Automatic acquisition and recording to min, max and mean values within adjustable sequencing intervals Acquisition of under-and overvoltages from > 10 ms Acquisition of voltage failures from > 10 ms Acquisition of starting or overcurrents from > 10 ms Acquisition of transient events from > 140 s
33
Technical data
Ambient conditions Overvoltage category Voltage measurement Ambient temperature range Storage temperature range Relative humidity Elevation Standard maximum power consumption Battery (internal) Operating time Measuring ranges Cable length Length of measuring loop Measuring error Input impedance Measuring range L-N Fundamental frequency Measuring error 600 V CAT III, 300 V CAT IV -10C ... +40C -20C ... +60C 15 ... 95% (not condensing) 0 ... 2000 m above sea level 180 ... 250 V~ (45 ... 65 Hz) 13 W / 20 VA Li-Ion, 7,2 V 20 min (up to 6 times) 200 Arms, 2000 Arms 2m 45 cm Typ. 1,5% 5 M 0 ... 500 V~ 15 Hz ... 800 Hz 0,20%
02
Voltage measurement
automatic adaptation with digital PLL, based on 57.6 kHz basic scanning frequency (all channels, voltage and current) Voltage and current internal (non-volatile) Serial Network 16 Bit 128 MB Flash USB 1.1 Fast Ethernet 19/100 Base-TX
Order data
Description Portable power quality analyzers Portable four wire network analyzer Flexible current transfomer Type Omniquant mobil MRG 503 LGF HT 3003 FLEX Ordering Code 52.12.015 52.07.404 52.05.205
Technical data
Flexible transformers
Measuring range Output sensitivity Line voltage max. Frequency range Accuracy (250 C) Measuring loop: Lenght (open) Diameter Inner diameter Voltage supply Battery life expectancy
HT 3003 Flex
300A / 3000A AC current, changed by choice 10mV / 1mV pro A 600V 10Hz bis 20kHz (-1dB) +-1% des Messbereiches (45-65HZ) 610mm, double insulated 14,3mm 178mm incl. two AA MN 1500 LR6 Alkali Batteries > 1000 hours
HT 3003 Flex
34