NPM 4100 (Network Power Manager) User Manual

NPM User Manual

Contents
. NPM Introduction.........................................................................................................................................3 . Function Description ....................................................................................................................................3 . Applied Range ..............................................................................................................................................3 . Product Picture & Description......................................................................................................................4 . Mounting Method .........................................................................................................................................5 . Hardware Introduction..................................................................................................................................5 1. Powering on & Self-check........................................................................................................................5 2. Current, Temperature & Humidity Monitoring.........................................................................................5 3. Water logging & Smog Monitoring ..........................................................................................................5 4. Outlet Fault Monitoring............................................................................................................................5 5. Individual Current, Total Current, Temperature & Humidity Over Limit Monitoring..5 6. Self-checking Parameter Monitoring........................................................................................................5 7. Stopping Alarm Monitoring......................................................................................................................5 8. Master / Slave NPM Configuration ..........................................................................................................5 9. Daisy-chain Connection Method ..............................................................................................................5 10. Radialized Connection Method ..............................................................................................................6 11. Software Upgrade in Hardware...............................................................................................................6 . Software Introduction ...................................................................................................................................7 1. Software Overview .... ...7 2. Software Function Description......7 3. Access Method ......8 4. HTML Interface.........8 5. NPM Daisy-chain Method...17 6. FAQ and Solution .....18

. Operation Steps.18 . Technical Parameter....18 . Quality warranty..19

NPM User Manual

. NPM Introduction
NPM can monitor, control and manage the power supply of many equipments in cabinets in data room all over the world through LAN or WAN. For meeting with the restrictions and requirements in different environment, NPM supplies many connection methods; can be connected through RJ45 in the LAN and WAN; can be accessed and controlled through standard network management station.

. Function Description
1. Monitoring: Through the display interface and knob on the NPM, can monitor the total load current, individual load current, power on/off state of individual outlet, temperature/humidity state, smog state, water logging state, door open/close state. 2. Controlling function: Controlling the power on/off of outlet; Configuring the interval when sequential power on/off. 3. Keeping the original state: Keeping the original state of each outlet when resetting. 4. User-defined alarming: the Min/Max limits value of total load current, individual outlet load current and temperature/humidity. 5. System default alarmingAlarming when the total load current over limited value, or the individual outlet load current over limited value, or individual outlet faults, or smog appears, or water logging or door opening happens. 6. Multi-alarming ways: The running indicator flashes and the buzzer alarms on the NPM controlling panel; the problem displays (flash) on the web managing interface and the PC buzzer alarms; automatically send e-mail to system administrator; SNMP sends alarm information. 7. Daisy-chain functions: can be daisy-chain connected at most 10 PCS using serial or radicalized connection method. 8. User management: User right configuration 9. Access method: through IE (as Web), SNMP or Telnet (other command lines console) to access and control. 10. Support multi-user operation system and software upgrade.

. Applied Range
1. NPM series products can be applied to server cabinet, network cabinet etc. 2. The socket quantity (12, 16, 20, or 24) and socket standard of NPM vertical series products can be selected. 3. NPM series products conform to RoHS instruction, suitable for 110VAC and 220 VAC power supply, can meet with the customers different requirements all over the world.

. Product Picture & Description


3

NPM User Manual

1. Mounting hole 2. Display the address and value of outlets 3. RUN: operation indicator 4. M/S: master/slave NPM indicator 5. OUTLET No.1: select outlet address (1-8way) 6. OUTLET No.2: Work with OUTLET No.1 to select the outlet address (adds 8 ports or reduce 8 ports) 7. RESET: master or slave NPM selection; reset button 8. Water: for connecting with water logging sensor 9. Smog: for connecting with smog sensor 10. Port2RS485 spare port 11. ND4101E12162product model 12. Current consumption meter 13. Voltage module 14. NET: if you want to control NPM through network, this port is used to connect with the RJ45 port of the PC, HUB, router or exchanger 15. SER: for daisy-chain 16. LINK: when daisy-chain many NPM, this port is connected with the SER port of the next NPM 17. Port1: the software upgrading port in hardware 18. Door1 & Door2: for connecting with door opening sensor 19. T/H1&T/H2&T/H3: for connecting with temperature/humidity sensor 20. Socket quantity is 24 at most 21. Mounting hole

NPM User Manual

. Mounting Method
Vertical Installation.

. Hardware Introduction
1. Powering on & Self-check The buzzer will make a sound when NPM is connected with AC power source, the panel LED is on and sequentially display (for example: ( (it means digitron is normal, any different display is fault), software version number ), serial number (For example: ), products series number

), baud rate (for example:

),socket quantity(for example:

), finally display the OUTLET No.1 and its value, and the running

indicator flashes, M/S indicator on means this NPM is master and off means this is slave NPM. 2. Current, Temperature & Humidity Monitoring OUTLET No.1 and OUTLET No.2 are used to monitor the relative outlet value (OUTLET No.2 has the function of adding 8 port or reducing 8 port when display). 3. Water logging & Smog Monitoring 3.1 When the water logging sensor monitoring the water, NPM screen displays same time. 3.2 When the smog sensor monitoring the smog, time. 4. Outlet Fault Monitoring When one outlet fault (For example: A1), the NPM screen will display relative fault (for example: the buzzer alarms at the same time. 5. Individual Current, Total Current, Temperature & Humidity over Limit Monitoring 5.1 When individual load current, total load current, temperature & humidity value are lower than limited minimum, the NPM screen displays as A.1 (that means the NO1 outlet is lower) 5.2 When individual load current, total load current, temperature & humidity value are higher than limited maximum, the NPM screen displays as A.1.. (that means the NO1 outlet is higher) 6. Self-checking Parameter Monitoring Make the OUTLET N0.1 display self-checking parameter for one minute. 7. Stopping Alarm Monitoring Click the RESET button to stop alarm for one minute (When NPM4101 has alarm information, the knob is not
5

and the buzzer alarms at the

NPM screen displays

the buzzer alarms at the same and

, and

, then press reset button, the NPM screen sequentially display the NPM

NPM User Manual


available, you have to stop the alarm for one minute then you can check other information. But if you dont modify the fault, it still alarms after one minute until you have modified the fault.) 8. Master / Slave NPM Configuration Press the RESET button for 10-13 seconds, the indicator of M/S on indicates the NPM is the master NPM; Press the RESET button for 5-8 seconds, the indicator of M/S off indicates the NPM is the slave NPM. Account the time please refer to the RUN indicator (T= 2S) 9. Daisy-chain Connection Method

9.1 Each NPM owns the sole serial NO. different from others which have been locked before leaving factory and can not be changed. 9.2 Configuring one master NPM and the others are slave NPM, can be daisy-chain 10 PCS NPM at most. 9.3 One end of the network wire connects to the LINK port of the master NPM, the other end connects to the SER port of the first slave NPM, then use one end of another wire connects to the LINK port of the first slave NPM, the other end connects to the SER port of the next slave NPM. Use the same way to connect other slave NPM. 9.4 One end of the network wire connects to the net port of the PC; the other end connects to the NET port of the NPM, then through IE to access. (Details please refers to the software introduction) 10. Radialized Connection Method

10.1 Configuring one master NPM and the others are slave NPM, can be daisy-chain 10 PCS NPM at most 10.2 One end of the network wire connects to the net port of the PC; the other end connects to the NET port of
6

NPM User Manual


the NPM 10.3 One end of the network wire connects to the LINK port of the master NPM, the other end connects to the RJ45 port of the HUB (special HUB for NPM daisy chain must from our company) 10.4 Use the end of another network wire connects to another in/out port of the HUB, the other end connects to the SER port of the slave. Each in/out port of HUB connects to the SER port of the slave NPM, can daisy-chain 10pcs at most. 10.5 Through IE to access (Details please refers to the software introduction) 11. Software Upgrade in Hardware

11.1 We will provide you the file of software upgrade 11.2 Please open the software upgrade file the software 11.3 Operate this software after installation, see the following picture:

and please save it in your PC then double click this file to install

11.4 The RJ45 end of the signal wire for upgrade software (special wire, it must from our company) inserts to the PORT1 on NPM, the other DB9 inserts to the RS232 port of PC

11.5 Please select the correct series port in

, make other selection according the picture

11.6 Click pane

in

, add the file

to the

NPM User Manual


11.7 Power on the NPM 11.8 Click , it will show when read successfully; if fails, please check the

connection wire and the communication port 11.9 Click , it will show when erase succeeds; If fails, please

check the connection wire and the communication port 11.10 Click , it will show when uploading the file succeeds; if fails,

please check the connection wire and the communication port 11.11 Power off the NPM 11.12 Power on the NPM, the panel will show the new version, the software upgrades successfully and then it can work normally.

. Software Introduction
1. Software Overview This software is embedded into the SCM and connected with NPM through internet to manage the equipment. It has the IE browser access method, WEB management interface, and multi-user operation system, compatible with different kind network connection. It can help NPM to meet the strong functions of SNMP, timely monitor, control the network equipment. After connect with the LAN or WAN through RJ45 port successfully, the administrator can monitor, control and manage many pieces power equipments in the cabinet all over the world through the software; adopt SNMP protocol to meet simple network management. Support sensor monitoring, Such as: temperature/humidity sensor, door open sensor, water logging sensor and smog sensor. 2. Software Function Description 2.1 Basic function description 2.1.1 Support the IE (Internet Explorer) browser access method, WEB interface and multi-user; 2.1.2 Network configuration, modify IP, subnet mask, gateway, DNS; 2.1.3 Support remote network monitoring, controlling and managing; 2.1.4 Support 10pcs NPM daisy-chain, configuration and management centralized; 2.1.5 Support monitoring individual load current and total load current; 2.1.6 Support controlling power on/off of individual outlet or several outlets at one time; (LED shows power on/off state)

NPM User Manual


2.1.7 Support resetting individual outlet or several outlets; 2.1.8 Support defining limit value of individual outlet load current, group outlet load current and total load current; 2.1.9 Support checking the total voltage, group current consumption and total current consumption 2.1.10 Support timing power on and power off the individual outlets 2.1.11 Support inquiring the alarm record 2.1.12 Keep the original state of outlets after reset; 2.1.13 Support defining limit value of temperature/humidity; 2.1.14 Monitor the state of temperature/humidity, smog, water and door open sensors in the cabinet; 2.1.15 Support sound, e-mail and SNMP alarm function 2.2 Advanced function description 2.2.1 Examine the information of NPM version, CPU capacity, and software run time and hardware address; 2.2.2 HTTP/SSL configuration information; 2.2.3 SNMP network management function; 2.2.4 Support the software system upgrade function; 2.2.5 Support the hardware system upgrade function; 2.2.6 Add/delete user, configure the user property and edit the user information etc; 2.2.7 NPM system reset 3. Access method 3.1 IE (Internet Explorer) browser access method 3.1.1 User open the IE (Internet Explorer) on the computer which connects with the network, enter the IP address of NPM to access, then monitor, control and manage the power supply of equipment which connect with the NPM 3.1.2 Default IP: 192.168.1.163 3.1.3 User name: clever; password: clever 3.1.4 The recommended computer display resolution is 1024*768; 3.2 SNMP access method 3.2.1 User selects the Enabled at SNMP Agent dropdown box list on the SNMP page and configures other information 3.2.2 Click Applybutton to submit and save configuration 4HTML interface HTML interface includes three parts: NPM system information interface, user guide menu, main controlling interface;
9

NPM User Manual


NPM system information interface: company Logo, company website, the IP of current NPM User guide menu: show the users login name, web interface to access, guide user to finish operation quickly and conveniently. Current User Name Basic function interface

Advanced function interface

Main page shows NPM current data, NPM series and version, the individual output controlling menu, total controlling menu, the individual output name, the individual load current, the total load current of each NPM, the sensor information of every NPM and other configurations. 4.1 Login method A. Open IE (Internet Explorer) browser and input the IP address, then input login name and password on the login frame, click yes button to enter the NPM system B. User has three chance to login, if the login name and password are continuously wrong for three times, the system will automatically login out; user have to repeat the operation of step A. 4.2 OUTPUTS controlling, see the picture below:

10

NPM User Manual

A. This interface is the NPM power controlling interface, which is corresponding to Device Control on the guide menu, click it then you can open this interface B. The submenu of Select Device is the daisy-chain NPM selecting menu, user select the NPM on the menu and open the NPM power controlling interface to manage each NPM. C. Interface shows the current NPM name, version and series. D. Interface shows the individual outlet name, the load current and power on/off state of this individual outlet; the drop-down menu of each outlet is its controlling menu, user select the ON OFF Reboot, then click the Apply button to control this individual outlet; user also can select ONOFFReboot of many individual outlets then click Apply button to control many individual outlets at the same time. E. Select the ON OFF Reboot item in the drop-down menu of All Outlets menu then click Apply button to

control all the outlets. F. G. H. I. J. Total Current matches with the total current of all outlets Total Voltage matches with the total voltage of all outlets Energy Meter matches with the current consumption of each group Total Energy Meter matches with the total current consumption The detailed page information are as the following table: NO. Output Name Current(Amps) Output Status(ON/OFF) ( power on, power off) the code NO. of individual outlet the individual outlet name the individual outlet load current the power on/off state of individual outlet

11

NPM User Manual


Control the drop-down menu of individual output

K. Click View sensors status link to check the current NPM sensors information 4.3 Sensor monitoring see the following picture

The interface is mainly used to monitor the NPM sensor state: environment temperature, environment humidity, smog, water logging and door opening state; When the temperature/humidity value exceed the defined value, the temperature/humidity value will become flashed red word to alarm. Sensor information: Sensor name, temperature/humidity value, smog, water logging, door opening state and relative data A. User selects each NPM from the drop-down menu of the daisy-chain equipment to examine the data information of each NPM sensor. B. When the sensor is not connected normally or is not connected, the sensor state shows Not found C. When the temperature/humidity value exceed the defined limit value, the temperature/humidity value will become flashed red word to alarm D. When the smog happens, the state value of smog sensor will become red flashed YES to alarm E. When the door is opened, the relative door value will show the red flashed OPEN to alarm F. When the water logging happens, the relative value will show the red flashed YES to alarm G. User can click the Refresh button any time to refresh the page to get the updated data information H. User can click the Threshold value to turn to sensor configuration interface 4.4 NPM configuration information see the following picture

12

NPM User Manual

This interface is mainly used to configure the daisy-chain NPM information, add or modify the daisy-chain NPM name, address, sequential interval, relative individual output name etc A. Select Device frame display the NPM name B. Input the NPM serial NO. on the right side of NPM Address No. frame. This serial NO. is exclusive and can not be the same as that of other NPM. Otherwise, the daisy-chain will fail. C NPM name frame is used to add NPM name, which is convenient for users management, the recommended NPM name is exclusive D. Sequence Interval frame is used to modify the interval of sequential power on. 1-24 frame is used to name the individual outlet of NPM E. The left list shows the name of current daisy-chain NPM; select any NPM to modify the relative information on the relative input frame. F. Click Apply button, save the NPM configuration information 4.5 Network configuration information

13

NPM User Manual

This network interface is used to configure NPM network information. The NPM administrator can configure the NPM IP address, subnet mask, gateway address, DNS and check the network connection state and speed and other information. A. User can use the default IP address through selecting the button of Obtain an IP address automatically B. User can configure the network information through selecting the Use the following IP address button IP Address192.168.1.n (2<n<254)

Corresponding to NPM IP address, n is an integer between 2 and 254. Subnet Mask255.255.255.0 Corresponding to NPM subnet mask, subnet mask is 255.255.255.0 when NPM IP is the third kind of IP. Default Gateway192.168.1.1 s Corresponding to NPM default gateway The NPM IP address can not be the same as the PC IP address and the NPM IP address must be in the same network segment as the PC IP address. C. Click Apply button, then power off the NPM to restart, the modified information will be valid 4.6 Timing power on/off controlling

A. User click Timing Control in the guide menu to open the HTML interface B. User can choose the daisy-chain NPM in the HTML interface and configure the timing power on and power off
14

NPM User Manual


the individual outlets C. Local Time display the users local time, NPM Clock display the NPM time, When the NPM time is not the same with the local time, user can click Setting button to modify the time D. The interface detailed information as the following table No. Output Name
ON Timing(yy/mm/dd) OFF Timing(yy/mm/dd)

Individual outlet number Individual outlet name The power on time of individual outlet The power off time of individual outlet

E. User can configure the timing power on and power off of individual outlet following the time format under the interface, and then click the Apply button, Set success information will show configuration successful 4.7 Alarm function and configuration 4.7.1 Current alarming function configuration See the following picture

F. F. User clicks the Alarm on the guide menu and then selects the Threshold Value to open relative HTML interface. G. User can defined the limit current alarm value on this interface through daisy-chain drop-down menu H. The interface detailed information as the following table NO. Output Name Current(Amps) Individual outlet number Individual outlet name Individual outlet load current

15

NPM User Manual


Overload Low limit High limit I. J. Individual outlet max load current Individual outlet minimal load current value Individual outlet maximal load current value

Total Current matches with the alarm value configuration of total current Click Apply button to submit and save the defined limit current data

4.7.2 Environment alarming function configuration A. User click the Alarm from the guide menu and then select the Threshold Value to open relative web

interface B. C. D. User can select the daisy-chain NPM from its drop-down menu Configure the temperature/humidity threshold on the Temperature/Humidity threshold setting frame The interface detailed information as the following table Name Current Temperature Low limit High limit Current Humidity Low limit High limit i. sensor name sensor current temperature value sensor minimal temperature threshold sensor maximal temperature threshold sensor current humidity value sensor minimal humidity threshold sensor maximal humidity threshold

Click Apply button to submit and save temperature/humidity sensor data

When the current value of individual output and temperature/humidity value exceed their defined alarm limit value, the NPM will make the buzzer sound to alarm and at the same time the relative current value /sensors value will become red flashed word to alarm. 4.7.3 Alarming method configuration There are three alarming method: sound alarm, e-mail alarm and SNMP Traps A. Configure the sound alarm method

Select the Enabled Sound Prompt to enable the sound alarm function, when something goes wrong, the administrator PC will sound to remind user. B. Configure the e-mail alarm method

Select the Enabled E-mail Prompt to enable the e-mail alarm function, when something goes wrong, it will automatically send an e-mail to the users defined e-mail address C. Configure SNMP Traps alarming method

4.8 Inquiry the alarm record


16

NPM User Manual

A. User can click the Alarm Logs to open the relative WEB interface; B. User can inquiry the alarm record information from the relative drop-down menu of daisy-chain NPM C. Alarm record information include: Alarm time and alarm affair description 4.9 System information see the following picture

User can check all the system configuration information of NPM on this interface A. Version number B. MAC hardware address C. Memory capacity D. Operation time 4.10. HTTP/SSL configuration information 4.10.1 HTTP function configuration A. B. C. D. User click the Web on the guide menu to open the relative page Select Enable on the drop-down menu of Server to enable HTTP function Input HTTP port number in the corresponding input frame of port. Click Apply to submit and save configuration.

HTTP protocol, hypertext transport protocols, is an application-level object-oriented protocol, because the HTTP protocol is simple and the scale of HTTP server is small, its communication speed is fast. .NPM system adopts HTTP protocol to make the system management, data traffic and controlling faster and more convenient. 4.10.2 SSL function configuration A. B. Select Enable in the Server drop-down menu to enable SSL function. Select Optional or Required in Secure Access drop-down menu to enable the unsafe HTTP and SSL

encryption HTTP interview; Select Required only to enable SSL encryption connection interview C. Click Apply button to submit and save configuration

Secure Socket Layers (SSL), used to ensure the safety of transport data when user interview NPM remotely. Using data encryption technology can ensure the data can not be intercepted and eavesdropped during network

17

NPM User Manual


transportation. Authorized user and server ensure that the data can be sent to the proper customers equipment and servers; Encrypt data to protect data from filching; maintain the data integrality, ensure the data is not changed during transportation; SSL provides two important function: authorize user and Encrypt data SSL Makes the NPM data system communication safer, network management more convenient. 4.11 SNMP function configuration The SNMP WEB page is used to set up and renovate the entire configuration to enable the SNMP function, it is also used to visit trap configuration page A. Click the SNMP in the guide menu to open the corresponding WEB page B. Select Enabled or Disabled inSNMP Agentdrop-down menu to confirm whether enable the SNMP function C. Configure the community string, input community string on the Get community frame, the string length

should be between 1 and 24 characters D. Configure SNMP calculagraph, input one trap calculagraph value in the Error Trap Repeat Time frame, the

trap calculagraph value should be between 1-65535 E. Configure trap object, input an IP address on the Trap Destination frame then click Apply button NPM support Simple Network management Protocol (SNMP), which enables administrator to use SNMP to search network information and control individual outlets through network management system. NPM system has SNMP function which include MIB I and MIB II; support remotely controlling function of the power. 4.12 Update configuration See the following picture

Administrator can upload a new version of NPM system software to NPM in the Update page, to update the NPM software system. A. User clicks the Update in the guide menu to open the corresponding WEB page. B. Administrator clicks browse button to select the updated .bin file, and then click Upload to upload this file

to the NPM. C. After finishing upload, the user must power off the NPM and reboot the NPM to complete the software updating. 4.13 User management User management page is mainly used to display, delete and edit the users information and user rights.

18

NPM User Manual


User information management See the following picture

A. Click User Manage in the guide menu to open the relative WEB page. B. This page shows all the user information of NPM system: User name, User level, control, detailed

operation etc C. Details of user management page information are as follows: User Name Level User name User lever, User level include two lever, one is senior user Administrator and the other is common user User

Control Rights

User rights editing, click Edit link to enter the user rights editing page.

Action

Detailed operation, user click Edit link to enter the user information editing page to edit user password, user lever Click Remove button to delete relative user

Senior use (Administrator) can operate all the functions of NPM system; common user (user) can only operate the basic functions of NPM system. D. Click New User link to enter new user creating page Create a new user: see the following picture

A.

When creating a user, administrator opens the new user creating page and then input a new user name on the

corresponding frame. B. Input the user password in Password frame and verified password on the Verify Passwordframe.

19

NPM User Manual


Password and verified password must be the same. C. User Level drops-down menu is the user level, Administrator is the senior user and User is the

common user. D. Click Apply button to submit data and the new user creating is finished successfully.

Edit user information see the following picture

A. B.

Administrator edits user information; User Name is the current editors user name. Modify the user password in Password frame, input verified password in Verify Password frame,

Password and verified password must be the same. C. User Level drop-down menu is the user lever, Administrator is the senior user and User is the common

user and then Click Apply button to finish user information editing. 4.14 Restart system User click the Restart button at the guide menu to restart the system 4.15 Logout system User click Logout in the guide menu, then click Yes button to logout NPM system 5NPM daisy-chain 5.1 Daisy-chain method A. Firstly configure one master NPM and some slave NPM, confirm the connection is correct.( when NPM M/S indicator is on, it is on master NPM state; otherwise ,it is on slave NPM state) Master NPM configuration Slave NPM configuration NPM is on slave NPM state, press RESET button for 12 seconds, M/S indicator on means configuration is successful NPM is on master NPM state, press RESET button for 6 seconds, M/S indicator off means configuration is successful

B. Input the IP address, open the master NPM WEB system, and open Device Configuration page; C. On the NPM configuration page, input the physical address of daisy-chain NPM in the corresponding frame of

NPM Address No. to name NPM.


20

NPM User Manual


D. Click Apply button to submit and save configuration information E. Click Device Control in the guide menu, open NPM control page, then select the daisy-chain NPM in the

drop-down menu of select device. If data information is correct, the NPM daisy-chain is correct. 5.2 Daisy-chain configuration A. Daisy-chain NPM, all the physical address of daisy-chain NPM must be exclusive; B. Name each daisy-chain NPM, their names must be different to avoid confusion; 6FAQ and solution 6.1 Input NPM IP then press enter but can not see the system login frame Solution: Firstly please confirm whether the NPM IP and the PC IP connected with NPM are in the same network segment, Ping NPM IP address to confirm whether the network connection is normal; 6.2 Input user name and password on the login frame but can not enter the NPM Web interface Solution: Please confirm whether the user name and password are correct, and then submit again 6.3 Entering into NPM Web interface but can not read the NPM state; Solution: Please open the Device Configuration to check whether the NPM address on the NPM Address No. frame is correct, after confirm this address is the same as the connected NPM address, please refresh to read; If the connected NPM address is not the same as the address on the NPM Address No. frame, please input NPM address on the input frame then click Apply to save and read NPM state again.

Operation steps
1Install the NPM vertically on the fixed place
2Connect the door, water logging, smog and temperature/humidity sensors correctly 3Select connecting method according to your requirement (details in chapter Six) 4Connect the NPM plug to the AC power source, configure the master and slave NPM, open the IE browser to configure correctly. (Details in chapter Seven)

Technical parameter
No. 1 Input Performance parameter rated input voltage input terminal type cable specification cable length 125/250VAC Technical parameter 50/60HZ

IEC60309 industrial standard plug/IP44 32.5mm36.0mm 2M

21

NPM User Manual


the Max input current socket standard outlet quantity 16A32A IEC320 C13C19 12162024Vertically installation X1 LED display power on/off state of individual outlet 2 Outlet replaceable fuse fitting(optional)

Outlet safety protection

Anti-fall protection fitting

Rated outlet voltage Outlet rated current the max total load current Network port 232/485 port daisy-chain port software upgrade port Temperature / humidity sensor port Smog sensor port Water logging sensor port Door open sensor port Spare sensor port Working state Master/slave NPM state Output ,temperature/humidity address Load current, temperature/humidity value

125/250VAC 10A 16A32A 1 1 1 1 RJ45 port RJ45 port RJ45 port RJ45 port

50/60HZ

Control port

3 1 1 2 1 1 1 3

RJ11 port RJ11 port RJ11 port RJ11 port RJ11port LED LED LED

Display

LED

Load current display technology requirement

Total current

Full-scale:32A/16A Accuracy:1+2 Resolution:200mA Response time:400ms Full-scale:10A Accuracy:1+1 Resolution:100mA Response time:400ms
22

Individual load current

NPM User Manual


Temperature/hu midity technology requirement Temperature Working range-40~+124 Accuracy1Response time4s Accuracy5RHResponse time4s X288.844.4mm X3 Black 1 set 2M, blue 2M, yellow 1 setCD Temperature/humidity sensor 10 Optional fittings Sensor Smog sensor Door sensor Water logging sensor Working temperature 11 12 Environment Relative humidity ROHS 10~90% compliance 0~55

Humidity Product sizeLWH

7 8

Product size Mounting hole Case color Color Installation bracket Network connection wire

Fittings Daisy-chain connection wire User manual

Quality Warranty
The NPM warrants to be free for repairing in two years from the date of purchasing. During this period, our obligation is limited to repair, replace or return to our company for repair. If the product has been beyond the warrant for repairing time or it has been damaged by accident, negligence or misapplication, you should pay some repair charge. The above warranty does not apply to the following situation 1 The damage caused by customers incorrect or inadequate repair; 2 The damage caused by unauthorized modification or misusing; 3 The damage caused by using out of the product allowed environment. Repairing Notice: 1 If you want to return the product for repair, please make sure it packed in the bandbox or carton. The damage caused during the transportation is not warranted to repair. 2 Please give a brief description of the repairing product about the problem and its operating process. 3 The customer should pay for the returning freight, all the tariffs and taxes. 4 Please write down your name, address and the telephone number by which we can contact you at anytime.