7/2001
Standard Operating Procedure for 1200 C Box Furnace Model: BF51732BC, Manufacturer: Lindberg/Blue M
I. Safety and Precautions
1. Do not unplug the furnace. 2. Do not move the furnace. 3. Use both door handles to open and close the door vertically. 4. Do not touch the insulator on the inside chamber walls. 5. Never inhale the particles of the insulator. 6. Get MSAL Supervisor approval before putting any new material in the furnace. 7. Use a sample boat or rack compatible with your process temperature. 8. Do not touch the furnace walls when operating at high temperature. 9. Use a crucible tong to handle the sample boat or rack when the furnace is hot. 10. Turn off the furnace completely when not in use. 11. Do not change settings of the controllers other than those referred to in this SOP. For other settings inform MSAL Supervisor. 12. Close the nitrogen cylinder valve and flowmeter knob when not in use. 13. Never exceed the maximum flow of the flowmeter (13 slpm).
II. Turning on the Furnace and Running and Stopping a Stored Program
1. Turn on the furnace by means of the MAIN POWER SWITCH (located at the bottom right corner of the front panel). After a few seconds, the PV displays (red, upper displays) on both controllers show the inside chamber temperature, the SP display (green, lower display) on UP150 controller shows the initial set point of the stored program, and the SP display on UT150L controller shows the set point of the limit control. All other lamps must be off. 2. If the OUT lamp on UT150L controller is on, press and hold RESET key on UT150L controller for at least one second to turn off the OUT lamp. 3. To run a stored program, press and hold RUN key on UP150 controller for at least one second. POWER lamp (located left to MAIN POWER SWITCH) and RUN lamp turn on and the controller starts the program. 4. To stop a running program press and hold RESET key for at least one second.
Page 1 of 2
7/2001
22.5. Change the SP display using the UP/DOWN keys according to the optimized PID coefficients table for integral coefficient. When the decimal point flashes, press SET/ENT key once to confirm the change. 22.6. Press SET/ENT key once. d appears on PV display. 22.7. Change the SP display using the UP/DOWN keys according to the optimized PID coefficients table for derivative coefficient. When the decimal point flashes, press SET/ENT key once to confirm the change. 22.8. Press and hold SET/ENT key for at least 3 seconds to exit the program parameters setting mode. The program is ready to run.
V. Monitoring the Program Status During Operation and Using Hold/Advance Functions on UP150 controller
1. When running a program, PV display always shows the chamber temperature, but SP display initially shows the target set point at the moment. The status of the running program can be monitored. 1.1. Press SET/ENT key once to see the current segment number on SP display. SEG lamp turns on in this state. 1.2. Press SET/ENT key again to see the remaining segment time on SP display. SEG lamp turns on in this state. 1.3. Press SET/ENT key again to return to he initial SP display. 2. A running program can be hold at any moment. 2.1. Press and hold SET/ENT key for at least 3 seconds. HoLd appears on PV display and oFF on SP display. 2.2. Change the SP display to on using UP/DOWN keys. When the decimal point flashes, press SET/ENT key once to confirm the change. 2.3. Press and hold SET/ENT key for at least 3 seconds to return to normal display. HLD lamp turns on. 3. To exit the hold mode: 3.1. Press and hold SET/ENT key for at least 3 seconds. HoLd appears on PV display and on on SP display. 3.2. Change the SP display to oFF using UP/DOWN keys. When the decimal point flashes, press SET/ENT key once to confirm the change. 3.3. Press and hold SET/ENT key for at least 3 seconds to return to normal display. HLD lamp turns off. 4. A running program can be advanced to the next segment at any moment. 4.1. Press and hold SET/ENT key for at least 3 seconds. HoLd appears on PV display and oFF on SP display. 4.2. Press SET/ENT key once. AdV appears on PV display and oFF on SP display. 4.2. Change the SP display to on using UP/DOWN keys. When the decimal point flashes, press SET/ENT key once to confirm the change. 4.3. Press and hold SET/ENT key for at least 3 seconds to return to initial normal display.
PV display (red) SP display (green) SEG lamp (green) AL1 lamp (red) RUN lamp (orange) HLD lamp (green) UP key (RESET key) DOWN key (RUN key) SET/ENT key
UP150 Controller Front Panel Process Value (chamber temperature), character information (parameter and error codes) Target set point, parameter values Lit when segment number or remaining segment time are displayed Lit when PV exceeds alarm temperature Lit when the operation mode is in RUN, flashed when the operation mode is in WAIT Lit when operation mode is in HOLD mode Increases a parameter value, stops a running program Decreases a parameter value, starts a program Switches the operation display, confirms data change, switches the parameters, changes controller mode
PV display (red) SP display (green) EXCEEDED lamp (green) AL1 lamp (red) OUT lamp (yellow) UP key (RESET key) DOWN key SET/ENT key
UT150L Controller Front Panel Process Value (chamber temperature), character information (parameter and error codes) Limit temperature set point, parameter values Lit while PV exceeds SP value Lit when PV exceeds alarm temperature Lit when PV exceeds SP value, goes out when confirming with RESET key Increases parameter value, puts out OUT lamp, resets PV maximum value and duration time Decreases parameter value Switches the operation display, confirms data change, switches the parameters, changes controller mode
Page 2 of 2