Details Mentioned in DPR for Boiler, Turbine and Generator

1. Generator Power Factor of 0.85. 2. The Valves Wide Open capacity of the steam Turbine will be around 693MW and the Boiler Maximum Continuous Rating (MCR) will be established to match the Steam requirement at VWO conditions and the auxiliary steam requirements. 3. Once through type Steam Generator. 4. The Steam Generator shall be guaranteed to meet the requirement of turbine & auxiliary steam requirement at 100% TMCR condition. 5. The Steam generator shall be capable to cater for 105% of the steam requirement with turbine control valve wide open conditions and other auxiliary steam requirements. 6. TYPE: The Steam Generator will be of single pass(tower type) or two pass type using spiral wall (inclined) or vertical plain/rifled type water wall tubing. The steam generator will be direct pulverized coal fired, top supported, single reheat, radiant, dry bottom, with balance draft furnace the evaporator of the steam generator will be suitable for variable pressure operation from sub-critical to supercritical pressure range. 7. RATING: The steaming capacity of the steam generator (steam flow at super heater outlet) at 100% maximum continuous rating (BMCR) conditions and with rated steam parameters are as follows:

Rated Steam Pressure Parameters bar (a) At super heater approx 250 outlet At re-heater outlet Approx 45

Temperature Degree C 571 569

Flow tph 2115 1715

The exact rating of the steam generator will be finalized by the BTG supplier depending on actual requirement of the turbine. 8. CONTROL RANGE: The automatic control range of steam generator will be from 40%-100% BMCR.

STEAM TURBINE: The steam turbine system shall consists of two (2) numbers of identical steam turbine units of condensing type with single reheat and supercritical steam inlet parameters. TYPE: The steam turbine will be of single reheat, condensing type with separate HP, IP and multiple LP cylinders. The steam turbine has eight (8) uncontrolled extractions for feed water and condensate preheating. RATING: Each steam unit will conform to the following design and duty conditions: Description Output under TMCR condition Turbine throttle steam pressure Turbine throttle main steam temperature Reheat steam temperature at turbine inlet Variations in rated steam temp. & pressure Pressure drop in reheat circuit Frequency variation range Value 660 MW 242 bar (a) 566 degree C 566 degree C As per IEC 10% of HPT Exhaust (+) 3% to (-) 5%

Turbine will also be capable of operating continuously with valves wide open (VWO) to swallow 105% of TMCR steam flow to the turbine at rated steam and reheat steam parameters.

GENERATOR: Generator will be directly driven by steam turbine at 3000 rpm. The generator and its excitation system shall have a capability at least matching the declared maximum continuous rated output of the associated steam turbine, for the specified secondary cooling water temperature, at all power factors between 0.85 lagging and 0.95 leading with +3% to -5% frequency variation, terminal voltage variation of +/-5% and combined voltage & frequency variation of 5%. Generator voltage will be in the range of 21 KV or as per the manufacturers standard. Generator shall be able to satisfy transmission load reactive requirements under all reasonable anticipated operating conditions. The generator excitation system shall be

brushless type with PMG or with static excitation system or any other modern excitation system to suit the system. The generator shall be designed with water cooled stator winding, direct hydrogen cooled for rotor winding & stator core. Generator shall be supplied with hydrogen cooling system, stator water cooling system and carbon di oxide supply system for purging of hydrogen and seal oil system.