INTRODUCTION
Radiation hazard
pick up from antenna and consequent problem with transmitter circuit
Normally this distance is either on 50 V/m field strength contour or minimum
half the wavelength at frequency of operation.
The feeder line should carry the power from the transmitter to Antenna with
Minimum loss
Minimum radiation.
There are three types of transmission lines used at RF. They are :
Characteristics impedance (Zo) is defined as the input impedance of an infinite line. This
is determined wholly by the geometry of its cross section. A transmission line can be
represented as having R, L,C.
Induction Course (Radio)
The inductance, resistance, capacitance and conductance of the line determine the
characteristics impedance. This is shown in the figure 1. G is the conductance of the
line.
Balanced lines : Where there are equal and opposite potential in both
wires.
Unbalanced lines : Here one wire is at high potential and the other side
is at low potential.
Z0 276 log 2 S / d
d
S
In MW band, normally the feeder lines used are unbalanced and has following
characteristics.
In SW, normally the balanced feeder lines are used. The impedances are
Copper Loss
R.F. Wave travels along the exterior of a conductor due to skin effect. The conductor
gets heated up resulting in losses in the feeder line. It can be reduced by increasing the
radius of conductor and also by using more no. of wires in parallel. It is directly
proportional to square root of frequency, so higher the frequency, more the losses.
Earth Loss
In unbalanced open wire lines there is division of charges between ground wires and
that induced in the earth under feeder lines resulting in part of the return current in the
ground. The rotation of return current in the grounded wires and to the total current in
live wires decides earth losses. It can be reduced by laying two nos. of copper wires in
the ground through out the length of feeder wire line and by increasing the height.
Radiation Loss
One cause of radiation from open lines is from the vertical connections at the ends.
Decreasing the height can reduce it, but if height is decreased, the ground losses will
increase. So best way-out is to use better shielding of high potential wires by using
greater number of ground wires.
When the feeder line impedance is chosen low, feeder current will be more, resulting
increase in copper loss and earth loss. When feeder line impedance is high, feeder
voltage will be high resulting in the use of higher voltage rating insulators. So the choice
depends upon the availability of components and technology in use.
230 ohm 6 wire (open wire) lines for all old 100 kW as well as 10/20 kW.
60 ohm quasi coaxial feeder line - megawatt of Chinsuraha, Rajkot and
Nagpur.
120 ohm quasi coaxial feeder - all 300 kW and all 100/200 kW new
version.
This type of feeder line is most popular and has been used in all old installations of
10/20/100 kW/MW XTRs. There are total 6 wire (8 SWG, app 4.064 mm). Two inner
are on high potential and four outer are ground conductors
In which there are 8 inner wires and 8 outer wires each of 8 SWG. This has
been used in all 100/200/300 kW XTRs.
In which there are 12 inner conductors of 6 mm dia and 16 screen conductors
of 8 SWG and this has been used at 1000 kW Nagpur, Calcutta (Chinsuraha)
and Rajkot.
Zo Z oc .Z sc
Zoc = Open circuit Impedance, measured at input by keeping the feeder line end open
Zsc = Short circuit Impedance, measured at input by keeping the feeder line end short
Generally Zoc & Zsc are either capacitive or inductive depending upon the length of
feeder line as multiple of /4.
Zoc & Zsc can be measured with VIM or RF bridge by keeping the line open and shorting
high potential wire (inner) with ground wire (outer) at other end.
Another method utilises the fact that when the feeder line is terminated by its
characteristic impedance, its input impedance is equal to the characteristic impedance.
Input impedance is measured for various termination. The characteristic impedance is
equal to that termination for which input impedance is same as the termination itself.
In practice, the maximum voltage that a line can handle/withstand with out flashover etc.
is 80% of the D.C. Value of max. voltage.
Bends should be gradual and free of any sharp corners (preferably of 120o or
so).
The exact and equal length of wires should be used at bends. To keep the
length same is more important than to maintain the equal spacing as it
increases the series inductance of line.
The poles should be placed at equal distance and symmetrically (app. 15
mtr),
Splitting joints should be smooth and free of any irregularity.
The height above ground should be uniform otherwise ground return current
will differ, varying the earth losses.