UR Bus Differential Relay

Digital bus protection and metering for HV or EHV busbars.

Features and Benefits


Low impedance bus differential elements FlexLogic and distributed FlexLogic Virtual and expandable I/Os Direct I/O transfer capability User-programmable LEDs User-programmable self tests User-programmable push buttons User-definable display messages Flash memory for field upgrades Common drawout modules Diagnostic features event recording, oscillography User-programmable fault report Multiple settings groups

Protection and Control


High-speed tripping, CT saturation immunity and CT trouble detection Restrained and instantaneous differential protection Phase, Neutral, Ground Instantaneous on time over-current protection Phase under-voltage and neutral and auxiliary over-voltage included Dynamic bus replica FlexElement universal comparator

Monitoring and Metering


Current, voltage, frequency Symmetrical components Trip circuit monitoring

Applications
Integrated bus protection and metering for HV and EHV substations Stand-alone or component in automated substation control system

User Interfaces
RS232, RS485 and Ethernet ports Includes enerVista software

GE Multilin

B30 UR Bus Differential Relay

Protection and Control


The B30, a digital bus differential relay, provides bus protection and metering in one integrated package. As part of the Universal Relay Family, the B30 provides superior protection that includes: Bus Protection The B30 can handle a basic configuration consisting of a single busbar with up to six feeders. Both restrained and unrestrained (instantaneous) differential protection elements are provided. The restrained bus differential element uses both differential and current directional comparison protection principles. The differential element uses a dual-slope, dual-breakpoint characteristic. The restraining current is formed as a maximum of the input currents for better stability during throughfault conditions and faster operation on internal faults. The current directional comparison principle checks the angular relationship between the differential zone currents.

The biased bus differential protection operates in the two-out-of-two mode for low differential currents. For high differential currents, bus protection operates using the differential characteristic alone if CT saturation is not detected. If CT saturation occurs, the relay switches to the two-out-of-two operating mode for better through-fault stability. Dynamic Bus Replica A dynamic busbar replica mechanism is provided by associating the breaker/switch status signals with the differential zone currents. This allows avoiding switching CT secondary circuits when protecting re-configurable busbars. Contact Discrepancy Alarm This function can be accomplished via FlexLogic in conjunction with the dynamic bus replica mechanism. CT Saturation Detection This mechanism detects CT saturation during external faults, without triggering on internal faults. No extra security measures are required, allowing very fast operation on internal fault. The CT saturation detection mechanism analyzes the trajectory of the differential and restraint currents.

CT Failure Detection This function monitors the level of the differential current. When the current remains above a setpoint for a pre-defined interval, a CT alarm occurs. Undervoltage Supervision Optional undervoltage supervision can be used to prevent operation of the differential protection due to CT troubles. Two-phase undervoltage elements are available for this purpose with the provision of voltage inputs. TOC Backup A phase TOC protection function provides backup for each circuit. External Check-Zone An optional external check-zone can be used to prevent operation of the differential protection due to CT troubles. If one B30 current input is left unused and an alternative set of current signals is available from independent CTs, the currents can be combined externally and connected to the relay. Two-phase overcurrent elements are available to check the level of this independently formed differential current to supervise the main differential protection.

Functional Block Diagram

VT input (optional)

Bus currents and the most important logic signals for the case of an external fault. Despite very fast and severe CT saturation, the B30 remains stable.

51P 50N 51N 50G 51G

51P 50N 51N 50G 51G

51P 50N 51N 50G 51G

51P 50N 51N 50G 51G

51P 50N 51N 50G 51G

51P 50N 51N 50G 51G

M e t e r i n g

Restraint Current Current Directional Comparison

CT Saturation Detection CT Trouble (50/74)

87B 50/87

F TM l e x E l e m e n t s

The bus differential protection element picks up due to heavy CT saturation

The CT saturation flag is set safely before the pickup flag Despite heavy CT saturation the external fault current is seen in the opposite direction

The directional flag is not set

The element does not maloperate

B30 Bus Differential Relay

50P

59N

59X

27P
836719AA.CDR

www.GEindustrial.com/Multilin

B30 UR Bus Differential Relay

Typical Wiring
V I

A B C
6H

DIGITAL I/O

CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON SURGE


I

H 8b U 1a U 1b U 1c U 2a U 2b U 2c U 3a U 3b U 3c U 4a U 4b U 4c U 5a U 5b U 5c U 6a U 6b U 6c U 7a U 7c U 8a U 8c U 7b U 8b N1a N1b N1c N2a N2b N2c N3a N3b N3c N4a N4b N4c N 5a N 5c N 6a N 6c N 5b N 7a N7c N 8a N 8c N7b N 8b
Tx1 Rx1 10BaseF Tx2 Rx210BaseF

V I

6H

Wet

DIGITAL I/O

CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON SURGE


I V I

6A

Dry

( DC ONLY )

CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON SURGE

DIGITAL I/O

9D

10BaseT D3b D4b D5b COM D5a D6a D7b

CPU

DC AC or DC

No. 10AWG Minimum

B 1b B 1a B 2b B 3a B 3b B5b HI B 6b LO B 6a B 8a B 8b

POWER SUPPLY

GROUND BUS

MODULES MUST BE GROUNDED IF TERMINAL IS PROVIDED

www.GEindustrial.com/Multilin

I V I V I V I V I V V V V V V V

H 1a H 1b H 1c H 2a H 2b H 2c H 3a H 3b H 3c H 4a H 4b H 4c H 5a H 5b H 5c H 6a H 6b H 6c H 7a H 7c H 8a H 8c H 7b

H1

IA5 IA

F 1a F 1b F 1c F 2a F 2b F 2c F 3a F 3b F 3c F 5a F 5b F 5c F 6a F 6b F 6c F 7a F 7b F 7c

H2 H3

IA1 IB5 IB IB1

F1

H4
CURRENT INPUTS 8C / 8D

IC5 IC IC1 IA5 IA IA1 IB5 IB IB1

H5 H6 H7a H7c H8a H8c H7b

GE Multilin

F2

B30 BUS DIFFERENTIAL RELAY

U1

IC5 IC

U2 U3

IC1

IA5 IA IA1

L 1a L 1b L 1c L 2a L 2b L 2c L 3a L 3b L 3c L 5a L 5b L 5c L 6a L 6b L 6c L 7a L 7b L 7c

U4 U5 U6 U7a U7c U8a U8c U7b

F3

IB5 IB IB1 IC5

CURRENT INPUTS 8C / 8D

IC IC1 IA5 IA IA1 IB5 IB

N1

F4

N2 N3

IB1 IC5

N4 N5a N5c N6a N6c N 5b N7a N7c N8a N8c N7b

IC IC1

IA5 IA IA1 IB5 IB IB1 IC5

S 1a S 1b S 1c S 2a S 2b S 2c S 3a S 3b S 3c S 5a S 5b S 5c S 6a S 6b S 6c S 7a S 7b S 7c

F5

NORMAL ALTERNATE COM 1 TEST ONLY RS485 COM 2 IRIG-B


SURGE GROUND CRITICAL FAILURE 48 VDC OUTPUT CONTROL POWER SURGE FILTER

MODULE ARRANGEMENT

836716 A5 .CDR
F
8 CT

CURRENT INPUTS 8C / 8D

IC IC1 IA5 IA IA1 IB5 IB IB1 IC5 IC IC1

F6

X W V
6

U T
8

S R
CT *

P N M
6 I/O * 8 CT *

J
6

H G

D
9 CPU

B
1 Power Supply

I/O * * Optional

I/O

B30 UR Bus Differential Relay

User-Definable Protection Functions Eight FlexElements can be programmed to respond to any variation in signals measured by the relay.

Monitoring and Metering


Advanced metering functions are common across the UR platform. The B30 provides monitoring and metering of the following currents:
Phase A, B, C, and residual phasors and RMS values Sequence currents phasors Differential and restraint currents for each phase

B30 Guideform Specifications


For an electronic version of the B30 guideform specifications, please visit: www.GEindustrial.com/ Multilin/specs, fax your request to 905-201-2098 or email to literature.multilin@indsys.ge.com.

Voltage metering available with the provision of voltage inputs.

Ordering
B30 - * 00 - H C/P * - F ** B30 E G H 00 H C H P H 8F 8G 8H 8J XX 4A 4B 4C 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 5A 5C 5D 5E 5F - H ** - L ** - N ** - S ** - U ** - W/X ** For Full Sized Horizontal Mount Base Unit RS485 + RS485 (ModBus RTU, DNP) RS485 + 10BaseF (MMS/UCA2, ModBus TCP/IP, DNP) RS485 + Redundant 10BaseF (MMS/UCA2, ModBus TCP/IP, DNP) No Software Options Horizontal (19" rack) Horizontal (19" rack) with 16 user-programmable pushbuttons 125 / 250 V AC/DC 24 - 48 V (DC only) Standard 4CT/4VT 4CT/4VT (1 Sensitive Ground) Standard 8CT 8CT (2 Sensitive Ground) No module 4 Solid State (No Monitoring) MOSFET Outputs 4 Solid State (Voltage w/opt Current) MOSFET Outputs 4 Solid State (Current w/opt Voltage) MOSFET Outputs 14 Form-A (No Monitoring) Latchable Outputs 8 Form-A (No Monitoring) Outputs 2 Form-A (Voltage w/ opt Current) & 2 Form-C Outputs, 8 Digital Inputs 2 Form-A (Voltage w/ opt Current) & 4 Form-C Outputs, 4 Digital Inputs 8 Form-C Outputs 16 Digital Inputs 4 Form-C Outputs, 8 Digital Inputs 8 Fast Form-C Outputs 4 Form-A (Voltage w/ opt Current) Outputs, 8 Digital Inputs 6 Form-A (Voltage w/ opt Current) Outputs, 4 Digital Inputs 4 Form-C & 4 Fast Form-C Outputs 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs 4 dcmA Inputs, 4 dcmA Outputs 8 RTD Inputs Maximum: 4 outpus 4 RTD Inputs, 4 dcmA Outputs Maximum: 24 I/O channels 4 dcmA Inputs, 4 RTD Inputs 8 dcmA Inputs 820 nm, multi-mode, LED, 1 Channel 1300 nm, multi-mode, LED, 1 Channel 1300 nm, single-mode, ELED, 1 Channel 1300 nm, single-mode, LASER, 1 Channel 820 nm, multi-mode, LED, 2 Channels 1300 nm, multi-mode, LED, 2 Channels 1300 nm, single-mode, ELED, 2 Channels 1300 nm, single-mode, LASER, 2 Channels Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels 1550 nm, single-mode, LASER, 1 Channel 1550 nm, single-mode, LASER, 2 Channels Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER IEEE C37.94, 820 nm, multimode, LED, 1 Channel IEEE C37.94, 820 nm, multimode, LED, 2 Channel

8F 8G 8H 8J XX 4A 4B 4C 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 5A 5C 5D 5E 5F

XX 4A 4B 4C 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 5A 5C 5D 5E 5F

8F 8G 8H 8J XX 4A 4B 4C 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 5A 5C 5D 5E 5F

XX 4A 4B 4C 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 5A 5C 5D 5E 5F 7A 7B 7C 7D 7H 7I 7J 7K 7L 7M 7N 7P 7R 7S 7T 7W 72 73 74 76 77

Accessories Interactive UR Training CD-ROM available. Visit www.GEindustrial.com/multilin/trainingcd to order.


Ordering Note:This order code is valid for the latest version of UR hardware and firmware version 4.0. The older hardware and previous firmware versions are still available and may be ordered through the usual channels. In addition, upgrade kits are available for users who wish to take advantage of the features in the newer models. Please see the GE Multilin On-Line Store (https://pm.geindustrial.com/login.asp) for the most up to date ordering information.

rev: 2.25.2004