Reply of Pre-Bid Queries for Data Centre in Power Transmission Corporation of Uttarakhand Ltd. as per tender specification o.

PTCUL/RFP-15/DC/2011-12
Queries Raised by: SIFY TECHNOLOGIES LIMITED S. No. RFP Reference/ Vendor Reference Data Centre-Final. Pdf RFP Clause 4.1 Project Plan The Bidder shall produce a detailed project plan and details of resource allocations inLine with experience of completion of project within 3 months time as defined timelines in this tender document. This plan should chalk out overall schedule requirements, timelines, dependencies, deliverables and milestones. 11. APPROPRIATE KVA CAPACITY UPS FOR SUSTAINING REQUIRED LOAD General Clarification Sought The detailed project plan is shared by the Execution Team or Delivery team during the Exection Stage of the project plan. We request you to consider High Level Project Plan instead of Detailed Project Plan at the time of submission of bid. Clarifications by PTCUL Detailed Project Plan and other requirements are to be met as specified in RFP. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17.

Data Centre-Final. Pdf 2 Data Centre-Final. Pdf 3 Data Centre-Final. Pdf

Request you to kindly provide the capacity of the UPS.

Request you to kindly provide the rating of the Rack power required.

General

Data Centre-Final. Pdf 5 Data Centre-Final. Pdf 6 Data Centre-Final. Pdf

General

1) Floor layout not provided in the RFP. Hence it is difficult to arrive at the civil component required. Request you to share the same in AutoCAD format. 2) Please confirm the floor of Server farm area. If it is not ground/Lowest floor, please confirm the floor load bearing capacity. Electrical scope of work is not clear. Request you to confirm the tap of point of hand off point. These is not specification of Emergency power backup please confirm the requirement of the same As per the RFP requirement 2 No's of 2TR Comfort AC required. Is this for UPS/Electrical Room or it is for Server Room. As comfort AC Could not able to provide controlled environment like temp & humidification it is not recommended for Data Centre. Request you to confirm the same.

Project Plan, Requirements and Bill of Materials (BoM) are already defined in RFP, therefore, Bidder is requested to plan accordingly to meet requirements. Project Plan, Requirements and Bill of Materials are already defined in RFP, therefore, Bidder is requested to plan accordingly to meet requirements. Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. -Do-

General

Requirements are to be met as specified in RFP. So, bidder is requested to read the RFP for clarity. As already mentioned in RFP, plan is to made for meeting requirements of Server Room, UPS Room and Lab. It is also requested to please read RFP carefully for BoM confirmation.

General

Data Centre-Final. Pdf Data Centre-Final. Pdf

General No of Racks

Scope of physical security not defined in the RFP. Request you to confirm the same. 1) Details of the rack specification not mentioned in the RFP. Request you to provide the same. 2) Please confirm the future expansion in terms of rack space and power. Technical specification from RFP document are not properly aligned and trimmed from right plane and unable to read. Request you to share the RFP in Word format. What would be the BW requirement at Access/Branch loacations. What is the size of back haul - Application & user details required. Pls provide the same. For sizing of Primary link - Application & user details required. Pls provide the same. Request you to kindly clarify the clause.

Requirements are to be met as specified in RFP. Requirements are to be met as specified in RFP. The said reqirement has already been mentioned in Part A: Technical Details of RFP from point no. 5. It is also requested to please read RFP carefully for BoM & Technical Specification confirmation. Please rearrange to download RFP properly.

Data Centre-Final. Pdf 10

General

11

General General

Please stick to requirements of RFP requested from Bidder. Please stick to requirements of RFP requested from Bidder. Please stick to requirements of RFP requested from Bidder. Broad Band/Internet/ Leased Line shall be provided by PTCUL. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. Please stick to requirements of RFP requested from Bidder.

12 General 13 Pg 14-CI 4.6.1 14 1.2 Eligibility (Pre Qualification) Criteria; page 9; clause 3. "Bidder shall ensure WAN connectivity for all sides (excluding Broad Band/Internet/ Leased Line Connectivity." should have an annual sales turnover of Rs. 2 Crore or more in each of the last Four years from Bidder and operations need to be profitable with positive net worth in the last Four years

15

The purpose is to validate the financial strength & the same can be established if an organization has an positive net worth. We would therefore request you to kindly amend the clause as "Should have an annual sales turnover of Rs 2 Crore or more in each of the last Four years from Bidder and with positive net worth in the last Four Years." The purpose of having 4years experince in Data Centre Development & Maintenance is to validate the strength of the company in terms of designing & implementing physical infra for DC Projects. In the recent Tenders of DIT like State Data Centres (SDC's); & also State Wide Area Network Tenders (SWAN's); IDC experience is allowed wherein experience for bidders who have built their own Data Centres for commericial purposes is condidered. We should also request you to consider Internet Data Centre (IDC) experience of those bidders who have built Data Centres for Commercial use.

1.2 Eligibility(Pre Qualification) Criteria; page9; clause 7.

Should be in existence for at least 8 years in India, out of 4 year in Data Centre Development &Management

Please stick to requirements of RFP requested from Bidder. As a practice certifications are submitted from Clients for confirmation and verification by the bidder. So, it is requested from bidder to please submit all relevant documentation for Pre-Qualifications to make bid responsive.

16

17

18

1.2 Eligibility(Pre Qualification )Criteria; page9; clause 3. Annexure 1CHECK LIST; page 45; clause 6. Annexure 1CHECK LIST; page 45; clause 7. Annexure4(P1), Page 50

Should have latest bank's certificate of solvency issued by schedule bank Proforma for Contract Performance Security as per Annexure 7

Please clarify the ammount of solvency required. Please clarify whether Annexure 7 has to be submitted at the time of bidding or only by the selected bidder. Please clarify whether Annexure 7 has to be submitted at the time of bidding or only by the selected bidder. Please clarify whether the rates quoted shall be valid for 5 years. If yes, we would request you to kindly re-consider/remove this clause as the same would not agreeable to most of the OEM's. Please clarify whether the REBATE COLUMN in the price Bid could be left blank. Please confirm whether we need to quote for both the options A & B under this clause. Please confirm whether Annexure 4(P2) has be filled only if there are Technical & Commercial Deviations.

Proforma for Contract as per Annexure 8

19

20

Page 50-52 21 Page 51, 22 Page 53, Annexure 4(P2)

Please note that PTCUL reserve complete right to normalize, change quantities mentioned below in order to compare the price bids submitted by various bidders. Validity of these rates shall atleast 5 years from the data of LOA. Prid Bid

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity. Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity as these details are already available in RFP. Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity. This is a standard clause in RFP.

Please mention any value in it.

Price Bid Clause 7 Pricing of Oracle

23

Schedule of Price Incidence on Account of Withdrawl of Deviations Mentioned in Technical Proposal

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity. Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

Queries Raised by: CMC Limited S. No. RFP Reference/ Vendor Reference Pg 10. Point 2.2.4 RFP Clause The gaps, missing links, functional processing requirements not explained in these specifications should not be treated as out of scope by the data center developer. Any such missing pieces of information can also get discovered during the testing, etc. and hence it is not scope deviation for the data cover developer. * Networking of sit offices shall be ensured by the Bidder to the Data Centre at Dehradun. * A Public IP & Link for Data Centre at Dehradun and Broadband for Sites will be provided. By PTCUL. Bidder shall ensure WAN connectivity for all sites (excluding Broad Band/Internet/Leased Line Connectivity). 4.6.2 Installation & Commissoning of Networking Components. For running the intended application as mentioned in the scope, the Bidder shall design, install and commission the network infrastructure including but not limited to the following. The network shall be designed to meet the user workload and performance requirements. the bidder shall submit the designed network architecture and network drawings to the Owner for validation, before commencing installation and commissioning. Typographical mistake. Clarification Sought Clause is very open ended and should be limited to run the harware/ software demanded through this tender document. Clarifications by PTCUL This is a standard clause in RFP.

Pg 14.

Terms are contradictory and need more clarity.

Broad Band/Internet/ Leased Line shall be provided by PTCUL. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17.

4.6.2

Requirement is very open ended and need to fix up the requirement. In case requirement change that can be address on pro-rata basis. In case technical solution need to design by bidder then there should be technical marking and should be consider with commercial to decide the lowest bidder.

This is a standard clause in RFP.

Pg 20 to Pg 27 4

13.2

13.2 Impact on Price No payment will be made to Bidder for such changes, it will be cover as scope of work.

We downloaded twice the tender document however there is problem in text wrapping in tables of technical specification. Hence request to load the updated complete tender document. In case of any additional hardware/service/software requirement due to change requirement which requirement additional licence/hardware/manpower etc. should be address and addition charges need to give to user. In case no impact on prices is the must requirement than scope of change requirement should be define and limited.

Please rearrange to download RFP properly.

This is a standard clause in RFP. Moreover Project Plan, Requirements and Bill of Materials (BoM) are already defined in RFP, therefore, Bidder is requested to plan accordingly to meet requirements.

Queries Raised by: HCL Infosystem Limited S. No. 1 RFP Reference/ Vendor Reference Part A Technical Details 1.2 Eligibility (Pre Qualification) Criteria Part A Technical Details 1.0 Part A point #2, Pg 9; 3.1 Pat A High Level scope of Work, Pg11 Part A Technical Details 3.1 Part B High Level scope of Work, Pg11 RFP Clause Should have Quality Certification for CMMI LEVEL iii or should have ISO 9001:2000 & ISO 270001 or equivalent/higher certification along-with provision of Lab for 10 Nodes Clarification Sought The CMMI & ISO 9001/ISO 27001 are diferent certification, so request you to kindly correct the same. Please clarify about the 10 Nodes Lab, whether Vendor is supposed to take the same under scope of work. As per this clause RHEL, UTM Subscriptions etc are not mentioned clearly. Clarifications by PTCUL Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity. Yes and it is already mentioned in RFP.

Support Services of Data Centre for next 5 years for Licensees, Annual Technical Support, Hardware and other peripheral equipment except PC's and Printers. Oracle Installation and Configuration

Need not to be mentioned separately, this all comes under scope of work as per RFP

Part A Technical Details 3.2 Other Scope of Work, Pg11

Part A Technical Details 4.6.4 SAN; Pg 14 5

The storage area network should be designed and implemented keeping in mind Owner's requirement of high availability and based on high availability architecture.

Only supply of Oracle Licenses should be considered under the scope of work, whereas installation and configuratin of Oracle Licenses is the part of application Vendor's Scope. Technically the Entire Solution is not designed in a High availability architecture, infact with no redundant insrastructure. This clause does not validate the design. Request you to kindly get the entire IT Infra to be in NSPOP mode (NO Singel Point of Failure. As per the best Pratices for the Implementation of the datacentre, The Firewall should be configured in High Availability Mode. Request you to kindly get the qty of Firewall Changed to 02.

BoM and Requirement have already been defined in the RFP, therefore, Solution and BoM needs to sticks to detailing in RFP to meet requirement.

Part A Technical Details 4.6.5 Security; Pg 14 6

Firewalls in Data Centre shall be configured as per best practices

Part A Technical Details 4.6.5 Security; Pg 15

The Network Architecture should be planned keeping in mind the following design criteria :d) Redundancy. e) Business Continulty. f) Investment protection.

5.0 Minimum specification for hardware 1. Database Server Specifications; Pg 15

Min 162.5' Drive Bays; 300GBx3 SAS Drive 10K/15K.

10

11

12

5.0 Minimum specification for hardware 1. Database Server Specifications Pg 16 5.0 Minimum specification for hardware 1. Database Server Specifications & Application Server Specifications; Pg 16 5.0 Minimum specification for hardware 3.19' 42 U Rack; Pg 17 5.0 Minimum specification for hardware 4. Storage Area Network (SAN); Pg 17

4Gb dual port fibre channel HBA

The Product proposed in RFP do not comply to the Network Architecture wrt to. 1. Redundancy - Broadband/ADSL Modem do not have and redundancy. 2. Business Continuity - Broadband connectivity / ADSL Modem do not support the features required for Business Continuity. 3. Investment Protection - The ADSL Modems do not provide teh investment protection. Request you to kindly change the Network Architecture from Broadband with ADSL Modem to the More secured Architecture with MPLS/Point to point leased line connectivity with Routers & LL Modems. As of now the DB Server is configurated with only 3 SAS drives, but the expandability is asked for 16 Bays.. Moreover there is another SAN box for database storage as a part of Solution. So why such a scalability is required? The Hardware configuration is not as per the Recommended Architecture of Oracle Database, Request you tou kindly modify the same. The necessary cables should also be included with the solution.

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

Proposed solution should care of these provisions.

Monior is not mentioned in the specifications, only keyboard and mouse are considered. Please insert the same or include KVM Switch with accessories and remove individual Keyboard/Mouse from the specifications. KVM Switch is not taken into account. We suggest that KVM switch should be included in the specifications for easy manageability of Servers. The requirment is not very clear as the Database serve has 16 bays expandability, while the storage has only 12 bays scalability. Please explain why these are two different requirement. These can be very well integrated into the same solution.

Keyboard and mouse are obviously required for monitor. Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

13

14

15

16

5.0 Minimum specification for hardware 4. Storage Area Network (SAN); Pg 17 5.0 Minimum specification for hardware 5. Backup Tape Driver; Pg 17 5.0 Minimum specification for hardware 5.0 Minimum specification for hardware

upto two drives in enclosure

The Storage specifications does not ask for any SAN Switch Specifications, whereas as per the BOM on page 50, it says with SAN Switch. Please clarify Whether SAN Switch is required as the part of solution. Please mention the number of drives required in the Tape drive.

This is a typographical error in it and Sl. No. 3 (a), Page No. 50, Annexure - 4 (P1) should be read with deletion of "with SAN switch".

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity. As per Bill of Material (BoM).

LTO4/LTO5 Drives

17

18

19

5.0 Minimum specification for hardware 6. RHEL Standard Server Edition; Pg 17 5.0 Minimum specification for hardware 9. Other Passive Components; Pg 17 5.0 Minimum specification for hardware 10. Unified Threat Management Applicance; Pg 21 5.0 Minimum specification for hardware 11. Appropriate KVA UP; Pg26 5.0 Minimum specification for hardware

All Servers must be provided with latest version of 64-bit Red Hat Enterprise Linux Operating System for 1 socket pair (i.e.2 populated sockets) up to 1 gues with 1 year Standard support. 2x24 Port Patch Panel

Please be specific which Tape Drive is required as there is cost difference between the same. Kindly deleted LTO4 or LTO5. Specifications for Backup software is not mentioned. We suggest to include the Detailed specifications of the Backup Software as per the Scope of Work under Backup. 1 Year Standard Support is mentioned, whereas as per clause mentioned on Page 11, the software support/subscription is required for 5 years. This needs to be changed to 5 Years Support. It should be 2x24 port Cat6A based Patch Panel.

Requirements are to be met as specified in RFP and propose in Technical Solution. So, Bidder is requested to plan accordingly to meet requirements. This is a typographical error in it and Sl. No. 6 (1), Page No. 17, Clause 5.0 Minimum Specification for Hardware should be read as "5 years".

Please stick to requirements of RFP requested from Bidder and is understood. It is also requested to please read RFP carefully for clarity.

Subscriptions of different functionalities such as IPS/IDS, Gateway Antivirus, Gateway Antispam are not mentioned specifically. We suggest, based on the clause mentioned on page 11, it should be bundled with 5 Year Subscription License. This wording "Appropriate" would lead to different vendors quoting different capacity UPS, thus it needs to be changed accordingly. We suggest, 5KVA UPS would suffice the requirment and the specs for same should be replaced. The specs seem to be more of a Higher Capacity UPS with features like Rack Mountable, 6U etc. The Specifications shuld be changed accordingly based on the 5KVA Features. Need more clarity on the Testing Procedure and Specifications. This is because as per the specs there are many features covered, which cannot be individually tested for each device. Please remove the clause.

Need not to be mentioned separately, this all comes under scope of work as per RFP

20

Project Plan, Requirements and Bill of Materials (BoM) are already defined RFP, therefore, Bidder is requested to plan accordingly to meet requirement.

21

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

22

6.0 Acceptance Testing Test Scenario at Data Center; Pg28

Test Specification - During the Test Specification phase, all approved and inspected specifications are to be verified.

This is a standard clause in RFP and Bidder needs to come up with proposal already in practice for Testing Procedure and Specifications verifications process.

6.0 Acceptance Testing 23

14.0 Backup Maintenance

and

Test Data - Test data is prepared for testing at each stage. The test data should be prepared in such a way that it covers basic path. The basic path should capture relevant data. Tools can also be used to generate test data. necessary training should be provided to End User, Managers & Admiistrators (datea center) about the new version, if applicable.

Test Data Prepartion and Testing is the part of Scope of the Application Vendor, we would provide the insfrastructure and integrate the same for seamles operation. Please make the necessary changes. This clause suggest that we need to provide training to mentioned users on the change/upgrade of the new Version of Software. But his in itself would be a tedious task, moreover the Application part is under the scope of work for the application Consultant. Please remove the same or mention it under scope or work of application Vendor. These Backup functionalities can be achieved by using a High End Backup Software, which is not included in the Solution. Please include the Specifications of the Backup Software as per the desired functionalities. All the functionalities mentioned under this clause can ONLY be achieved using a Agents based Backup Software Package. As of now on Backup Software Package is included in the Solution. Moreover the by default backup software option with LTO Drive is a Temporary Solution and cannot provide functionalities such as scheduling backups etc. Please include the Specifications of the Backup Software as per the desired functionalities.

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

It is requested to please read RFP carefully for clarity. It is obviously clear that Bidder shall facilitate training already mentioned in context to RFP to meet requirement.

24

25

17.0 Post Implementation Support 17.3 Storage Administrator; Pg31

To ensure that regular and proper backups of all Servers & Storage to protect against data losses.

Project Plan and Requirements are to be mentioned in Technical Proposal of Bidder which should take care of these functions and mentioned in RFP. It is requested to plan accordingly.

17.0 Post Implementation Support 17.4 Backup and Restore; Pg 32 26

Project Plan and Requirements are to be mentioned in Technical Proposal of Bidder should take care of these functions as mentioned in RFP. It is requested to plan accordingly.

27

Part C: Annexures and Forms Annexure 4 (P1); Pg 50

Fiber optic based 2 TB or more row capacity (approx.) external RAID-5 or better Dual RAID controller with 1GB cache each with SAN switch. Tape Library, LTO-5 or better/Backup Tape Drive

Fiber Optic based Storage is expected with a SAN Switch based solution, but on the contrary the specifications do not include and SAN Switch. Please refine the statement. This statement contradicts with the specifications of device. LTO-4/LTO-5 will give he flexibility of quoting for either of them but there is a cost difference in both. Please suggest which drive is required. Specs mentioned in Technical Specs section is for a Layer - 2 POE Switch, thus the same needs to be changed. UPS rating with Battery Back up and no of units required. It should be changed to 5KVA UPS or the capacity finalised by the Technical members.

Please refer to clarification mentioned above.

28

Part C: Annexures and Forms Annexure 4 (P1); Pg 51

As per Bill of Material (BoM).

29

30

Part C: Annexures and Forms Annexure 4 (P1); Pg 51 Part C: Annexures and Forms Annexure 4 (P1); Pg 51

Layer 2 Swtich Switch(24)

(Managed)/Layer

Please read RFP carefully and proposed according to Specifications mentioned. Project Plan, Requirements and Bill of Materials (BoM) are already defined RFP, therefore, Bidder is requested to plan accordingly.

Appropriate KVA UPS

31

Part C: Annexures and Forms 8.0 Responsibilities; Pg 29

The Bidder shall depute a senior engineer not less than graduated in IT/CS background at Data Centre of PTCUL and report to the officer in charge in PTCUL.

32

Part A Technical Details 13.0 SITE DEVELOPMENT AS PER ROOM DIMENSIONS, Pg 27

The Entire Data Center would demand a Professional with relevant Experience in System Administration, Network Administration, Security Administration. So request you to kindly specify the relevant Experience. Area of the data cener required for designing. Layout (with L x B x H) of the server area needed.

Project Plan, Requirements and Bill of Materials (BoM) are already defined RFP, therefore, Bidder is requested to plan accordingly.

33

34

Part A Technical Details 13.0 SITE DEVELOPMENT AS PER ROOM DIMENSIONS, Pg 27 Part A Technical Details 13.0 SITE DEVELOPMENT AS PER ROOM DIMENSIONS, Pg 27

Power requirement for the DC is required.

What is the distance from Main electrical Panel to the data center electrical room.

35

Part A Technical Details 13.0 SITE DEVELOPMENT AS PER ROOM DIMENSIONS, Pg 27

Is there is any quantified/measurable quantities for the electrical and civil supply works (eg; Area for glass partition, false ceiling, furniture amount, no of earthing cable lengths (specifications).

36

37

38

Part A Technical Details 13.0 SITE DEVELOPMENT AS PER ROOM DIMENSIONS, Pg 27 Part A Technical Details 13.0 SITE DEVELOPMENT AS PER ROOM DIMENSIONS, Pg 27 Support/Warranty Period Clause Annexure 4(P1); pg 52; Maintencance/ Warranty Cluause; Pg 31

Four Split/Stand/Roof mounted ceiling Ac's (2 Ton)

Cooling requirement for the data center not mentioned. Cooling Requirement should be more precise.

Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. Project Plan, Requirements and Bill of Materials (BoM) are already defined RFP, therefore, Bidder is requested to plan accordingly. However, a primary supply shall be provided by PTCUL at a point desired by bidder in DC. Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. As per details in RFP.

Earthing, Fixming of Rods, Fans, Four Split/Stand/Rood mounted ceiling AC's (2 Ton), Separate Wiring of UPS,

Do you require fans in the Data Center? Also is lightening part of requirement. Please clarify.

As per details in RFP.

All the deliverables, products and services given to PTCUL within the scope of this work shall have a maintenance/warrantee period of 60 months.

It seems from the Tendor, that the total support required is for 5 years; but as per the Price Bid format, it seems 1+5 Years support. We require clarity on whether it says the devices should be included with 1 year support and further 4 years AMC. Please clarify!

As per details in RFP.

39

Part C: Annexures and Forms Annexure 4(P1);

7 Oracle (Option 8)

For Option, Weblogic, Forms, and Report and Services line item needs to added. Please include the same.

This is typographical error and has been rectified.

Queries Raised by: INFINITE COMPUTER SOLUTIONS S. No. 1 Page 17, Clause No. 5 2 Page No. 17, Clause No. 6 Page No. 17, Clause No. 5 4 What is the retention period for the backups. Page No. 18, Clause No. 5 Page No. 18, Clause No. 7 6 Network Router and Switch IPSEC WAN/INTERNET ROUTER Specification of two different Makes. Suggest single Make for ease of Administration and Support Router specification indicates Firewall and UTM to be integral with routing functionality. When separate UTM appliance is already proposed in the BOM Please provide Clarity on the POE functionality. Is this Switch being used for VOIP and or Wireless AP Please Clarify if a Modern or Router is required. Modem is provided by the ISP. Please provide specification of Router of or Modem+Router as required. As two racks are mentioned in the BO<. Please provide the rack utilization to calculate power load. Please stick to requirements of RFP requested from Bidder. Please stick to requirements of RFP requested from Bidder. RED HAT ENTERPRISE LINUX STANDARD SERVER EDITION Backup RFP Reference/ Vendor Reference Page 17, Clause No. 4 RFP Clause STORAGE AREA NETWORK (SAN) BACKUP TAPE DRIVE Clarification Sought No Mention of Storage Switch and its specification or if redundancy is to be achieved using more than one switch. Backup Software and specifications not mentioned. Requires additional Server. Clarifications by PTCUL Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity. Requirements are to be met as specified in RFP and propose in Technical Solution. So, Bidder is requested to plan accordingly to meet requirements.

Please change to Redhat or SUSE Linux Server. The backup mentioned. window hasnt been Project Plan and Requirements are to be mentioned in Technical Proposal of Bidder which should take care of these functions as mentioned in RFP. It is requested to plan accordingly to meet requirement.

Page No. 19, Clause No. 8 Page No. 27, Clause No. 14

L2 SWITCH POWER ON ETHERNET (PoE) REQUIREMENTS FOR FIELD SITES (BROAD BAND MODEM (ADSL IPSec enabled, with minimum 4 LAN Ports) with installation) 19" 42U RACK

Page No. 17, Clause No. 3 9

10

Page No. 25, Clause No. 11

APPROPRIATE KVA CAPACITY UPS FOR SUSTAINING REQUIRED LOAD

Please provide the UPS capacity required for support of 2 racks and devices. (Pis also refer to above query)

Project Plan and Requirements are to be mentioned in Technical Proposal of Bidder should take care of these functions as mentioned in RFP. It is requested to plan accordingly to meet requirement. Project Plan, Requirements and Bill of Materials (BoM) are already defined RFP, therefore, Bidder is requested to plan accordingly to meet requirement.

Page No. 61, Annexure 10 11

DIMENSION OF SERVER & UPS ROOM

Please provide the existing floor diagram, indicating partitions required and other information if any

Page No. 27, Clause No. 13 12

Glass & Aluminum Partitioning, Vinyl Flooring, Fall Ceiling, Distemper, Vanishing Blinds and infrastructure items like

Please provide the minimum specification required.

Page No. 27, Clause No. 13 13

Earthing, Fixing of Roads, Fans, Four Split /Stand/Roof mounted ceiling Ac's (2 Ton), Separate Wiring of UPS, Lighting

Please provide the minimum specification required.

Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17.

Queries Raised by: TULIP TELECOM LIMITED S. No. 1 1.1 RFP Reference/ Vendor Reference 1 a RFP Clause Business Continuity The RFP is silent on following apects/arovisions of Business continuity such as High Availability a The components Switch, Firewall, UTM and UPS all are single units and are not provisioned in HA b Specification for FireAlarm System FireDetection & suppression system VESDA are missing c For DC Physical security CCTV Sureillance. Access control System are crucial e The cooling provisioned is not appropriate to serve Hardware/appliances being used for Business critical applications. It is highly suggested to use Precision Airconditioning for such business critical system f Kindly confirm the Fire Retardent capability (in hours) of the following products False Flooring of Server Farm Clarification Sought Clarifications by PTCUL

Kindly confirm if these products needs to be provisioned in HA

Kindly confirm if all or few of these products needs to be provisioned in Solution as mandatory Also. Provide specifications (if any) Kindly confirm it these products needs to be provisioned in Solution as mandatory?

Kindly confirm

Project Plan, Requirements and Bill of Materials (BoM) are already defined RFP, therefore, Bidder is requested to plan accordingly to meet requirements. Project Plan and Requirements are to be mentioned in Technical Proposal of Bidder which should take care of these functions as mentioned in RFP. It is requested to plan accordingly. Project Plan, Requirements and Bill of Materials (BoM) are already defined RFP, therefore, Bidder is requested to plan accordingly to meet requirements. Project Plan, Requirements and Bill of Materials (BoM) are already defined RFP, therefore, Bidder is requested to plan accordingly to meet requirements.

e.1

Entry & Exit doors of Server Farm e.2

Project Plan and Requirements are to be mentioned in Technical Proposal of Bidder should take care of these functions as mentioned in RFP. It is requested to plan accordingly to meet requirements. Project Plan and Requirements are to be mentioned in Technical Proposal of Bidder should take care of these functions as mentioned in RFP. It is requested to plan accordingly to meet requirements. Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17.

Doors for UPS room

e.3

Glass Partioning

e.4

Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. Kindly confirm Please stick to requirements of RFP requested from Bidder. Please stick to requirements of RFP requested from Bidder. Please stick to requirements of RFP requested from Bidder and clarification already issued above. Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. Already mentioned in the RFP.

1.2 2

b 2 3

Is any BMS needed Kindly confirm if a separate Media Room, Staging room is needed Kindly confirm if the WAN Link Media & Bandwidth needs to be provisioned by Bidder or PTCUL Kindly confirm if Fireproof Vault is to be provisioned by bidder or will be providd by PTCUL..Kindly mention the capacity (in ltrs). If this needs to be provisioned by the bidder them mention the Fire Retardent capacity (in Hours) Rfer Section 8 Page#29 Hardware failure/replacement calls should be resolved within 24 Hours Hardware failure/replacement at sites shoult be resolved within 3 working days UTM kindly confirm if the Service. Firewall. VPN Concentrator. Gateway Antivirus. Gateway Antispam Content Filtering. IPS all these are required to be available & functional from day one or it is only the support for these services is required. UPS As UPS is to be sized as per load & may differ with each bidder. The following specification should be removed as this makes the UPS specs Vendor specific. Minimum 6U Rack Space for Power electronics Cabinet Minimum 6U Rack Space for Battery Cabinet. The UPS shall be contained in two rugged steel cabinets one containing the power electronics and the other containing

3 4

5 5

Kindly clarifyif 24 hours is for DC & 3 Working days is for other sites?

Obviously from the day one.

Project Plan, Requirements and Bill of Materials (BoM) are already defined RFP, therefore, Bidder is requested to plan accordingly to meet requirement.

7.1

Please stick to requirements of RFP requested from Bidder.

7.2 8 8 9 9

The UPS and battery cabinets shall be capable of conversion between Tower/Stack and Rack-Mount Configuration O&M The RFP expects Operations & Maintenance for 5yrs. But is silent on the Qty of Manpower Required. Refer Price Bid Sno 5(b) L-3/L2 Switch

Please stick to requirements of RFP requested from Bidder.

Kindly fix the type & qty of manpower to size up for commercials & bring a bidders at common platform. Kindly confirm if Layer 2 or Layer -3 Switch is expected (Thought the specs given at page # 19 are of L-2 Switch)

Already mentioned in the RFP.

Please read RFP carefully and proposed according to Specifications mentioned.

Queries Raised by: WIPRO LIMITED S. No. RFP Reference/ Vendor Reference Page 11, Section 3, Subsection 3.1 RFP Clause How would the call flow work for end user issues? Is the vendor expected to setup a centralized service desk for same? Does the vendor need to provide end user support services at individual locations of PTCUL? What are the number of user at each of the location supported? Who will provice the tools for Ticket Management, Patch Management etc? Any SLA requirements for support services required? Conduct Basic Training of user as specified. Please confirm the level of training required for users - Basic Computer operating training or application training? What will be the approximate number of users to be trained? All the trainings to be conducted at on location or trainings to be conducted ate different locations? Will PTCUL provide the traing infrastructure like - training rooms, projector and courseware? Set-up field level assistance units for user handholding and troubleshooting as specified by service levels. Please specify the locations and number of days of handholding required at each location. PTCUL has aked for IP Sec VPN connectivity between sites, Is this an alternate connectivity for redundancy or this will be primary connectivity? Clarification Sought Clarifications by PTCUL Please read RFP carefully and proposed according to Specifications mentioned.

Page 11, Section 3, Subsection 3.2

Please read RFP carefully and proposed according to Specifications mentioned.

Page 11, Section 3, Subsection 3.2 3

Please read RFP carefully and proposed according to Specifications mentioned.

Page 14, Section 4, Subsection 4.6.1 4

Page 27, Section 14, Subsection 14 5

Requirement for Field Sites (24 Remote Locations) - What are the locations address and number of user at each location? What are the services provided to be at these locations? How will these locations be connected to Data Center?

Please read RFP carefully and proposed according to Specifications mentioned. Broad Band/Internet/ Leased Line shall be provided by PTCUL. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. Please read RFP carefully and proposed according to Specifications mentioned. Broad Band/Internet/ Leased Line shall be provided by PTCUL. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17.

5.0 MINIMUM SPECFICATION FOR HARWARE, 7.IPSEC WAN/INTERNET ROUTER, Point 5 MPLS Support

Layer 2 VPN (VPLS)

5.0 MINIMUM SPECFICATION FOR HARWARE, 7.IPSEC WAN/INTERNET ROUTER, Point 7 IPSec VPN 5.0 MINIMUM SPECFICATION FOR HARWARE, 7.IPSEC WAN/INTERNET ROUTER, Point 11 Flash and Memory 5.0 MINIMUM SPECFICATION FOR HARWARE, 7.IPSEC WAN/INTERNET ROUTER, Point 12 Physical Specifications

Concurrent VPN tunnels 512 MB

Please remove this clause. As shown in Figure 1 at Page 13 of RFPand mentioned in section 4.6.1 of RFP, A WAN network is to be setup by the vendor using IP-Sec VPN technology which has been asked in router already. Whereas Virtual Private LAN Services (VPLS) is a class of VPN that supports the connection of multiple sites in a single bridged domain over a managed IP/MPLS network. VPLS is used by Service provider. So, request you to remove the same. Please clarify/remove this clause. Please clarify this clause as in performance specifications of router you have already asked the 256 VPN tunnels and 400 Mbps of throughput. This clause seems to be repetitive and contradictory to earlier clause. So please remove this clause. Please remove this clause and increase the flash upgradeble requirement to 8 GB. Please remove the specific requirement of mentioning the number of DIMM slot. We request you to ask for the sufficient scalability in terms of Flash Memory rather then mentioning number of DIMM slots. Please amend this clause to 19" Rack Mountable. Fixed configuration modular routers comes in rack size from 1RU to 4 RU. So, we request you to ensure that router should be rack mounted but not to bind the same with 2 RU specification.

Please read RFP carefully and proposed according to Specifications mentioned. Broad Band/Internet/ Leased Line shall be provided by PTCUL. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17.

This is a typographical error in it and Sl. No. 7 (7), Page No. 18, Clause 5.0 Minimum Specification for Hardware should be read as "Concurrent VPN tunnels".

Should have 4 DIMM Slots

Please stick to requirements of RFP requested from Bidder.

19" Rack Mountable, 2U

Please stick to requirements of RFP requested from Bidder.

Addition Requested

10

11

Page No. 25, Clause No. 11 Appropriate KV Capacity UPS for sustaining requried Load

Router should have minimum EAL4 certification. The common criteria for Information Technology Security Evaluation (abbreviated as Common Criteria of CC) is an international standard (ISO/IEC 15408) for IT security certification. Common Criteria is an internationally recognized standard to assess the security of IT products. It is recognized by over 26 countries around the world. Common Criteria have the following objectives in developing, operating, and maintaining an evaluation and validation scheme. To meet the needs of government and industry for cost-effective evaluation of IT products. To encourage the formation of commercial security testing industry. To ensure that security evaluations of IT products are performed to consistent standards. To improve availability of evaluated of IT products. Since you have asked for the modular UPS which doesn't have the isolation transformer as the IT load is critical load isolation transformer is must for IT load so we request you to go for conventional UPS with isolation transformer. Please provide the Data Centre area and basic layout. This will help to provide you the fair pricing. Also apart from the server farm area what other area you are looking, i.e., NOC Room, Staging area, Electrical Room, BMS room if any pls provide the details. Please provide the furniture details how many people seating plan you have, assuming the furniture means chair and computer table if any please let us know. since the height of floor is 3 mtrs so the access flooring will not be possible in this case please confirm.

12

Page No. 27, Clause No. 13, Site development as per room dimensions civil work

Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. Already mentioned in the RFP.

Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17.

What size of media storage space you are looking please clarify the capacity.

13

Page No. 27, Clause No. 13, Site development as per room dimensions electrical work

Also provide the scope of job from main EB source to Data Centre IT panel and assuming that after Data Centre LT Panel the bidder has to take care the futher distribution in data centre area.

Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. Site was shown to bidders present in the Pre-Bid Meeting and provisions for work has to be made as per site. Other Bidders are free to visit site to make a comprehensive plan before bid submission. Other details are already mentioned in Part A: Technical Details of RFP from point no. 3 to 17. Yes this is solution specific and technical solution should be such so as to meet requirements mentioned in RFP. Please stick to requirements of RFP requested from Bidder.

General 14

General 15

since you have asked for the Generator please provide the DG capacity and its specification or shall bidder calcalculate its own as per the load, pls confirm. Since precision cooling is preferable for Data Centre request you to pls add on the Precision cooling specification for server farm area and rest other area can be by comfort cooling. Bid has not asked for CCTV, Access control, BMS, Fire and detection and other Data Centre security product as its important for data securing, please clarify. Please specify working hours. The uptime % is not mentioned however the client has specified resolution time. Please include query if we need to know the uptime%.

Please stick to requirements of RFP requested from Bidder.

16

Page No. 11, Point 3.2

Queries Raised by: IBM S. No. RFP Reference/ Vendor Reference RFP Clause Clarification Sought Clarifications by PTCUL Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

5.0 Minimum specification for hardware, Database Server Specifications;Pg 15

Min 162.5' Drive Bays; 300GBx3 SAS Drive 10K/15K.

5.0 Minimum specification for hardware, Database Server Specifications;Pg 16 5.0 Minimum specification for hardware, Database Server Specifications & Application Server Specifications;Pg 16 5.0 Minimum specification for hardware, 19' 42 U Rack; Pg 17 5.0 Minimum specification for hardware, Storage Area Network (SAN); Pg 17

4Gb dual port fibre channel HBA

As of now the DB Server is configurated with only 3 SAS drives, but the expandability is asked for 16 Bays.. Moreover there is another SAN box for database storage as a part of Solution. So why such a scalability is required? The Hardware configuration is not as per the Recommended Architecture of Oracle Database, Request you tou kindly modify the same. The necessary cables should also be included with the solution.

Proposed solution should care of these provisions.

5.0 Minimum specification for hardware, Storage Area Network (SAN); Pg 17 5.0 Minimum specification for hardware, Backup Tape Driver; Pg 17 upto two drives in enclosure

Monior is not mentioned in the specifications, only keyboard and mouse are considered. Please insert the same or include KVM Switch with accessories and remove individual Keyboard/Mouse from the specifications. KVM Switch is not taken into account. We suggest that KVM switch should be included in the specifications for easy manageability of Servers. The requirment is not very clear as the Database serve has 16 bays expandability, while the storage has only 12 bays scalability. Please explain why these are two different requirement. These can be very well integrated into the same solution. The Storage specifications does not ask for any SAN Switch Specifications, whereas as per the BOM on page 50, it says with SAN Switch. Please clarify Whether SAN Switch is required as the part of solution. Please mention the number of drives required in the Tape drive.

Keyboard and mouse are obviously required for monitor. Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

This is a typographical error in it and Sl. No. 3 (a), Page No. 50, Annexure - 4 (P1) should be read with deletion of "with SAN switch".

5.0 Minimum specification for hardware 5.0 Minimum specification for hardware

LTO4/LTO5 Drives

Please be specific which Tape Drive is required as there is cost difference between the same. Kindly deleted LTO4 or LTO5. Specifications for Backup software is not mentioned. We suggest to include the Detailed specifications of the Backup Software as per the Scope of Work under Backup.

As per Bill of Material.

Requirements are to be met as specified in RFP and propose in Technical Solution. So, Bidder is requested to plan accordingly to meet requirements.

10

5.0 Minimum specification for hardware, RHEL Standard Server Edition; Pg 17 Part C: Annexures and Forms, Annexure 4 (P1); Pg 50

All Servers must be provided with latest version of 64-bit Red Hat Enterprise Linux Operating System for 1 socket pair (i.e.2 populated sockets) up to 1 gues with 1 year Standard support. Fiber optic based 2 TB or more row capacity (approx.) external RAID-5 or better Dual RAID controller with 1GB cache each with SAN switch. Tape Library, LTO-5 or better/Backup Tape Drive

1 Year Standard Support is mentioned, whereas as per clause mentioned on Page 11, the software support/subscription is required for 5 years. This needs to be changed to 5 Years Support. Fiber Optic based Storage is expected with a SAN Switch based solution, but on the contrary the specifications do not include and SAN Switch. Please refine the statement. This statement contradicts with the specifications of device. LTO-4/LTO-5 will give he flexibility of quoting for either of them but there is a cost difference in both. Please suggest which drive is required.

This is a typographical error in it and Sl. No. 6 (1), Page No. 17, Clause 5.0 Minimum Specification for Hardware should be read as "5 years".

Please refer to clarification mentioned above.

11

12

Part C: Annexures and Forms, Annexure 4 (P1); Pg 51

Please refer to clarification mentioned above.

Queries Raised by: MUDRA S. No. RFP Reference/ Vendor Reference RFP Clause Clarification Sought Clarifications by PTCUL Please stick to requirements of RFP requested from Bidder and is understood. It is also requested to please read RFP carefully for clarity.

5.0 Minimum specification for hardware, Other Passive Components; Pg 17 5.0 Minimum specification for hardware, Unified Threat Management Applicance; Pg 21

2x24 Port Patch Panel

It should be 2x24 port Cat6A based Patch Panel.

Part C: Annexures and Forms, Annexure 4 (P1); Pg 51

Layer 2 Swtich (Managed)/Layer 3 Switch(24)

Subscriptions of different functionalities such as IPS/IDS, Gateway Antivirus, Gateway Antispam are not mentioned specifically. We suggest, based on the clause mentioned on page 11, it should be bundled with 5 Year Subscription License. Specs mentioned in Technical Specs section is for a Layer - 2 POE Switch, thus the same needs to be changed.

Need not to be mentioned separately, this all comes under scope of work as per RFP

Please read RFP carefully and proposed according to Specifications mentioned.

Queries Raised by: HP & M/s ESDS SOFTWARE SOLUTION PVT. LTD. S. No. RFP Reference/ Vendor Reference 7. IPSEC WAN/INTERNET ROUTER/Page No.18 RFP Clause Port Configuration: Shall have at least 4 nos of 10/100/1000 RJ45 LAN Ports Clarification Sought 225 KPPS of Router performance is asked . With this performance the router will use maximum 100 Mbps bandwidth on port , and the gigabit port is not required at all. More over, the gigabit bandwidth contains more electrical interferences hence it is less stable as compare to fast ethernet and at router end the link stability is very important, hence we request you to modify the clause as "Shall have at least 4 nos of 10/100 RJ45 LAN Ports" As compared to Router performance which is 225 KPPS the VPN performance asked is extremely high. With this router performance the VPN performance must not exceed 250 Mbps, hence we request you to modify the clause as "AES256+SHA1/3DES+SHA-1 VPN performance of at least 250 MBPS" . Currently the clause is favoring a Single OEM and hence request you to make the chnage to make it generic without impacting the overall requirement as submitted please As per the envisaged network infrastructure there is not much requirement of BGP. BGP is generally used for backing the core routing decision on internet . Within intranet OSPF is used and OSPF which is the requirement of this network, its routes asked are very low hence we request you to modify the clause as "Should support 30K/10K BGP/OSPF Routes" to make it generic for all OEMs and enable them to bid VPN tunnels is not a memory term hence it should not be measured in MB. VPN tunnel is generally only numbers, hence we request you to modify the clause as "Concurrent VPN tunnels 512" Clarifications by PTCUL Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

7. IPSEC WAN/INTERNET ROUTER/Page No.18

Performance: AES256+SHA-1/3DES+SHA-1 VPN performance of at least 400 MBPS

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

7. IPSEC WAN/INTERNET ROUTER/Page No.18

Routing Should support 64K/5K BGP/OSPF Routes

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

7. IPSEC WAN/INTERNET ROUTER/Page No.18

IPsec VPN Concurrent VPN tunnels 512MB

Please refer to clarification mentioned above.

7. IPSEC WAN/INTERNET ROUTER/Page No.18

Flash and Memory Shall have 512MB DRAM, upgradeable to 2 GB

7. IPSEC WAN/INTERNET ROUTER/Page No.18 7. IPSEC WAN/INTERNET ROUTER/Page No.18

Flash and Should have 4 DIMM Slots

Memory

Every OEM has different architecture and their config file size will vary as per the architecture, so the clause should be made as ' router should have sufficient memory to run all the applications & configurations . Hence request you to modify the clause as " Router should have sufficient memory to run all applications and configurations OR "shall have 256 MB DRAM, upgradable to 1GB" as different OEMs have different architecture and to enable all the OEMs to bid without comprising on performance 2 DIMM slots are sufficient to fullfill the memory requirement ,hence we request you to modify the clause as "should have 2 DIMM slots" Every OEM has different architecture and their config file size will vary as per the architecture, so the clause should be made as ' router should have sufficient memory to run all the applications & configurations . Hence request you to modify the clause as " Router should have sufficient memory to run all applications and configurations OR "shall have 256 MB DRAM, upgradable to 1GB" as different OEMs have different architecture and to enable all the OEMs to bid without comprising on performance The POE available power asked in RFP is 370 Watts, and as such the switch should be POE not POE+ . Poe switch has 15.4 watt power per port which means 15.4x24=370 W approx ,for POE+ the power should be 24x30=720 W,hence we request you to modfy the clause as "24 Ethernet 10/100/1000 POE Ports" Every OEM has different architecture and their config file size will vary as per the architecture, and in HP's architecture Flash is not needed beyond 16 MB. Hence request you to modify the clause as " 16 GB or More to enable all the OEMs to bid . Currently the clause is OEM specific IEEE 802.3ah is old terminology which is used in ethernet switches which used the fast ethernet ports for uplink. But in RFP gigabit switch is asked , hence it should also have Gigabit uplink atleast, hence we request you to remove this clause which is not the requirement of the RFP

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity. Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

Flash and Memory Should have 512MB Flash, upgradeable to 1GB

8. L2 SWITCH POWER ON ETHERNET (PoE)/Page No.19 8

Switch Architecture Interfaces : 24 Ethernet 10/100/1000 PoE+ ports

8. L2 SWITCH POWER ON ETHERNET (PoE)/Page No.19 9

Switch Architecture Flash Memory : 64 MB or more

8. L2 SWITCH POWER ON ETHERNET (PoE)/Page No.20 10

IEEE 802.3ah (100BASE-X single/multimode fiber only)

8. L2 SWITCH POWER ON ETHERNET (PoE)/Page No.20 11

1000BASE-ZX (SFP)

8. L2 SWITCH POWER ON ETHERNET (PoE)/Page No.20 12

4.(SAN) Host Interface 13 4. (SAN) RAID Configuration 14

1000BASE-CWDM SFP 1470 nm 1000BASE-CWDM SFP 1490 nm 1000BASE-CWDM SFP 1510 nm 1000BASE-CWDM SFP 1530 nm 1000BASE-CWDM SFP 1550 nm 1000BASE-CWDM SFP 1570 nm 1000BASE-CWDM SFP 1590 nm 7 Standards 1000BASE-CWDM SFP 1610 nm Storage to be provided with 4 or moe 8 Gbps Fibre connectivity ports with 8 port fibre channel HBA RAID controller should support RAID levels 0, 1, 3, 5, 6, and 10

1000BASE ZX is non standard gigabit Ethernet transmission using 1,550 nm wavelength to achieve distances of at least 70 km over single-mode fiber.Today's standard use 1000Base-LH(SFP) using 1550nm to achive 70 Km distance,hence we request you to modify the clause as 1000BASE-ZX(SFP)/1000BASE-LH(SFP) This network infrastructure doesnt have need of CWDM.CWDM is used in telecom & defence organizations and it is generally feature of industry grade switches hence we request you to remove this clause" which is not the requirement of the RFP/department.

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

Instead of 8 port fibre channel it should be 8 port FC redundant switches. Please clarify

Please stick to requirements of RFP requested from Bidder. It is also requested to please read RFP carefully for clarity.

Hardware RAID is not mentioned which results in better reliability and performance and hence request you to kindly amend the clause as " RAID controller should support Hardware RAID levels 0, 1, 3, 5, 6, and 10 PCI ports have been replaced by PCI-e ports and hence request you to kindly amend the clause as : 4 PCI-e slots scalable to min 6 slots for future expansion

1.Database Server 15