Anda di halaman 1dari 4

Modular Terminal Blocks with Multi-Stage Surge Voltage Protection TERMITRAB

TT... are surge arresters for use in measurement and control circuits. The circuits are accommodated in 6.2 mm wide modular terminal block housings. A connection to the mounting rail is made directly via the terminal foot. The surge arresters are installed in series in front of the signal input to be protected. TT-2/2- 24DC includes protection for two conductors with common reference potential (mounting rail). TT-2-PE- 24DC includes two-conductor protection for oating signal circuits. TT-2-PE/S1-24DC includes two-conductor protection for oating signal circuits without decoupling elements.

Phoenix Contact GmbH & Co. KG 32823 Blomberg, Germany Phone +49 52 35 3-00 Fax +49 52 35 3-4 12 00 www.phoenixcontact.com Local Contact: www.phoenixcontact.com/salesnetwork

TT-2/2-24DC

Technical data
TERMITRAB, modular terminal block for the protection of two signal wires with common reference potential, for mounting on 3 End cover

Type

Order No.

Pcs. Pkt.
10

TT-2/2-24DC

28 38 17 3

D-DEK 1,5 BK

28 38 99 5

50

Technical data IEC category/VDE requirement class: Arrester rated voltage (highest cont. operating voltage) UC: Lightning test current (10/350)s: Nominal current IN at 40C: Nom. discharge surge current In (8/20)s: Core-6 Residual surge current (8/20)s: Core-6 Output voltage limitation at In (8/20)s: Core-6 Residual voltage: Core-6 Response time tA: Core-6 Resistance per path: Temperature range: Inflammability class in acc. with UL 94: Type of protection: Approvals: Based on test standards Connection: solid/stranded/AWG Insulation housing: Stripping length/screw thread: Torque: C1, C2, C3, D1 30 V DC/21 V AC 500 mA/per path 300 mA 5 kA 10 kA 42 V 70 V 1 ns 6.6 20 % - 40 C to + 85 C V2 IP 20

IEC 61643-21:2000-09, E VDE 0845 part 3-1:1999-07 0.2 mm2 - 2.4 mm2/0.2 mm2 - 2.5 mm2/24-14 PA 6.6 8 mm / M3 0.8 Nm

79,6
1 3

IN
54,6

OUT

unprotected

protected

Circuit design

PHOENIX CONTACT page 2 of 4

TT-2-PE-24DC TT-2-PE-110AC

Technical data
TERMITRAB, modular terminal block for the protection of a oating double conductor, for mounting on 3 End cover

Type

Order No.

Pcs. Pkt.
10 10 50

TT-2-PE-24DC TT-2-PE-110AC D-DEK 1,5 BK

28 38 18 6 28 58 48 3 28 38 99 5

Technical data IEC category/VDE requirement class: Arrester rated voltage (highest cont. operating voltage) UC: Lightning test current (10/350)s: Nominal current IN at 40C: Nom. discharge surge current In (8/20)s: Core-6 Residual surge current (8/20)s: Core-6 Output voltage limitation at In (8/20)s: Core-6 Residual voltage: Core-6 Response time tA: Core-6 Resistance per path: Temperature range: Inflammability class in acc. with UL 94: Type of protection: Approvals: Based on test standards Connection: solid/stranded/AWG Insulation housing: Stripping length/screw thread: Torque:

TT-2-PE-24DC C1, C2, C3, D1 30 V/21 V 500 A/ pro Pfad 300 mA 5 kA/5 kA 10 kA 44 V/ 650 V 53 V/ 650 V 1 ns/ 100 ns 3.7 5 % - 40 C bis + 85 C V2 IP 20

TT-2-PE-110AC

C1, C2, C3, D1 170 V/120 V 500 A/ pro Pfad 300 mA 5 kA/5 kA 10 kA 250 V/ 650 V 60 V/ 1 ns/ 100 ns 9.4 5 % - 40 C bis + 85 C V2 IP 20 A IEC 61 643-21:2000-09, E VDE 0845 T.3-1:1999-07 0.2 mm2 - 2.5 mm2/0.2 mm2 - 2.5 mm2/24-14 PA 6.6 PA 6.6 8 mm / M3 8 mm / M3 0.8 Nm 0.8 Nm

79,6
1 3

IN
54,6

OUT

unprotected

protected

Circuit design

PHOENIX CONTACT page 3 of 4

TT-2-PE/S1-24DC

Technical data
TERMITRAB, modular terminal block for the protection of a oating double conductor without decoupling, for mounting on 3 End cover

Type

Order No.

Pcs. Pkt.
10

TT-2-PE/S1-24DC

28 39 53 8

D-DEK 1,5 BK

28 38 99 5

50

Technical data IEC category/VDE requirement class: Arrester rated voltage (highest cont. operating voltage) UC: Lightning test current (10/350)s: Nominal current IN at 40C: Nom. discharge surge current In (8/20)s: Core-6 Residual surge current (8/20)s: Core-6 Output voltage limitation at In (8/20)s: Core-6 Residual voltage: Core-6 Response time tA: Core-6 Resistance per path: Temperature range: Inflammability class in acc. with UL 94: Type of protection: Based on test standards Connection: solid/stranded/AWG Insulation housing: Stripping length/screw thread: Torque: C1, C2, C3, D1 30 V/21 V 500 A/ pro Pfad 10 A 300 A/5 kA 10 kA 50 V/ 1500 V 80 V/ 50 V 1 ns/ 100 ns 5 m - 40 C bis + 85 C V2 IP 20 IEC 61 643-21:2000-09, E VDE 0845 T.3-1:1999-07 0,2 mm2 - 2,5 mm2/0,2 mm2 - 2,5 mm2/24-14 PA 6.6 8 mm / M3 0,8 Nm

79,6
1 3

IN
54,6

OUT

Circuit design

PHOENIX CONTACT page 4 of 4

TNR: 5124868-02 12.11.2003

Phoenix Contact 2003

unprotected

protected

Anda mungkin juga menyukai