Rated current Rated dreaking current Rated short-time withstand current (3s) Peak withstand current Circuit breaker

Full breaking time Rated operating duty First-pole-clean factor Operating mechanism Rated current Disconnector Rated short-time withstand current (3s) Operating mechanism Rated short-time withstand current (3s) Earthing switch Operating mechanism Rated current Type of enclosure Busbar Material enclosure Material conductor Rated current ratio Capacitive Current transformer Accuracy 1 2

A kA kA kA ms

2000/2500/3150/4000 40/50/63 40/50/63 100/125/160 40/50 O-0.3s-CO-180s-CO 1.5 Pneumatic

A kA

2000/2500/3150/4000 40/50/63 Pneumatic or Motor-spring

kA

40/50/63 Pneumatic or Spring for FES; Manual or Motor for ES

2000/2500/3150/4000 Main bus: 3 phases in 1 enclosure Others: 1 phases in 1 enclosure Steel/Al. Al.
300-400-600-750-1000-1200-1500-2000/5

VA

15/20/25/30/40/50 Measurement:0.2, 0.5; protection:10P20, 5P20

The secondary winding can be supplied for measurement which rated secondary current is 1A. For the higher accuracy of CT, please contact with us for further discussion. Rated primary voltage kV V VA 300/ 3 100/ 3 75~300 Metal oxide-zinc kV kA 200 10 300 363/ 3

Voltage transformer

Rated secondary voltage Rated burden Type

Lightning arrester

Rated voltage Normal discharging current

NR NS

TYPICAL LAYOUT
Double-Busbar Scheme

E 22000 22000

5000

5000

5000

5000

400

M2 M1

3400

3400

3400 D

8400

3400 E

6800 F

5000 G

3400

LCP

LCP

LCP

LCP

LCP

LCP

LCP

LCP

LCP

LCP

BSG

E_E
10T

G_G

DS ES ES DS M2 DS M1

CT CB
4071 9000

DS ES DS M3 M1

CT CB CT
3458

CT OMB
2160 3458

OMB
2160

5400

4240

1200

1200

5000

5000

5000

Key
CB Circuit breaker DS Disconnector ( isolator ) ES Earthing ( grounding ) switch CT Current transformer VT Voltage transformer SM Spring operating mechanism LA Lightning Arrestor FES Fault earthing switch CSE Cable-sealing-end chamber LCP Local contring mechanism BSG Bushing OMB Operating mechanism Box M1-M2 Main busbar

Air Receiver

Compressor Control Panel

6800

LCP

LCP

3500

F_F
VT ES CT ES DS M2 DS M1 CT
3035

D_D
VT ES DS CB AR M2 M1 ES DS ES AR
3458 2300

OMB
2000 2300

2500

1200

1200

NT NU

252kV GIS

1. 252kV GIS for Fujian Xiamen Dongdu North S/S, China; 1999 2. 252kV GIS for Jiangsu Changzhou S/S, China; 2002 3. 252kV GIS for Hangzhou Yunhe S/S, China; 2002 4. 252kV GIS for Chashma Npp Construction, Pakistan; 1995 5. 252kV GIS for Beijing Asian Village S/S, China; 1993 2

FEATURES
1 Safety and reliability
All of live parts of the GIS are sealed in a metal enclosure. The SF6 gas in the enclosure works not only as insulating medium, but also as arc-extinguishing one for CB. The operators are free from the danger of electric shock and the GIS with minimized maintenances.

2 Strong resistance to environment


All of live parts of the GIS are sealed in a metal enclosure, it is therefore unaffected not only by weather, but also by pollution and higher elevation.

3 Minimum work at assembling site


The advanced processing devices and an all-round quality control system have been adopted in the manufacture of the GIS. The GIS is assembled and tested against the conditions of assembling site, packed in transport unit after tested, for easy and convenient transport and minimizing work at site.

4 Reliable conductivity
The self-reliance contact fingers are used in the conductive circuit of the CB. By their own elastic force, those contact fingers press tightly the conductive parts without some other springs so that no disintegration of the springs occurs. The CB has a long life electrically (20 times in opening full capability and 2000 times in opening rated working current).

5 Small loss of eddy current


Almost all the parts of the GIS are made up of aluminum (Except for VT and LA) so that the GIS has a light weight, strong anti-corrosion ability and smaller loss of eddy current.

6 Excellent construction of enclosure


A special cold edge-folded processing is used in the manufacture of the metal enclosure (round tubes) of the GIS so that the welding seams of both vertically intersected tubes are not located on their inter-through lines, improving distribution of electric field and minimizing dimensions construction of GIS.

7 High insulating reliability


The insulating spacers, tubes, levers and insulating desks etc for the GIS are made with the casting machines from Germany and under the chemical directions and production processing from Mitsubishi. The power frequency withstand test and partial discharge test have been done on those parts, and the values of the partial discharge are lower than the requirements by IEC.

NV OM

SWITCHGEAR CROSS SECTION


Double-Busbar Scheme

Key
5

3 1

1 2 3 4 5 6 7 8 9 10

Circuit breaker Disconnector ( isolator ) Earthing ( grounding ) switch Current transformer Voltage transformer Cable-sealing-end chamber Gas barrier Supporting insulator Main busbar Reserve busbar
5

10

Single-line diagram Live parts lnsulator SF6 gas Enclosures


6 4 7 2 8 8

Current transformer

3 3 4 7 2 7 2 3

7 7 7

1 0

MODE OF ARRANGEMENT
The main buses of 3 phases are in a common enclosure, and the other in separate ones. A building-block arrangement is used for the standard parts, which can be extended with flexibility and ease, and meet the different needs for main wiring. The central distance between bays is 3m and that between poles is 0.8m onIy.This GIS has a small size, pocket construction and less assembling space. The CB in the GIS has both vertical type and horizontal one according to the , requirements. (Most of CB s selected are vertical ones ). All of the operating mechanisms for the GIS are arranged at the place where viewing and maintenance is convenient and accessible.

Double-bus bar arrangement of 252kV GIS

lNTRODUCTION TO STANDARD BAYS


At present, the design and production of the GIS have been performed according to the special properties of program and standard function units and bays, accomplishing the standard and modular design and production.

Bushing inlet ( outlet ) bay

Cable inlet ( outlet ) bay

Bus connection bay

VT/LA protection bay

ON OO

TYPICAL LAYOUT
Double-Busbar Scheme
D

3500

3500

3500

3500

A 3500

E 6000 3000

F 3000

G 3000

K 3000 3000 3000

VT

VT 3000 3000

3000

H M2 M1

Compressor Control Panel 12000

D Air Receiver

LCP

LCP

LCP

LCP

LCP

LCP

LCP

3500 E

3500 41000

3500

3500

D_D
BSG VT DS ES DS M2 DS M1 CT CB CT
3035

K_K

VT

6200

DS CSE FES ES DS OMB M3 DS M1


1200

CT CT OMB
2000 4340

ES LA

3500

1300

2500

1200

2000

2500

BSG VT11 LA11 FES11 DS13 CT6 CT5 CT4 ES12 PT32 CB11 CT4 CT3

CSE VT51

BSG VT71 LA11 FES71 DS73 CT6 CT5 CT4 ES72 PT81 CB71 CT3 CT2 CT1 DS72 ES71 DS71

CSE VT91

DS32 CT6 ES34 CT5 CT4 CB41 CT2 CT1 DS31 ES34 DS21 ES21 ES31 DS31 ES32 PT31 ES22 DS23 DS41 ES41 CT3 CT2 CT1

FES51 DS53 ES52

FES91 DS93 CT6 CT5 CT4 ES92

CT3 CT2 CT1 DS12

ES34

CB51 ES51 DS51

ES82 DS81

CB91 CT3 CT2 CT1 ES91 DS91

ES11 DS11

DS52

L 3000

M2 M1

ES81 DS92

DS22 CT1 CT2 CT3 CT4 CT5 CT6

DS62 CT1 CT2 CT3

DS61 ES61

M3 M1

CB21

CB61 CT4 CT5 CT6

ES62 DS63 ES63

M3
BSG

ES23 BSG

M1

VT

L_L
L

E_E
BSG

VT
LCP LCP

ES DS M3
1200

CB DS M2 M2
1200

ES

ES

DS M1

CT OMB
2000 3000 3500

F_F
10T VT VT DS ES
7000

G_ G

H _H

CT ES DS M1 CT
3035 4340

ES ES DS M2
1200

ES DS M1 ES

APPROX4500

DS DS DS M3 M2

M2

OMB
2000

1200

OP OQ

6200

ES

CT

DS

RATINGS
Main Technical Data for 252kV GIS ( Based on IEC )
Ratings Item Unit 252kV Installaton Ambient temperature Humidity (per month) Applied ambient Height above sea level conditions Wind velocity Earthquake intensity Creepage distance Rated voltage Rated current Rated short-time withstand current (3s) Peak withstand current General data Lighting impulse withstand voltage(peak) Power frequency withstand voltage(r.m.s) Rated SF6 gas pressure(exclusive of CB) Annual leakage rate of SF6 gas Rated current Rated dreaking current Rated short-time withstand current (3s) Peak withstand current Circuit breaker Full breaking time Rated operating duty First-pole-clean factor Operating mechanism ms 40/50 O-0.3s-CO-180s-CO 1.5 Pneumatic or Motor-spring kV kV MPa % A kA kA kA 0.4 1 2000/2500/3150 40/50 40/50 100/125 1050 460 0.5 1 min 20 m/s g cm/kV kV A kA kA 35 Horizontal acceleration: 0.15, 0.3 Vertical acceleration: 0.2 Accelerated simultaneously Calculated to rated voltage m 1000~3000 % Indoor or outdoor -30~40 90 At 25 Remarks

1.7, 2.1, 2.5 252


2000/2500/3150 40/50 100/125

Ratings Item Unit 252kV Type Rated current Disconnector Rated short-time withstand current (3s) Operating mechanism Rated short-time withstand current (3s) Earthing switch Operating mechanism Rated current Type of enclosure Busbar Material enclosure Material conductor Rated current ratio Capacitive Accuracy Current transformer 1 VA A kA kA 40/50 Pneumatic or Motor or motor-spring 40/50 Pneumatic or motor-spring for FES manual or Motor for ES 2000/2500/3150 Main bus: 3 phases in 1 enclosure Others: 1 phase in 1 enclosure Steel/Al. Al.
300-400-600-750-1000-1200-1500-2000/5

Remarks

GR/GL A 2000/2500/3150

15/20/25/30/40/50 Measurement:0.2, 0.5; protection:10P20, 5P20

The secondary winding can be supplied for measurement which rated secondary

current is 1A. 2 For the higher accuracy of CT, please contact with us for further discussion. 252/ 3 100/ 3 75~300 Metal oxide-zinc kV kA 200 10

Rated primary voltage Voltage transformer Rated secondary voltage Rated burden Type Lightning arrester Rated voltage Normal discharging current

kV V VA

OR OS

145/126/72.5kV GIS

1. 145kV GIS for Cha Kwo Ling S/S, Hong Kong; 2002 2. 145kV GIS for San Rafael Reservoir, Colombia;1996 3. 145kV GIS for Jalanpantai S/S, Malaysia; 2000 4. 126kV GIS for Dan Jiang Kou Hydraulic Power Works of Hu Bei Provice, China; 1987 5. 72.5kV GIS for Suansom S/S, Thailand;1995 2

FEATURES
1 Superior interrupting capability
The circuit breaker is equipped with self-energized interrupter that is characterized by a self-adapting ability breaking of both small and large currents. These breakers can cope with all known switching phenomena. Their efficiently designed interrupter clears both the severe rate of rise of the recovery voltage of short-line faults and the high recovery voltage peak of out-of-phase interruption. In magnetizing current switching, the overvoltage is less than twice the applied voltage. No restrike or reignition occurs in charging current switching.

2 Reduced maintenance work


The CB is equipped with a spring operating mechanism that is characterized by low operating energy and less maintenance work. Since the spring operating mechanism requires neither compressed air nor hydraulic fluid, inspection and maintenance work is minimized. Also, these breakers seldom require inspection since SF6 gas deterioration and arcing contact wear, owing to arc breaking, are negligible.

3 Minimum operating noise


Since no gas is exhausted from these breakers and no compressed air is used in the spring operating mechanism, operating noise is so low that these breakers can be used in residential areas.

4 Reliable earthquake-withstand capability


These dead tank SF6 circuit breakers are substantially resistant to seismic shock because of their lowered center of gravity.

5 Oil-free and air-free


Since all operating mechanisms are motor spring types, hence neither compressed air supply system nor oil is requested, thus achieving oil-free and air-free, and the service is more reliable and safe.

6 Less gas leakage


The SF6 system is monitored and controlled in decentralized way without SF6 valves and SF6 pipings. The new-typed self-sealing adapters and SF 6 gas densimeters are used so to reduce the possibility of SF 6 gas leakage from outside of GIS, thus reducing SF6 gas leakage.

OT OU

SWITCHGEAR CROSS SECTION


Double-Busbar Scheme

5 4 3 2 3

Key
1 2 3 4 5 6 7 Circuit breaker Disconnector ( isolator ) Earthing ( grounding ) switch Current transformer Voltage transformer Cable-sealing-end chamber

lnsulating spacer 8 Supprting insulator 9 Main busbar 10 Reserve busbar 11 Spring operating mechanism

Live parts lnsulator SF6 gas Current transformer Enclosures

4 7

7 3 7 11 2 3

2 3 6

8 7 9

7 7 10

MODE OF ARRANGEMENT

Double bus arrangement of 72.5~145kV GIS

STANDARD BAYS
At present, the design and production of the GIS have been performed according to the special properties of program and standard function units and bays, accomplishing the standard and modular design and production. Four types of standard bays are shown below.
BSG FES

M2 M1
DS CT1 CT2 DS ES CB1 CT3 CT4 CT5 CB ES DS FES DS

ES CT4 CT3 CT2 CT1 ES

DS

CSE

Bushing inlet ( outlet ) bay

Cable inlet ( outlet ) bay

PT LA

M2 M1
DS ES DS ES

ES DS ES

M2 M1
ES DS DS

CT4 CT3 CB CT2 CT1 PT

LA

Bus connection bay

PT/LA protection bay

OV PM

TYPICAL LAYOUT

Double -Busbar Scheme

1 CSE M1 M2 DS

2 CSE

3 CSE DS

4 CSE

5 CSE DS

6 VT

10 VT

11

12 CSE

13 CSE

14 CSE DS

15 CSE

16 CSE DS M3 M4

DS DS CT CT

DS

CT

DS CT VT LCP

DS

CB LCPSM

CB LCPSM

CB LCPSM

CB LCPSM

CB LCPSM LCP

VT

CB LCPSM CB LCPSM

6000

CB LCPSM

CB LCPSM

CB LCPSM

CB LCPSM

CB LCPSM

CB LCPSM

1500

1500

1500

1500

1500

1500

1500

1500

1500

1500

1500

1500

FES61 VT61 DS91 CT92

VT101 FES101

M1 M2
DS11 DS12 ES11 CT11 CT12 CB11 CT13 ES12 DS13 FES11 CSE11 FES62 VT62 DS22 DS21 ES21 CT21 CT22 CB21 CT23 FES21 DS32 DS31 ES31 CT31 CT32 CB31 CT33 ES32 DS33 FES31 CSE31 DS42 DS41 ES41 CT41 CT42 CB41 CT43 FES42 DS52 DS51 ES51 CT51 CT52 CB51 CT53 ES52 DS53 FES51 CSE11 DS71 ES71 CT71 CT72 CB71 CT73 DS81 DS72 FES72 ES81 CT81 CT82 CB81 CT83 VT102 FES102 DS82 DS111 ES111 FES82 CT111 CT112 CB111 CT113 DS112 DS122 DS121 ES121 FES112 DS132 DS131 ES131 DS142 DS141 ES121 DS152 DS151 ES151 DS162 DS161 ES161

M3 M4

ES122 DS123 FES121

CT121 CT122 CB121 CT123

CT131 CT132 CB131 CT133 FES131 CSE131

CT141 CT142 CB141 CT143 ES142 DS143 FES141 CSE141

CT151 CT152 CB151 CT153 FES151

CT161 CT162 CB161 CT163 ES162 DS163 FES161 CSE161

CSE21

CSE11

CSE121

CSE151

10

11

12

13

14

15

16

Key
CB Circuit breaker DS Disconnector ( isolator ) ES Earthing ( grounding ) switch CT Current transformer VT Voltage transformer SM Spring operating mechanism FES Fault earthing switch CSE Cable-sealing-end chamber LCP Local contring mechanism M1-M4 Main busbar

RATINGS
Main Technical Data for 72.5~145kV GIS ( Based on IEC )
Ratings Item Unit 72.5kV Installaton Ambient temperature Humidity (per month) Applied ambient Height above sea level conditions Wind velocity Earthquake intensity Creepage distance Rated voltage Rated current Rated short-time withstand current (3s) Peak withstand current General data Lighting impulse withstand voltage(peak) Power frequency withstand voltage(r.m.s) Rated SF6 gas pressure(exclusive of CB) Annual leakage rate of SF6 gas Rated current Rated dreaking current Rated short-time withstand current (3s) Peak withstand current Full breaking time Circuit breaker Rated operating duty First-pole-clean factor Operating mechanism O-0.3s-CO-180s-CO 1.5 Pneumatic or Motor-spring m/s g cm/kV kV A kA kA kV kV MPa % A kA kA kA ms 325 140 72.5 35 Horizontal acceleration: 0.4 Vertical acceleration: 0.2 1.7, 2.1, 2.5, 3.1 126 1250/1600/2000 31.5/40 80/100 550 230 0.4 1 1250/1600/2000 31.5/40 31.5/40 80/100 60 650 275 1 min 20 145 Accelerated simultaneously Calculated to rated voltage m 1000~3000 % 126kV 145kV Remarks

Indoor or outdoor -30~40 90 At 25

PN PO

Ratings Item Unit 72.5kV Type Rated current Disconnector Rated short-time withstand current (3s) Operating mechanism Rated short-time withstand current (3s) Earthing switch Operating mechanism Rated current Type of enclosure Busbar Material enclosure Material conductor Rated current ratio Capacitive Accuracy Current transformer 1 VA Steel/Al. Al.
300-400-600-750-1000-1200-1500-2000/5

Remarks 126kV GR/GL 145kV

A kA

1250/1600/2000 31.5/40 Motor or Motor-spring

kA

31.5/40 Motor-spring for FES; Manual or Motor for ES

1250/1600/2000 3 phases in 1 enclosure

15/20/30 Measurement:0.2, 0.5; Protection:10P20, 5P20

The secondary winding can be supplied for measurement which rated secondary

current is 1A. 2 For the higher accuracy of CT, please contact with us for further discussion. Rated primary voltage Voltage transformer Rated secondary voltage Rated burden Type Lightning arrester Rated voltage Normal discharging current kV kA 42 kV V VA 72.5/ 3 126/ 3 100/ 3 75~300 Metal oxide-zinc 73 10 115 145/ 3

126kV GIS of XD is selected by KEMA into its propaganda paper due to successful test.

lnternational production licence of 126/145kV GIS obtained after a successful test in KEMA.

PP PQ

SALES NETWORK OVER THE WORLD

The products are successful in operation in China, Hong Kong SAR, Singapore, Malaysia, Thailand, Colombia, and etc.

SF6 GIS Supply Including Units Under Manufacturing ( as of Dec.2002 )

Number

Rated voltage (kV)

Number of bays

1 2 3 4

550 363/300 252 145/126/72.5

23 78 354.5 2485