nxuong-BMTBD-TBD-V1

Functions of a miniature circuitbreaker


Trip in case of overload or short-circuit Break overcurrent (overload, short-circuit) Secure on mounting device Connect to load and line Switch on-off upon user s request Withstand electrical and mechanical schocks

nxuong-BMTBD-TBD-V1

The Technology

Top terminal : thermal strip :

connection overload tripping

Power contact : overcurrent breaking Arc chute : toggle : switch-on / off upon user s request overcurrent breaking

magnetic coil :

short-circuit tripping

Bottom terminal : connection

Clip :

securing

nxuong-BMTBD-TBD-V1

Time / current tripping curve

Overload protection: thermal tripping device Cable thermal withstand limit

Short-circuit protection : magnetic tripping device

nxuong-BMTBD-TBD-V1

Overload protection
A bimetal strip is used to protect the cable against overloads : avoid current exceeding cable heating withstand

symbol:

bimetal tripping bar

nxuong-BMTBD-TBD-V1

Overload protection acc. to IEC / EN 60 898 standards


time (sec) 3600 / 7200

In = rated current

60 / 120 NO TRIP TOLERANCE 100% TRIP 1.13 In x In 1.45 x In 2.55 x In 1

Current (I/ In)

nxuong-BMTBD-TBD-V1

Short-circuit tripping device


A magnetic coil is used to protect the cable against shortcircuits

symbol

magnetic coil

nxuong-BMTBD-TBD-V1

Short-circuit tripping
Magnetic tripping curve acc. to IEC / EN 60 898 standard
time (sec)

In = rated current

NO TRIP TOLERANCE 100% TRIP

0.1 sec

Type B Type C Type D

3 5 10

5 10 20

Current ( I/In)

nxuong-BMTBD-TBD-V1

Selection of tripping curve


B curve Tripping: 3 to 5 In (IEC 60898); protection of generators, long cables... C curve Tripping: 5 to 10 In (IEC 60898); general applications : lighting, power outlets D curve Tripping: 10 to 20 In (IEC 60898), 10 to 14 In protection of circuits with high current inrush: transformers, motors, sodium lights, large inductive loads

nxuong-BMTBD-TBD-V1

Switching off short-circuit current


IEC 60 364: the breaking capacity (Icn) of the circuit-breaker must be greater than or equal to the prospective short circuit-current (Isc). The prospective short-circuit current (Isc) depends on the power of the supply system (transformer) the impedance of the cable in between

Example Example : : for a usual 630 kVA transformer (delivering 800 Amps) for a usual 630 kVA transformer (delivering 800 Amps) : : Isc = 22 kA rms at transformer terminals; --Isc = 22 kA rms at transformer terminals; -Isc = 9 kA at the end of 120 sq.mm / /50 m cable - Isc = 9 kA at the end of 120 sq.mm 50 m cable Isc = 5 kA at the end of add. 35 sq.mm 30 m cable --Isc = 5 kA at the end of add. 35 sq.mm / /30 m cable

nxuong-BMTBD-TBD-V1

10

C60 circuit-breaker choice tables

nxuong-BMTBD-TBD-V1

11

MCB Tripping Characteristics B, C and D Types


B, C and D curves, as in standard 60898 (NF C 61-410) The operating range of the magnetic release is as follows: for B curve: between 3 In and 5 In, for C curve: between 5 In and 10 In, for D curve: between10 In and14 In The curves show the cold thermal tripping limits when poles are charged and the electromagnetic tripping limits with 2 charged poles.

nxuong-BMTBD-TBD-V1

12

Energy Let-through Characteristics

nxuong-BMTBD-TBD-V1

13

Temperature derating according to ambient temperature


Ambient temperature is the temperature inside the enclosure or switchboard in which the circuit-breakers are installed. C60N: B and C curves

nxuong-BMTBD-TBD-V1

14

c thng s MCB

multi9 C25 400Va 6000 3


10kA IEC 947.2

1 3

2 4

nxuong-BMTBD-TBD-V1

15