data No Kode Bay TM 2 CCB 22 CBDF 23 CBTR 35 LPA TSS 38 P2GFR 39 P2OCR 41 PTF Bus 53 TCS1 Section 2 BI 4 CB TSD 7 ES 10 LR 11 RACK 2 CB RCD 6 LR
Fungsi Counter of Circuit Breaker Circuit Breaker Drive Failure CB Trip Low Pressure Alarm Ground Fault Relay Over Current Relay Protection Faulty Trip Coil Supervisory 1 Bus Isolator Switch Closed/Opened Circuit Breaker Closed/Opened Earth Switch Closed/Opened Local Remote Circuit Breaker Rackin/Rackout Circuit Breaker Closed/Opened Local Remote
Tipe A A A A A A A I I I I I
Jmh 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1
164
CAPACITOR BAY
DB -12
L/R
Teleinformasi Data Untuk Capasitor Bay Group Data No Kode Fungsi Bay 2 CCB Counter of Circuit Breaker 4 I Arus 5 KVARH Kilovar Hour TM 6 KWH Kilowatt Hour 7 P Daya Aktif 9 Q Daya Reaktif 22 CBDF Circuit Breaker Drive Failure 23 CBTR CB Trip 35 LPA Low Pressure Alarm 37 P1DEF Directional Earth Fault TSS Capasitor 38 P2GFR Ground Fault Relay 39 P2OCR Over Current Relay 41 PTF Protection Faulty 53 TCS1 Trip Coil Supervisory 1 2 BI Bus Isolator Switch Closed/Opened 3 CAM Capacitor Auto/Manual TSD 4 CB Circuit Breaker Closed/Opened 7 ES Earth Switch Closed/Opened 10 LR Local Remote 2 CB Circuit Breaker Closed/Opened RCD 6 LR Local Remote
Tipe
Jmh 1 3 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1
A A A A A A A A I I I I I
165
DB -13
PBO
I V
Group Bay
Data
TM
No
4 10 15 17 18 25 26 27 33 42 7 9 10 5 6 1 2 4 10 15 17 20
Kode
I V 220F 48RF 48SF DCG DOOR FOTF HFD RADF ES LBS LR LBS LR AMF CCB I V 220F 48RF AR
Fungsi
Arus Tegangan 220 VAC Failure 48 VDC Rectifier Failure 48 VDC Supply Failure DC Ground Door Activated FO Terminal Faulty Homopolar Fault Detector Radio Link Faulty Earth Switch Closed/Opened Load Break Switch Closed/Opened Local Remote Load Break Switch Closed/Opened Local Remote Amperes Fault Counter of Circuit Breaker Arus Tegangan 220VAC Failure 48VDC Rectifier Failure Circuit Breaker Auto Reclose
Tipe
Jmh
3 3 1 1 1 1 1 1 3 1 1 1 1 1 1 3 1 1 3 1 1 1
TSS Keypoint
TSD RCD
A A A A A A A A I I I
TM TSS PBO
A A A
166
Group Bay
Data
No
21 22 23 25 26 27 31 35 36 42 53 1 4 10 12 1 2 6 8
Kode
ARO CBDF CBTR DCG DOOR FOTF GFRF LPA OCRF RADF TCS1 ARU CB LR RR ARU CB LR RR
Fungsi
Auto Reclose Off Circuit Breaker Drive Failure CB Trip DC Ground Door Activated FO Terminal Faulty Ground Fault Relay Failure Low Pressure Alarm Over Current Relay Failure Radio Link Faulty Trip Coil Supervisory 1 Auto Recloser Use/Unuse Circuit Breaker Closed/Opened Local Remote Recloser Reset Auto Recloser Use/Unuse Circuit Breaker Closed/Opened Local Remote Recloser Reset
Tipe
A A A A A A A A A A A I I I I
Jmh
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TSD
RCD
167
DB-14: SUTM radial dengan keypoint tanpa PBO SUTM RADIAL DENGAN KEYPOINT TANPA PBO
DB -14
KP
Group Bay
Data
TM
No
4 10 15 17 18 25 26 27 33 42 7 9 10 5 6
Kode
I V 220F 48RF 48SF DCG DOOR FOTF HFD RADF ES LBS LR LBS LR
Fungsi
Arus Tegangan 220 VAC Failure 48 VDC Rectifier Failure 48 VDC Supply Failure DC Ground Door Activated FO Terminal Faulty Homopolar Fault Detector Radio Link Faulty Earth Switch Closed/Opened Load Break Switch Closed/Opened Local Remote Load Break Switch Closed/Opened Local Remote
Tipe
Jmh
3 3 1 1 1 1 1 1 3 1 1 1 1 1 1
TSS Keypoint
TSD RCD
A A A A A A A A I I I
168
DB-15: SUTM loop dengan beberapa keypoint SUTM LOOP DENGAN BEBERAPA KP
DB -15
L/R I V
I V L/R
L/R I V
Group Bay
Data
TM
No
4 10 15 17 18 25 26 27 33 42 7 9 10 5 6
Kode
I V 220F 48RF 48SF DCG DOOR FOTF HFD RADF ES LBS LR LBS LR
Fungsi
Arus Tegangan 220 VAC Failure 48 VDC Rectifier Failure 48 VDC Supply Failure DC Ground Door Activated FO Terminal Faulty Homopolar Fault Detector Radio Link Faulty Earth Switch Closed/Opened Load Break Switch Closed/Opened Local Remote Load Break Switch Closed/Opened Local Remote
Tipe
Jmh
3 3 1 1 1 1 1 1 3 1 1 1 1 1 1
TSS Keypoint
TSD RCD
A A A A A A A A I I I
169
DB-16: Spindle 20 kV
SPINDLE 20 kV
DB -16
GI
20 kV Busbar
GD GT GD GH
L/R L/R
Group Bay
Data
No
15 17 18 25 26 27 33 42 7 9 10 5 6 15 17 18 25 26 27 33 42 7 9
Kode
220F 48RF 48SF DCG DOOR FOTF HFD RADF ES LBS LR LBS LR 220F 48RF 48SF DCG DOOR FOTF HFD RADF ES LBS
Fungsi
220 VAC Failure 48 VDC Rectifier Failure 48 VDC Supply Failure DC Ground Door Activated FO Terminal Faulty Homopolar Fault Detector Radio Link Faulty Earth Switch Closed/Opened Load Break Switch Closed/Opened Local Remote Load Break Switch Closed/Opened Local Remote 220 VAC Failure 48 VDC Rectifier Failure 48 VDC Supply Failure DC Ground Door Activated FO Terminal Faulty Homopolar Fault Detector Radio Link Faulty Earth Switch Closed/Opened Load Break Switch Closed/Opened
Tipe
A A A A A A A A I I I
Jmh
1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1
TSD
A A A A A A A A I I
170
Group Bay
Data
No
10
Kode
LR LBS LR
Fungsi
Local Remote Load Break Switch Closed/Opened Local Remote
Tipe
I
Jmh
1 1 1
RCD
5 6
171
172
STRUKTUR INFORMASI
Struktur informasi terdiri dari 112 karakter yang dapat dikelompokkan menjadi sembilan bagian, yaitu: A B C D E F G H I
Bagian A: Nomor ID, terdiri dari 6 digit (sebagai primary key) Bagian B: Time stamp, sebanyak karakter 23 karakter Bagian C: Nama GI/GH/GT/KP, sebanyak 20 karakter Bagian D: Level tegangan, sebanyak 5 karakter Bagian E: Nama bay / feeder, sebanyak 20 karakter Bagian F: Kode nama peralatan atau nama alarm atau nama elemen, sebanyak 5 karakter Bagian G: Status peralatan atau status alarm, sebanyak 15 karakter Bagian H: Nama user yang melakukan aksi (seperti remote control, dan sebagainya), sebanyak 10 karakter Bagian I: Prioritas alarm, sebanyak 8 karakter Struktur di atas ditentukan dalam field yang berbeda. Contohnya dapat dilihat pada Tabel 1 berikut:
Tabel 1. Struktur informasi
A RCC Cawang
110007 110009
C
Cawang Gandul Rungkut Waru Gondang Wetan Gondang Wetan
D
150 150 150 150 20 20
E
Gandul-1 Cawang-1 Waru-1 Bangil-1 Bromo Semeru
F
BI1 ARO LT CB CB CBTR
G
Close Appear Disappear Invalid Open Appear
I
Class-3 Class-2 Class-1 Class-4
02/03/2007 11:10:05.320 05/03/2007 07:00:55.115 11/04/2007 17:44:21.220 12/04/2007 20:11:51.312 25/04/2007 00:30:35.000 19/11/2007 10:00:05.520
RCC Waru
140104 140085 430011 430012
DCC Pasuruan
Adi Class-1 Class-1
A. Nomor ID
Nomor ID (bagian A) terdiri dari dua bagian. Bagian A1 terdiri dari 3 digit yang menyatakan kode area. Bagian A2 terdiri dari 3 digit merupakan nomor RTU bersangkutan. Nomor ID dinyatakan dengan susunan sebagai berikut A1 Bagian A1: Kode area Bagian A2: Nomor RTU A2
173
Kode area
Kode area yang terdiri dari 3 karakter adalah sebagai berikut: NCC : 900 IRCC IRCC Jawa-Bali IRCC Sumatera IRCC Kalimantan IRCC Sulawesi IRCC di Indonesia Timur RCC di Jawa-Bali RCC Cawang RCC Cigereleng RCC Ungaran RCC Waru RCC di Sumatera RCC Medan RCC Padang RCC Palembang RCC di Kalimantan RCC Banjarbaru RCC Balikpapan RCC di Sulawesi RCC Makassar RCC Manado RCC di Indonesia Timur IDCC IDCC Jawa-Bali IDCC Sumatera IDCC Kalimantan IDCC Sulawesi IDCC di Indonesia Timur : : : : : : : : : : : : : : : : : : : : : : : : : : : : x00 100 200 300 400 500 1xx 110 120 130 140 2xx 210 220 230 3xx 310 320 4xx 410 420 5xx x00 100, 200, 300, 400 500, 600 700 800 900 : : : : : : : : 0xx 1xx 2xx 3xx 4xx 5xx 6xx 7xx 8xx 9xx
DCC di Jakarta DCC daerah Jawa bagian Barat DCC daerah Jawa bagian Tengah DCC daerah Jawa bagian Timur dan Bali DCC daerah Sumatera DCC daerah Kalimantan DCC daerah Sulawesi DCC daerah Indonesia Timur
Nomor RTU
Nomor RTU terdiri dari 3 digit (001 999)
174
B. Time stamp
Struktur informasi yang menggambarkan time stamp atau waktu suatu kejadian terdiri dari 23 karakter. Struktur informasinya berturut-turut terdiri dari tanggal (2 karakter), bulan (2 karakter), tahun (4 karakter), jam (2 karakter), menit (2 karakter), dan detik (6 karakter atau sampai dengan orde milidetik). Contohnya: 25/04/2007 00:30:35.000 19/11/2007 10:00:05.520
C. Nama GI/GH/GT
Nama GI/GH/GT dituliskan dalam bentuk nama lengkap (maksimal 20 karakter). Contohnya adalah sebagai berikut: Cawang Gandul Gondang Wetan Rungkut Waru Cawang Gandul Waru Rungkut Gondang Wetan : menyatakan GI Cawang (dikontrol oleh RCC Cawang). : menyatakan GI Gandul (dikontrol oleh RCC Cawang). : menyatakan GI Waru (dikontrol oleh RCC Waru). : menyatakan GI Rungkut (dikontrol oleh RCC Waru). : menyatakan GI/GH/GT Gondang Wetan (dikontrol oleh DCC Pasuruan).
D. Level Tegangan
Level tegangan terdiri dari 5 karakter. Contohnya dapat dilihat pada Tabel 2 berikut:
Tabel 2. Level tegangan
175
Nama Bay / Feeder Pusat Listrik Pusat Listrik Tenaga Air Pusat Listrik Tenaga Diesel Pusat Listrik Tenaga Gas Pusat Listrik Tenaga Panas Bumi Pusat Listrik Tenaga Nuklir Pusat Listrik Tenaga Uap Pusat Listrik Gas/Uap (Combine Cycle) Pusat Listrik Tenaga Mikrohidro Pusat Listrik Tenaga Angin/Bayu Peralatan di Gardu Induk Line Bay (Feeder Bay)
Kode PLTA PLTD PLTG PLTP PLTN PLTU PLTGU PLTMH PLTB Format penulisan: IRCC/RCC: Nama GI lawan + - + nomor penghantar. Contohnya: o Gandul-1 o Cawang-1 DCC: Nama Feeder. Contohnya: o Bromo o Semeru UNIT BUSBAR KOPEL BUSSECT TRAFOx (X adalah Kode Tegangan dari primer dan sekunder trafo) DAMTR SHTXL SHTXC SPARE
Bay ke Unit Generator Busbar Kopel (Bus Tie) Bus Section Trafo Diameter Shunt Reactor Shunt Capacitor Cadangan
Nama Bay Bay 500 kV diameter 1 busbar A 7A1 Bay 500 kV diameter 3 antara busbar A 7AB3 dan B Bay 500 kV diameter 5 busbar B 7B5 Kode tegangan dari primer dan sekunder trafo dapat dilihat pada Tabel 4 berikut:
Tabel 4. Kode tegangan dari primer dan sekunder trafo
Tegangan Tegangan Rendah (TR) Tegangan Menengah (TM) Tegangan Menengah (TM)
176
Kode 0 1 2
Tegangan Tegangan Menengah (TM) Tegangan Tinggi (TT) Tegangan Tinggi (TT) Tegangan Tinggi (TT) Tegangan Ekstra Tinggi (TET) Tegangan Ekstra Tinggi (TET) Tegangan Ekstra Tinggi (TET)
Range 30 sampai 60 kV 60 sampai 90 kV 90 sampai 200 kV 200 sampai 400 kV 400 sampai 600 kV 600 sampai 1000 kV 1000 kV ke atas
Kode 3 4 5 6 7 8 9
Nama Circuit Breaker Bus Isolator #1 Bus Isolator #2 Line Isolator Ground Fault Over Current Line Trip Breaker Fault Power Supply Faulty Daya MW Daya MVAr Arus Load Break Switch Recloser
Kode nama peralatan dapat juga berupa kode teleinformasi (telesignal, telemeasurement atau remote kontrol seperti ditunjukan pada Lampiran A-D).
177
I. Prioritas Alarm
Prioritas alarm terdiri dari 8 karakter, menunjukkan kelas alarm yang ditampilkan. Class 1 merupakan kelas alarm yang menempati prioritas paling tinggi. Contohnya sebagai berikut: Class-1 Class-2 Class-3 Class-4
Struktur Informasi Khusus Penamaan Pemutus Tenaga Pada Gardu Induk 1 Breaker.
Struktur informasi khusus untuk pemutus tenaga pada gardu induk 1 breaker dipakai untuk tujuan komunikasi verbal diantara operator. Kode tersebut hanya ditampilkan di VDU (Video Display Unit), dan dipergunakan di dalam database. Struktur informasi dinyatakan dengan susunan sebagai berikut: X Y Z
Bagian X: kode referensi tegangan Bagian Y: kode nama CB Bagian Z: nomor diameter Contoh: A untuk breaker yang terhubung langsung ke busbar A B untuk breaker yang terhubung langsung ke busbar B AB untuk breaker yang terhubung ke breaker A dan breaker B Contohnya dapat dilihat pada Gambar 4 dan Gambar 5 berikut: Untuk tegangan 500 kV diameter no. 1 Untuk tegangan 150 kV diameter no.4
178
Contoh :
UNIT 4
BANDUNG SELATAN 2
7AB1
7AB2
7AB3
7AB4
7AB5
7B1 BUSBAR B
7B2
7B3
7B4
7B5
CIBINONG 1
CIBINONG 2
CIRATA 1
CIRATA 2
BANDUNG SELATAN 1
179
180
181
Tampilan Status
ITEMS
CB CLOSED CB OPENED PBO PBO CLOSED PBO OPENED LBS CLOSED LBS OPENED DS CLOSED DS OPENED ES CLOSED ES OPENED RACKED IN CB CLOSED RACKED IN CB OPENED RACKED OUT CB CLOSED RACKED OUT CB OPENED GARDU PORTALTIANG GARDU TEMBOK/BESI CUT OUT FUSE GENERATOR PBO
SYMBOL
REMARK
Busbar s color, filled ' Busbar s color, blank ' Feeders colorfilled , Feeders colorblank , Feeders color Feeders color Feeders colorfilled , Feeders colorblank , Feeders color Feeders color Feeders colorfilled , Feeders colorblank , Feeders colorfilled , Feeders colorblank , Feeders color Feeders color Feeders color Feeders color
TRANSF 2 WINDINGS .
Feeders color
TRANSF 3 WINDINGS .
Feeders color
REACTOR
Feeders color
CAPACITOR
Feeders color
VOLTAGE STATUS :
LIVE DEAD
182
WARNA TAMPILAN
Tabel 6 berikut ini menjelaskan mengenai warna tampilan yang berlaku untuk monitor dan layar tayang.
Tabel 6. Warna tampilan
URAIAN
WARNA
Single line diagram 500 kV Single line diagram 275 kV Single line diagram 150 kV Single line diagram 70 kV Single line diagram 30 kV Single line diagram 20 kV Single line diagram 12 kV Single line diagram 6 kV Single line diagram 0.4 kV All devices Invalid device Device saat loss connection (RTU out of poll) Background color Ground color Kondisi tidak bertegangan Perubahan status karena gangguan Perubahan status karena local dari gardu induk Perubahan status karena remote dari dispatcher Telemetering Invalid telemetering Telesignal Alarm
Biru Biru-muda Merah Kuning Hijau Coklat Abu-abu Merah muda Hijau-muda Warna Busbar Ungu dan perubahan simbol Oranye Hitam Biru-tua Putih Frame CB warna merah, blinking Warna Busbar, blinking + karakter L Warna Busbar, blinking Putih Ungu Warna kuning, blinking
Keterangan: Untuk change of state gangguan, setelah acknowledge blinking hilang, warna merah pada frame CB mengikuti warna busbar. Untuk level tegangan yang tidak tercantum dalam tabel di atas, menggunakan warna pada single line diagram level tegangan terdekat. Warna jaringan sesuai dengan feeder colouring. Untuk detail kode warna akan dijelaskan pada SPLN mengenai kode simbol dan warna.
183
Pengelola Standardisasi: PT PLN (Persero) Litbang Ketenagalistrikan Jalan Durentiga Jakarta 12760, Telp. 021-7973774, Fax. 021-7991762, www. pln-litbang.co.id.
184