JAP006-D73/COM/D21/2165

CONTRACT - JAP006-D73 132/11kV PALM,JUMEIRAH S/S (4 Nos) 11kV SWITCHGEAR VT CALCULATION

A)

General Data : i) System Voltage , kV ii) System Fault current , If iii) VT manufacturer = = =

B)

Lead Resistance Calculation ( R L ) : The lead length from VT secondary to relay =

2.5 Sq.mm Cable From Manufacturer's table ,

With a size of 2.5 Sq.mm cable the lead resistance at 200C

= =

Temperature co-efficient of resistance ( a 20 ) Lead Resistance , RL at 750C For 5 Meters , R20 Therefore RL at 750C

= = = =

JAP006-D73/COM/D21/2165

JAP006-D73/COM/D21/2165

I)

11kV - IDT Incomer Circuits : VT Ratio =

Class of accuracy Vector Group Rated Burden Actual Burden On VT Secondary : 1) Secondary ( Y - Y ) :

= = =

1.1) VT Monitoring relay - MVAP 22 1.2) Power Factor Control Relay - NOVAR 315 1.3) KWhr - Prometer 1.4) BCU - REF 545 Total Burden 1.5) Lead Burden : The secondary current / phase based on the above VA burden . IVT

= = = = =

= Hence lead burden = = = Hence total connected burden =

JAP006-D73/COM/D21/2165

Required burden Burden provided by the manufacturer Hence VT Burden is adequate

= =

JAP006-D73/COM/D21/2165

II )

11kV - Outgoing Feeder Circuits With Metering : VT Ratio =

Class of accuracy Vector Group Rated Burden Actual Burden On VT Secondary : 1) Secondary ( Y - Y ) :

= = =

1.1) VT Monitoring relay - MVAP 22 1.2) KWhr - Prometer 1.3) BCU - REF 545 Total Burden

= = = =

1.4) Lead Burden : The secondary current / phase based on the above VA burden . IVT =

= Hence lead burden = = = Hence total connected burden =

Required burden Burden provided by the manufacturer Hence VT Burden is adequate

JAP006-D73/COM/D21/2165 =

JAP006-D73/COM/D21/2165

III )

11kV - Capacitor Bank Feeders : VT Ratio =

Class of accuracy Vector Group Rated Burden Actual Burden On VT Secondary : 1) Secondary ( Y - Y ) :

= = =

1.1) VT Monitoring relay - MVAP 22 1.2) Over Voltage & Under Voltage relay - 7RW600 1.3) BCU - REF 545 Total Burden

= =

= =

1.4) Lead Burden : The secondary current / phase based on the above VA burden . IVT =

= Hence lead burden = = = Hence total connected burden =

JAP006-D73/COM/D21/2165 =

Required burden Burden provided by the manufacturer Hence VT Burden is adequate

= =

JAP006-D73/COM/D21/2165

IV )

11kV - Bus section : - [ Bus VT 1 , 2 & 3 ] VT Ratio =

Class of accuracy Vector Group Rated Burden Actual Burden On VT Secondary : 1) Secondary ( Y - Y ) :

= = =

1.1) VT Monitoring relay - MVAP 22 1.2) BCU - REF 545 ( For outgoing feeders without metering ) 1.3) BCU - REF 545 Total Burden

= =

= =

1.4) Lead Burden : The secondary current / phase based on the above VA burden . IVT =

= Hence lead burden = = = Hence total connected burden =

JAP006-D73/COM/D21/2165

Required burden Burden provided by the manufacturer Hence VT Burden is adequate

= =

JAP006-D73/COM/D21/2165

CONTRACT - JAP006-D73 1kV PALM,JUMEIRAH S/S (4 Nos)

SWITCHGEAR VT CALCULATION

11kV 25 kA for 3 Sec. M/s. Tesar, Italy (for S/S J1 & J2) M/s. Risho, Japan (for S/S J3 & J4)

Meters

7.41 0.00741 0.00393

Ohms/kM Ohms/Meter

R20 [ 1 + a 20 ( T2 - T1 ) ] 0.03705 0.045 Ohms Ohms

JAP006-D73/COM/D21/2165

JAP006-D73/COM/D21/2165

11kV 3 Class 0.5 Y - Y 30 VA

110V 3

6.35 7 2 0.5 15.85

VA VA VA VA VA

Connected VA Burden / Phase 110V / 3 15.85 110V / 3 0.250 2 x IVT2x RL 2 x 0.25 2 x 0.045 0.006 VA 15.85 + 0.006 = 15.856 VA

JAP006-D73/COM/D21/2165

15.856 30

VA VA

JAP006-D73/COM/D21/2165

11kV 3 Class 0.5 Y - Y 30 VA

110V 3

6.35 2 0.5 8.85

VA VA VA VA

Connected VA Burden / Phase 110V / 3 8.85 110V / 3 0.139 2 x IVT2 x RL 2 x 0.139 2 x 0.045 0.002 VA 8.85 + 0.002 = 8.852 VA

8.852 30

VA VA

JAP006-D73/COM/D21/2165

JAP006-D73/COM/D21/2165

11kV 3 Class 0.5 Y - Y 30 VA

110V 3

6.35 0.2

VA VA

0.5 7.05

VA VA

Connected VA Burden / Phase 110V / 3 7.05 110V / 3 0.111 2 x IVT2 x RL 2 x 0.111 2 x 0.045 0.001 VA 7.05 + 0.001

7.051 VA 7.051 30 VA VA

JAP006-D73/COM/D21/2165

JAP006-D73/COM/D21/2165

11kV 3 Class 0.5 Y - Y 30 VA

110V 3

6.35 6

VA VA ( 12 x 0.5 )

0.5 12.85

VA VA

Connected VA Burden / Phase 110V / 3 12.85 110V / 3 0.202 2 x IVT2 x RL 2 x 0.2022 x 0.045 0.004 VA 12.85 + 0.004 = 12.854 VA

JAP006-D73/COM/D21/2165

12.854 30

VA VA