Contents
2 10
Functional units
15
28 38 40 42
Presentation
Fields of applications
Food-processing
Requirements
Solutions
> Specific anti-corrosion treatment on conductive parts. > Tightness ensured by IP54 guaranteed parts.
> Tightness ensured by IP54 elements. > Fault prevention by intelligent motor control centers (iMCC).
Water treatment
Requirements
Solutions
Presentation
Fields of applications
Functions
Electrical distribution
Motor control
Presentation
Blokset solution
Our MotorSys iPMCC solutions help your teams optimise the energy efficiency of your assets, offering the following benefits: b Dependability, even in severe industrial environments, b Safety of personnel and assets, maintainability and upgradability, b Lead time management and risk as well as cost reduction throughout your installation's entire lifecycle.
> MotorSys iPMCC solutions communicate with the major industrial local area networks on the market (Ethernet TCP/IP, Profibus-DP, DeviceNet, Modbus, etc.). > With data delivered in real time, your operational and maintenance staff will have immediate access to the relevant information to control your motors and electrical distribution locally or remotely. > Warning messages can be sent automatically to a mobile phone in the event of an alarm or group of alarms.
Presentation
Blokset solution
With information delivered to ensure the traceability of electrical distribution, motor operation and power consumption data, installations are constantly improved. > MotorSys iPMCC solutions make it easy to collect all the statistics you need to develop effective plans covering the operation, maintenance, optimisation and upgrading of your installations, as well as energy efficiency.
MotorSysTM iPMCC solutions integrate perfectly into your site network infrastructure, whatever the communication protocol, but also into energy management control systems and process control systems
Presentation
Blokset solution
Innovation
Mw2 cubicles
Distribution busbar
tric
Installed in a partitioned compartment at the rear of the drawers area, it consists of 8 mm thick bars whose cross-section depend upon the current to be distributed in the cubicle.
The distribution busbar system can be single or double. The architecture depends on the electrical performance and on the functional unit size (full width or half width). The distribution busbar is extremely safe: the tap-off outlets make the busbar unaccessible to operators. Tap-off outlets open and close when the functional unit moves between connected and test position. Up to 630 A, functional units are directly connected to the vertical busbar. In double busbar architecture, the current flow is balanced in both vertical busbars thanks to the link system.
Drawer positions
Drawers operation is very simple. Using the indexing pushbutton, the operator can simply move the drawer in the draw-in, test, draw-out positions. Each position are mechanically marked with a mechanical indicator on the drawer sides.
Draw-in
Test
b b b b b The functional unit is not operational. Only auxiliaries are connected. Padlocking is possible to keep the drawer in this position. Allows the functional unit testing. Allows maintenance on the process.
Draw out
b b b b The functional unit is not operational. Power and auxiliaries are disconnected. Padlocking is possible to keep the drawer in this position. Allows maintenance on the process.
Withdrawn
b b b b The drawer can be fully extracted. Allows quick replacement. Allows switchboard live change. Padlocking is possible on the fixed part.
Presentation
Blokset solution
Innovation
Auxiliaries connection
r ect r El ide t hne paten Sc ic
The innovative mechanism guarantees the auxiliary contacts to be connected: b from the test position when the drawer is drawn in, b to the test position when the drawer is drawn out.
Presentation
Blokset solution
Implementation
> The switchboards are type tested assemblies. They have a complete electrical and mechanical inspection in factory. > The modularity of the cubicle makes the installation of a new functional unit easy.
Continuity of supply
> Withdrawable feeders for quick maintenance operations. > Schneider Electric devices association guarantees the continuity of supply.
> Internal arc protection, in compliance with the requirements of the international regulations (technical reports IEC 61641). > Continuity of supply guaranteed by limitation of harmful effects of the internal arc in the switchboard. > Quick repair of the area where the arc was confined. > Safety of people and equipment guaranteed during the occurrence of the fault. > Insulated busbars prevents flashover and propagation of the arc.
Type tested
Blokset is totally type-tested in accordance with CEI 60439-1 and 61439-2 Certified by independant labs: LOVAG, ASEFA and KEMA. As well as by a permanent control in Schneider Electric test laboratories. Type-tests carried out: o temperature-rise limit, o dielectric properties, o short-circuit withstand, o effectiveness of the protective circuit, o conformity of the clearance and creepage distances, o mechanical operation, o degree of protection.
> The conductive parts treated against corrosive atmospheres (according to IEC 721-3-3 standard). > IP54 tightness for the dusty and / or damp environments. > Earthquake safety versions*. > Forced ventilation for environments with ambient temperatures exceeding 45 C or for devices with high heat loss.
Presentation
Blokset solution
Implementation
3 specific compliances
Standard
Earthquake safety
For seismic zones up to Richter 9.
Industry
Cubicle partitioning
Protective screens (side partition + vertical busbar screen) prevent tracking of an arc in the cubicle.
Type-tested solution
At functional unit level, the drawers are type tested against internal arc at both broken unit sides.
WWW
Shutting down only the concerned functional unit, but test of the control system possible before the resumed operation.
Shutting down only the concerned functional unit without connections handlings.
Addition of a functional unit without shutting down the switchboard, free addition in non-equiped spare slots.
2b
b b -
3b
b b b -
4a
b b b b -
4b
b b b b b
Solution overview
D
4000/5700 A NW40b/63b NW40b/63b
D
3000/3600 A NW40/NW32/NS3200 NW40 /NW32/ NS3200
y 630A
10
Solution overview
rs
D
800/3300 A NW08-25 /NT06-16/NS630b-2500 NW08-25/NT06-16/NS630b-2500
D
800/3300 A NW08-25/NT06-16/NS630b-2500 NW08-25/NT06-16/NS630b-2500
DC
800/3300 A -
C60/EZC100/NSX100-630/ NS100L/NS400L
11
Solution overview
Feede
rs
cubicle
Mf
800/3300 A b fixed mounting plate y 250 kW
Ms
800/3300 A
12
Solution overview
Mw2
400/2000 A b drawer y 250 kW
Blokset Mw2
For MCC application drawers, Mw2 is an optimized solution, robust, reliable and secure. The Mw2 satisfy the motor control needs of the most demanding processes.
13
Functional units
Composition
p p p
3rd letter: auxiliaries connection (coils, contacts, ) 2nd letter: Power downstream connection 1st letter: Power upstream connection Letters and signification
FFF DDD WWW Connection is fixed Connection is deconnectable Connection is withdrawable
Blokset offers several options to answer the installation needs and the service continuity required. FFF power upstream and downstream connections are fixed, auxiliaries are fixed. DDD power upstream and downstream connections are disconnectable, auxiliaries are disconnectable. WWW power upstream and downstream connections are withdrawable, auxiliaries is withdrawable.
Operation
Setting Padlocking
Maintenance
Checking Cleaning Repairing
Evolution
Not required
FFF Setting, padlocking may disturb remaining part of switchgear DDD Functional unit shut down possible without disturbnce on the remaining parts
Expected
DDD Functional unit shut down possible with no operation on cables Functional unit replacement in a short time
Mandatory
WWW Functional unit shut down possible without disturbance on the remaining parts Test position offered ith power disconnected
WWW Functional unit shut down possible with no operation on cables Functional unit replacement in a short time
WWW -
14
Functional units
fixed device
device on base
PCC drawers
Half width Half width C60 2 modules (100 mm) 4 modules (200 mm) 6 modules (300 mm) 8 modules (400 mm) NG125 NSX100 Drawer size
25
MCC drawers
110 Full size 75 Full size 45 30 18.5 15 Full size Half size 2 modules (100 mm) 4 modules (200 mm) 6 modules (300 mm) Drawer height 8 modules 10 modules 12 modules (400 mm) (500 mm) (600 mm) Full size Half size
15
Functional units
Electrical distribution
In > 630 A
Cubicle
type D 800 < In < 3300 85 85 85 85 2 3 2 2 NW20-25 NW16 NS2000 - NS2500 NS1600b NS630b NT06-16 3200
type D 800 < In < 1600 85 50 / 85 50 / 85 42 / 85 3 4 6 4 NW08-16 NS630b - NS1600 NS630b - NS1000 (horizontal position) NT06-16 1600
type D (1) These are recommended configurations. For extended one, please consult us.
16
Functional units
Electrical distribution
In y 630 A
In (A)
In < 63 63 < In < 125 16 < In < 100
Device
C60 NG125 NSX100
Cubicle
125 < In < 160 200 < In < 400 400 < In < 630 Drawer 100 < In < 250 100 < In < 250 400 < In < 630
NSX160 NSX 250-400 NSX630 NSX100-250 vertical position NSX100-250 horizontal position NSX400-630 vertical position
1 1 1 1 2 1
4 modules full width 6 modules full width 8 modules full width Mw2 6 modules 8 modules 8 modules
type D Plug-in 100 < In < 250 100 < In < 250 100 < In < 250 400 < In < 630 NSX100-250 vertical position NSX100-250 horizontal position NSX100-250 horizontal position NSX400-630 horizontal position 4 1 2 1 6 modules 3 modules 3 modules 4 modules
type D Fixed In < 63 63 < In < 100 100 < In < 250 100 < In < 250 100 < In < 250 400 < In < 630 (1) Depending on Iq. C60 EZC100 vertical position NSX100-250 vertical position NSX100-250 horizontal position NSX100-250 horizontal position NSX400-630 horizontal position 24 6 4 1 2 1 3 modules 6 modules 6 modules 3 modules 3 modules 4 modules type D
In (A)
In < 100 100 < In < 400
Device
NS100L NS400L
Cubicle
Mw2 Fixed In < 100 100 < In < 250 400 < In <630 NSX160 / NS100L NSX 250 1 1 3 modules 3 modules 4 modules
NSX400-630 / NS400L 1
type D
17
Functional units
Selection
U max = 415 V U max = 690 V
polluted network
polluted network
It is however recommended that measurements be carried out on site to check that the correct solution is adopted.
18
Functional units
Selection of cubicle
Rated voltage (V)
415
Type
without self (50Hz) without self (60Hz)
Ventilation
natural forced natural forced natural forced natural forced natural forced natural forced
Power (kVAR)
up to 192 up to 516 up to 192 up to 456 up to 182 up to 538 up to 168 up t o 396 up to 199 up to 398 up to 160 up to 422
without self (60Hz) without self (60Hz) without self (50Hz) without self (60Hz)
19
Functional units
Motor control
Example of an Ethernet communication architecture of a MotorSysTM iPMCC solution, at a process unit level
Innovation
20
Functional units
Motor control
Protection
Short-circuit, Thermal overload, Overcurrent, Ground current Current phase imbalance & phase loss Current phase reversal Undercurrent Long start (stall) & Jam (locked rotor) Motor temperature sensor Rapid cycle lockout Load shedding Voltage phase imbalance, phase loss, & phase reversal Undervoltage & Overvoltage, Underpower & Overpower, Under & Over power factor
Measurements
Line currents, Ground current, Average current, Current phase imbalance, Thermal capacity level Motor temperature sensor Frequency Line-to-line voltage, Line voltage imbalance, Average voltage Active & Reactive power, Power factor, Active & Reactive power consumption
Operational modes
Consignment Starters test position Maintenance & Upgrade live Control at motor level PC set-up Remote management Local HMI "Nominal current only" set-up (screwdriver)
(1) PLC: Programmable Logic Controller Standard Optional
21
Functional units
Motor control
22
Functional units
Motor control
Selection of the functional unit -MotorSys iMCC 1 component - rated 415 V - 50 / 60 Hz - IP31 / 35 C
Withdrawability
Drawer
Starter
DOL DOL
Circuit breaker
Tesys U Tesys U
Power (kW)
0 to 15 0 to 15
Cubicle
2M full 4M half
Mw2
Selection of the functional unit -MotorSys MCC 2 components - rated 415 V - 50 / 60Hz - IP31 / 35 C
Withdrawability
Drawer
Starter
DOL Reverse Star-delta
Circuit breaker
GV2P GV3P GV2P GV3P GV2P GV3P
Power (kW)
0 to 15 18.5 to 30 0 to 15 18.5 to 30 0 to 15 18.5 to 30
Cubicle
Mw2
Selection of the functional unit -MotorSys MCC 3 components - rated 415 V - 50 / 60 Hz - IP31 / 35 C
Withdrawability
Drawer
Starter
DOL
Circuit breaker
GV2L GV3L NS80HMA NSX100SMA NSX100*MA NSX160*MA NSX250*MA NSX400*MA NSX630*MA
Power (kW)
0 to 15 18.5 to 30 18.5 to 30 37 18.5 to 30 37 45 55 75 90 to 110 132 to 160 200 220 to 250 0 to 15 18.5 to 30 18.5 to 30 37 18.5 to 30 37 to 45 55 75 90 to 110 132 to 160 200 to 250 0 to 15 18.5 to 30 18.5 to 30 37 18.5 to 45 55 to 75
Cubicle
Reverse
GV2L GV3L NS80HMA NSX100SMA NSX100*MA NSX160*MA NSX250*MA NSX400*MA NSX630*MA GV2L GV3L NS80HMA NSX100*MA NSX160*MA
Star-delta
4M half 4M full 4M full 4M full 6M full 4M full 6M full 4M full 6M full 8M full 10M full 10M full 12M full 4M full 4M full 4M full 6M full 6M full 8M full 6M full 8M full 10M full 12M full 12M full 4M full 6M full 6M full 8M full 8M full 8M full
Mw2
(1) Depending on additional equipments. (2) In number of vertical modules (1 module = 50 mm).
23
Functional units
Motor control
Selection of the functional unit - MotorSys MCC and iMCC 3 components - rated 415 V - 50 / 60 Hz - IP31 / 35C
Withdrawability
Drawer
Starter
DOL
Power (kW)
0 to 4 5.5 to 15 18.5 to 30 18.5 to 37 18.5 to 30 37 45 55 to 75 90 to 110 132 to 160 200 220 to 250 0 to 15 18.5 to 30 18.5 to 37 18.5 to 30 37 to 45 55 to 75 90 to 110 132 to 160 200 to 250 0 to 15 18.5 to 30 18.5 to 37 18.5 to 45 55 to 75 0.37 to 15 0.18 to 37 0.37 to 30 37 to 45 55 to 75 90 to 110 132 to 160 200 to 250 0.37 to 15 0.18 to 37 0.37 0.55 to 37 55 to 75 90 to 110 132 to 160 200 to 250 1.5 to 11 1.5 to 15 18.5 to 37 3 to 11 15 to 37 45 55 to 75 90 to 110 132 to 160 200 to 250
Cubicle
Mw2
Reverse
GV2L GV3L NS80HMA NSX100*MA NSX160*MA NSX250*MA NSX400*MA NSX630*MA GV2L GV3L NS80HMA NSX100*MA NSX160*MA GV2 NS80 NSX100 NSX160 NSX250 NSX400 NSX630 GV2 NS80 NSX100 NSX160 NSX250 NSX400 NSX630 GV2 NS80 NSX100 NSX160 NSX250 NSX400 NSX630
Star-delta
Fixed
DOL
REV
Star-delta
Mf
(1) Depending on additional equipments. (2) In number of vertical modules (1 module = 50 mm).
24
Functional units
Motor control
Motor control - MotorSys MCC and iMCC 1 component - rated 690 V - 50 Hz - IP31 / 35C
Withdrawability
Drawer
Starter
DOL
Power (kW)
0 to 18.5
Cubicle
Mw2
Motor control - MotorSys MCC and iMCC 2 components - rated 690 V - 50 Hz - IP31 / 35C
Withdrawability
Drawer
Starter
DOL Reverse Star-delta
Power (kW)
0 to 22 18.5 to 22 0 to 22 0 to 15 18.5 to 22
Cubicle
Mw2
Motor control - MotorSys MCC and iMCC 3 components - rated 690 V - 50 Hz - IP31 / 35C
Withdrawability
Drawer
Starter
DOL
Power (kW)
0 to 15 18.5 to 22 0 to 55 75 90 to 250 0 to 22 0 to 1.5 2.2 to 55 75 90 to 250 0 to 15 18.5 to 22 0 to 1.5 2.2 to 55 75
Cubicle
Reverse
Star-delta
Mw2
(1) Depending on additional equipments. (2) In number of vertical modules (1 module = 50 mm).
25
Functional units
Altistart ATS 48
b The Altistart ATS 48 soft start - soft stop unit is a controller with 6 thyristors, which is used for the torque-controlled soft starting and stopping of three-phase squirrel cage asynchronous motors. b The Altistart ATS 48 must be selected on the basis of 3 main criteria: v the power supply voltage range (this catalogue deals only whith the devices connected to a 415V or 690V network), v the power and the nominal current of the motor, v the type of application and the operating cycle.
Altistart ATS 48
Altivar ATV 61
Altivar ATV 71
26
Functional units
Modularity (1 M = 50mm)
9 9 12 18 18 24 24 36 9 9 12 12 18 18 24 24 24 36 12 12 18 24 36 9 9 12 24 24 9 9 12 24 24 12 12 24 24 9 9 12 24 24 9 9 12 12 24 12 12 24 24
Cubicle
Ms
690
ATV 61
415
690
ATV71
415
27
Cubicles
Device installation zone Single horizontal busbar Modularity Double horizontal busbar 34 modules 28 modules
vertical busbar
28
Cubicles
Type of connection
RC columns panorama
switchboard depth 600 mm
device cubicle width 700 mm
C A/C
700 600
400 600
A
700
C V
200
400 600
A/C
700
600
V
200
A
700
A C V
C A/C
1200 600
400 600
A
1200
A
700
C
200 / 400
600
V
200
A
700
C
200 / 400
600
A C V
29
Cubicles
Presentation
Cubicle
The Blokset switchboards consist of a framework and busbar assembly designed to combine in the same cubicle functional units of varying technologies, grouping both distribution and motor control applications. A complete range of configurations to satisfy the requirements of each site: b cubicles available in 1 height, 8 widths and 3 depths, to allow integration in all environments and ensure optimum installation modularity, b switchboard supplied by busbar trunking and / or cables, b front or rear, top and / or bottom connections, b choice of functional unit output partitioning: v incomers: forms 3b, 4b, v feeders: forms 2b, 3b, 4a, 4b.
Busbars
Busbar coating
Busbar coating horizontal busbar vertical busbar D vertical busbar Mw2 protection against ... none silver tin nickel epoxy
b b b
b b b
b b b
corrosive environment corrosive environment
b b
internal arc
Horizontal busbar
Selection table
Allowable intensity at 35 C IP31 (A) Horizontal busbar Single busbars 1500A from 1500 to 2550 from 2550 to 3250 from 3250 to 3800 from 3800 to 4100 Double busbars from 4100 to 6000 from 6000 to 6600 Icw max. (kA) 50 50 / 85 50 / 85 50 / 85 50 / 85 100 100 2x4 2x5 Qty of bars 100 x 5 mm 125 x 5 mm 1 2 3 4 5
30
Cubicles
Type D
Functional unit
Busbar for type D cubicle
b very high power, b dedicated to NW40b-63 devices, b height-reduced busbar.
Allowable intensity at 35 C IP31 (A) Horizontal busbar 6000 6600 Icw max. (kA) 100 100 Qty of bars 100 x 5 mm 2x4 2x5
Dimensions
Type of distribution 1 incomer or 1 distribution feeder 2 incomers + 1 coupling 1 source changeover Type of connection b direct connection from the bottom b front or rear connection b direct connection from the bottom b front or rear connection b direct connection from the bottom b front or rear connection Qty of cubicle 1 3 2
31
Cubicles
Type D
Functional unit
Busbar for type D cubicle
b high power, b dedicated to NW and NS devices, b height-reduced busbar.
Allowable intensity at 35 C IP31 (A) Horizontal busbar 3250 4100 Icw max. (kA) 50 / 85 / 100 50 / 85 / 100 Qty of bars 125 x 5 mm 3 5
Dimensions
Type of distribution 1 incomer or 1 distribution feeder 2 incomers + 1 coupling 1 source changeover Circuit breaker Masterpact NW32-40 Compact NS3200 Masterpact NW32-40 Compact NS3200 Masterpact NW32-40 Compact NS3200 Type of connection b direct connection from the top b direct connection from the bottom b front or rear connection b direct connection from the top b direct connection from the bottom b front or rear connection b direct connection from the top b direct connection from the bottom b front or rear connection Qty of cubicle 1 3 2
32
Cubicles
Type D
125 x 5 mm 1 2 3 4 5
Dimensions
Type of distribution Incomer or distribution feeder Circuit breaker Masterpact NW08-25 (2 or 3) Type of connection b direct connection from the top b direct connection from the bottom b front or rear connection Qty of cubicle 1 1 2 2 1 1
Masterpact NT06-16 (3 or 4) b direct connection from the top Compact NS630b-2500 (3 or 4) b direct connection from the bottom b rear connection 2 incomers + 1 coupling Masterpact NW08-25 (2 or 3) b direct connection from the top b direct connection from the bottom b front or rear connection
Masterpact NT06-16 (3 or 4) b direct connection from the top Compact NS630b-2500 (3 or 4) b direct connection from the bottom b front or rear connection 1 source changeover Masterpact NW08-25 (2 or 3) b direct connection from the top b direct connection from the bottom b front or rear connection
Masterpact NT06-16 (3 or 4) b direct connection from the top Compact NS630b-2500 (3 or 4) b direct connection from the bottom b front or rear connection
33
Cubicles
Type D
125 x 5 mm 1 2 3 4 5
Dimensions
Type of functional unit Fixed Fixed Plug-in Withdrawable Rating (A) < 63 63 to 100 100 to 630 100 to 630 100 to 630 No. of pole 3P / 4P 3P / 4P 3P / 4P 3P / 4P 3P / 4P Type of connection b front connection b front connection b front connection b rear connection b front connection b rear connection b front connection b rear connection
34
Cubicles
Mw2
Functional unit
Vertical Mw2 busbar
b designed for MCC functional units in drawer, b full height busbar.
Rated current In (A) IP31 / 35C Single vertical busbars 400 630 1000 800 1250 2000
1 x 20 x 8 1 x 30 x 8 1 x 50 x 8 2 x 20 x 8 2 x 30 x 8 2 x 50 x 8
25 37.5 60 50 75 85
Dimensions
All functional units
Type of functional unit Drawer Type of connection b side connection from the front b rear connection
35
Cubicles
Mf
Functional unit
Busbar for Mf cubicle
b designed for MCC fixed functional units, b full height busbar.
Rated current In (A) IP31 / 35C Horizontal busbar Single busbars 1500 2550 3250 3800 4100 Double busbars 6000 6600
Dimensions
All functional units
Type of functional unit Fixed in functional unit Type of connection b side connection from the front b rear connection
The dimensions of the functional units are in the MCC choice pages, page 23.
36
37
Example
Example of configuration
1
5,5 kW 35 kW
Customers needs
250 A
100 A
100 A
250 A
1250 A
1,5 kW
1,5 kW
1,5 kW
1,5 kW
1,5 kW
1250 A
100 A
1,5 kW
1,5 kW
35 kW
15 kW
15 kW
100 kW
150 kW
G
800 A
35 kW
35 kW
45 kW 100 kVAR
3200 A
Reference standards Rated insulation voltage Rated operation voltage Vertical busbar rating Rated short-circuit current Rated peak current Rated frequency Busbar number of phases material insulation external internal Form Degree of pollution Rated auxiliary circuit voltage Energy compensation Cable entry Access Temperature Altitude Panelling colour 38
3200 A
Example
Example of configuration
2 3
Type of functional units Technology No. of vertical modules (1 module = 50 mm) Cubicles, rear connection with around 10 % of reserve
250 A
100 A
100 A
250 A
1250 A
5,5 kW
1,5 kW
1,5 kW
1,5 kW
1,5 kW
1,5 kW
1250 A
100 A
1,5 kW
1,5 kW
35 kW
35 kW
15 kW
15 kW
100 kW
150 kW
G
800 A
35 kW
35 kW
45 kW
fixed 24 1 cubicle type Dc 39 20 x 5.5 kVAR fixed EC 100 kVAR VVD
3200 A
3200 A
PCC
PCC
chassis
chassis
chassis
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer 2
fixed
fixed
fixed
2.5
2.5
2.5
2.5
2.5
10
12
12
12
1 cubicle type D
To determine the dimensions of each functional unit, see the selection table. INC: high power circuitbreaker incoming. C: coupling. EC: Power factor compensation. ED: electrical distribution. MC: motor control. VVD = Variable speed drive and soft starter.
1 cubicle type Ms
1 cubicle type D
12
fixed
VVD
ED INC C
INC
INC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
ED
ED
ED
ED
Installation
Cubicle installation
Fixing points
Ground fastening
A: 350 mm for a depth of 400 mm 550 mm for a depth of 600 mm 950 mm for a depth of 1000 mm b Section width 700 b Section width 900 (200 + 700) b Section width 1100 (200 + 700 + 200)
122,5
455
25
322,5
125
455
25
322,5
125
455
25 197,5
122,5
455
195
205
25
122,5
955
25
322,5
125
455
195
205
25
550
350
687,5
737,5
697,5
625
900
100
25
687,5
550
350
25
625
800
900
1000
25
122,5
355
600
b class 8.8 screws: M10 TH screws + washers (external 25 mm, thickness 3 mm) + CS contact washers 10 mm.
350
625
40
600
600
1000
600
1000
Installation
Cubicle installation
Switchboard positionning
(mm)
(mm)
(mm)
Rear connection.
Front connection.
41
Blokset performances
General data
Standard environment
reference standards climatic resistance damp heat withstand dry heat withstand low temperature withstand salt spray withstand installation earthquake withstand environment (CEM) IEC 60439-1 / IEC 61439-2 IEC 60529 IEC 60068-2-30 IEC 60068-2-2 IEC 60068-21 IEC 60068-2-11 indoor IEC68-3-3 and UBC / CBC HN20E53 type 2
Mechanical data
cable entry access degree of protection (IP) form withdrawability dimensions (mm) height width depth installation modularity in a cubicle panel coating panelling colour height 2200 mm top / bottom front / rear 20 / 31 / 42 / 54 2b / 3b / 4a / 4b FFF / WWW 2200 600 / 700 / 800 / 900 1000 / 1100 / 1200 / 1300 400 / 600 / 1000 40 modules of 50 mm epoxy / polyester powder polymerised, > 50 RAL 9002 / 7016
Electrical data
rated insulation voltage (Ui) rated operational voltage (Ue) rated frequency (F) rated impact withstand voltage (Uimp) rated auxiliary circuit voltage surge category degree of pollution rated current (In) vertical busbar rating horizontal busbar vertical busbar short-term rated current (Icw) 1s short-term rated current (Icw) 1s 1000 V 415 / 690 V CA 50 / 60 Hz 12 kV 230 V AC max. IV 3 6300 A 3200 A 50 / 85 / 100 kA rms 50 / 85 kA rms up to 100 kA 85 kA eff 0.3 s TT-IT-TNS-TNC up to 5650 A up to 250 kW 415 / 690 V
rated conditional short-circuit current (lcc) internal arcing protection according to IEC 61641 earthing diagram current limit of power incoming and outgoing feeders power limit of motor control feeders
42
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this document.
Design: Schneider Electric Photos: Schneider Electric Edition: Altavia Connexion Printing: