VAC A75 Wide Body Aircraft Maintenance Hangar Tan Son Nhat Airport, Ho Chi Minh City, Vietnam Hydraulics Services
SERVICE PIT PUMP SCHEDULE Pump No Wetwell Pump No. 1 Submersible explosion proof pump 0.50 minimum 75 Wetwell Pump No. 2 Submersible explosion proof pump 0.50 minimum 75
Type Grundfos Flow rate (L/s) Estimated head (kPa) Minimum motor size (kW) Motor speed (rpm) Water temperature (oC) Pump working pressure (kPa) Mount type Minimum static deflection (mm) Pumpline material
15-45
15-45
QDC/guide rails
QDC/guide rails
Notes: 2x Submersible Pumps to be installed in dual operation mode inside of each service pit pump out station. Control panel is to alarm when a pump breaks down and switch to the other pump.
OUTDOOR SERVICE PIT 1 AND 2 PUMP SCHEDULE Pump No Wetwell Pump No. 1 Submersible pump 1 minimum 100 Wetwell Pump No. 2 Submersible pump 1 minimum 100
Type Grundfos Flow rate (L/s) Estimated head (kPa) Minimum motor size (kW) Motor speed (rpm) Water temperature (oC) Pump working pressure (kPa) Mount type Minimum static deflection (mm) Pumpline material
QDC/guide rails
QDC/guide rails
Notes: 2x Submersible Pumps to be installed in dual operation mode inside of each outdoor service pit pump out station. Control panel is to alarm when a pump breaks down and switch to the other pump.
Schedules Page 5 of 23
VAC A75 Wide Body Aircraft Maintenance Hangar Tan Son Nhat Airport, Ho Chi Minh City, Vietnam Hydraulics Services
OILY SEWER PUMP FOR DISCHARGE FROM GRATED TRENCH SCHEDULE Pump No Wetwell Pump No. 1 Submersible explosion proof pump 1.5 minimum 200 Wetwell Pump No. 2 Submersible explosion proof pump 1.5 minimum 200
Type Grundfos Flow rate (L/s) Estimated head (kPa) Minimum motor size (kW) Motor speed (rpm) Water temperature (oC) Pump working pressure (kPa) Mount type Minimum static deflection (mm) Pumpline material
15-45
15-45
QDC/guide rails
QDC/guide rails
Notes: 2x Submersible Pumps to be installed in dual operation mode inside of the oily sewer pit pump out station. Control panel is to alarm when a pump breaks down and switch to the other pump.
OUTSIDE SERVICE PIT 1 AND 2 PUMP SCHEDULE Pump No Wetwell Pump No. 1 Submersible explosion proof pump 2 minimum 100 Wetwell Pump No. 2 Submersible explosion proof pump 2 minimum 100
Type Grundfos Flow rate (L/s) Estimated head (kPa) Minimum motor size (kW) Motor speed (rpm) Water temperature (oC) Pump working pressure (kPa) Mount type Minimum static deflection (mm) Pumpline material
15-45
15-45
QDC/guide rails
QDC/guide rails
Notes: 2x Submersible Pumps to be installed in dual operation mode inside of the outside service pits 1 and 2. Control panel is to alarm when a pump breaks down and switch to the other pump.
Schedules Page 6 of 23
VAC A75 Wide Body Aircraft Maintenance Hangar Tan Son Nhat Airport, Ho Chi Minh City, Vietnam Hydraulics Services
SAFETY AREA PUMP SCHEDULE Pump No Wetwell Pump No. 1 Submersible explosion proof pump 0.5 minimum 50 Wetwell Pump No. 2 Submersible explosion proof pump 0.5 minimum 50
Type Grundfos Flow rate (L/s) Estimated head (kPa) Minimum motor size (kW) Motor speed (rpm) Water temperature (oC) Pump working pressure (kPa) Mount type Minimum static deflection (mm) Pumpline material
15-45
15-45
QDC/guide rails
QDC/guide rails
Class 12 UPVC
Class 12 UPVC
Notes: 2x Submersible Pumps to be installed in dual operation mode inside of each safety are pit pump out station. Control panel is to alarm when a pump breaks down and switch to the other pump.
Schedules Page 7 of 23
VAC A75 Wide Body Aircraft Maintenance Hangar Tan Son Nhat Airport, Ho Chi Minh City, Vietnam Hydraulics Services
COLD WATER BOOSTER PUMP SCHEDULE Pump No Cold Water Pump No. 1 CWP1 Grundfos 3.5 500 Cold Water Pump No. 2 CWP2 Grundfos 3.5 500
Type Flow rate (L/s) Estimated head (kPa) Minimum motor size (kW) Motor speed (rpm) Water temperature (oC) Pump working pressure (kPa) maximum Mount type Minimum static deflection (mm)
15-20
15-20
Floor mounted
Floor mounted
Schedules Page 8 of 23
VAC A75 Wide Body Aircraft Maintenance Hangar Tan Son Nhat Airport, Ho Chi Minh City, Vietnam Hydraulics Services
10
COLD WATER FILTRATION & UV TREATMENT FOR TANK RE-CIRCULATION LINE Specification Grundos 316 s/s circulating pump Estimated Head 150kpa Flow Rate (l/s) Minimum
Equipment Pump
Bag Filtration
2 x WFL BPG 2C 316 2 BSP 316 L Stainless Steel Bag Housing Filter bags to be 5 Micron
UV Treatment
Schedules Page 9 of 23
VAC A75 Wide Body Aircraft Maintenance Hangar Tan Son Nhat Airport, Ho Chi Minh City, Vietnam Hydraulics Services
^
FU2
11
COLD WATER FILTRATION SCHEDULE Filter No Filtration Unit No 1 90 micron 600 FU1 Filtration Unit No 2 90 micron 600
Turbidity and suspended matter removal (down to) Maximum operating pressure (kPa) Maximum test pressure of system (kPa) Minimum operating inlet pressure (kPa) Maximum continuous flow Rate (l/s) Water temperature (oC) Maximum power requirement (kW) Mount type
15-20
15-20
Floor
floor
Notes: Water filters to be installed on the outlet side of the pump in a dual configuration. Filters to be 2x BWT RF multipur DN 80mm auto backwash filters complete with 90 micron screen 316 stainless steel. Electronic timer pressure differential switches pressure gauges with BMS voltage free contacts for power failure monitoring. Filter is capable of 10L/sec.
Schedules Page 10 of 23
VAC A75 Wide Body Aircraft Maintenance Hangar Tan Son Nhat Airport, Ho Chi Minh City, Vietnam Hydraulics Services
12
HOT WATER PUMP SCHEDULE Pump No Hot Water Circulating Pump No 1 HWCP1 Grundfos B series Inline 0.1-0.2 Hot Water Circulating Pump No 2 HWCP2 Grundfos B series Inline 0.1-0.2
Type Flow rate (L/s) Operating pressure (kPa) Minimum motor size (kW) Motor speed (rpm) Water temperature (oC) Test pressure of system (kPa) Mount type Minimum static deflection (mm)
65
65
Notes: 2x circulating pumps to be installed per hot water plant. 2x pumps to be installed to allow for continual operation during breakdown and maintenance.
Schedules Page 11 of 23
VAC A75 Wide Body Aircraft Maintenance Hangar Tan Son Nhat Airport, Ho Chi Minh City, Vietnam Hydraulics Services
13
LEVEL CONTROLLER PROBE SCHEDULE Multitrode Multisensored probes as follows: No. - 0.2/1/10M single sensor for hi-lo alarm only - 0.5/3/10M - 1.0/10/10M - 1.5.10/10M - 2.0/10/10M - 2.5/10/10M - 3.3/10/10M (special)
Notes: Level sensor to be installed in 2000L Hazardous Waste Pit. High level alarm to be connected to flashing light and BMS (Connection by Others).
Schedules Page 12 of 23