Anda di halaman 1dari 2

Electronic Pressure Measurement

Differential Pressure Transmitters Type A2G-55, air2guide ECO

WIKA Datasheet A2G-55

Applications
Measuring the differential pressure of air and other Monitoring of overpressure in clean rooms

non-combustible and non-aggressive gases. and laboratories.

Monitoring of overpressure in containment systems

Ideal for the building automation to monitor air ventilation

ducts and air filters

Special Features
Easy installation Maintenance free Compact and robust construction ECO differential pressure transmitter air2guide ECO Type A2G-55

Description
Version Electromagnetic compatibility per 89/336/EEC 2002/95/EG RoHS (restriction of the use of certain hazardous substances in electrical and electronic equipment) Accuracy Linearity error: 1.0 % FS Measuring accuracy at + 32...122 F: 3.0 % FS at +14...+50 C: 5.0 % FS Typical overall deviation: 2.0 % FS Measuring ranges 0 1 InWC, 0 2 InWC, 0 3 InWC, 0...4 InWC, 0...5 InWC, 0 10 InWC, 0 15 InWC, 0 20 InWC, 0 25 InWC Maximum pressure Ranges: 0 1 InWC up to 0 3 InWC: 20 InWC Ranges: 0 4 InWC up to 0 25 InWC: 5 times full scale Burst pressure Ranges 0...1 InWC up to 0 ... 3 InWC: 40 InWC Ranges 0...4 InWC up to 0 ... 25 InWC: 10 times of full scale Operating temperature Ambient: -4 ... +160 F Media: +14... +122 F Ingress protection NEMA 3 (IP 65 per EN 60529 / lEC 529) Weight 8.7 ounces

WIKA Datasheet A2G-55 05/2011

Page 1 of 2
R

Standard features
Process connection Hose barb 0.2, stainless steel Measuring element Piezoresistive sensor (Silizium) Case Plastic (ABS) Electrical connection PG-Gland M16 Output signal DC 0 10 V, 3-wire Optional 4 20 mA, 2-wire Supply voltage DC 13 ... 32 V Long-term stability 0 ...250 to 0... 750 Pa: 8 Pa annually 0 ...1,000 to 0... 5,000 Pa: 24 Pa annually Ranges 0...1 InWC up to 0...3 InWC: 0.03 InWC annually 0...4 InWC up to 0...25 InWC: 0.10 InWC annually

Dimensions in inches
1.97 1.5

2.09

0.22 0.55 0.32 0.71 Legend Pin 1: Pin 3: Loop Loop + Loop WIKA Datasheet A2G-55 05/2011
R

2.56

Wire diagram
Output signal DC 0 10 V, 3-wire
DRW_E_55.02

Output signal 4 20 mA, 2-wire


DRW_4-20mA.01

Uv

Out Gnd

Uv

Out

Gnd

Legend Pin 1: Pin 2: Pin 3:

Supply voltage (+) Output signal Ground

The specifications given in this document represent the state of engineering at the time of publishing. We reserve the right to make modifications to the specifications and materials.

Page 2 of 2
Ordering information Pressure gauge model / Nominal size / Scale range / Size of connection / Optional extras required Specifications and dimensions given in this leaflet represent the state of engineering at the time of printing. Modifications may take place and materials specified may be replaced by others without prior notice.

0.53

1.0

1.4

WIKA Instrument Corporation 1000 Wiegand Boulevard Lawrenceville, GA 30043 Tel (770) 513-8200 Toll-free 1-888-WIKA-USA Fax (770) 338-5118 E-Mail info@wika.com www.wika.com

0.18

2.56