To Read and Download all our Products catalogs: http://www.scribd.com/sunil_jha To Read and Download Online our MV-VFD Catalogs http://www.scribd.com/doc/63980384/MV-Drives To Watch Online Video Presentation on YouTube: http://www.youtube.com/watch?v=W2AVlS4-0SM To Read MV-VFD Presentation Online on our website: http://eaglewanlida.com/vfdpresentation.aspx To Read and Download online our relays catalog: http://www.scribd.com/doc/73143176/MMPR-620-HB-Micro-Computer-M otor-Protection-and-Monitoring-Device

Users manual for MTPR-650Hb main transformer backup protection device

Manufactured by ZuHai Wanlida Electric co Ltd, China.

Sole Distributor in India: EAGLE TECHNOLOGY


Prepared by Proofed by Approved by

Document No.WLD[K]-JY-228-2010 Date of publicationJuly, 2010 Copyright: Zhuhai Wanlida Electric Co., Ltd.

Version No.: V2.00.01

Note: Our company reserves the right to modify this manual. For any inconsistency between the product and this manual, please contact us for relevant services.

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Foreword
1. Model description
MTPR-650Hb device: microcomputer transformer low voltage side backup protection measuring and control, the structural type is Hb.

2.

References General specification for static protection, security and automatic equipment, DL 478-2001 Technical code for relaying protection and security automatic equipment, GB/T 14285-2006 Design code for relaying protection and automatic device of electric power installation, GB50062-92

3.

Caution
Negative sequence voltage involved in this series of protection is combined with phase voltageall of low voltage component depend on line voltage in compound voltage blockif one of the three line voltages is lower than low voltage setting, low voltage component will operate and unblock over current protection. Three-section over-current respectively has composite voltage block on/off words controlling on/off of each composite voltage block function.

The appearance should be inspected before power is applied, to ensure that the panel is OK without scratch, the screws are tightened, the device is grounded firmly, all screws of plug-ins are tightened and in good contact.

When power is applied, the Run indicator on the panel should flash, nixie tube displays primary measuring value in cycle and LCD displays protective, measuring value etc. in cycle.

Terminals D25D28 are DC 420mA measuring circuit, the signal must be provided by specific equipment when testing, it is prohibited to apply the signal by relay testing device.

The operation circuit in the device fits DC power only, if it is to connect with AC power, the power should be rectified and filtered. It is prohibited to plug or unplug the plug-ins when power is present, in order to avoid damage to the device. It is prohibited to do binary output test when the device is running with primary equipments.

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 1

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

1.
1.1

Product description
Scope of application MTPR-650Hb microcomputer transformer low voltage side backup protection device

applies to 110KV power system. MTPR-650Hb, MTPR-630Hb differential protection device and MTPR-640Hb microcomputer transformer high voltage side backup protection device together constitute a complete protection for a large transformer. 1.2 Function and specification 1.2.1 Protective function Three-sectionthree time limit for each sectioncomposite voltage block direction over-current protection Zero sequence voltage alarm function Bus charging protection Zero sequence current protection Overload Starting fan Block voltage regulation composite voltage block output PT failure alarm/block CT failure alarm 1.2.2 Auxiliary Function Harmonic spectrum analysis Phase display Integral energy Alarm on device self-test fault Protective settings read and modified by remote Fault recorder 2-way programmable 420mA output Provide ethernet print function(manual print setting value, manual/auto print reports). 1.2.3 Measuring and controlling function Power measurementremote measurement Voltage, current, active power, reactive power, active energy, reactive energy, power factor, power grid frequency, non-electric quantity measurement and so on Remote signal: 19 binary inputs, including: 16 for outside collection, 3-way for the internal collection 1.2.4 Communication capability

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 2

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

2 standard RS485 multipoint communication ports 2 industrial ethernet ports Supports single, dual network communication, it is fully qualified for network redundancy and backup IEC-60870-5-103 RS485 communication mode, IEC-60870-5-104 industrial ethernet communication mode standard communication protocol 1.2.5 GPS clock synchronization function

The device is able to receive GPS clock minute synchronization (or second synchronization) through RS485 differentiate voltage, and it can be done with monitoring system to accomplish GPS precise clock synchronization. 1.2.6 Device specifications

32-bit DSP microprocessor Real-time multi-task operating system and C++ program techniques, realizing online programming Double-screen display (LCD display and nixie tube display), easy for inspection 2-way 4~20mA DC quantity output, which can be set flexibly as any corresponding electric quantity (such as current, voltage, power, frequency, etc.) Collecting 2 ways of 4~20mA DC quantities for measurement of non-electric quantities, such as temperature, pressure, and realizing online monitoring Power quality analysis capabilities, complete harmonic analysis function Integration of perfect meter function, measuring function Excellent hardware interchangeability, easy user maintenance and reduced quantity of spare parts Protection output relays can be configured flexibly for user convenience Using a 6U, 19/3 standard enclosure in a rear plug-in structure; the device can be installed in site on a switchboard or combined in a centralized manner 1.2.7 Main technical specifications

Rated data
Power supplyDC/AC 86265V Operating voltageDC 220V or DC 110V AC voltage100/ 3 V or 100V AC current5A or 1A

Frequency: 50Hz Power consumption

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 3

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

DC circuit

10Wnormal operation15Wprotection operation.

AC voltage circuit0.5VA/phase AC current circuit1VA/phaseIn=5A0.5VA/phaseIn=1A.

Overload capability
AC voltage circuit1.2 times rated voltage continuous operation Measuring current1.2 times rated current continuous operation Protection current2 times rated current continuous operation 10 times rated currentallowed for 10 s 40 times rated currentallowed for 1 s

Range and error of setting value


Maximum range of setting value: Voltage component1V120V Current component0.1In20In Frequency45.00Hz55.00Hz Delay component0.00s100.00s Error of setting value Current and voltage setting value3% of setting value Frequency setting value0.02Hz Angle setting value2 Whole-group operation time (including relays intrinsic time):

Intrinsic operation time of percentage differential protection: 1.5 times the setting value not greater than 40ms. Measuring accuracy
AC current: Class 0.2 AC voltage: Class 0.2 420mA DC quantity input 1% Power: Class 0.5 Integral energy: Class 1 (active), Class 2 (reactive) Frequency: 0.02Hz SOE resolution: 2ms Pulse width of pulse quantity: 10ms

4~20mA DC quantity output: 1% Capacity of trip/closing output contact Can be connected to DC 250V8A for prolonged periods

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 4

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

GPS time synchronization error


Synchronization error2ms

Environmental conditions
Ambient temperature Operating-20+55. Storage-25+70rainproof and snow-proof rooms with relative humidity not greater than 80%, ambient air free of acid, alkaline or other corrosive and explosive gas; no excitation quality is applied at the limits, the device shall not have any irreversible change; after temperature restoration, the device shall operate properly. Relative humidity: The average relative humidity of the most humid month shall not be greater than 90%, the average minimum temperature of this month not lower than 25 and there shall be no surface condensation; at the highest temperature of +40, the average maximum humidity shall not exceed 50%. Atmospheric pressure80kPa110kPa(below relative altitude of 2km). 1.2.8 Hardware structure The device uses a 6U, 19/3 standard enclosure, with aluminum alloy casing and installed by overall embedding. The display panel is mounted in the front, and the other plug-in modules are rear mounted. From the rear view, the power, I/O, CPU and AC plug-in modules are from the left to the right.

External dimensions and boring diagram

Structural and dimensional diagram

Boring diagram for installation

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 5

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Devices fabricated on-screen steps: first release on-screen stents unfastening screws, remove the stents; installed the device on the screen from the front and push until close to the fixed plate; install the stent 2, and then stent 1, and then use fastening screw to insertion hole from rear of stent1, and then screwed into stent 2 and tighten screw; the stents from up and down are installed in the same way; use grounding screws to connect grounding line.

2.
2.1

Functional description
Three-section composite voltage block direction over-current protection This device sets up three-section over-current protection. Each has three time delays.

By setting the control word soft strap, it can be set that whether each of the protection is on or off and whether it is equipped with direction judgment( it can be set as positive or reverse), and whether it is blocked by composite voltage. Direction operating zone is -60~120when it is in positive directionsuppose U is 0the phase of I is changeable when in the opposite direction, the operating zone is the remaining 180in whichIa corresponds to UbcIb corresponds to UcaIc corresponds to Uab. Composite voltage component consists of negative sequence voltage U2(over-vlotage) and phase-to-phase low-voltage U the minimum line voltage is used .It for block over-current protection when any fault occurs. When either negative sequence voltage U2 or low-voltage U is satisfied, over-current protection can be on, otherwise, over-current protection is blocked.

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 6

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

When composite voltage operates, the device will output the signal to other side backup protection through output terminal, in order to control the over-current protection output. That is to say, besides accepting its side composite voltage block, the over-current protection can also accept other sides composite voltage block. The protection logic is
Over-current protection control word ON I> Over-current protection plate closing Directional component operating Hard plate function ON/OFF Directional block ON/OFF & Other side compound voltage block Other side compound voltage Compound voltage block ON/OFF T1 delay Protection output

T2 delay

Protection output

T3 delay

Protection output

Low voltage component operating U2>

Compound voltage output ON/OFF

Compound voltage output

shown in Fig.2-1 Fig 2-1 Operation logic of composite voltage block direction over-current protection 2.2 Zero sequence voltage alarm function

When zero sequence voltage is more than zero sequence voltage setting, the protection will operate after delay. The protection logic is shown in Fig2-2.
Zero sequence voltage alarm ON/OFF T Protection output sequence

U0>zero sequence voltage setting value

Fig 2-2 Operation logic of Zero sequence voltage alarm function 2.3 Bus charging protection Bus charging protection is the time limit instantaneous over-current protection. The protection is only on for bus charging for a short time. When the device detects its side breaker changing from trip to close, bus charging protection will be on for a short time. When the operating condition is met, the protection will trip its side breaker after set delay. The on time can be set. When the on time is over, the bus charging protection will be off. The protection logic is shown in Fig 2-3.

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 7

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Breaker position from tripping to closing T<opening time

&

Charged protection plate closing Imax>current setting value of bus charging protection

Hard plate function ON/OFF Bus charging protection ON/OFF

&

Delay

Protection output

Fig 2-3 Operation logic of bus charging protection 2.4 Zero sequence current protection When zero sequence current is more than zero sequence over-current setting, the protection will operate after delay. The protection logic is shown in Fig 2-4.
Zero sequence overcurrent protection ON/OFF

I0>zero sequence overcurrent setting value

Protection output sequence

Fig 2-4 Operation logic of Zero sequence current protection 2.5 Over-load protection Three phase A, B, C when maximum phase current is more than over-load setting, the protection will operate after delay. Protection operating logic is as Fig 2-5.
Imax>over load setting value Over load ON/OFF T Protection output sequence

Fig.2-5 Operation logic of Over-load protection 2.6 Starting fan

When a certain phase current is more than starting fan setting, the output relay will block. The protection logic is shown in Fig 2-6.
ON/OFF

I>

t/0

Protection output sequence

Fig.2-6 Operation logic of Starting fan

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 8

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

2.7

Block voltage regulation

When a certain phase current is more than block voltage when a certain phase current is more than block voltage regulation setting, the output relay will block after delay. The protection logic is shown in Fig2-7.
ON/OFF

I>

t/0

Protection output sequence

Fig 2-7 Operation logic of Block voltage regulation 2.8 PT failure alarm The criteria of PT failure differ depending on different wiring mode. When PT failure block function is on, if PT failure occurs, the device will block the complex voltage components and current direction components. The criteria of PT failure are as follows V-V wiring mode The current of the phase with the maximum current is less than the maximum load-currentuse the load-current setting. The maximum phase-to-phase voltage is less than 30V and the maximum phase current is more than 0.1In Negative sequence voltage is more than 8V, When any of the above condition is met, the device will report PT failure after delay (settable). When the failure disappears, the alarm will return. Y-Y wiring mode The current of the phase with the maximum current is less than the maximum load-currentuse the load-current setting. When |Ua+Ub+Uc|>7V and the difference between the maximum line voltage and the minimum line voltage is more than, it is considered as one-phase or two-phase PT failure When |Ua+Ub+Uc > 7V and the minimum line voltage is less than 18Vit is used for checking two-phase failure. When MAX{UabUbcUca}<7V and the maximum phase current is more than 0.1In, its considered as PT three-phase failure. When any of the above condition is met, the device will report PT failure after delay (settable). When the failure disappears, the alarm will return.

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 9

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Max{IaIbIb}<Igfh MaxU<30V & Max{Ia,Ib,Ic}>0.1*In U2>8V & V-V wiring & PT failure ON/OFF

PT failure component

| U a U b U c | 7V
|MaxU-MinU|>18V &

| U a U b U c | 7V
MinU<18V &

TPT &

PT failure operation information

MaxU<7V Max{Ia,Ib,Ic}>0.1*In &

MaxU=Max(Uab,Ubc,Uca) MinU=Min(Uab,Ubc,Uca)

Fig 2-8 Operation logic of PT failure alarm protection 2.9 signal. When in normal operationthe sum of the three phase current of each side is zero. (less than 0.1 times rated current).When one phase CT failure occursthe sum of three phase current is not zero (more than 0.1 times rated current). In order to distinguish with ground faultthe following judgment should be conducted Among the three phasesthe current of the one with the minimum current is zero. (less than 0.1 times rated current). The current of the one with the maximum current is not zero. (more than 0.1 times rated current) but less than CT failure block current. 2.10 Integral Energy Active power and reactive power are accumulated into active energy and reactive energy in real-time by software. 2.11 Fault record See the communication coding table for the protection voltage and current waveform data collected by the recording unit. CT failure alarm When CT failure function is on, if CT failure occurs, the device will send alarm

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 10

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

3.
3.1

List of parameters and setting values


System parameters Parameters Range Description

Basic parameters setting Secondary rated currentIn PT ratio CT ratio PT wiring mode 0-1 1-1500 1-5000 0-1 Set step:1factory default 0005A011A Set step:1factory default 100 Set step:1factory default 100 Set step:1factory default 000Y-Y01V-V Harmonic calculation choice corresponding reference Harmonic calculation channel choice when it is YY wring mode 0-11 00Off 1:Ia,2:Ib,3:Ic,4:I0,5:IA,6:IB,7:IC, 8:Ua,9:Ub,10:Uc,11:U0 Wave Recrod Hardword on/off Earth Mode 1/0 1/0 0-2 1/0On/Off (factory default Off) 1/0On/Off (factory default Off) 00No Earth01Earth02Res. Earth (factory default 0) D/A Channel setting

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 11

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Parameters

Range

Description Select DA12 output corresponding reference 00:No 1:IA,2:IB,3:IC,4:Ua,5:Ub,6:Uc,7:Uab,8:Ubc, 9:Uca,10:P,11:Q Voltage reference 0120V corresponding to

4mA20mA Rated 5A DA12 Channel choice Current 0-11 reference 06A corresponding to

4mA20mA Power reference 01000W corresponding to 4mA20mA. Rated 1A Current reference 01.2A corresponding to

4mA20mA Power reference0200W corresponding to 4mA20mA. DA12 Adjusting Factor 3.2 0.5-1.5 Adjust parameter of channel D/A 124-20mA

List of setting value Setting name

Range Protection On/Off

Description

Over-current 1 section protection Overcurrent 1 Over-current 2 section protection Overcurrent 2 Over-current 3 section protection Overcurrent 3 Over-current 1 section direction OC 1 Direction Over-current 2 section direction OC 2 Direction

1/0

1/0On/Off (factory default Off)

1/0

1/0On/Off (factory default Off)

1/0

1/0On/Off (factory default Off)

1/0

1/0On/Off (factory default Off)

1/0

1/0On/Off (factory default Off)

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 12

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Over-current 3 section direction OC 3 Direction Over-current 1 section compounded voltage latching OC 1 CV Lock Over-current 2 section compounded voltage latching OC 2 CV Lock Over-current 3 section compounded voltage latching OC 3 CV Lock Zero sequence alarm (ZS Voltage Alarm) Bus charging protection (Bus Charge PROT) Zero sequence over-current protection (ZS OC Protect) Overload Startup cooling Block voltage regulation (V Adjust Lock) External side composite voltage block (Other CV Lock) Composite voltage block output (CV Out Lock) PT failure alarm PT failure block CT failure alarm

1/0

1/0On/Off (factory default Off)

1/0

1/0On/Off (factory default Off)

1/0

1/0On/Off (factory default Off)

1/0

1/0On/Off (factory default Off)

1/0 1/0 1/0 1/0 1/0 1/0

1/0On/Off (factory default Off) 1/0On/Off (factory default Off) 1/0On/Off (factory default Off) 1/0On/Off (factory default Off) 1/0On/Off (factory default Off) 1/0On/Off (factory default Off)

1/0

1/0On/Off (factory default Off)

1/0 1/0 1/0 1/0

1/0On/Off (factory default Off) 1/0On/Off (factory default Off) 1/0On/Off (factory default Off) 1/0On/Off (factory default Off)

Three-section composite voltage block direction over-current protection

Overcurrent
Low voltage 10.0090.00V Set step:0.01V(factory default 90V)

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 13

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Negative sequence voltage NS Voltage Over-current 1 section current Overcurrent 1 Over-current 2 section current Overcurrent 2 Over-current 3 section current Overcurrent 3 Over-current 1 section direction OC 1 Direction Over-current 2 section direction OC 2 Direction Over-current 3 section direction OC 3 Direction Over-current 1 section delay1 T1 Overcurrent 1 Over-current 1 section delay 2 T2 Overcurrent Over-current 1 section delay 3 T3 Overcurrent 1 Over-current 2 section delay 1 T1 Overcurrent 2 Over-current 2 section delay 2 T2 Overcurrent 2 Over-current 2 section delay 3 T3 Overcurrent 2 Over-current 3 section delay 1 T1 Overcurrent 3 Over-current 3 section delay 2 T2 Overcurrent 3 Over-current 3 section delay 3 T3 Overcurrent 3

5.00-30.00V

Set step:0.01V(factory default 10V)

0.1-20In

Set step:0.01A(factory default 20In)

0.1-20In

Set step:0.01A(factory default 20In)

0.1-20In

Set step:0.01A(factory default 20In) Set step:1factory default 0


00Positive01Reverse

0-1

0-1

Set step:1factory default 0


00Positive01Reverse

0-1

Set step:1factory default 0


00Positive01Reverse

0.00-100.00s

Set step:0.01s(factory default 5s)

0.00-100.00s

Set step:0.01s(factory default 5s)

0.00-100.00s

Set step:0.01s(factory default 5s)

0.00-100.00s

Set step:0.01s(factory default 5s)

0.00-100.00s

Set step:0.01s(factory default 5s)

0.00-100.00s

Set step:0.01s(factory default 5s)

0.00-100.00s

Set step:0.01s(factory default 5s)

0.00-100.00s

Set step:0.01s(factory default 5s)

0.00-100.00s

Set step:0.01s(factory default 5s)

Zero sequence voltage alarmZS Voltage Alarm

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 14

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Zero sequence voltage setting ZS Voltage Vaule Zero sequence voltage delay ZS Voltage Time

0-200V

Set step:0.01V(factory default 120V)

0.00-100.00s

Set step:0.01A(factory default 100s)

Bus charging protectionBus Charge PROT Bus charging protection current setting (Bus Char.Current) Bus charging protection delay setting (Bus Char.Time) Bus charging protection on time (Bus Char. Open T) 0.00-15.00s 0.00-15.00s Set step:0.01s(factory default 1s) Set step:0.01s(factory default 3s) 0.1-20In Set step:0.01A(factory default 20In)

Zero-sequence over-current protectionZS OC Protect Zero-sequence over-current setting (ZS OC Vaule) Zero-sequence over-current delay (ZS OC Time) 0.00-100.00s Overload Overload current Overload time 0.1-20In 0.00-100.00s Set step:0.01A(factory default 20In) Set step:0.01s(factory default 100s) Set step:0.01s(factory default 100s) 0-100A Set step:0.01A(factory default 2A)

Starting fun Startup Cooling Starting fan current (Cooling Current) Starting fan delay (Cooling Time) 0.00-100s Set step:0.01s(factory default 5s) Block voltage regulationV Adjust Lock Block voltage regulation setting (V Adjust Value) Block voltage regulation delay (V Adjust Time) 0.00-100s PT/CT Failure CT failure block current (CT Failure Lock) CT failure delay (CT Failure Time) 5.00-100s Set step:0.01s(factory default 15s) 1-10.00A Set step:0.01A(factory default 10A) Set step:0.01s(factory default 5s) 0.00-50.00A Set step:0.01A(factory default 50A) 0.00-50.00A Set step:0.01A(factory default 50A)

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 15

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

PT failure delay (PT Failure Time) 5.00-100s Set step:0.01s(factory default 15s)

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 16

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

4.Description of binary input/output and analog quantities


4.1 Monitoring analog quantities UnderProtection Data Measuring DataIntegral Energy menu inState Display, monitor analog quantity. Press the , keys to flip over. The precision of the device has been calibrated. The protection current is calibrated at double the rated current, and the measuring current is calibrated at a time the rated current. The list and description are as follows: Analog quantity terminal Terminals D01, D02 Terminals D03, D04 Terminals D05, D06 Terminals D07, D08 Terminals D11, D12 Terminals D13, D14 Terminals D15, D16 Terminals D17, D18 Analog quantity name Protecting Phase A current(Ia) Protecting Phase B current (Ib) Protecting Phase C current (Ic) Zero sequence current(I0) Testing phase A current(IA) Testing phase B current (IB) Testing phase C current (IC) Phase A Voltage(Ua)

Testing method Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add one times the rating, displayed deviation not exceed 0.2% Add one times the rating, displayed deviation not exceed 0.2% Add one times the rating, displayed deviation not exceed 0.2% Add 50V displayed deviation not exceed 0.5% Add 50V displayed deviation not exceed 0.5% Add 50V displayed deviation not exceed 0.5% Add 50V displayed deviation not exceed 0.5% Add 10mA displayed deviation not exceed 3% Add 10mA displayed deviation not

Terminals D19, D20

Phase B Voltage (Ub)

Terminals D21, D22

Phase C Voltage (Uc)

Terminals D23, D24

Zero voltage(U0)

Terminals D25, D26 Terminals D27, D28

420mA DC input1 420mA DC input2

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 17

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Analog quantity terminal Add current to terminals D11, D12 D15, D16 according to polarity add voltage to D17, D18 D19, D20 D21, D22 according to polarity Add current to terminals D11, D12 D15, D16 according to polarity voltage to add D17, D18D19, D20 D21, D22 according to polarity 4.2

Analog quantity name

Testing method exceed 3%

Add one times rated currentadd100V Three-phase active power line voltage Change phase angledisplayed power deviation not exceed 0.5%

Add one times rated currentadd100V Three-phase reactive power line voltage Change phase angledisplayed power deviation not exceed 0.5%

Check of binary input quantity


Under Binary inputmenu inState Displaymenucheck binary input, press the

, keys to flip over. Binary input terminal B01 Binary input common terminal used to be connected with the negative pole of DC220 and DC110V external power B02 B03 B04 B05 B06 B07 B08 Breaker position Trolley operation position Trolley test position Grounded knife position Spring non-storage Other side composite voltage operation Binary input 7 Binary input can be connected to external 220V or110V DC power. Connect negative pole to terminal B01 connect positive pole to terminals B02 B13 under Binary
input menu inState Display, the input

Binary input name

Check method

state can be seen. This device also provides 24V DC power. If a self-generated power is used, terminal B14 can be connected to terminals B02 B13 under Binary input menu in State Display,the input state can be seen. For the choice of input power, please specify

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 18

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

B09 B10 B11 B12 B13 B14 C12 C13 C14 C15 C16 A17 A15 A07 A08 4.3

Binary input 8 Binary input 9 Binary input 10 Binary input 11 Binary input 12 Positive pole of self-generated DC 24V Binary input 13 Binary input 14 Charging protection strap Over-current protection strap Binary input common terminal (+24V) Manual trip binary input Manual close binary input Operation circuit failure

in the order. Factory default is external DC220V

Connect C16 to C12, C13, C14, C15, under Binary input menu in State Display, the input state can be seen.

Connect 220V to A17A19 grounding Connect 220V to A15A19 grounding Connect 220V to A20A13or A14 grounding

Check of binary output quantity

UnderOutput Test menu monitor binary output. Press the , keys to flip over. Binary output terminal Binary output name Check method B15-B16 B17-B18 B19-B20 B21-B22 B23-B24 B25-B26 B27-B28 B29-B30 B31-B32normal open B32-B33 B34-B35normal open B35-B36 A22-A23 Block voltage regulation Remote close output Device fault signal Block this side backup power Starting fan Trip this side section breaker Trip this side breaker Trip other side breaker 1 Trip other side breaker 1 Composite voltage output1 Composite voltage output 2 Enter On/Off menu, use +, -keys should to be operate. The corresponding terminals connected.

B31-B32 and B34-B35 are normal open terminals that should be closed.

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 19

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

A22-A24

Remote open output

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 20

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

4.
5.1

Operation instructions
Control panel of device

128*64 matrix LCD (The LCD will go off after a period of absence of keyboard operation; the LCD will be illuminated automatically when any key is pressed or in case of protection trip or alarm.) Signal indicator: run, communication, operation, alarm, body, fault (device fault). Circuit breaker state indication: indicating the current state of the circuit breaker (Open, Close position indication) Key pad: Cancel, -, +, Enter, Revert The 6-bit nixie tube displays the primary measuring value in real time: Ia, Ib, Ic, Uab, Ubc, Uca, P, Q, Cos(Please set the PT, CT transformation ratios properly in the System Parameters menu). The maximum display range is 99999.

NoteMeasuring IaAAMeasuring IbbA, Measuring IcCA


Voltage UabAbkVVoltage UbcbCkVVoltage UcaCAkV Active power PkW Reactive power qkvar Power factor: H 5.2 Instructions for use of key pad and LCD display During the devices normal operation, it will display the measuring current, power, time in cycle. Press the Enter key to enter the main menu, which is a multi-level tree menu. Press the , keys to move the cursor to the desired entry, press the Enter

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 21

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

key to enter this entry, and press the Cancel key to return to the next higher level of screen. If this screen is still a menu, continue to press the , key to select the desired entry, press the Enter key to enter the next level of screen, and press the Cancel key to return to the next higher level of menu. If there is no menu screen, be sure to press the Cancel key to return to the next higher level of menu. The main menu is shown at the center of the following figure, with the corresponding submenus on both sides.. The main interface displays the primary operating parameters in turn. The maximum displayed current is 6000.0A. For systems with a rated current of 5A, the set CT transformation ratio shall not exceed 2000.Primary display power unit will be MW, when the power is higher than 1000kW, otherwise it is kW
1. State display Protection Data Measuring Data Binary Input Integral Energy Phase Angle Harmonic Data DC Input Date Trip Times 4Output Test Device Failure Local Lock Startup Cooling Trip Native Trip Native SW Trip Other SW 1

Main menu 1. State Display 2. Signal Revert 3. Report Display 4. Output Test 5. SYS Parameter 6. Setting Value 7. Clock Setting 8. Password 9. Version Info
EAGLE TECHNOLOGY

Trip Other SW 2 Comp. V Out 1 Comp. V Out 2 V Adjudt Lock Remote Close Remote Trip Operate All

2. Signal Revert Enter 3. Report Display Trip Report Binary Report Event Report Report Clear

6Settingsnote 2 Protecion on/off ...... Note: See protection setting table for.

5. System Parameters Note 1 Setting Zone No. Comm. Setting B. Parameters D/A Setting Integral Energy Trip Times Clear Output matrix

8Input Password

7Clock Setting Date -- Time ::

E-mail:

Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 TypeMTPR-650Hb(Note 3 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Ver V.. Date: 20-- CRC H

Page 22

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Note 1 Basic parameters in system parameters and D/A setting are different according
to devices, see device description for details.

Note 2See protection setting table for detailed setting menus. Note 3 Corresponding to 103, 104version, program shows 103CRC, 104CRC
respectively.

State Display
State Displaymenu contains 8 submenus, protection data, measuring data, binary

input, pulse energy, phase angle display, harmonic data, DC display, switch open counting . It is described as follows

Protection Data

Ia Ib Ic Uab Ubc Uca I0 F

= = = = = = = =

A A A V V V A Hz ......

Protection CT secondary current value

PT secondary line voltage value

Zero sequence voltage Frequency

IA = A IB = A IC = A Ua = V Ub = V Uc = V P = W Q = var Cos = ......


Meas. Data E-mail:

Measuring CT secondary current value

PT secondary phase voltage value, when VV wring mode, not display Convert to PT, CT secondary active power Convert to PT, CT secondary reactive power Cosine value of the angle between voltage and current, when 90<<90 COS will be positive; when 90<<270 COS will be negative.

EAGLE TECHNOLOGY
Page 23

Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Binary Input Breaker Trolley Run Trolley Test Earth Switch Spring Other CV Input 7 Input 8 Input 9 Input 10 ......

When closed, means breaker is closed; when opened, means breaker is opened. Note: Position of breaker is relative to protective. When closed, means trolley is at operating position When closed, means trolley is at testing position When closed, means it is closed When closed, means energy not storaged

Description depends on protection device, see corresponding terminal diagram for details.

NoteIn the standard configurations, the input circuit of binary input has the connection
to an external 220VDC control power supply. When no DC control power supply or control system is available on site, but a 110VDC control power supply is available, a 110VDC control power supply may be used for direct connection through local hardware adjustment, or the 24V power supply of the device may be used as the input power supply (when the input common terminal is +24V, terminal number: B14, Terminal B01 is kept float). However, this must be specified upon ordering
Integral Energy

kWh kvh kWh kvh

The device real-time computes time accumulation of active and reactive power+ is positive- is negative.

Phase Angle

Ua=. Ub=. Uc=. Ia=. Ib=. Ic=. IA=. IB=. IC=. ......

The angles are with respect to Ua, which default value is 0. When its V V connectionUa, Ub, Uc are changed into Uab, Ubc and Uca. Protection current with respect to Ua

Measuring current with respect to Ua

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 24

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Harmonic

2nd % 3rd % 4th % 5th % ...... 11th r%

The order of harmonic from 211 is selected in system

DC Input DC1mA DC2mA External DC input 4~20mA (2-way)

Trip Times TotalTimes

Signal Revert
In the [Signal Revert] menu, press the Enter key, the signal relay and the Operation

indicator on the panel will be reset.

Report Display
The [Report Display] menu includes 4 submenus, including trip report, remote signal

report, event report and clear report. Event recording includes: device self-check fault, device setting value modification, system parameter modification and setting zone number modification, etc. The maximum events can be stored are: 50, 100, and 30. Beyond this, the latest report will overwrite the earliest one. Press the Enter key to enter the corresponding [To view xx report, please enter report number: 00] menu, and enter 0~99, press the Enter key to display the contents of that report. The screen is as follows.

Report No. --

Year, month, day Hour, minute, second and millisecond when it took place Report content description

Press key to see the specific operation value. Press the keys and to flip over.

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 25

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Operation values
Ia Ib Ic I0 U2 U0 Ua Ub Uc = = = = = = = = = ...... A A A A V V V V V

Output Test
After entering the [Output Test] menu, the correct password is required to enter the

[Output Test] menu. It displays the following


4 Output test Device Failure Local Lock Startup Cooling Trip Native Trip Native SW Trip Other SW 1 Trip Other SW 2 Comp. V Out 1 ...... Operate All Press Enter key


Press Cancel key Device fault signal On Off

(NoteAfter the signal relay closes, make sure to press Revert key or select Signal revert menu and press Enter key to revert the signal relay.When doing output test to the 6 protection outputs, the startup relay will be closed automatically. The +, - keys are used for switching between the On/Off control).

System Parameters
After entering the [SYS Parameters] menu, the correct password is required to enter

the [SYS Parameters] menu. It displays the following


5Parameters Setting Zone No. Comm. Setting B.Parameters D/A setting Integral Energy

EAGLE TECHNOLOGY
Page 26

Trip Times Clear Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 E-mail: eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Output Matrix

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Setting zone number setting: range 00~07. Communication settin


Com. Setting RS485 device address


Communication address of device 0199 00 2.4KB 01 4.8KB 02 9.6KB 03 19.2KB 0438.4KB05115.2KB

RS485 baud rate

IP address Subnet mask K W default value

Setting of basic parameters


B. parameters

Setting CT rated secondary current 005A011A Setting PT ratio11500 Setting CT ratio15000 Setting PT secondary wring mode 00 Y-Y 01 V-V Setting the harmonic analog channel to be monitored 07select 0 to quit harmonic calculation function Setting fault recorder on/off 01 select 0 to quit fault recorder function

Rating Current PT ratio CT ratio PT wring mode Harmonic Channel Wave Record ...... D/A setting

The device has two 4~20mA outputs. The DA1~DA2 adjustment factor is used to adjust the accuracy of the channel output. The DA1~DA2 channel selection is used to select the corresponding analog quantity channel (see the description of the protection device for specific reference quantities). In the accuracy test, make sure the field ground is in good contact; otherwise the accuracy might be affected. Integral energy setting The initial value of energy can be set including: positive active energy, positive reactive energy, negative active energy and negative reactive energy. Clear trip count

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 27

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Clearing statistical count of trip.

Settings
After entering the password, you can enter the [Setting Value] menu. See the

setting description of the protection device for the detailed description.

Clock Setting
A battery-back real-time clock is provided in the device, which can perform time

adjust remotely via the communication network or in-site time adjust in the [Clock Setting] menu.
7. Clock Setting Date20 Time Enter this menu and press the Enter key, the clock will stop refreshing and a cursor will appear. Move the cursor to the desired position for modification by pressing the , keys, modify to the desired value with the +, - keys. Press the Enter key to complete setting. If the Cancel key is pressed, the setting will be cancelled and the screen continues to refresh the clock.

Password
The [Password] menu is used to modify the password for entry into the Settings,

System parameters and Output Test submenus. The initial password is provided by the factory. The universal password is 1000.
Move the cursor to the desired position for modification by Input Password pressing the , keys, modify to the desired password with the +, - keys. Press the Enter key to enter the new

0 0 0 0

password setting menu as above; press the Cancel key to cancel the setting.

GPS clock synchronization


The GPS clock synchronization signal is input as rs485 differential voltage, the

device is able to receive GPS clock minute synchronization (or second synchronization). If there is GPS signal, there will be otherwise wont. The principle of GPS clock synchronization: The second pulse or minute pulse act with the monitoring system, the time base with second precision is sent by monitoring system, when the GPS second differential signal arrives, the time base is unified and the milliseconds are cleared.. Version Information In the main menu, after entering the [9. Version Info.] menu, the model, software and flashing on the bottom of cycle menu;

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 28

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

version and date of the device will be displayed. Note: For a corresponding nonstandard model, the devices displayed model does not have to be changed.

5.
6.1

Check of protection function


Check of over-current protection Over-current protection can be divided into three sections and each section can be set as On/Off. All are based on the same principle. Take the example of over-current section I, wire as Fig 6-1set over-current section I protection to on, set over-current section I direction to on and set over-current sectionI composite voltage block to on, set hard strap protection to offwhen in on, over-current protection strap C15 should be connected.

MTPR-650Hb Ia(Ib, Ic) Ia(Ib, Ic) Ua Ub Uc Ua(Ub, Uc) D1(3,5) D2(4,6) D17 D19 D21 D18(20,22) 14(16,18)
Set according to the following table. Measure the operating current and take down in the following table. When over-current section I operatesdelay has T1, T2, T3, the corresponding terminals should be connected according to output matrix. Add phase A current Ubc, add voltage 30V, voltage phase as reference check the operating zone. Add phase B current Uca, Over-current section I setting (A) 1 ln 2 ln 5 ln 10 ln Operating zone Over-current section I settingA Operating value 1ln 2ln 5ln 10ln

A01
Power supply

A02

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 29

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

add voltage 30V, voltage phase as reference check the operating zone Add phase C current Uab, add voltage 30V, voltage phase as reference check the operating zone

Operating value

Operating zone

Over-current section I setting (A) Operating value

1 ln

2 ln

5 ln

10 ln

Operating zone

Low voltage Instantaneous over-current protection setting is 5A Add current 6A 6.2 setting(V) Low voltage block value Negative sequence voltage setting( V) Negative voltage block setting

20

40

60

80

10

15

20

Check of Zero sequence voltage alarm Zero sequence voltage alarm is judged by Zero sequence voltage. Wire as Fig 6-2

set Zero sequence voltage alarm to on.

MTPR-650Hb U0 D23 A01


Power supply

U0

D24 A02

Fig 6-2

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 30

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Set according to the following table. Measure the operating current and take down in the following table. When zero sequence voltage alarm operates, the corresponding terminals should be connected according to output matrixfactory fault of output matrix is 0. Zero Zero Zero Zero 6.3 sequence sequence sequence sequence voltage voltage voltage voltage setting(V) delay(s) operating value(V) operating time(s) Check of Bus charging protection Bus charging protection is judged by the maximum phase current. Wire as Fig 6-3set Bus charging protection to on, set hard strap function to offwhen in on charging protection strap C14 should be connected. 60 5 100 4 120 2 180 1

MTPR-650Hb Ia(Ib, Ic) D1(3,5) A01


Power supply

Ia(Ib, Ic)

D2(4,6) A02

Fig 6-3
According to binary input checking method, let the breaker position B02 change from open to close. The bus charging protection is effective during on time. When exceeding on time, the bus charging protection is automatically off. Set according to the following table. Measure the operating current and take down in the following table. When over-load alarm operates, the corresponding terminals should be connected according to output matrix. Bus Bus charging charging protection protection current setting (A) 1ln 6 2 ln 5 5 ln 3 10 ln 1

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 31

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

delay setting(s) Bus charging protection on time (s) Bus Bus 6.4 charging charging protection protection operating value (A) operating time(s) Check of zero sequence over-current protection Zero sequence over-current protection is judged by zero sequence current. Wire as Fig 6-4set zero sequence over-current protection to on. 3 3 3 3

MTPR-650Hb I0 D07 A01


Power supply

I0

D08 A02

Fig 6-4
Set according to the following table. Measure the operating current and take down in the following table. When zero sequence over-current protection operates, the corresponding terminals should be connected according to output matrix. Zero Zero Zero over-current value(A) Zero over-current time(s) sequence operating sequence sequence sequence operating over-current setting (A) over-current delay(s) 1 5 2 4 5 2 10 1

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 32

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

6.5

Check of over-load protection Over-load protection is judged by the maximum phase current. Wire as Fig 6-5set

over-load to on.

MTPR-650Hb Ia(Ib, Ic) D1(3,5) A01


Power supply

Ia(Ib, Ic)

D2(4,6) A02

Fig 6-5
Set according to the following table. Measure the operating current and take down in the following table. When over-load alarm operates, the corresponding terminals should be connected according to output matrix. Over-load setting(A) Over-load delay(s) Over-load operating value(A) Over-load operating time(s) 6.6 Check of PT, CT Failure Wire as Fig 6-1simulate PT failure or CT failurethe device will send alarm signal and the alarm light will lit. The checking method of other protection functions such as starting fan, block voltage regulation, composite voltage block output is easy. We are not going to elaborate it here; users may refer to "device function" section of this manual. 5 10 10 5 15 2 20 1

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 33

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Appendix 1Device terminal diagram

POWER

I/O
B01 B02 B03 B04 B05 B06 B07 B08 B09 B10 B11 B12 B13 B14 B15 B16 B17 B18 B19 B20 B21 B22 B23 B24 B25 B26 B27 B28 B29 B30 B31 B32 B33 B34 B35 B36

CPU
Net1
D01

AC
Ia Ia' D02

D03

Ib

Ib' D04

ON OFF

Net2

D05

Ic

Ic' D06

Input 7 Input 8 Input 9 Input 10 Input 11

COM1 COM2 Run

D07

I0

I0' D08

D09

D10

D11

IA

IA' D12

A01 A02 A03 A04 A05 A06 A07 A08 A09 A10 A11 A12 A13 A14 A15 A16 A17 A18 A19 A20 A21 A22 A23 A24

Debug

Input 12 (+24V)

D13

IB

IB' D14

D15

IC

IC' D16

Power off Power off

D17

Ua

Ua' D18

Closure coil

Trip coil -WC +WC

C01 C02 C03 C04 C05 C06 C07 C08 C09 C10 C11 C12 C13 C14 C15 C16 C17 C18 C19 C20

GPSA GPSB COM1A COM1A COM1B COM1B


D23 U0 U0' D24 D21 Uc Uc' D22 D19 Ub Ub' D20

COM2A COM2A COM2B COM2B


Input 13 Input 14

D25 D26 D27 D28

DCSIn1+ DCSIn1DCSIn2+ DCSIn2-

DCS1+ DCS1DCS2+ DCS2-

Note: 1.Ia1,Ib1,Ic1 are protection currents. 2.IA,IB,IC are measure currents. 3.I0 is zero sequence current. 4.Ua,Ub,Uc,U0 are voltages. 5.DCSIn12 are 2-way 420mA inputs. 6.DCS12 are 2-way 420mA outputs. 7.COM1 and COM2 are 485 interfaces, Net1 and Net2 are ethernet ports. 8. Whether +24V on IO board is the standard configuration or not can be fixed when using internal +24V as feeder.

Terminals diagram of MTPR-650Hb microcomputer transformer backup protection measuring and control device

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Page 34

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Appendix 2Device typical wiring diagram

Breaker

Ua Ua'

Ub Ub'

Uc Uc'

U0 U0' Ia

Ia'

Ib

Ib'

Ic

Ic'

I0

I0'

IA

IA'

IB

IB'

IC

IC'

Bus voltage

Zero sequence voltage

Protection current AC plug-ins

Zero sequence current

Measuring current

Standby

DCSIn1+ DCSIn1DCSIn2+ DCSIn2-

Ethernet port Net 1 Ethernet port Net 2


Debugging port

MTPR-650Hb transformer backup protection device


Power supply +

AC plug-ins

Power supplyShielded ground Shielded ground

Power off
GPSA GPSB

COM A COM B COM B

Power plug-ins

CPU plug-ins

COM A

Operation circuit disconnected

I/O plug-ins

Trip position

Start wind cooling Start wind cooling Trip section of this side Trip section of this side Trip section of this side Trip section of this side Trip switch 1 of the other side Trip switch 1 of the other side Trip switch 2 of the other side Trip switch 2 of the other side Compound voltage output 1 Compound voltage output 1 Compound voltage output 2 Compound voltage output 2

Block voltage regulator

normally open Block voltage regulator common

Block voltage regulator

COM A COM A COM B COM B


Input 13 Input 14
Charged protection plate

Closure position Closure position monitor

normally closed

Trip coil
Trip position monitor

Closure coil

-WC
Remote control common port Remote control closure Manual closure input

WC

Input common port-

Trolley working position Trolley test position

Compound voltage of the other side

Breaker position

Input 10

Input 11

Input 12

Input 7

Input 8

Input 9

DCSOut1+ DCSOut1DCSOut2+ DCSOut2-

(+24V)

Block backup power auto-switching of this side

Input common (24V)

Block backup power auto-switching of this side

Device fault signal

Over-current protection plate

Grounded cutter position Spring energy non-storaged

Device fault signal

Remote control trip Manual trip input

+WC

WC

Note: 1.ZK(remote/local switchover switch) and KK(manual operation switch) in the diagram are installed on the plate of panel, and when using remote/local switchover switch and manual operation button of device panel, terminal A21 would be put in +KM. 2.PT secondary in the diagram is wye-connection, and when it is V V connection on site, terminals D 15,D20 would be connected with phase A of PT secondary , terminals D16,D17 with phase B of PT secondary, terminals D 18,D19 with phase C of PT secondary.

MTPR-650Hb transformer backup protection device typical wiring diagram

E-mail:

Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

WC

WC

EAGLE TECHNOLOGY
Page 35

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

Appendix 3 Operation circuit of MXPR-600Hb series device


Traditional operating circuits are started by current, while a voltage maintaining circuit realizes electric trip prevention. An anti-trip relay will be selected depending on the current of the trip/closing circuit of the circuit breaker. However, this has poor generality and can hardly be realized for circuit breakers with low trip and closing currents (such as 10KV circuit breakers from AEG Company in Germany, whose trip and closing currents are not greater than 0.2A). To simplify wiring and design finalization, and to improve the generality of the product, we offer a new operating circuit shown below..
Small bus Fuse A20

SHJ TBJ1 HBJ TBJ2 TCJ1 Jn

HBJ TBJ

DL A16

HQ

Tn3 Tn4 Protection closure

ZK

KK

A15 A24

SHJ

ZK

YHJ
A22

A19

YTJ
A23 6 ZK 8 6 KK 7 A17 Tn1 2LP

STJ

Jn
Tn2

TCJ2
A20

STJ

TCJ HWJ TWJ HWJ TWJ

DL A18 A13 DL A14 A12 A10 A08

TQ Trip output

A11 A09 A07

HWJ

TWJ

Schematic diagram of operating circuit

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Trip circuit

Manual trip

Closure circuit

1LP

Page 36

Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010

In the diagram, KK is the traditional operation switch used for manual trip/closing operation. ZK is the shift switch used for shift between local and remote control. When ZK is in the Remote position, the remote control circuit power will be connected, i.e., Terminal A22 of the device is connected to +KM, while the manual operation circuit power will be cut off and manual closing and manual trip wont work. On the contrary, when ZK is in the Local position, the manual operation circuit power will be connected, while the remote control circuit power will be cut off. Note: In the dotted frame, there is the internal circuit of the protection device. All of our devices marked with anti-trip circuit are designed according to this operation circuit. Terminals Tn1, Tn2 corresponding to protection relay Jn are determined by the corresponding protection output control word. Jn can be any one or more of Protection outputs 1-8. Whether in local control or in remote control, jump phenomenon occurs on the premise that terminal A15 of the device is always connected with +WC. After manual or remote closing, if a short-circuit fault occurs, the protection will operate to trip the circuit breaker. Though Terminal A15 of the device is connected with +WC. The closing circuit is disconnected by TBJ1. Therefore, the circuit will not be closed again. The circuit breaker jump phenomenon can be effectively avoided in this way.

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com