Anda di halaman 1dari 6

Development of Economical Analysis and Technical Solutions for Efficient

Distribution Transformers
A.F. Picanço1*, C de Salles1, M.L.B. Martinez1, P.C. Rosa1, H.R.P.M. de Oliveira2
1
Federal University of Itajubá and 2AES Sul Utility Company
Rua Cel. Rennó, 05, Itajubá, MG, Brazil, CEP 37500-050

Telephone number: +55 35 3622 3546 and E-mail address: alessandra@lat-efei.org.br

Some utilities in Brazil normally purchase stacked core


ABSTRACT: Transformers are equipments applied to transformers that are built using steel silicon grade M2 or
electrical systems to adjust voltage levels for consumption, M3 in rectangular geometry. Therefore, low density
distribution, transmission, and generation needs. Actual magnetic flux is obtained increasing the transversal section
technology indicates that they are responsible for and results in reduced no-load losses. The windings are
approximately one third of total network losses. These normally constructed using copper wiring or foils and in
losses can be accounted as power utility costs, costs to this case the increase of the mass of copper results in
society and to the environment itself. The aim of this paper reduced load losses. This also results in an increase of the
is to study the relationship between the transformer costs core window and also in the no-load losses [3-6]
and its losses. A method for collecting cost data and for The proposal of this study is to solve this contradiction
building cost surfaces - the so called “Production and Total through the analysis a set of transformer designs presenting
Cost Surfaces” is presented. The economic analysis of reduced losses. This subject has been object of study since
transformer designs considers a variation of the reference the 60´s [4-8]. The solution is to search out an optimal
data of the main constructive parameters of a standard transformer design, considering the restrictions imposed by
transformer. Therefore, changes are introduced, amongst the short circuit impedance, the daily load, the interest rate
others, in the core dimensions, such as the column and the energy price.
circumscribed area, its diameter and the yoke area. This The present study is divided, firstly in the recognition of
approach helps the power utilities to purchase equipment the problem, secondly in the construction of a set of
according to the forecast demand, decreasing the total problem solutions and thirdly, in the search for the optimal
network losses. design.

Keywords: Cost of Losses, Demand, Design, Distribution II. MANUFACTURING AND TOTAL COST
Transformer, Energy, Optimization. SURFACES

I. INTRODUCTION The manufacturing and total cost surfaces show a set of


design possibilities considering manufacturing cost and
Operational power losses of distribution transformers are total cost versus no-load and load losses. This method
basically related to the core – no-load losses and to the indicates the interaction between investment and
windings – load losses. The load losses depend on the operational costs and losses.
square of the load current during a standard daily operation The manufacturing costs consider the quantity and the
cycle. The no-load losses depend on the core magnetization price of the commodities used for building the transformer,
and can usually be considered as being constant during as defined by (1). [9,10].
standard operation.
The losses are an important parameter in the evaluation C Manufacturing = C fixed + Ccore M core + Ccopper M copper (1)
of the total transformer costs i.e. investment and operation
costs. They can lead to a reduction of the utility net Where:
economical result and can, ultimately, be considered as a CManufacturing is the manufacturing cost in US$;
“Loss to Society”. Cfixed is the transformer fixed cost in US$;
In distribution systems, transformers are responsible for Ccore is the core material cost in US$;
roughly one third of the total power losses. This is the Ccopper is the cost of copper in US$;
driving force behind the loss and cost reduction efforts [1]. Mcore is the core total mass in kg;
The aim of the harmonization of the European Union (EU) Mcopper is the copper total mass in coils in kg.
documents (HD 428 and HD538) and of the United States
(US) NEMA TP-1 and Technical Support Document The total, or operational, cost of a distribution
(TSD) [2] is the reduction of the loss costs and transformer is obtained by adding the manufacturing costs
consequently the decrease of power losses in the network. to the no-load loss costs, and to the load losses considering
These documents evaluate the capitalized costs and the a daily loading cycle, as shown by (2). [3].
efficiency of transformers considering their daily loads.
The first step in designing an efficient transformer for a C Total = C TR / Analysis + CW 0 + CWL (2)
specific region is to carefully model the supplied load. The Where:
parameters that define the load behavior are basically the CW0 is the cost of no-load losses in US$;
load, peak and factor, and the load increase rate. CWL is the cost of load losses in US$;
CTotal is the total cost of transformer in US$;
CTR/Analysis is the transformer cost in US$. Three-dimensional matrixes are built considering the
following design parameters:
The first step of this method considers variations in a) thickness of the conductor of the LV winding;
design parameters: magnetic induction density – no-load b) width of the conductor of the LV winding;
losses, LV winding current density and HV winding c) diameter of the conductor of the HV winding;
current density – load losses. Each point on the d) magnetic induction;
manufacturing surfaces - Figure 1- represents a transformer e) insulation thickness;
design. f) clamp dimensions;
g) design of the end insulation;
h) Gap between LV and HV windings.

Fig. 1 – Manufacturing cost surfaces considering variations in LV


winding current density, HV winding current density and magnetic
induction density. Fig. 3 – Total cost surfaces considering variations in LV winding
current density, HV winding current density and magnetic induction
density.
The total cost depends on the impact of the energy costs
on the no-load and load losses. The load loss costs can be
This method considers design possibilities stored in
calculated based on a parameter defined as “Time
three-dimensional matrixes (11x11x22), as in Figure 4, and
supplying the maximum rated power”, TSMP, (3) or the design surfaces as in Figure 1.
period of the day, in hours, that the transformer operates in
full load condition with the same area – “energy” – below
the load cycle profile.
Figure 2 shows the load cycle used to calculate the total
costs in this paper. The TSMP is 8.72.

2
⎛ kVAi
24

TSMP = ∑ ⎜⎜ ⎟⎟ (3)
i =1 ⎝ kVAN ⎠

Fig. 4 – Scheme of three-dimensional 11x11x22 matrix

The design surfaces allow verifying the influence of each


constructive parameter on the losses and the associated
manufacturing cost impact. Considering the current density
of the HV winding and magnetic induction as being
constant, it is possible to verify that the increase of the
thickness of LV conductor results in two opposite effects;
the decrease of the load losses and the increase the no-load
Fig. 2 – Load cycle used as an example to generate the total cost losses, effects that must be properly balanced. It is also
surface presented in Figure 3 observed that the short circuit impedance is acceptable only
for a determined thickness range of the LV conductors.
The behavior of the total cost surfaces versus losses for For this specific transformer design, the behavior of
the load cycle of Figure 2 is shown in Figure 3. short circuit impedance is as shown in Figure 5, where
variations on the current density of the HV winding, on the
III. DESIGN SURFACES: ESTABLISHING A SET OF insulation thickness and on the magnetic induction were
SOLUTIONS considered. The shape of this trend is not standard once it
depends on the transformer rated power, rate voltages and
The second step of this method is to define sets of supplied load. Therefore each specific case must be
solutions. The searching tool will try to find an optimal properly studied and analyzed.
design in these sets.
h) Variation of current density of the HV winding,
insulation thickness and gap between coils.

IV. OPTIMAL DESIGN BASEAD ON THE SURFACES

In the present study, the optimal transformer design must


present reduced loss costs. Therefore, an optimization tool
[12, 13] is applied to the design solution sets to find a
minimum cost point on a surface.
The points on the total cost surfaces represent an element
of the three-dimensional design matrixes, shown in Figure
4. The comparative and iterative procedure adopted to
search for the minimum cost point is as follows:
Fig 5 – Short circuit impedance surface versus losses
a) The first minimum cost is a random value;
b) For the iteration k, in the column j, each element
Figure 6 presents the hot-spot temperature surfaces c(i,j,k) is compared with the minimum cost value;
versus short circuit impedance and payback in years. The [c(1, j, k ), c(2, j, k ),K, c(N , j, k )]T
lowest hot spot temperature [11], which is associated to the c(i, j, k ) < C Mínimo
transformer life span, is about 137°C. The design has a
c) The search must satisfy the level of the no-load losses,
current density of the HV winding, an insulation thickness
load losses and short circuit impedance according the
and a magnetic induction 50% higher compared to a
national or utility standards in the set of solutions;
WN (i, j , k ) ≤ W N ( ABNT )
standard transformer. This, as occurs in other cases, is not
feasible, due to manufacturing and cost restrictions. Some
of the cost restrictions are well defined by the negative WTotal (i, j , k ) ≤ WTotal ( ABNT )
payback results that are associated to the solution process Z %(i, j , k ) ≤ Z % ( ABNT )
of the cost equations.
d) The payback is defined by the customer.
0 < TRI (i, j, k ) ≤ 5 years

In some cases, the local minimum point results in a


design in which the purchase price is not attractive to the
customer. Because of this, global minimum points located
between the local minimum and the costs presented by a
standard transformer can be attractive economical
solutions.
The search procedure and determination of the global
points is as follows:
a) Find the factor R: the ratio between the minimum
and the standard transformer total costs;
b) If R>1, the global point is close to the standard
transformer total cost;
Fig 6 – Hot-spot temperature surface versus short circuit impedance c) If R<1, for each iteration, a multiplier M(k) is
and payback. defined as follows:
M (k ) = R + 0,1 ⋅ k
The design surfaces presented in this paper are based on d) If M(k)<1, a value for the minimum total cost
solution sets considering variations on several transformer CMin(k) is estimated. This point is close to the local
parameters and grouped in the following way: minimum tending to move toward the standard
a) Variations of current density of the LV and HV transformer total cost. In this way, all the global
windings and magnetic induction; minimum points are collected;
b) Variations of current density of the HV winding, C Min (k ) = C S tan dard ⋅ M (k )
insulation thickness and magnetic induction; e) For each iteration k, and for each column j, the total
c) Variations of current density of the HV and LV cost element c(i,j,z) is compared to the estimated
winding, insulation thickness; minimum total cost;
d) Variations of current density of the HV winding, gap C Min (k − 1) < c(i, j , z ) < C Min (k )
between coils and magnetic induction;
e) Variations of the design of the end insulation,
clamping dimensions, insulation thickness and Figure 7 presents the flow chart of the above discussed
magnetic induction; process.
f) Variation of the gap between coils, insulation
thickness and magnetic induction; V. OPTIMAL DESIGN RELATED TO THE TIME
g) Variation of current density of the LV winding, SUPPLYING THE MAXIMUM RATED POWER
insulation thickness and design of the end insulation
and clamp dimensions; In this paper, the economic restrictions for the
application of the proposed optimization process are: an
energy cost of 59.87 US$/MWh, an interest rate of 8% per presents one local (k=0) and another ten global minimum
year, and a 10-year analysis period. points.
Table 1 shows a comparison between the technical
characteristics of the efficient and standard designs. Table 2
presents a comparison between the payback and operational
cost reduction and energy saved.
This analysis considers point (k=0) as being the “best”
solution because it presents the maximum total cost
reduction. However, from a payback perspective, this is not
the “best” solution. Assuming that all design options in
Table 1 are feasible for manufacturing, the final solution
will be related to the utility policy. For instance, from a
payback standpoint, the answer is design 7. However,
design 9, which presents the second operational cost
reduction, would also be a possible choice.

Table 2 – Economic results attached to Table 1


Reduction Operational
Pay-
of the Cost Reduction Energy Saved
k back,
Total Cost per unit, [MWh/Year]
[Years]
[%] [US$/Year]
0 5,66 2,50 75,09 1,3248
1 5,60 2,06 67,02 1,1195
2 5,40 2,20 66,07 1,1036
3 5,35 2,22 65,82 1,0995
4 4,91 2,49 64,40 1,0757
5 4,84 3,00 72,39 1,2092
6 4,78 3,26 59,84 0,9996
7 4,67 1,98 54,29 0,9068
8 4,66 2,02 54,36 0,9125
9 4,34 3,31 70,64 1,1801
10 4,04 2,38 51,51 0,8604

Fig 7 – Flow chart to find global minimum points.

Figures 8 to 10 show three daily load cycles, presenting


different load peaks and TSMP. With them it is possible to
express the concept that for each TSMP there are several
efficient transformers to supply the load. Some of them
have the “best” manufacturing characteristic and therefore
are a logical choice. In theory this is the “optimal technical
and economical solution”: One efficient transformer per
load. However, spare, maintenance and purchase polices of
the utility, together with mass manufacturing restrictions
can modify this and, in the end the final design option may
point to a “unique” solution, with an improved economical Fig 8 – Load characteristic for a TSMP of 12.56
profile.
The minimum total cost (k=0) is a design that presents
Table 1 – Transformer designs presenting losses lower than the standard
Reduction of Reduction of No- Reduction of
reductions of 50% on the current density of the HV
k winding, 30% on the gap between the windings and 40%
Total Cost [%] Load Losses [%] Load Losses [%]
0 5,66 4,44 33,60 on the dimensions of the end insulation. The hot-spot
1 5,60 3,15 30,36 temperature is a common concern for the utility.
2 5,40 2,70 30,11 Considering a daily ambient temperature of 40°C and the
3 5,35 3,03 29,84 load cycle of Figure 8, during the period from 6 to 7 p.m.,
4 4,91 1,46 29,88 the top-oil and the hot-spot temperature are around 107°C
5 4,84 2,01 33,42
and 140°C, respectively, a reduction of approximately 1°C
6 4,78 0,64 28,10
7 4,67 1,93 24,87
compared to the design of a standard transformer [4].
8 4,66 0,90 25,50 Figure 9 shows a daily load cycle with a TSMP of 8.7.
9 4,34 2,17 32,52
10 4,04 1,66 23,68

For a daily load cycle according to Figure 8, having a


TSMP of 12.56, and considering variations on the current
density of the HV winding, on the gap between the coils
and on the design of the end insulation, the set of results
Fig 9 – Load characteristic for a TSMP of 8.7 Fig 10 – Load characteristic for a TSMP of 4.5

This case considered variations on the current density of This new case considered variations on the current
the HV windings, on the insulation thickness and on the density of the HV windings, on the insulation thickness and
gap between the LV and HV windings, a different solution on the gap between the LV and HV windings. Tables 5 and
compared with the previous one. Tables 3 and 4 show a 6 show a comparison between the technical and economical
comparison of the technical and economical characteristics characteristics presented by the efficient and standard
presented by the efficient and standard designs. The set of designs. The set of results presents one local and six global
results presents one local and seven global minimum minimum points.
points. The three studies presented have a different number of
global minimum points. This is a normal result and is
Table 3 – Transformer designs presenting losses lower than the standard related to the optimization process and to some technical
Reduction of Reduction of No- Reduction of Load restrictions.
k
Total Cost [%] Load Losses [%] Losses [%]
0 5,57 2,92 36,25 Table 5 – Transformer designs presenting losses lower than the standard
1 5,53 2,82 36,23
Reduction of Reduction of No- Reduction of
2 5,14 2,04 35,88 k
Total Cost [%] Load Losses [%] Load Losses [%]
3 5,13 3,18 23,47
0 3,14 3,18 23,47
4 4,97 2,77 23,88
1 2,98 2,77 23,38
5 4,43 1,86 22,58
2 2,46 1,86 22,58
6 4,15 0,31 29,12
3 2,24 2,92 36,25
7 3,35 0 20,98
4 2,20 2,82 36,23
5 1,81 2,04 35,88
Table 4 – Economic results of Table 3 6 1,44 0,31 29,12
Operational
Reduction of Pay-
Cost Reduction Energy Saved
k the Total back, Table 6 – Economic results of Table 5
per unit, [MWh/Year]
Cost [%] [Years] Operational
[US$/Year] Reduction
Pay- Cost
0 5,57 1,71 55,85 0,9329 of the Energy Saved
k back, Reduction
1 5,53 1,73 55,72 0,9308 Total Cost [MWh/Year]
[Years] per unit,
2 5,14 1,95 54,48 0,9100 [%]
[US$/Year]
3 5,13 0,09 37,39 0,6246 0 3,14 0,16 20,92 0,3495
4 4,97 0,18 36,87 0,6149 1 2,98 0,33 20,08 0,3417
5 4,43 0,50 34,83 0,5818 2 2,46 0,93 18,98 0,3171
6 4,15 1,85 42,93 0,7172 3 2,24 3,33 30,41 0,5080
7 3,35 1,28 30,75 0,5137 4 2,20 3,39 30,30 0,5061
5 1,81 3,91 29,29 0,4893
In this case, one recommended solution is design (k=2), 6 1,44 3,81 22,49 0,3757
which presents a reduction of 30% in the current density of
the HV winding, 10% of insulation thickness and 20% of Design 2 (k=2) presents a good solution, in that it
the gap between the LV and HV windings when compared presents a reduction of 10% on the current density of the
to the standard project of a distribution transformer. This HV winding, 10% of the insulation thickness, which must
can be attractive due to the fact that the technical and be verified by proper dielectric checking, and a rise of 20%
economical characteristics are quite close and that this of the gap between the LV and HV windings as compared
solution presents a lower manufacturing cost compared to to the standard values. In this case the amount of copper is
the local minimum point (k=0), reducing the investment. reduced and the solution presents an operational cost close
Figure 10 shows a daily load cycle with a TSMP of 4.5. to the minimum point. The payback is 0.93 years and there
is an energy savings of 0.3171 MWh per year.
Design 5 (k=5) is also a satisfactory solution when
energy savings is a priority in the utility policy. The
constructive parameters result in a reduction of 30% on the
current density of the HV winding, 10% of the insulation
thickness and 20% of the gap between the LV and HV
windings. The payback is 3.91 years and energy saved is [3] Blume, L.F., Boyajian, A., Camilli, G., Lennox, T.C.,
0.4893 MWh per year. Minneci, S., Montsinger, V.M. “Transformer Engineering:
Finally, the shape of the total cost surface for this case is A Treatise on the Theory, Operation, and Application of
shown in Figure 11. Transformers”. John Wiley&Sons, Inc., 1951.
[4] Bean, R.L., Chackan, N., Moore, H.R., Wentz, E.C.,
“Transformers for the Electric Power Industry”. McGraw-
Hill Book Company, Inc., 1959.
7800
[5] DelVecchio, R.M.,Poulin,B.,Feghali, P.T.,Shah,
7600
D.M., Ahuja, R. “Transformer Design Principles” CRC
7400 Press, 2001.
Total Cost

7200 [6] Kulkarni, S.V. and Khaparde, S.A., “Transformer


7000 Engineering: Design and Practice”. Marcel Dekker, CRC
6800
Press, Taylor&Francis Group, 2004.
6600
[7] Putman, T.H. “Economics and Power Transformer
2000
Design” IEEE, December 1963.
185
1000 180 [8] Jabr, R.A., “Application of Geometric Programming
0 175
Wcu Watts W0 Watts to Transformer Design”, IEEE Transaction on Magnetics,
Vol. 41, No.11, November 2005.
Fig 11 – Surface for the set of designs with variation on the current
density of HV winding, on the insulation thickness and on the gap [9] Picanço, A.F., de Salles, C., Rosa, P.C., Martinez,
between LV and HV windings considering TSMP of 4.5 M.L.B., Oliveira, H.R.P.M., de Jesus, N.C. “Designing
Transformers According to Load”. 15th ISH International
VI. CONCLUSION Symposium on High Voltage Engineering, Ljubljana,
Slovenia, August 2007.
The time supplying maximum rated power (TSMP) is the [10] Targosz, R. “The Potencial for Global Energy
first parameter to be considered in the design of an efficient Savings from High Efficiency Distribution Transformers”.
distribution transformer. This is related to the influence this Leonardo Energy Transformer – European Copper
parameter bears on the cost of the transformer designs, Institute, February, 2005.
mainly because it directly controls the load losses and plays [11] IEEE C57.91 – 1995. “IEEE Guide Loading
an important indirect role in controlling the no-load losses. Mineral-Oil-Immersed Transformer” IEEE Power
A statistical study of the load is necessary to define one Engineering Society, 2003.
or several load profiles. The spare and maintenance policies [12] Fletcher, R. “Practical Methods of Optimization,
of the utility also play an important role in the process of John Wiley & Sons, 1980.
loss cost reduction. Therefore, these issues, together with [13] Pierre, A.D. “Optimization Theory with
transformer sampling to define design loads, are key factors Applications”. Dover Publications, Inc., 1986.
to reach optimal solutions and must be object of careful
consideration. For reading:
As shown, each load profile presents a set of efficient [1] Picanço, A.F. “Avaliação Econômica de
transformers. This is not a practical solution for a utility; Transformadores de Distribuição com Base no
however, this can be useful for industrial consumers. The Carregamento e Eficiência Energética”. Thesis of Master
final choice must consider financial restrictions, Degree, Federal University of Itajubá, Brazil, April 2006.
manufacturing process restrictions and recommendations,
the price of the main transformer commodities, the utility IX. BIOGRAPHIES
internal policy and governmental energy saving
regulations, all of which are normally conflicting issues and Alessandra Freitas Picanço was born in 1978 in Manaus, Amazonas
State, Brazil. She received her B.Sc. in electrical engineering in May 2002
therefore must be properly balanced. from the Federal University of Amazonas – UFAM and M.Sc. degree in
May 2006 from Federal University of Itajubá – UNIFEI. She is currently
VII. ACKNOWLEDGEMENT obtaining her Doctor Degree in Transformer Designs.

Alessandra Picanço acknowledges the financial support Credson de Salles was born in 1975 in Bueno Brandão, Minas Gerais
of CAPES, AES-Sul S.A. and PROCOBRE BRASIL. She State, Brazil. He received his B.Sc and M.Sc in electrical engineering in
from the Federal University of Itajubá where nowadays is a PhD Student.
also acknowledges the Prof. Dr. Estacio Tavares
Wanderley Neto for your support.
Hermes R. P. M. de Oliveira was born in 1960 in São Lourenço, Minas
Gerais State, Brazil. He received his B.Sc. and M.Sc. degrees in electrical
VIII. REFERENCES engineering from EFEI (UNIFEI). He has worked in AES Sul Company
since 1998.
[1] European Copper Institute. “The Scope for Energy
Saving in the EU through the Use of energy-Efficient Manuel L.B. Martinez was born in 1959 in Santos, São Paulo State,
Brazil. He received his B.Sc. and M.Sc degrees in electrical engineering
Electricity Distribution Transformers”. European
from the Federal University of Itajubá (UNIFEI) and Ph.D. degree from
Communities, 1999. PEA-USP. He has been responsible for the High Voltage Laboratory of
[2] U.S. Department of Energy. “Distribution UNIFEI since 1995.
Transformers Final Rule Technical Support Document –
TSD”. Washington, DC 20585, 2007.

Anda mungkin juga menyukai