ENCLOSURE FANS MODIFICATION PROPOSAL Prepared by: Khaled Al Raies

Contents: 1. Proposal Study Case a. Proposal Number 1 b. Proposal Number 2 2. Current TPD396_1 Enclosure Vent Fan DP (Flow) Transmitter Monitoring Routine 3. Enclosure Fans Behavior Routine 4. Current TPD396_2 (Enclosure Pressure Monitor) Routine 5. First Proposal for TPD396_1 Enclosure Vent Fan DP (Flow) Transmitter Monitoring Routine 6. Second Proposal for TPD396_1 Enclosure Vent Fan DP (Flow) Transmitter Monitoring Routine

1|P a g e

Proposal Study Case


Proposal Number_1

This proposal suggests voting between both DP transmitters TPD396_1 and TPD396_2 to ensure that we have a real drop in the enclosure pressure. At that case, once Turbine Enclosure Vent Fan DP (Flow) reaches 0.35 inH2O and the enclosure pressure transmitter reaches 0.3 inH2O, the following would happen: 1. Turbine Enclosure Vent Fan Failure (AL_B596_1_Fail) in case Vent Fan 1 was selected. 2. The PLC Controller will switch to the second fan B596_2 after stopping the first one. 3. In case the second fan could not achieve the required flow after 30 seconds (Turbine Enclosure Vent Fan DP (Flow) is still below 0.35 inH2O) and enclosure pressure transmitter is still below 0.3 inH2O, this will annunciate Turbine Enclosure Vent Fans 1 and 2 Failure.

TPD396_1

TPD396_2 Turbine Enclosure Vent Fans 1 and 2 Failure

Follow the Link to the TPD396_1 routine modification

2|P a g e

Proposal Number 2

This proposal suggests voting between both DP transmitters TPD396_1 and TPD396_2 to ensure that we have a real drop in the enclosure pressure. At that case, once Turbine Enclosure Vent Fan DP (Flow) reaches 0.35 inH2O and the enclosure pressure transmitter reaches 0.25 inH2O, the following would happen: 1. Turbine Enclosure Pressure Low (AL_TPD396_2_L) will be annunciated on the HMI. 1. Turbine Enclosure Vent Fan Failure (AL_B596_1_Fail) in case Vent Fan 1 was selected. 2. The PLC Controller will switch to the second fan B596_2 after stopping the first one. 3. In case the second fan could not achieve the required flow after 30 seconds (Turbine Enclosure Vent Fan DP (Flow) is still below 0.35 inH2O) and enclosure pressure transmitter is still below 0.25 inH2O, this will annunciate Turbine Enclosure Vent Fans 1 and 2 Failure.

TPD396_1

TPD396_2 Turbine Enclosure Vent Fans 1 and 2 Failure

Follow the Link to the TPD396_1 routine modification


3|P a g e

Current TPD396_1 Enclosure Vent Fan DP (Flow) Transmitter Monitoring Routine

4|P a g e

5|P a g e

6|P a g e

Enclosure Fans Behavior Routine

7|P a g e

8|P a g e

9|P a g e

10 | P a g e

Current TPD396_2 (Enclosure Pressure Monitor) Routine

11 | P a g e

12 | P a g e

13 | P a g e

First Proposal for TPD396_1 Enclosure Vent Fan DP (Flow) Transmitter Monitoring Routine

14 | P a g e

15 | P a g e

16 | P a g e

Second Proposal for TPD396_1 Enclosure Vent Fan DP (Flow) Transmitter Monitoring Routine

17 | P a g e

18 | P a g e

19 | P a g e