Ty p e 2 3 2
Actuator with rotation drive 15 Nm
Page:
2 3 4 10 11 - 12 13 - 14 15 16 9
Content:
General overview Summary 232, 15 Nm Technical characteristics, Type 232, 15 Nm Mounting examples Specific characteristics of continuous control Exploded drawings Notes Your way to Gruner
GR
UNER he frie t
alte dly n
rnative
Type
Torque
227
2
232
2
231
2
228
2
238
5 Nm (appr.1 m ) 15 Nm (appr.3 m ) 20 Nm (appr.4 m ) 5 Nm (appr.1 m ) 15 Nm (appr.3 m2) 8 Nm (appr.1.6 m2) 30 Nm (appr.6 m2)
Control
Tri-state On / Off Continuous (0) 2...10 VDC or (0) 4...20 mA with 500
Power supply
24 VAC/DC 230 VAC
Options
Potentiometer Auxiliary switch(es) LON Interface VAV Interface Binding clamp Form locking
Applications
Motorised control of dampers, ball and butterfly valves. Application in mixed air and shut-offer damper control. For primary HVAC air-handling and zone units. Smoke and air isolation shut-off damper control for ventilation systems Ball valve control for domestic and drinking water, condensation water, air (i.e. zone units). The actuator 231L has digital communication capabilities and can be networked with a LON-Bus system. All actuators correspond to the UL, CSA & DIN-VDE standards, CE guidelines.
= Standard = Optional
Type
Torque Control Tri-state On / Off Continuous control (0) 2...10 VDC or (0) 4...20 mA
15 Nm 15 Nm 15 Nm 15 Nm 15 Nm 15 Nm 15 Nm
Power supply
24 VAC/DC 230 VAC 4 4 4 6 6 6 8
Options
Potentiometer Feedback signal Auxiliary switch(es) Page
All actuators dispose of manual override button, a mechanical limitation of the angle of rotation and setting button for the rotation direction (cw/ccw). Actuators according to US-standards available upon demand.
Technical characteristics
Control Connecting voltage Power consumption Angle of rotation Direction of rotation Running time Torque Auxiliary switches Switching power auxiliary switch Potentiometer Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight On / Off + Tri-state 24 VAC (50/60 Hz) / DC 20% 4.5 W / 8.0 VA 0...95 changeable from outside 40...80 s @ 90 15 Nm 2, adjustable from inside 24 VAC / 5 (2.5) A, change-over switch 5 k cable 900 mm / 0.75 mm2 III IP54 (cable downwards) 140 x 75 x 58 mm -30...+50C maintenance-free 73/23/EWG, 89/336/EWG 700 g
232-024-15
Connection scheme
232-024-15-P5
Connection scheme
232-024-15-S2
Connection scheme
BU BNBK
On / Off
BU BNBK
BU BNBK
BU BNBK
2 1 3 BU BNBK
Tri-state
BU BNBK
Potentiometer
S1
S2
1 2 3 4 5 6
Auxiliary switches
m)
40 20 30 75 60 45 30 15
10
(m
)m m(
0 90
S1
S2
BU BN BK
1 2 3 4 5 6 24 VAC 5 (2,5) A
Technical drawing
232-024-15
Technical characteristics
Control Connecting voltage Power consumption Angle of rotation Direction of rotation Running time Torque Auxiliary switches Switching power auxiliary switch Potentiometer Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight Tri-state 230 VAC (50/60 Hz) 15% 3.5 W / 3.5 VA max. 95 can be selected by type of connection 120 s @ 90 15 Nm 2, adjustable from inside 250 VAC / 5 (2.5) A, normally-open contact 5 k cable 900 mm / 0.75 mm2 II IP54 (cable downwards) 140 x 75 x 58 mm -20...+50C maintenance-free 73/23/EWG, 89/336/EWG 700 g
232E3-230-15
Connection scheme (Tri-state)
232E3-230-15-P5
Connection scheme (Tri-state)
232E3-230-15-S2
Connection scheme S1 (Tri-state) S2
1 2 3 4 BU BNBK BU BNBK 2 1 3
Potentiometer
Auxiliary switches
BU BNBK
N L
N L
N L
m)
40 20 30 75 60 45 30 15
10
(m
)m m(
0 90
Technical drawing
232E3-230-15
232C-024-15
Applications
To regulate dampers, valves or other regulatory functions: sturdy drive maintenance-free torque 15 Nm position indication direction of rotation changeable from outside electromagnetic compatibility controlled
Technical characteristics
Control Control signal Y Continuous control 0...10 VDC or 2...10 VDC (standard) or 0...20 mA or 4...20 mA Feedback signal U 0...10 VDC or 2...10 VDC (standard) or 10 VDC or 15 VDC Connecting voltage Power consumption Angle of rotation Direction of rotation Running time Torque Connection Safety class Protection Dimensions Ambient temperature 24 VAC (50/60 Hz) / DC 20% 5.5 W / 7.0 VA max. 95 changeable from outside 40...80 s @ 90 15 Nm cable 900 mm / 0.75 mm2 III IP54 (cable downwards) 140 x 75 x 58 mm -30...+50C maintenance-free 73/23/EWG, 89/336/EWG 700 g
232C-024-15
Connection scheme (Continuous control)
Maintenance CE Weight
BUBN BK GY Y U
232C-024-15
1 Indication of the angle of rotation (fig. 1)
The damper position is indicated on the scale 0...90.
75
10
40 20 30 60 45 30 15
(m
m)
)m m(
0 90
ON 1 2 1, 2
1, 2 2 1 -
4, (1) 4 3, 5 3
3 3, (1) 4 4, 5
0...10 VDC 15 VDC / 5 mA 10 VDC / 5 mA Switches actually unused must be at position OFF.
The constant voltage 15 VDC can be used i.e. for the power supply of the positioner FGEB.
Technical drawing
232C-024-15
10
MOUNTING EXAMPLES
Figure 1
Direct mounting to the damper shaft by locking clamp to the damper shaft... ...and fixing by the enclosed anti-torsion bow.
Figure 2
Direct mounting by two hexagon screws M4 x 30, SW 7, if the actuator is not mounted directly on the damper.
Figure 3
Mounting if the damper is too short.
- +
232C
- +
232C
BU BN BK GY
L2 L1 max. cable length
24VAC
BU BN BK GY
(I +I ) R >
A G L max. cable length L2 L1
24VAC
transformer
R < L
transformer
DC 0(2)...10V
DC 0(2)...10V
by the actuator
by the controller
current of set valve selector actuator current cable cross section cable resistance 0,75 mm2 1 cable length cable cross section mm2 1,5 mm2 2,5 mm2 23 m 31 m 46 m 76 m max. cable length
For several actuators switched in parallel the max. cable length must be divided by the number of actuators.
BUBN BK GY
15 VDC
12
Actuator
Positioner
- +
U Input
Y Output
BU BN BK GY
+ 1
+ 3
Actuator
Positioner
- +
U Input
Y Output
BU BN BK GY
+ 1
15 VDC
+ 3
15 VDC
EXPLODED DRAWINGS
232-024-15-S2
13
232-024-15-P5
14
EXPLODED DRAWINGS
232E3-230-15 / -S2 / -P5
232C-024-15
NOTES
15
Stuttgart
A8
Mnchen
Balingen Karlsruhe
Schmberg
Freudenstadt
A81
Wehingen
B27
Gosheim Frittlingen Denkingen
Tuttlingen
Strasbourg
Rottweil B14
Schramberg Aldingen
Spaichingen
34
B27
Donaueschingen
Singen Zrich
Basel N1 N3