Features
q Simple, robust construction q Small size q Wide range of settings q Proven design q Circuit breaker tripping capability
Types Available
MCAG 11 Fixed current setting MCAG 12 Variable current setting in seven equal steps by means of a plug bridge MCAG 13 Continuously adjustable by a knurled knob against a calibrated scale MCAG 31,32,33 These are the respective triple pole versions
Application
The relays are designed for instantaneous phase or earth fault protection, instantaneous high set overcurrent protection. Instantaneous high set overcurrent relays are used to rapidly clear heavy short circuits which can occur near power sources, where inverse time trip and alarm contacts are paralleled with those of the inverse time overcurrent relay.
Description
The relays are attracted armature units of simple and robust construction, such that the units are highly reliable and virtually maintenance free.
Case earth
1 3 5 13 2 4 6 14
21
22
28
Notes 1 (a)
27 28
CT shorting links make before (b) & (c) disconnect Short terminals break before (c) Long terminals
(b) (c)
Case earth
1 3 5 13 2 4 6 14
17 19 21 23 25 27
18 20 22 24 26 28
CT shorting links make before (b) & (c) disconnect Short terminals break before (c) Long terminals
A B C
P2
P1
A B C
P2
See Note 1
S2 S1
P1
A C B Phase rotation
23 24 25 26 27 28
Case earth see Note 2 Case earth see Note 2 Note 1 CT connections are typical only 2 Earthing connections are typical only MCAG
23 1 3 2 4
Alarm Trip
24 25 26 27 28
MCAG
1 3 2 4
Alarm Trip
12
10
Operating time ms
10
Technical Data
Coil ratings Continuous Short time ratings (3s) MCAG 11,12 2 x any current setting MCAG 13 1.5 x minimum current setting MCAG 11 MCAG 12 MCAG 13 40 x setting current 20 x setting current 10 x maximum setting for setting currents up to 20A, and 4 x maximum setting for setting currents above 20A 0.5VA 0.7VA 1.4VA at lowest setting 18VA at highest setting
Burdens
Current settings MCAG 11 MCAG 12 Current ranges in amps ac Fixed settings up to 20A ac Adjustable settings in seven equal steps over a 4:1 range 0.05 0.2 0.1 0.4 0.15 0.6 0.2 0.8 0.25 1.0 0.3 1.2 0.4 1.6 0.5 2.0 0.8 3.2 1.5 6.0 2.5 10.0 Continuously adjustable over a 4:1 range 0.05 0.2 4 16 0.1 0.4 5 20 0.2 0.8 8 32 0.25 1.0 10 40 0.4 1.6 20 80 0.5 2.0 25 100 1.0 4.0 40 160 1.5 6.0 50 200 2.0 8.0 2.5 10.0 Continuously adjustable over a 2:1 range
MCAG 13 dc
Accuracy
All relays are fitted with two pairs of self reset contacts. 2 make or 1 make 1 break
Normally open contact are rated as follows Make and carry continuously AC 1250VA with maxima of 5A and 660V 1250W with maxima of 5A and 660V Make and carry for 0.5s 750VA with maxima of 30A and 660V 7500W with maxima of 30A and 660V Break 1250VA with maxima of 5A and 660V 100W resistive 50W inductive with maxima of 5A and 660V
DC
The make and carry for 0.5s rating of a normally closed contact is 3750VA with maxima of 15A and 660V Durability Loaded contact 10,000 operations minimum Unloaded contact 100,000 operations minimum Operation indicator A hand reset operation indicator is fitted as standard Typically less than 10ms at 5 x Is. See Figure 5 Typically less than 50ms from 5 x Is to zero 50 or 60Hz 47 51Hz or 57 61Hz
Operating times
Resetting times
Frequency Frequency range High Voltage Withstand Dielectric Withstand IEC 255-5:1977
2kV rms for 1 minute between all terminals and case earth. 2kV rms for 1 minute between terminals of independent circuits including contact circuits, with terminals on each independent circuit connected together. 1kV rms for 1 minute across open contacts of output relays.
Three positive and three negative impulses of 5kV peak, 1.2/50s, 0.5J between all terminals and all terminals and case earth.
Electrical Environment EMC Compliance 89/336/EEC Compliance with the European Commission Directive on EMC is claimed via the Technical Construction File route. Generic Standards were used to establish conformity.
EN50081-2:1994 EN50082-2:1995 Atmospheric environment Temperature IEC 255-6:1988 IEC 68-2-1:1990 IEC 68-2-2:1974 Humidity IEC 68-2-3:1969 Enclosure Protection IEC 529:1989 Mechanical environment Vibration IEC 255-21-1:1988
Storage and transit -25C to +70C Operating -25C to +55C Cold Dry Heat 56 days at 93% RH and 40C IP50 (dust protected)
Response Class 1
45
4 holes 4.4
13 24
168
159
177
157 max.
Reset
51
Flush mounting
All dimensions in mm
Cases
MCAG 11, 12, 13 MCAG 31 MCAG 32, 33 Size 2 Size 4 Size 6
168 159 97
4 holes 4.4
52 23.5
177
157 max.
Reset
103
Flush mounting
11
All dimensions in mm
149
4 holes 4.4
103.6 24
168
159
157 max.
Flush mounting
11
All dimensions in mm