GENERATION CAPACITIES IN AP AS ON 31-10-10

A. AP GENCO 1 THERMAL 2 HYDAL 3 WIND TOTAL B. JOINT SECTOR 1 GAS (APGPCL) C. PRIVATE SECTOR 1 THERMAL (COAL) 2 HYDAL 3 MINI HYDAL 4 WIND 5 CO-GEN & BIO MASS 6 MINI POWER PLANT 7 OTHER ( ISO. Gas Wells+ Waste
Heat + Indust waste)

INSTALLED CAPACITY OF AP GENCO 1. THERMAL


VTPS Stage 1,2,3&4 RTPS Stage 1&2 KTPS a,b &c KTPS Stage -5 RAMAGUNDAM TPS KAKATIYA TPS 6X210 + 500 4x210 4x60 + 4x120 2X250 1X62.5 1X500 TOTAL 3X17 + 3X23 8X9 5X39 4x60 1X25 4X115 7X110 6X150 1X110 + 7X100.8 3X30 2X30 2X5 4X9 2X10 2X7.5 23 UNITS 2X0.5 2X1 TOTAL 10X0.2

MW MW MW MW MW MW MW MW MW MW MW MW MW MW MW MW MW MW MW MW

4382.5 3751.36 2 8135.86 272 0 2494.62 104.4 114.94 490.55 74.31 119.8 3398.62 899.34 46.14 339.02 221.32 1000 429.67 2935.49

2. HYDAL
MACHKUND (70%) TB DAM (80%) JURALA HES UPPER SILERU DONKARAI LOWER SILERU SRISAILAM RBH SRISAILAM LBH N SAGAR PH N SAGAR R CANAL PH N SAGAR L CANAL PH NIZAM SAGAR PH POCHAMPADU PH PENNA PH SINGUR PH PEDDAPALLI MINI CHETTIPETA MINI PALERU MINI

TOTAL D. CENTRAL SECTOR 1 RAMAGUNDAM STPS 2 MAPP ATOMIC 3 NEYVELI LIG CROP 4 KAIGA NUCLEAR 5 SIMHADRI TPS 6 TALCHER 2 PHASE
(UNIT 3,4,5,6)

TOTAL SHARE CENTRAL

TOTAL (A+B+C+D)

MW

14742

3. WIND
RAMAGIRI

TOTAL (1+2+3)

GENCO MW
1760 840 720 500 62.5 500 4382.5 84 57.6 195 240 25 460 770 900 815.6 90 60 10 36 20 15 9.16 1 2 3790.36 2

8174.86

CLASSIFICATION OF VOLTAGES
1 Low Voltage 2 Medium Voltage 3 High Voltage 4 Extra High Voltage 250 V 650 V More than 650 V & up to 33 KV > 33 KV

1.CLEARANCES along / across the road and cross country ( Refer IE Rule No 77) Clearance other than along & across the road slno Voltage Across Road Along Road
If bare conductor If insulated Conductor

1 Low & Medium 2 HV up to 11KV 3 HV above 11 KV up to 33 KV

19ft / 5.791 m 20ft / 6.096 m 20ft / 6.096 m

18ft / 5.486 m 19ft / 5.791 m 19ft / 5.791 m

15 ft / 4.572 m 15 ft / 4.572 m 17 ft / 5.182 m

13 ft/ 3.963 m 13 ft/ 3.963 m

Note : 1. For extra high voltage lines, the clearance above ground shall not less than 17 feet (5.182 m) plus 1 foot (0.30 M) for every 33 KV or part there of by which the voltage of the line exceeds 33 KV 2. The minimum clearance along or across any street shall not be less than 20 feet (6.096 m)

2.CLEARANCES from building ( Refer IE Rule No 79) slno Voltage 1 Low & Medium voltage and service line 2 a. HV up to 11KV b. HV above 11 KV up to 33 KV 3 For EHV Line ( for additional 33 KV or part there of)

Vertical clearance 8 ft /2.439 m 12ft / 3.658 m 12ft / 3.658 m 1 ft / 0.305 m *

Horizontal clearance 4 ft / 1.218 m 19ft / 5.791 m 19ft / 5.791 m 1 ft / 0.305 m *

3.CLEARANCES between lines of different voltage on same or independent supports slno Voltage Horizontal clearance 8 ft / 2.439 m 1 Between 66,33,22,11,LT or Telephone line and 66 KV lines 9ft / 2.744 m 2 Between 110,66,33,22,11,LT or Telephone line and 110 KV lines 3 Between all lines up to 220 KV or telephone lines and 220 KV lines 15ft / 4.572 m 4.CLEARANCES over the river
Minimum 10 feet ( 3.048 m) over highest Hood level for rivers which are not navigable. For navigable rivers , clearances to be fixed in relation to the tallest mast, in consultation with the conserned authorities.

5.CLEARANCES for trees


1. For EHT lines all tall trees with 40 feet (12.19 m) on either side of the line and all tree which are falling or would fall , to be cut. 2. All bush growth 20 feet (6.096 m) on either side to be completely cleared. Grafted fruit trees which will not grow tail may be left out. 3. All branches or leaves which are width 3 feet (0.914 m) from the conductors , neutral and earth wise in case of LT line shoulb be cut.

1. For EHT lines all tall trees with 40 feet (12.19 m) on either side of the line and all tree which are falling or would fall , to be cut. 2. All bush growth 20 feet (6.096 m) on either side to be completely cleared. Grafted fruit trees which will not grow tail may be left out. 3. All branches or leaves which are width 3 feet (0.914 m) from the conductors , neutral and earth wise in case of LT line shoulb be cut.

6.CLEARANCE from supporting structure of another line


1. Low or medium voltage lines 4 feet (1.218 m) 2.High voltage lines 6 feet ( 1.828 m) 3.Extra high voltage lines 9 feet ( 2.744 m)