Central Battery System Type CPS 220/SV

Catalogue CPS 220/SV

Sicherheitstechnik GmbH

CPS 220/SV
The modular emergency lighting system

INOTEC Sicherheitstechnik GmbH is a company with the target to create innovative and customer oriented solutions for the Emergency Lighting market. A dynamic team of highly professional and flexible employees covers all aspects regarding products, engineering and standards. Modern, technical advanced products set new standards world wide, i.e. JOKER technology for Emergency Lighting Systems or the Dynamic Escape Routing concept realised in the D.E.R.-System. This catalogue contains the INOTEC Standard Central Battery Emergency Lighting Systems (CPS) and some complementing products. Should you require additional functions or special features please do not hesitate to ask our regional technical sales team for support.

Content
CPS 220 The modular emergency lighting system

Page
Function, design and features Advantages and function of Joker-technology Installation sample System components and options Control module Charger Circuit change-over devices Stairwell light switch module TLS Relay interface RIF 5 Light switch monitors LSA8.1 Phase monitors Luminaire monitoring and supply modules Low voltage halogen LED - Power Led Electronic ballasts Monitoring modules External supervision and display Mimic panel, wall MTB/AP Mimic panel, recessed MTB/UP InoWeb / InoLan / InoWeb-Control RTG interface Technical data, systems overview 3-4 5 6-7 8-12

13-15

16-17

Copyright: INOTEC Sicherheitstechnik GmbH, Ense Publications and copies, even partial, only with manufacturers permission. Subject to technical changes.

18-20

Designs sample, system engineering and tables 21-23

CPS 220/SV
Function, design and features
220 V-central battery system with fully automatic function monitoring including individual lamp- and circuit failure detection without additional data line Internal and external system-bus Automatic system configuration Individual monitoring- and change-over devices for maintained- /non- maintained light Simple design and engineering due to free selectable luminaire operation modes

Patented "Joker-Technology" function for mixed operation of maintained, non-maintained and switched luminaires on one line Included logbook for all relevant data within a minimum 2 year period Centronics printer interface Lead acid gas recombination OGi-battery with >10 years design life

Mains Mains monitoring Controller with display


Betrieb Batt.Betrieb Strung

CPS 220/SV

INOTEC
SV-ZENTRALE
01.07.95 12:00

Betrieb
Funktionstest 2.7.95 8:30

Emergency and safety luminaires


Key-board

Ladestrung

Drucker Cetronics

Charge monitoring
Netz Netz

Batterie 10AT Ein

Emergency and safety luminaires

Charger Change-over modules

Battery 220V

Function principle: With functional mains all connected consumers are supplied with mains and the battery is charged / monitored. If mains fails or a partial light sub.-distribution or circuit failure is detected the supply is triggered by the emergency lighting system.

CPS 220/SV
Function, design and features
The CPS 220 series covers various load requirements and housing sizes. Joker-Technology, individual lamp- and circuit monitoring are our standard System features Modular design, various enclosure sizes for main-, sub-stations, battery-racks and battery enclosures 19" inch - rack modules Isolation terminals for easy connection and insulation resistance measurement of luminaire circuits Load for standard systems: from 1,5 KVA to 22 KVA Compact design: Up to 48 circuits 3A (max. 576 monitored luminaires at 12 luminaires per circuit) or 24 circuits 6A on one system controller Low maintenance and service costs due to central monitoring of stations and all connected luminaires Automated or manually releaseing function test facility with logbook for status and failure information Earth failure measurement and test facility

Control module for the programming, data processing and information storage, with: 4 line liquid crystal text display free programmable via incorporated buttons or external key-board various languages available luminaire failure display with location info

CPS Funktionstest Betrieb U=247V I= 0.0A 6-03 14:59 Menue

Technical data: Mains supply: 1~/N/PE, 230V AC, 10% or 3~/N/PE, 400V AC, 10% Emergency supply: 220V DC, +10/-20% EMC protection to EN 55081/EN 55082 Protection class : I Protection category : IP20 Permissible ambient temperature: for system: -5 C to +35 C for battery: see datasheet

luminaire function test and battery duration test cycles free programmable manual reset on mains return selectable delay on mains return (0 - 15 min) selectable deep discharge protection with info Connection possibilities to building management systems or in-house central monitoring systems

CPS 220/SV
Advantages and function of Joker-technology
Joker-technology - a cost saving innovation Each INOTEC CPS emergency lighting system can be built-up to three different supply luminaire switching modes on the same output at the same time. Luminaires with Joker high frequency electronic ballast (common standard on INOTEC-SV luminaires) or Joker switch modules, for third party electronic ballast, must be used. These components allow an easy setting of the monitoring address and luminaire mode. Advantages of the Joker - technology Simple design and engineering Reduced installation material content Cut down on installation time Higher load level for final end circuits Switching mode settable on each luminaire

The patented JOKER-technology of INOTEC reduces the design- and installation time and cuts down on material cost.

The sample pictured shows the kind of installation savings which can be achieved.

Conventional systems and installations with the switching modes maintained-, non-maintained- and switched maintained mode, require 6 final end circuits to feed 9 luminaires in a part of the building shown.
Conventional installation requires 6 final end circuits

Circuit 1

Circuit 3

Circuit4

Circuit 2

The Joker-technology reduces the number of circuits required. Our sample needs only 2 final end circuits to feed the same number of luminaires due to the fact that the operation of all switching modes on one circuit is possible. The maintained and switched maintained luminaires are active during mains presence. During mains failure, however, all luminaries, regardless of their operation mode, will be switched on and supplied by the central battery system.

Circuit 5 Circuit 6

Circuit 1

Circuit 2

Joker technology with 2 final end circuits

German Patentnumber: DE 19807844 European Patentnumber: EP 0939476

Maintained

Non-maintained

Switched maintained

CPS 220/SV
Installation sample
INOTEC Standard SVPC- Software
Em-light Systems
Status Data line Functiontest: Durationtest: Button

Operation
Seminar room

Select Button

Operation
Seminar room Button

Operation
System 3

Functions

Button Data line

Com-Port
Em-light Systems
Systemtype Location Seminar room Status Data line System address Functiontest: Durationtest: Status Operation Luminaire status Battery status

Complex installations with a multiple of systems should be supervised from a cen-tral location. Wether the INOTEC own RTG-BUS, an existing network or the internet is used for this purpose depends on the specific individual project requirements.

Button
Selection

Button

SVPC - Software max. 8x32 systems


L1 L2 L3 N PE L1 L2 L3 N PE

Luminaire location Workshop, mid-section Toile Work Sale No.


Safe manut autom

Button
Kitchen Status Data line Toilett-men, gf Functiontest: Durationtest:
Zurck
R T
G/

Em-light Systems
Date Time

+24V
RS232

Log book
Address System
1 1 1 1 1 1 1 1 1 1 1 1 1

Button
Event Selection

DB

DB

reset

INOTEC InoLan 990 063 GND RxD TxD

512 513 514 515 516 517 518

04.04.01 13:13 04.04.01 13:13 04.04.01 13:14 04.04.01 16:25 04.04.01 16:26 04.04.01 16:28 04.04.01

Operation Operation Sub.-dist. failure Operation Sub.-dist. failure Funktiontest o.k. DT interrupted Status Data line

Button

RTG or interface InoLan 230V 50/60HZ

RTG

DP U< S+

S-

DP U< S+

S-

09:16 1 Eintrg

Button
Functiontest: Durationtest:

Eintrge insgesamt 520

Funktiontest Durationtest Charge failure Transmission failure Manual reset Discharge protection

Op Fail Fail Blo ISO Sys

Em-light Systems

Button
Workshop Selection

General lighting

General lighting

Button
Office Women Lager Men Kitchen Layout

Button
Seminar room Sales dept. Back

Monitoring Mains

Engineering

Sekrt.

MD

Button
Help

or

9 0 1 8 7 6 5 4 2 3

9 0 1 8 7 6 5 4 2 3

CPS 220
Betrieb

INOTEC
SV-ZENTRALE
01.07.95 12:00

CPS 220
Betrieb Batt.Betrieb Strung

Batt.Betrieb Strung

+
TEST

Betrieb
Funktionstest 2.7.95 8:30

INOTEC
SV-ZENTRALE
01.07.95 12:00

+
TEST

Ladestrung R T

Drucker Cetronics

Betrieb
Funktionstest 2.7.95 8:30

Key-board

UH 5AT

Ladestrung R T

Drucker Cetronics

Key-board

RS232

INOWEB Ethernet- or Internet connection

UH 5AT
SU / SV - J 2x3A SU / SV - 2x3A SU / SK- J 2x3A SU / SV - 1x6A SU / SK - 2x3A SU / SK - 1x6A SU / SV - 2x3A SU / SK- J 2x3A

Strung SU / SV - J 2x3A SU / SV - 2x3A SU / SK- J 2x3A SU / SV - 1x6A SU / SK - 2x3A SU / SK - 1x6A SU / SV - 2x3A SU / SK- J 2x3A Si 5AT BLEin DLEin

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT

Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin

Strung Si 5AT BLEin DLEin

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT

Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin Strung Si 5AT BLEin DLEin Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin Si 10AT Si 5AT Ein Strung Si 5AT Si 10AT Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin

G/

+24V
Strung Si 5AT BLEin DLEin

Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin Si 10AT

Si 5AT Ein Strung Si 5AT Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin SU / SV - J 2x3A SU / SV - 2x3A SU / SK- J 2x3A SU / SV - 1x6A SU / SK - 2x3A SU / SK - 1x6A SU / SV - 2x3A SU / SK- J 2x3A

Strung Si 5AT BLEin DLEin

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT

Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin

reset

RTG

Si 5AT Strung Si 5AT BLEin DLEin Ein Strung Si 5AT Si 5AT Strung BLEin DLEin Si 10AT

Si 5AT Ein Strung Si 5AT Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin

INOTEC InoLan 990 063 GND RxD TxD


192.100.100.103 inoweb.ense.inotec-licht.de 192.100.100.39 First floor First floor Ma i n H ot el bu i l di n g Failure Functiontest Operation Systemfail. Systemfail. Systemfail.

Netz Netz

Batterie 10AT Ein

Ladeteil 220V / 7,5A

Failu re S ystem fail.: L um ina ire failu re U ba t t = 24 6,0 Volt, I b at t =+ 0,0 A mp .

Other monitoring options (i.e. TCP/IP, LON, KOM-module) on request

CPS 220/SV
Installation sample
Each CPS system operates with its integrated controller as a complete independent unit. This allows to link different emergency lighting panels/sub-stations together (see below). One integrated controller can handle up to 48 circuits and, in addition, stores the systems logbook.
L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE

DB

DB

DB

DB

DP U< S+

S-

DP U< S+

S-

DP U< S+

S-

DP U< S+

S-

General lighting

General lighting

General lighting

Monitoring Mains lighting circuits sub db

Safety lighting

Safety lighting

+ + 24VBUS
BIF INOTEC

extern
990013

+ + 24V24V

+ + BUSBUS

9 0 1 8 7 6 5 4 2 3 8 7

9 0 1 6 5 4 2 3

Netz N N

Netz L L

St.-Kreis1 N L+

St.-Kreis2 N L+

St.-Kreis3 N L+

St.-Kreis4 N L+

St.-Kreis5 N L+

St.-Kreis6 N L+

Batt.

Batt.

IB BB

Adresse

Stromkreis Platz 1 links

Stromkreis Platz 2 mitte

Stromkreis Platz 3 rechts 3.1 / 3.2 6.1 / 6.2 9.1 / 9.2 12.1 / 12.2 15.1 / 15.2 18.1 / 18.2 21.1 / 21.2 24.1 / 24.2
9
8

CPS 220
Betrieb Batt.Betrieb Strung Betrieb

SU / SV - J 2x3A

SU / SV - 2x3A

SU / SK- J 2x3A

SU / SV - 1x6A

SU / SK - 2x3A

SU / SK - 1x6A

SU / SV - 2x3A

SU / SK- J 2x3A

INOTEC
SV-ZENTRALE
01.07.95 12:00

Strung Si 5AT BLEin DLEin

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT

Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin

0 1 2 3 4 5 6 7 8 9

1.1 / 1.2 2.1 / 2.2 4.1 / 4.2 5.1 / 5.2 7.1 / 7.2 8.1 / 8.2 10.1 / 10.1 11.1 / 11.2 13.1 / 13.2 14.1 / 14.2 16.1 / 16.2 17.1 / 17.2 19.1 / 19.2 20.1 / 20.2 22.1 / 22.2 23.1 / 23.2 keine Funktion keine Funktion

SV-ZENTRALE
01.07.95 12:00

Funktionstest 2.7.95 8:30

Strung

Funktionstest 2.7.95 8:30

TEST
Si 5AT Si 5AT Strung Si 5AT BLEin DLEin Si 10AT Ein Strung Si 5AT Si 10AT Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin

Ladestrung R T

Drucker Cetronics

Ladestrung R T Key-board

Drucker Cetronics

Key-board

Strung Si 5AT BLEin DLEin

Ein Strung Si 5AT

Netz N L

UH 5AT

5AT

Stromkreis 1
SU / SV - J 2x3A SU / SV - 2x3A SU / SK- J 2x3A SU / SV - 1x6A SU / SK - 2x3A SU / SK - 1x6A SU / SV - 2x3A SU / SK- J 2x3A SU / SV - J 2x3A SU / SV - 2x3A SU / SK- J 2x3A SU / SV - 1x6A SU / SK - 2x3A SU / SK - 1x6A SU / SV - 2x3A SU / SK- J 2x3A
Ein Strung

Strung Si 5AT BLEin DLEin

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT

Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin Si 5AT

Strung BLEin DLEin

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT

Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin

Si 5AT Strung Si 5AT BLEin DLEin Ein Strung Si 5AT Si 5AT Strung BLEin DLEin Si 10AT

Si 5AT Ein Strung Si 5AT Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin Strung Si 5AT BLEin DLEin

Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin Si 10AT

Si 5AT Ein Strung Si 5AT Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin

INOTEC
SU / SV - J 2x3A SU / SV - 2x3A SU / SK- J 2x3A SU / SV - 1x6A SU / SK - 2x3A SU / SK - 1x6A SU / SV - 2x3A SU / SK- J 2x3A

Netz Netz

Batterie 10AT

Strung Si 5AT BLEin DLEin

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT

Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin

Si 5AT Strung Ein Strung Si 5AT Si 5AT Strung BLEin DLEin Si 10AT

Si 5AT Ein Strung Si 5AT Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin

Ein

Si 5AT

BLEin DLEin

Ladeteil 220V / 7,5A

Betrieb

Batt.Betrieb

Betrieb

BUS

5AT

5AT

5AT

5AT

5AT

5AT

5AT

5AT

5AT

5AT

5AT

Batt. +

Stromkreis 2
Ein Strung

Stromkreis 3
Ein Strung

Stromkreis 4
Ein Strung

Stromkreis 5
Ein Strung

Stromkreis 6
Ein Strung

CPUSB220/6

Safety luminaire (non-maintained) Safety luminaire (switched maintained) Emergency luminaire (maintained)
DP U<

Under voltage monitoring Battery line Data line Mains

Netz N N

Netz L L

Adresse St.-Kreis1 S1 N L+ INOTEC US6B


3

St.-Kreis2 N L+

St.-Kreis3 N L+

St.-Kreis4 N L+

St.-Kreis5 N L+

St.-Kreis6 N L+

BUS B B +24V

Batt.

Batt.

INOTEC

Adresseinstellung

1
2 3

Sicherheitstechnik GmbH

CPS 220/SV
System components and options

Change-over devices 19"-slide-in modules, double pole fused, for individual circuit(s) Circuit- (SK) or individual lamp monitoring (SV) JOKER function optional No data line required for monitoring LEDs in the front plate to indicate fault / healthy status and circuit switching mode completely wired to 3-tier terminals 4mm, with isolating neutral Individual lamp monitoring Circuit module max. load Joker technology Fuse Order number J-SU/SV 2x3A 2x 3A yes 5AT/250V, 6,3x32 929006 SU/SV 2x3A 2x 3A no 5AT/250V, 6,3x32 929001 SU/SV 1x6A 1x 6A no 10AT/250V, 6,3x32 929000 Circuit monitoring Circuit module max. load Joker technology Fuse Order number J-SU/SK 2x3A 2x 3A yes 5AT/250V, 6,3x32 919011 SU/SK 2x3A 2x 3A no 5AT/250V, 6,3x32 919001 SU/SK 1x6A 1x 6A no 10AT/250V, 6,3x32 919000

CPS control module Microprocessor controlled free programmable module with internal/external BUS, 4 line liquid crystal display, CENTRONICS interface for external printer connection, keyboard connection port, logbook, LED status indicators, push buttons for programming and detailed status-/failure interrogation, blocking function for the complete system or the mains lighting. Electronically monitored 24V loop for voltage monitoring of any number of lighting sub-distribution boards. Accessible display information: All available status information for the complete CPS-System Fault information for every circuit or individual luminaire with location text-info Achieved battery duration (in minutes) during the last endurance test Available battery capacity Logbook entries Programming possibilities: SV-monitoring functions - Single luminaire / lamp monitoring - Circuit monitoring Panel address Date / time for function test Date / time for duration test Manual reset Stairwell light switching Time delay on mains return 1-15 min Earth leakage monitor with test facility Deep discharge protection Log-book LED-display for: Operation (mains healthy - green) Battery operation (mains failed or test during mains healthy - yellow) General failure (red) Charge failure (red)

Charger 220 V/3,0 A and 220 V/7,5 A For all available 216V lead-acid accumulators Service-friendly 19'' - housing Modern, microprocessor controlled design - high efficiency - low weight Battery charge- and discharge current information is permanently available at the CPS controller Constant charger- and battery circuit monitoring with fault display at the CPS controller in case of - blown battery fuse - missing or defect battery block - faulty charger - open battery circuit - battery voltage to high / low Temperature controlled charging to ensure longer battery life

CPS 220/SV
System components and options

TLS 1 Staircase light switching module, 1 channel 19''- slide-in module each CPS rack can accommodate one TLS 1 Details see TLS 5

TLS 5 Staircase light switching module, 5 channels The TLS 5 module allows to utilise the same push button for the control of mains- and safety-/exit luminaires. The emergency function of a certain circuit or circuits is only given, for a preset time, after pushing a button. The modules 5 channels are galvanic separated and have terminals for the push button connection and the volt free contact. Via the TLS 5 all glow-wire indication lamps with the push buttons are energised. Max. 20 (each 0,8mA) or 10 (each with 1,5mA) push buttons-indicator lamps can be connected to the respective terminals (1/1 - 5/5). Maximum cable length for the push-button line is 500m. Each potential free contact for mains lighting can be used up to 3A, 230V, 50/60 Hz. The emergency luminaires are supplied via the allocated change-over devices of the CPS-system. This is programmable in the control module of the CPS. Free programmable push-button / emergency circuit(s) allocation 1-15 min. run time for emergency Illuminated push buttons during all material times

L N

N L

L N further luminaires

Each contact - max. switching load 3A at 230V 50/60Hz

further push buttons further push buttons each channel max. 20 illuminated push buttons, 0,8mA glow lamp or max. 10 illuminated push buttons, 1,5mA glow lamp Lengh of the cable to the push buttons max. 500m BUS-connection Battery 220V Internal wiring

CPS 220/SV
System components and options

INOPRINT available at the parallel port of a CPS-system can be stored as a text file on INOPRINT. Via PC / USB-interface the information can be stored and printed.

RIF 5 Function: Interface for remote status indication and system blocking function. Free programmable, in connection to a switch, for - maintained and non maintained emergency light ON/OFF - maintained emergency light ON/OFF With or without loop monitoring 5 voltfree contacts for - operation - battery operation - failure (general) - failure (battery-/ charge circuit)) - free programmable Battery sensor for temperature controlled charging, if required With phase monitor (sub-db or main-db), single phase Contacts: 24V / 1A EMC protected to EN 55015 Dimension: H = 59, W = 71.5, D = 90 (mm) System status Operation Sumfailure Failure 1-2 close open Operation 3-4 close open Battery open open operation 5-6 Option 1 selectable Option 2 selectable Battery operation close open close

Relay contacts

Remote switch Volt free contacts 24V DC max.100mA 24V Monitoring loop

850 009

single phase supply monitor battery voltage internal wiring

Temp. sensor

10

CPS 220/SV
System components and options

LSA 8.1 with DP/BUS Light switch monitor, 8 channels For the common switching (on/off ) of safety luminaires along with the mains lighting and for phase monitoring. Each channel is galvanic separated. Up to two channels can be allocated by software to every individual, or a number of CPS-change-over-device (output circuit). This switch/channel allocation happens during the set-up/ commissioning and is programmable on the CPS control module. Three-phase-monitor, DP/BUS - free selectable phase connections - 1 change-over contact - monitoring low voltage and mains failure - for single-phase monitoring too - voltage 230V AC, 400V AC - threshold 0,85 x UN - deactivation switch Failure info at the CPS-controller with location Supply voltage: Available in 230V AC 50/60 Hz or 24V DC EMC protected to EN 55015 Dimension: H = 59, W = 71,5, D = 90(mm)

LSA 8.1 INV with DP/BUS Light switch monitor, 8 channels, inverted For the switching (on/off ) of safety luminaires along with the mains lighting and for the selective activation of emergency light circuits at partial mains failures. Each channel is galvanic separated. Up to two channels can be allocated by software to every individual, or a number of, CPS-change-over-device (output circuit). This switch/channel allocation happens during the set-up/ commissioning and is programmable on the CPS control module. Three-phase-monitor, DP/BUS - free selectable phase connections - 1 change-over contact - monitoring low voltage and mains failure - for single-phase monitoring too - voltage 230V AC, 400V AC - threshold 0,85 x UN - deactivation switch Failure info at the CPS-controller with location Supply voltage: Available in 230V AC 50/60 Hz or 24V DC EMC protected to EN 55015 Dimension: H = 59, W = 71,5, D = 90(mm)

L1 N PE

Sub-db

L1 L2 L3 N PE

Sub-db 2
General lighting

U<

General lighting

A failing general lighting circuit or lighting sub-db triggers only the necessary safety lighting circuit for this area.

850 008

LSA 8.1 INV

11

CPS 220/SV
System components and options

DP Three Phase Monitor To detect phase- or circuit failures in general lighting sub-distribution panels With volt-free failure indication contact LED-indication for L1, L2, L3 free selectable phase connections 1 change-over contact monitoring low voltage and mains failure in three-phase networks for single-phase monitoring too acc. to IEC 255 for DIN rail mounting For the connection to INOTEC central- and group supply battery systems. Voltage: 230V/400V AC 50/60 Hz Threshold 0,85 x UN Perm. temp.: -20C ... +60C EMC protected to 55015 Dimension: H =58, W = 17,5, D = 90(mm)

DP/B.1 Three Phase Monitor with BUS, addressable To detect phase- or circuit failures in general lighting sub-distribution panels. With location info at CPS-controller of monitored sub-distribution panel in case of phase failure. With volt-free failure indication contact. LED-indication for L1, L2, L3 free selectable phase connections 2 x n/o contacts monitoring low voltage and mains failure in three -phase networks for single-phase monitoring too acc. to IEC 255 for DIN rail mounting Detailed phase failure with location info of the sub db at CPS controller For the connection to INOTEC central- and group supply battery systems. Voltage: 230V/400V AC 50/60 Hz Threshold 0,85 x UN Perm. temp.: -15C ... +40C EMC protected to 55015 Dimension: H = 58, W = 36, D = 90(mm)

DB 1
L1 L2 L3 N PE

DB 2
L1 L2 L3 N PE

DB ...
L1 L2 L3 N PE

L1

L2

L3

L1

L2

L3

L1

L2

L3

L1 L2 L3

Adresse 1 bis 31 Einer


4
3

L1 L2 L3

Adresse 1 bis 31 Einer


4
3

L1 L2 L3

Adresse 1 bis 31 Einer Zehner


4
3

DP / B.1
2

6
7

890 414

DP / B.1
890 414

6
7

DP / B.1
890 414

6
7

Zehner

4
3

4
3

Zehner

Kontakte (1 / 2) + (3 / 4) ffnen bei Netzausfall

6
7

Kontakte (1 / 2) + (3 / 4) ffnen bei Netzausfall

6
7

Kontakte (1 / 2) + (3 / 4) ffnen bei Netzausfall

6
7

EMC: gem. EN 55015

EMC: gem. EN 55015

EMC: gem. EN 55015

SL+
FS SL FS+ SL+ FS Fernschalter SL Stromschleife

Address setting is mandatory for full functionality

850 009

INOTEC
SL
890 415 - Batt. + N HV L

HV Hauptverteiler

RIF5 RIF5

oder or

SL SL

Klemmleiste terminal rail

12

+24V IB

1 3

2 4

+24V BUS

1 3

2 4

+24V BUS

1 3

2 4

+24V BUS

gem. VDE 0108 ta: -15 bis 40C

gem. VDE 0108 ta: -15 bis 40C

gem. VDE 0108 ta: -15 bis 40C

9
8

9
8

9
8

INOTEC

INOTEC

INOTEC

Wire link on last DP/B.1 mandatory

CPS 220/SV
Luminaire monitoring and supply modules

N-ET 20-70W Luminaire module for he supply of low-voltage halogen lamps 20 - 70W. For the connection to INOTEC central- and group supply battery systems. Input voltage: 230V AC 50/60 Hz 220V DC 20 % Output voltage: 11,5V DC Output current: 150-490 mA Perm. temp.: 0C ... +65C EMC protected to EN 55015 Dimension: H = 31, W = 42, D = 102(mm)

J-ET 9/24 SV Constant current luminaire module for the supply and monitoring of LEDs. Light output in mains adjustable. With easy accessible address-switch and JOKER function, switch to select maintained or non-maintained mode and individual light source failure detection For the connection to INOTEC central- and group supply battery systems. Input voltage: 230V AC 50/60 Hz 220V DC 20 % Output voltage: 24V DC Output current: 320 mA constant Perm. temp.: -15C ... +50C EMC protected to EN 55015
31

Dimension: H = 28, W = 40, D = 90(mm)

102 86

42

13

CPS 220/SV
Luminaire monitoring and supply modules

EVG 4-6 EVG 4-13.1 EVG 18 Compensated high frequency electronic ballast for fluorescent and compact fluorescent lamps TL/TC/TCD-EL 4-18 W. EVG 4-6 designed for low power loss at 4 Watt. Automatic deactivation of electronics in case of lamp failure. Suitable for emergency lighting systems to EN 50171 / EN 50172. Designed to be installed inside of luminaires. For the connection to INOTEC low power- or central power battery systems like ELS or CPS. Voltage: 230V AC 50/60 Hz 220V DC 20 % Perm. temp.: -15C ... +50C EMC protected to EN 55015

J-EVG 4-6 SV J-EVG 4-13 SV J-EVG 18 SV Compensated high frequency electronic ballast for fluorescent and compact fluorescent lamps TL/TC/TCD-EL 4-18 W, with easy accessible address switch, JOKER function and individual lamp monitoring. The JOKER function allows luminaries to be operated in maintained and non-maintained mode on the same final end circuit. Automatic deactivation of electronics in case of lamp failure. Suitable for emergency lighting systems to EN 50171 / EN 50172. Designed to be installed inside of luminaires. For the connection to INOTEC low power- or central power battery systems like ELS or CPS. Voltage: 230V AC 50/60 Hz 220V DC 20 % Perm. temp.: -15C ... +50C EMC protected to EN 55015

PE N L

20 3

General lighting

EVG 4-6 EVG 4-13.1 EVG 18 80 90 Light switch J-SV-Modul.2/S NS L+ J-SV-Modul.3/S NL+ J-SV-Modul.4/S L+
N- J-SV-Modul/S NLS

28

40

80 90 4,2

Input

J-EVG 4-6/SV-S J-EVG 4-13/SV-S J-EVG 18/SV-S 80 90

J-EVG 4-6/SV J-EVG 4-13/SV J-EVG 18/SV J-Modul/S J-SV Modul/S J-ET 9/24 SV

30 3

Fluorescent lamps with high frequency electronic ballast standard bulbs or halogen lamps

40 4

40

NS LS NL+

N-

J-SV-Modul.L/S
L+

Fluorescent lamps with high frequency electronic ballast standard bulbs or halogen lamps

17,9

240,4 J-SV Modul.L/S J-SV-Modul.L/S 235,4 249,4

4,2

Circuit CPS 220 J/SV

J-EVG4-6/SV-S 1 2 L+ J-EVG 4-13/SV-S 3 L+ J-EVG 18/SV-S 4

NN-

LS NS

26,4

Out

14

CPS 220/SV
Luminaire monitoring and supply modules

J-EVG 4-6 SV/S J-EVG 4-13 SV/S J-EVG 18 SV/S Compensated high frequency electronic ballast for fluorescent and compact fluorescent lamps TL/TC/TCD-EL 4-18 W, with easy accessible address switch, JOKER function and individual lamp monitoring. This electronic ballast features a sense-input or an inverted phase monitor too. J-EVG 4-6 SV designed for low power loss at 4 Watt. The JOKER/S function allows luminaires to be operated in maintained, non-maintained and switched mode on the same final end circuit. Automatic deactivation of electronics in case of lamp failure. Suitable for emergency lighting systems to EN 50171 / EN 50172. Designed to be installed inside of luminaires. For the connection to INOTEC low power- or central power battery systems like ELS or CPS. Voltage: 230V AC 50/60 Hz 220V DC 20 % Perm. temp.: -15C ... +50C EMC protected to EN 55015 Individual lamp monitoring Component Type Joker technology J-EVG 4-6 SV EVG yes J-EVG 4-13 SV EVG yes J-EVG 18 SV EVG yes J-EVG 4-6 SV/S EVG yes J-EVG 4-13 SV/S EVG yes J-EVG 18 SV/S EVG yes SV Modul.1 SV Modul.2 J-SV Modul/S J-SV Modul.2/S J-SV Modul.3/S J-SV Modul.4/S J-SV Modul.L/S Module Module Module Module Module Module Module no no yes yes yes yes yes

J-SV-Modul/S J-SV-Modul.2/S J-SV-Modul.3/S J-SV-Modul.4/S J-SV-Modul.L/S Single luminaire monitoring module for fluorescent- (T16/T5) compact fluorescent, halogen and incandescent lamps. With easy accessible address switch, JOKER function and individual lamp monitoring. This module features a sense-input or an inverted phase monitor too. The JOKER/S function allows luminaries to be operated via these J-SV-modules in maintained, non-maintained and switched mode on the same final end circuit. Suitable for emergency lighting systems to EN 50171 / EN 50172. Designed to be installed inside of luminaries. For the connection to INOTEC low power- or central power battery systems like ELS or CPS. Voltage: 230 V AC, 50/60 Hz 220 V DC, 20 % Perm. temp.: -15C ... +50C EMC protected to EN 55015

Load 4-6W 4-13W 18W 4-6W 4-13W 18W 5-120W 20-300W 5-120W 20-300W 2-30W 18-120W 5-120W

Sense-input no no no yes yes yes no no yes yes yes yes yes

Treshhold

Order number 860008 860004 861003 860010 860005 861004 851001 851003 851002 851004 851025 851029 851026

Failure < 10mA < 45mA < 10mA < 45mA < 8mA < 45mA < 10mA

O.k > 20mA > 70mA > 20mA > 70mA > 12mA > 70mA > 20mA

Circuit monitoring Component EVG 4-6 EVG 4-13 EVG 18 J-Modul/S Type Joker technology Load Sense-input EVG no 4-6W no EVG no 4-13W no EVG no 18W no Module yes max. 600W yes Order number 860007 860003 861002 851018

15

CPS 220/SV
External supervision and display

MTB The MTB-remote mimic panel (MTB/AP = wall mounting, MTB/UP = recessed wall-/panel mounting) are used for external status- and failure indication of emergency lighting systems. Furthermore it allows to block the system via the integrated key-switch. Functions: Key-switch free programmable for: maintained and non maintained light ON / OFF maintained light ON / OFF Displayed: Green LED - operation Yellow LED - battery operation Red LED - failure (battery / luminaire) Connection to RIF-module of CPS-system; max cable length with 0,8mm 500m Voltage: UN= 24V DC +/-10% Mode: Permanent operation Temp.-range: -15C ... +40C Protection: IP20 MTB/UP; IP 30 MTB/AP Housing: Stainless steel/polycarbonate EMC protection to EN 55015 Wall mounting:

RTG interface Interface between PC-serial port and internal INOTEC RTG-BUS. The SVPC-software is required to view all relevant data of CPS -systems on a standard PC. Displayed: Yellow LED - SVPC recieves data Greene LED - SVPC transmitt data Technical data: 1 m power cord 230V with Euro-plug INOTEC RTG cable (1m) Socket for serial port (1m cable) Voltage: UN = 230V +/-10% Mode: Permanent operation Temp.-range: -15C ... +40C Protection: IP20 Housing: Thermoplast EMC protection to EN 55015

Notlicht
Betrieb Batt.-Betrieb Ein Aus INOTEC

Strung

90

58

SVPC-software The INOTEC-SVPC-software is used to central supervise and programme up to 32 central battery-, group battery- or self-contained battery systems. For standard and mixed installations with CPS 220-, CPUS 220-, LPS24-, ELS/SV and BNS 32/59. Status- and failure information of luminaires, batteries and other system components are monitored, stored and displayed. Luminaire failures and localisation can be individually identified / verified due to free destination text programming. A resulting printout can help during the repair process. System requirements: Operating system: Windows 2000 / XP Screen: VGA (640 x 480), 256 colours and above Hard disc capacity: min. 50 MB Interface: serial port

43

Recessed wall mounting:


Notlicht
Betrieb Batt.-Betrieb Ein Aus INOTEC

Strung

90

58

16

74

CPS 220/SV
External supervision and display

InoLan-module Interface between Ethernet and internal INOTEC RTG-BUS. The SVPC-software is required to view all relevant data of CPS -systems via an existing Ethernet on a standard PC. Displayed: Yellow LED - Ethernet connected Green LED - Network active Connection possibilities: Ethernet RJ45 port INOTEC RTG BUS-terminals RS 232 terminals or DB9-port Voltage: UN= 24V DC +/-10% Load: 1,7 VA Mode: Permanent operation Temp.-range: -15C bis +40C Protection: IP20 (terminals); IP40 (housing) Housing: Thermoplast, for DIN rail mounting Switch "Reset" for configuration Switch RS 232 / RTG EMC protection to EN 55015

InoWeb-module To display all relevant data of CPS -systems as a HTML-page via standard-web-browser (Explorer, Mozilla, Opera..) on an existing Ethernet. An IP-address can be programmed or allocated via a DHCP-server. Function indication and technical data: see InoLan.

InoWeb-control-software The InoWeb control software can be installed on a standard PC with Ethernet access. This software will start automatically and run in the background once the PC is started. A small icon in the taskbar shows the current status of the entire system. By double clicking on the icon in the taskbar you open the main screen of the software. Features: Set time for function test and start test Set time for battery duration test (endurance test) and start test Logbook function for all connected systems Automatic sending of e-mails after test or failure found

36

45

90

48 58

InoWeb Control HUB Ethernet

G/

+24V
RS232

G/

+24V
RS232

G/

+24V
RS232

InoWeb
reset RTG

InoWeb
reset RTG

InoWeb
reset

INOTEC InoLan 990 063 GND RxD TxD

INOTEC InoLan 990 063 GND RxD TxD

INOTEC InoLan 990 063 GND RxD TxD

CPS

CPS

CPS

System requirements: Operating system: Win 98/2000/XP/Vista Ultimate/Vista Business/Vista Enterprise Screen: VGA (800x600), 256 colours and above Hard disc capacity: min. 200 MB (without log book 25MB) Interface: Network interface Network protocol: Ethernet (IEEE 802.3), TCP/IP v4, HTTP Software: MS Internet Explorer Version min. 6.0.2800.1106

RTG

17

CPS 220/SV
Technical data, systems overview
Technical data: Rated voltage: 1~N/PE, 230V AC 10%, 50/60Hz 3~N/PE, 400V AC 10%, 50/60Hz
1030 mm

CPS 220 / 48

CPS 220 / 32

CPS 220 / 16

CPS 220 / 11 / SC

Betrieb Batt.Betrieb Strung Ladestrung

INOTEC
+
TEST
Drucker Cetronics

Key-board

UH 5AT

Betrieb Batt.Betrieb Strung Ladestrung

INOTEC
+
TEST
Drucker Cetronics

Key-board

UH

830 mm

830 mm

800 mm

Protection class: I Protection category: IP20

5AT

Betrieb Batt.Betrieb Strung Ladestrung

INOTEC
+
TEST
Drucker Cetronics

Key-board

UH 5AT

Betrieb Batt.Betrieb Strung Ladestrung

INOTEC
+
TEST
Drucker Cetronics

Key-board

UH 5AT

Perm. ambient temperature for system: - 5C bis + 35C for battery: see battery data sheet
1200 mm 1200 mm 1200 mm

Battery voltage: 220V DC Charger: 3Amp or 7,5Amp Housing color: RAL 7035 Plinth (optional) 100mm or 200mm Cable inlet from top

Depth 400 mm 800 mm

Depth 400 mm 800 mm

Depth 400 mm 800 mm

1000 mm

Depth 300 mm 600 mm

Free module slots (2 x 3A or 1 x 6A) Space for options *2 - with function preservation Supply 3-phase (option) Max. installed battery capacity Conductor cross section, max. (mm) Mains supply Battery supply Outgoing to luminaires Outgoing data line (RTG) Outgoing 24V monitoring Outgoing mains to CPUS Outgoing battery to CPUS Dimensions H x W x D (mm) with function preservation (option) - with function preservation Cable inlets

24 14 TE yes 70 Ah 35 35 4 4 4 35 35 2230 x 800 x 400 22 x M 20 64 x M 25 6 x M 32 2 x M 50 3TE


for sub-station (Neozed)

16 19 TE yes 70 Ah 35 35 4 4 4 35 35 2030 x 800 x 400 BRS 10 *1 2460 x 1200 x 595 22 x M 20 64 x M 25 6 x M 32 2 x M 50 4TE


LSA 8.1 SKW PSU 24

8 25 TE 13 TE yes 70 Ah 35 35 4 4 4 35 35 2030 x 800 x 400 BRS 10 *1 2460 x1200 x 595 22 x M 20 64 x M 25 6 x M 32 2 x M 50 5TE 6TE
LSA 8.1 INV 24V incl. 4 terminals

11 12 TE 12 TE 27,8 Ah 16 35 4 4 4 1800 x 600 x 300 BRS 10 *1 2460 x 1200 x 595 4 x M 32 33 x M 25 10 x M 20

Required space for options 1TE 2TE


J-Modul S/U DSM/U1 DP INOLAN INOWEB DP/B1 Fuse protection Battery NH00 (as a replacement for Neozed) (CPS 5/11) TLS 1 + terminal Terminal - requirement for mains supply 3-phase Mains supply terminals for sub-station - 3-phase

7 TE
TLS 5

Fuse protection Battery supply RIF 5

PSU 48 Terminals for sub-station at CPS 16/32/48

18

CPS 220/SV
Technical data, systems overview
CPS 220 / 5 / SC CPS 220 / 5 / SC CPUS 220 / 48 CPUS 220 / 32 CPUS 220 / 16

600 mm

Betrieb Batt.Betrieb Strung Ladestrung

INOTEC
+
TEST
Drucker Cetronics

Key-board

UH 5AT

600 mm

Betrieb Batt.Betrieb Strung Ladestrung

INOTEC
+
TEST
Drucker Cetronics

Key-board

UH 5AT

1000 mm

Betrieb Batt.Betrieb Strung Ladestrung

INOTEC
+
TEST
Drucker Cetronics

Key-board

UH 5AT

Betrieb

INOTEC
+
TEST
Drucker Cetronics

830 mm

830 mm

Batt.Betrieb Strung Ladestrung

Key-board

UH 5AT

600 mm

600 mm

Betrieb Batt.Betrieb Strung

INOTEC
+
TEST
Drucker Cetronics

Depth 300 mm 600 mm

Depth 300 mm 600 mm

Depth 400 mm 800 mm

Depth 400 mm 800 mm

Depth 300 mm
Ladestrung

Key-board

UH 5AT

600 mm

5 15 TE 15 TE 27,8 Ah

5 15 TE 12 Ah

24 11 TE yes -

16 16 TE 3 TE -

8 22 TE 9 TE -

16 35 4 4 4 -

16 35 4 4 4 -

35 35 4 4 4 830 x 800 x 400 BRS 08 1374 x 624 x 334 22 x M 20 64 x M 25 6 x M 32 2 x M 50

35 35 4 4 4 830 x 800 x 400 BRS 08 1374 x 624 x 334 22 x M 20 64 x M 25 6 x M 32 2 x M 50

35 35 4 4 4 600 x 600 x 300 BRS 08 1374 x 624 x 334 4 x M 40 33 x M 25 10 x M 20

1600 x 600 x 300 1200 x 600 x 300 BRS 10 BRS 10 2460 x 1200 x 595 2460 x 1200 x 595 4 x M 40 33 x M 25 10 x M 20 4 x M 40 33 x M 25 10 x M 20

*1 max. 55Ah *2 Standard: mains 1ph., 24V-monitoring loop, ext.-dataline, terminals for outgoing circuits, battery fuse (Neozed) Attention: take care of the max. cable inlet number!!!

19

CPS 220/SV
Technical data, systems overview
Technical data: Rated voltage: 1~/N/PE, 230V AC 10%, 50/60Hz Protection class: I Protection category: IP54 optional for electronics compartment Perm. ambient temperature for system: -5C bis +35C Housing color: RAL 7035 Cable inlet from top CPUSB 220 / 6
Wall mounting enclosure
500 mm

CPUSB 220 / 6
F30 wall mounting

CPUSB 220 / 6
F30 recessed mounting

CPUSB 220 / 6
for panel mounting

600 mm

874 mm

574 mm

500 mm

Depth 150mm 400 mm

Depth 334 mm 624 mm

Depth 334 mm 624 mm

335 mm

Depth 65 mm 380 mm

Number of circuits 3A CPUSB 220 / SK CPUSB 220 / SV CPUSB 220 / J / SV or J / SK Conductor sizes(mm): Mains supply Battery supply Outgoing to luminaires Outgoing data line (RTG) Dimensions H x W x D (mm) Cable inlets
*1 fixed number of circuits

2/4/6 2/4/6 2/4/6

2/4/6 2/4/6 2/4/6

2/4/6 2/4/6 2/4/6

2/4/6 2/4/6 2/4/6

10 10 4 4 600 x 400 x 150 4 x M 32 13 x M 25

10 10 4 4 1374 x 624x 334 2 x d=36mm 16 x d=21mm

10 10 4 4 1074 x 624 x 334 4 x d=29mm 13 x d=21mm

10 10 4 4 335 x 380 x 65 -

Custom built, sample design

+ + 24VBUS
BIF INOTEC

extern
990013

+ + 24V24V

+ + BUSBUS

9 0 1 8 7 6 5 4 2 3 8 7

9 0 1 6 5 4 2 3

CPS 220
Betrieb Batt.Betrieb Strung

SU / SV - J 2x3A

SU / SV - 2x3A

SU / SK- J 2x3A

SU / SV - 1x6A

SU / SK - 2x3A

SU / SK - 1x6A

SU / SV - 2x3A

SU / SK- J 2x3A

INOTEC
SV-ZENTRALE
01.07.95 12:00

Strung Si 5AT BLEin DLEin

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT

Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin

+
TEST

Betrieb
Funktionstest 2.7.95 8:30

Si 5AT Ladestrung

Si 5AT Strung Si 5AT BLEin DLEin Si 10AT Ein Strung Si 5AT Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin

Drucker Cetronics

800 mm

Key-board

Strung Si 5AT BLEin DLEin

Ein Strung Si 5AT

UH 5AT

SU / SV - J 2x3A

SU / SV - 2x3A

SU / SK- J 2x3A

SU / SV - 1x6A

SU / SK - 2x3A

SU / SK - 1x6A

SU / SV - 2x3A

SU / SK- J 2x3A

Strung

Netz Netz

Batterie 10AT

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT

Si 5AT

BLEin DLEin

Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin

Si 5AT Strung Ein Strung Si 5AT Si 5AT Strung BLEin DLEin Si 10AT Si 5AT

Si 5AT Ein Strung Si 5AT Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin

Ein

BLEin DLEin

Ladeteil 220V / 7,5A


SU / SV - J 2x3A SU / SV - 2x3A SU / SK- J 2x3A SU / SV - 1x6A SU / SK - 2x3A SU / SK - 1x6A SU / SV - 2x3A SU / SK- J 2x3A

Netz Netz

Batterie 10AT

Strung Si 5AT BLEin DLEin

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT

Ein Strung Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT

Strung BLEin DLEin

Si 5AT Strung Ein Strung Si 5AT Si 5AT Strung BLEin DLEin Si 10AT

Si 5AT Ein Strung Si 5AT Si 10AT

Si 5AT Ein Strung Si 5AT Si 5AT Strung BLEin DLEin

Ein

Si 5AT

BLEin DLEin

Ladeteil 220V / 7,5A

Depth 400 mm 200

Depth 400 mm

Depth 400 mm

Depth 400 mm

Technical data: Rated voltage: 1~/N/ PE, 230V AC 10%, 50/60Hz 3~/N/PE, 400V AC 10%, 50/60Hz Protection class: I Protection category: IP20 for battery compartment IP54 for electronics Perm. ambient temperature for system: -5 C to +35 C for battery: see datasheet Battery: 220V DC, max. 182Ah Charger: 2 x 7,5A Color: RAL 7035 Plinth (optional) 100mm or 200mm Cable inlet from top Dimensions H x W x D (mm) 2030 x 3200 x 400 2130 / 2230 x 3200 x 400 (optional)

1200 mm

800 mm

800 mm

800 mm

800 mm

20

CPS 220/SV
Designing a CPS-system
The dimensioning of a CPS-central battery system can be achieved with the given table contents and the below described way in a fast and easy way. Step 1 - Select number and type of luminaires The positioning of the required luminaires on a given project drawings has given us the number of safety- and Exit-luminaires. The Exit luminaire types have been selected out of the INOTEC range (see table A / sample); for the safety luminaire we do supply 200 electronic ballasts type J-EVG 4-13W for 13W TC-DEL. Step 2 - Calculate battery current Table 1 gives IBat per luminaire which allows us to calculate the total required battery current; 14,08A in our sample. Step 3 - Define circuits and change over devices As we do not want to have more than 10 luminaires on every circuit we can define the total number required (36). But want to have the possibility to mix maintained and non-maintained on the same output and therefore use J-SU/SV 2x3A change-over modules. Step 4 - Select battery The building type and local standards define the required emergency duration (1h, 2h, 3h or 8h). With this in mind and the calculated IBat total we select the battery required. Considering specific project requirements (spare capacity / aging effect 25%) we should at least have 14,8 + 25% = 18,8A. Table 4 shows us at the 3h column that we do require a 75,3Ah battery with Imax 19,2A. Step 5 - Select charger required Table 5 gives us the number and type of charger(s) required (as per EN 50171 for recharge of 80% capacity within 12hours) for the selected battery. We have to use 7,5A. Table B our example Luminaire type Qty. SNP 1018 J/SV (8W FL) SNP 7188 J/SV (8W FL) J-EVG 4-13W fr 13W TC-DEL Charger 3 A Charger 7,5 A Over all 40 120 200 1 Load [VA] mains 8,4 8,4 14,0 1109 2587 Load [kVA] mains over all 0,34 1,01 2,80 2,59 6,73 Table A our example Luminaire type SNP 1018 J/SV (8W FL) SNP 7188 J/SV (8W FL) J-EVG 4-13W for 13W TC-DEL Over all Qty. 40 120 200 360 IBat. [A] IBat. [A] Outgoing Circuit modules luminaire over all circuit 2x3A 0,033 1,32 4 2 0,033 0,044 3,96 8,80 14,08 12 20 36 6 10 18

Step 6 - Mains load and back-up fuses Table 1 gives us the load for all luminaires which we put into Table B / sample. The charger selected we can now complete Table B / sample and calculate the complete mains load. The complete load gives us in table 6 the back-up fuse for the system (single phase supply). After completion of this data we are now in a position to select a CPS - system. Depending on the building limitations, installation preferences and space available we can choose (see pages 18 - 20) various system options with/without substations. Some possibilities are: - One CPS 220 SV/48 with 7.5A charger, 36 circuits 3A (18 modules J-SU/SV 2x3A) and 75,3Ah battery compartment - One CPS 220 SV/32 with 7.5A charger, 26 circuits 3A (13 modules J-SU/SV 2x3A) and 75,3Ah battery compartment plus one substation CPUS 220/16 with 10 circuits 3A (5 modules J-SU/SV 2x3A)

21

CPS 220/SV
System design and tables
Battery current for lamps used for emergency / safety lights. Table 1 Data for INOTEC high frquency ballasts during mains- and battery operation. Lamp type T 16 Base G5 INOTEC EVG 4-6W / 4-13W 4-6W / 4-13W 4-13W 4-13W 4-13W 4-13W 4-13W 4-13W 4-13W 4-13W 18W 13W 18W 18W 36W
(50% / 100% Light output)

Lamp 4W 6W 8W 13W 5W 7W 9W 11W 10W 13W 18W 13W 18W 18W 36W 58W 18W 18W

TC-SEL

2G7

TC-DEL

G 24 q1 G 24 q2 GX 24 q1 GX 24 q2 G 13

TC-TEL T 26

IBat. Mains [mA] load [VA] 20 4,2 25 6,3 33 8,4 44 14 24 5,3 26 7,4 33 10 44 12 35 11 44 14 90 19 44 14 90 19 90 19 100 / 150 37 140 / 235 90 90 60 19 19

58W
(50% / 100% Light output)

TC-F TC-L

2 G 10 2 G 11

18W 18W

Table 2 Data for INOTEC LED luminaire with Power LED. (J-ET 9/24 ... SV) For specific luminaire details see luminaire catalogues. Qty. LED 1W 1 2 3 4 5 6 IBat. [mA] 12 18 25 32 40 45 Mains load [VA] 4,8 8,3 9,8 11,1 13,2 14

Table 3 Data for glow wire lamps (AGL) and halogen lamps with electronic transformer. 220V Glow wire lamp 7W 15 W 25 W 40 W 60 W 75 W 100 W IBat. [mA] 30 70 110 180 270 340 450 Halogen lamp 20 W 35 W 50 W 75 W 100 W IBat. [mA] 115 210 285 420 560

22

CPS 220/SV
System design and tables
Table 4 Battery data Capacity C10-1,8V/Z 5,0 8,0 12,0 18,1 27,8 33,0 45,4 50,9 69,2 74,0 75,3 81,4 91,8 91,0 102,1 134,0 153,6 205,2 Weight [kg] Block Total 2,5 45,0 3,6 64,8 5,6 100,8 5,9 106,2 10,0 180,0 11,8 212,4 14,9 268,2 18,2 327,6 26,1 469,8 31,3 563,4 24,1 433,8 26,4 475,2 30,1 541,8 37,2 669,6 33,1 595,8 42,5 765,0 47,0 846,0 67,2 1209,6 Housing Max.discharge current [A] Batt. 8h 3h 1h 1*1 0,7 1,5 3,2 1*1 1,0 2,1 4,5 1*1 1,3 2,8 6,2 1*1 2,0 4,8 11,0 1*1 3,4 8,3 20,8 1*1 4,0 9,2 22,8 5,3 12,0 28,9 1*1 1*1 6,2 14,5 35,2 1*1 8,4 19,6 46,5 1*1 8,9 20,3 51,0 1*1 8,7 19,2 47,5 2*2 9,6 21,6 55,1 2*2 10,8 24,1 60,3 2*2 11,1 25,3 64,0 2*2 12,2 28,6 69,8 2*2 15,8 35,2 78,0 18,2 41,4 102,2 24,7 58,2 143,2

*1 Battery housing included in CPS assembly *2 1 Battery housing included in CPS assembly

Table 5 Chargers and ventilation Recharging 12 hours / 80% Capacity C10 -1,8V/Z 5,0 8,0 12,0 18,1 28,7 33,0 45,4 50,9 69,2 74,0 75,3 81,4 91,8 91,0 102,1 134,0 153,6 205,2 Qty. charger 3,0 A 7,5 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 Free airflow [m / h] 0,03 0,04 0,06 0,10 0,15 0,18 0,25 0,27 0,37 0,40 0,41 0,44 0,50 0,49 0,55 0,72 0,83 1,11 Ventilation [ cm ] 0,90 1,20 1,70 2,80 4,20 5,10 7,00 7,60 10,40 11,20 11,50 12,40 14,00 13,80 15,40 20,20 23,30 31,10

Table 6 Fuse protection mains supply Over all connection power Table 6 Fuse protection Min. conductur cross-section

to 8 kVA 35A 6mm

8 - 11 kVA 11 - 14 kVA 14 - 18 kVA 18 - 22 kVA 50A 63A 80A 100A 10mm 16mm 25mm 35mm

The specificaton are min. conductur cross-sections. For the max. permissible line drop the dimensioning of the conductor is to be made according to the distance and the connection power. (max.line drop: 3%)

23

INOTEC Sicherheitstechnik GmbH Am Buschgarten 17 D - 59 469 Ense Tel Fax +49 29 38/97 30-0 +49 29 38/97 30-29 info@inotec-licht.de www.inotec-licht.de

Sicherheitstechnik GmbH

707 064 Ausgabe 2009/08