Anda di halaman 1dari 40

Low voltage products

Cable current transformers types: KOLMA, KOLA, KOKM, KORI, KOLT

2 Cable current transformers

Index

Transformers for residual current measurement KOLMA, KOLA ............................................................................................................. 4 How to select the correct residual current transformers ............... 4 Technical data ............................................................................................................ 4 Installation ..................................................................................................................... 4 Ordering data ............................................................................................................. 6 Overall dimensions ................................................................................................. 7 Indoor cable current transformers KOKM ................................................................................................................................. 8 Technical data ............................................................................................................ 8 Ordering data .......................................................................................................... 10 Overall dimensions .............................................................................................. 12 KOKM (for ZX panels) ........................................................................................... 17 Technical data ......................................................................................................... 17 Overall dimensions .............................................................................................. 19 KOKM (for RMU) ...................................................................................................... 28 Electrical parameters ......................................................................................... 28 Terminal marking ................................................................................................... 29 Overall dimensions, connection diagram ............................................. 30 Indoor special current transformer KORI ................................................................................................................................. 33 Technical data ......................................................................................................... 33 Overall dimensions .............................................................................................. 34 Current transformers for oil-immersed transformers KOLT ................................................................................................................................ 35 Technical data ......................................................................................................... 35 Overall dimensions .............................................................................................. 37

Cable current transformers 3

Transformers for residual current measurement types KOLMA, KOLA

KOLMA_ and KOLA_ cable current transformer are used to measure the sum of 3-phase currents in a 3-phase cable. Under normal operating conditions this sum is zero. In the event of an earth-fault it is equal to the earth-fault current and a corresponding current flows in the secondary winding. These transformer types are used together with static earth-fault relays, and as well as measuring residual current, for example, they can be used to prewarn of, or locate an earth-fault. An busbar or cable serves as the primary conductor. How to select the correct residual current transformers The transformer for an earth-fault relay is selected according to dimension of the window and construction of the transformer. For types KOLMA 06 A1, and KOLMA 06 D1, the number of turns used in the secondary winding is selected according to the relay setting value and the earth-fault current or the required current ratio. In addition correct functioning of the earth-fault protection relays for KOLMA 06 A1 and KOLMA 06 D1 is easy to test by means of the transformer test winding (terminals P1x - P2x). The test winding is rated for 6 A maximum continuous current. Table 1. Selection of residual current transformers
Type KOLMA 06 A1 KOLMA 06 A2 KOLMA 06 B2 KOLMA 06 D1 KOLMA 06 D2 KOLA 06 B2 KOLA 06 D2 Window diameter [mm] 90 58 100 180 180 100 180 Ring core, multi-tap secondary Ring core Ring core Ring core, multi-tap secondary Ring core Split ring core Split ring core Construction Weight [kg] 7.0 2.9 5.4 11.5 11.4 6.0 11.0

Table 2. Technical data


Rated voltage Insulation test voltage 50 Hz 1 min Frequency Rated thermal current Short-time withstand current Ith 1 s Peak withstnad current Idyn Secondary terminals Operating temperature range Conformity with standards
(1) (2)

0.72 kV

(1)

3 kV (IEC 60044-1) 50 Hz (60 Hz) 1.2 x I pn 60 x Ipn


(2)

2.5 x Ith for 6 mm2 conductor 25 ... +40C IEC 60044-1

The insulation level of the primary conductor determines the maximum operating voltage. KOLA 06 B2 is type tested for 10 kA 3 s.

The primary winding of indoor type cable current transformers is either a cable or a busbar, which is insulated for the application voltage. The secondary winding and ring shaped iron core is cast in resin which has good electrical and mechanical properties. Installation The KOLMA-type transformers must be installed before the cables and cable terminations are connected. With the KOLA 06 B2 and KOLA 06 D2 types, the ring core can be opened and the transformer installed even though the cable is already connected. The two halves of the ring core are tightened together with four screws, which also guide the halves to the correct position. The secondary winding is distributed over both halves of the core. The two sections of the winding are joined together with two connecting pieces. Cable current transformers are fastened either by means of the fixing base or by the nuts cast into the transformer frame. When

4 Cable current transformers

installing the transformer, the effect of the current on the metal armour or in the protective conductor must be eliminated. In case the metal armour or the protective conductor is drawn through the transformer, the earthing conductor must be drawn back through the transformer for earthing. The earthing conductor between the cable termination box and the transformer must not be connected to conductive structures, and the metal cable termination box must be insulated from the supporting structures. On a multi-ratio transformer the unconnected secondary winding terminals and test winding must not be short circuited. Number of turns and terminal markings
Cable P1 P2 10 S1 S2 20 S3 70 S4 Cable P1 100 S1 S2 P2 50 20 S5 P1x P2x Test winding

KOLMA 06 A1 KOLMA 06 D1 KOLMA 06 KOLMA 06 KOLMA 06 KOLA 06 KOLA 06 A2 B2 D2 B2 D2

Openable residual current transformers, type (KOLA 06 B2) complete with fixing base KOLMA-ZK 1 and terminal cover KOK-ZAX 14.

Table 3. Current ratios and rated burdens for accuracy class 10P10
Current ratio [A] 50/1 70/1 100/1 150/1 50/5 100/5 150/5 250/5 350/5 500/5 600/5 750/5 Secondary terminals S4 - S5 S3 - S4 S1 - S4 S1 - S5 S1 - S2 S2 - S3 S1 - S3 S4 - S5 S3 - S4 S1 - S4 S3 - S5 S1 - S5 Burden/VA Type KOLMA 06 A1 1.0 2.0 2.5 5.0 1.0 2.5 4.0 7.5 10.0 15 20 20 KOLMA 06 D1 0.5 1.0 2.0 4.0 0.5 1.5 3.0 5.0 7.5 10 15 15

Cable current transformers 5

Table 4. Standard technical parameters for KOLMA_ and KOLA_


Type KOLMA 06 A2 KOLMA 06 B2 KOLMA 06 D2 KOLA 06 B2 KOLA 06 B2 KOLA 06 B2 KOLA 06 B2 KOLA 06 B2 KOLA 06 B2 KOLA 06 B2 KOLA 06 B2 KOLA 06 B2 KOLA 06 B2 KOLA 06 D2 KOLA 06 D2 KOLA 06 D2 KOLA 06 D2 KOLA 06 D2 KOLA 06 D2 KOLA 06 D2 KOLA 06 D2 KOLA 06 D2 KOLA 06 D2 KOLA 06 J2 KOLA 06 J2 KOLA 06 J2 KOLA 06 J2 Primary current [A] 100 100 100 50 100 200 200 400 500 600 1,250 1,500 1,600 50 100 150 200 200 300 400 400 1,000 1,800 50 100 1,250 1,250 Secondary current [A] 1 1 1 1 1 1 5 5 5 1 1 1 5 1 1 1 1 5 1 1 5 1 5 1 1 1 5 Accuracy class [A] 10P10 10P10 10P10 10P10 10P10 10P10 10P10 5P10 5P20 10P10 5P20 5P10 1 10P10 10P10 10P10 10P10 10P10 10P10 10P10 5P10 5P10 1 10P10 10P10 5P20 10P10 Burden [VA] 2 2 2 0.5 2 4 4 5 2.5 2 5 2.5 20 0.5 2 2 5 2 5 5 5 10 20 0.5 1 5 1 inner [mm] 58 100 180 100 100 100 100 100 100 100 100 100 100 180 180 180 180 180 180 180 180 180 180 300 x 497 300 x 497 300 x 497 300 x 497 Dimensions outer [mm] 140 196 270 228 228 228 228 228 228 228 228 228 228 315 315 315 315 315 315 315 315 315 315 410 x 610 410 x 610 410 x 610 410 x 610 height [mm] 65 65 80 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 90 90 90 90

If other electrical parameters other than those given in the tables are required please contact our sales department.

Table 5. Selection of accessories for KOLMA_ and KOLA_


Description of accessory Fixing base Fixing base Fixing base Fixing base Fixing base Fixing base Fixing base Secondary terminal cover Secondary terminal cover Secondary terminal cover Secondary terminal cover Type Suitable for use together with transformer KOLMA-ZK 1 KOLMA-ZK 1 KOLMA-ZK 1 KOLMA-ZK 1 KOLMA-ZK 2 KOLMA-ZK 2 KOLMA-ZK 2 KOK-ZAX 14 KOK-ZAX 14 KOK-ZAX 14 KOK-ZAX 14 KOLMA 06 A1 KOLMA 06 A2 KOLMA 06 B2 KOLA 06 B2 KOLMA 06 D1 KOLMA 06 D2 KOLA 06 D2 KOLMA 06 A2 KOLMA 06 B2 KOLA 06 B2 KOLA 06 D2

Incorrect transport Incorrect storage A failure to follow instructions correctly during installation and operation Incorrect selection of the transformer for the electric power system Ordering data The order should contain the following data: Type of current transformer Rated primary current/rated secondary current [A/A] Rated burden and accuracy class for each winding [VA] Short-time thermal current Ith Standard Quantity Order example KOLA 06 B2; 100/1 A/A; 2 VA; 10P10; Ith = 60xIpn/1s; IEC 60044-1; 12 Pcs.

Warranty A two-year warranty period is granted from the date the transformer starts to operate. However, a maximum warranty period of three years is granted from the time of purchase. The warranty only covers manufacturing defects and does not include defects due to:

6 Cable current transformers

Overall dimensions

KOLMA 06 A1
52

52

M8

KOLMAM5 A2, B2 06
39 78

KOK-ZAX 14 12,5 KOK-ZAX 14

KOLMA-ZL2,3 KOLMA 06 D1, D2

25

80 23

M8

M5

KOLMA-ZL2,3
P1

17

25

80 23

78 39 KOLMA-ZL 2,3

AB

12,5 C

17
P1
180
335

P1

KOLMA-ZL 2,3

14

AB
M8 52 65

C
18 KOLMA-ZK1

180

140

335

245

P1
90 238

14

M8

52
145 175

65

18 KOLMA-ZK1

15

140 18
15

245

90
14 96 186

113 238

145

175

130 150 190 270 130

115 145 KOLMA-ZK2 18

113 18
KOLMA-ZK1

78 D

150 190 270

115 145 KOLMA-ZK2

14

96 186

18

78 D

KOLMA-ZK1

Type KOLMA 06 A2 KOLMA 06 B2

Dimensions [mm] A 58 100 B 177 229 C 196 249 D 140 196

KOLA 06 B2
M5

KOLA 06 D2
7 KOK-ZAX 14 KOK-ZAX 14
M5

KOLA 06 J2
M5
7

M5
7

15

a2 a1

18,5

KOK-ZAX 14 KOK-ZAX 14

M6

113

80 18,5

23

7
0

15

410 370 300

462

M5

M5

P1 10

0 P1 10

109

109 219 238

219

20 410 370 300

219
52

R1

10 0

10 0

238
18 M8

16

110

110

219
14

238
18 M8
150

0 18

140 16

293

293
3

315

315

b2 b1
20

M8

P2

36 228

36 20 228

20

20
85

20

619

S2

M5

85

36 315
1 2

36 315
1

P1

P2
a1 a2 b2 b1

20
2

85 115 20 85 115 145

145
S1

S2

36 228

36 20 228

20
36 315

36 315

ABB

22,5

11

11 130

a1 a2 b2 b1

90

S1

62

52

52

KOLMA-ZK1 KOLMA-ZK1 85 85

M8

20

150

M10

P1 a2 a1

P1

14

14

18

20

150

3 18 KOLMA-ZK 2 18 M10 130 KOLMA-ZK 2 85 115 145 20 85 115 145 20

P2

18

619

M5

P2

S1 S2

22,5

11

11 130

a2 b2 b1 a1
20

497 +3 0 570 610

62

52

14 110 110 KOLMA-ZK1 KOLMA-ZK1

3 140 150 18 140 KOLMA-ZK 2 18 16 130 KOLMA-ZK 2 16

0 R4

497 +3 0 570 610


P1
S1 S2

M10

90 20 R1 4

M10

462

109

109

238

M5

M5

0 18 P1

0 18 P1

153 293

23

153

a2 a1

18,5

M5

M5

M5 P1

M5 P1

KOK-ZAX 14 KOK-ZAX 14

M5

M5

P1M5

P1M5

KOK-ZAX 14 KOK-ZAX 14

40

M6

113

80

18,5

6
a b

293

0 18

153

153
a b

315
a b

315

40

140

0 R4

ABB

Cable current transformers 7

Indoor cable current transformers type KOKM

KOKM_ current transformers are suitable for measuring phase currents. A busbar or cable serves as the primary conductor. Series KOKM current transformers can also be used for measuring the phase current at voltages higher than 0.72 kV (for KOKM 06) or 1.2 kV (for KOKM 1), if the insulation of the primary conductor satisfies the requirements of the respective standards for the operating voltage. The secondary winding and ring shaped iron core are cast in resin which has good electrical and mechanical properties. Table 6. Technical data
Transformer type Rated voltage Power frequency test voltage Lighting test voltage Frequency Max. primary current Rated secondary current Rated thermal current Short-time withstand current Peak withstand current Secondary terminals Operating temperature range Transport and storage Electrical standards
(1) (2)

KOKM 06_ Um U p (1 min) U pp fn Ipn I sn Icont I th (1 s) I dyn [kV] [kV] [kV] [Hz] [A] [A] [A] [kA] [kA] [C] [C] 0.72
(1)

KOKM 1_ 1.2
(1)

3 50 or 60 50 2,000 1 or 5 1.2 x Ipn


(2)

6 50 10,000

60 x I pn (Max. 100 kA) 2.5 x Ith (Max. 250 kA) for 6 mm2 conductor -25 +40 -40 +55 IEC, VDE, ANSI, BS, AS, CAN

The insulation level of the primary conductor determines the maximum operating voltage. Max. Icont for KOKM 06 Icont = 2 400 A, for KOKM 1 Icont= 10 000 A.

8 Cable current transformers

Table 7. Standard parameters for KOKM 1_


Type KOKM 1 BC10 KOKM 1 DC8 KOKM 1 DF12 KOKM 1 DC6 KOKM 1 DC14 KOKM 1 DC12 KOKM 1 DC16 KOKM 1 DH10 KOKM 1 EC8 KOKM 1 EF16 KOKM 1 EC8 KOKM 1 EC6 KOKM 1 EC16 KOKM 1 EH16 KOKM 1 EC10 KOKM 1 EF14 KOKM 1 FC6 KOKM 1 FC16 KOKM 1 FC8 KOKM 1 FC12 KOKM 1 FC8 KOKM 1 GF6 KOKM 1 GF8 KOKM 1 GF6 KOKM 1 HF8 KOKM 1 HF8 KOKM 1 HH16 KOKM 1 HF12 KOKM 1 HK10 KOKM 1 HK10 KOKM 1 HK10 KOKM 1 HK10 KOKM 1 HK14 KOKM 1 HF6 KOKM 1 HF6 KOKM 1 HJ8 KOKM 1 KH8 KOKM 1 KH8 KOKM 1 KH18 KOKM 1 KH18 KOKM 1 KH10 KOKM 1 KH8 KOKM 1 KH8 KOKM 1 KH8 KOKM 1 KK10 KOKM 1 NK8 KOKM 1 NK12 KOKM 1 NK20 KOKM 1 NL14 KOKM 1 NL8 KOKM 1 RL12 KOKM 1 RL8 KOKM 1 RL12 KOKM 1 RL8 KOKM 1 RL20 KOKM 1 UT10 KOKM 1 UP16 Current primary [A] 200 100 100 150 150 300 400 5,000 100 100 150 200 250 250 400 400 50 300 600 600 1,000 50 1,000 1,500 50 50 50 100 150 200 250 300 400 400 500 2,000 50 50 200 300 1,000 1,000 1,500 2,000 2,500 50 50 50 50 3,000 50 100 100 150 300 50 100 secondary [A] 5 1 5 1 5 5 5 5 1 1 1 1 1 1 1 1 5 5 5 5 5 5 5 5 1 5 5 1 1 1 5 5 1 5 1 1 1 5 5 5 1 5 5 5 5 1 1 1 1 1 1 1 1 1 5 1 5 5P20 10P10 0.5 5P20 5P10 5P10 5P20 1 5P20 0.5 5P20 5P20 5P10 5P20 5P10 5P20 10P10 5P10 0.5 0.5 0.5 10P10 0.5 0.5 10P10 10P10 10P10 10P20 5P10 5P10 5P20 5P20 5P20 10P10 1 5P20 10P10 10P10 5P20 5P20 5P10 5P20 0.5 0.5 5P20 10P10 10P10 10P10 10P10 5P20 10P10 5P10 5P10 10P10 5P20 10P10 10P10 Accuracy class Burden [VA] 5 2 3 1 10 15 10 10 1 1 1 1 20 20 10 20 0.5 10 15 50 50 0.5 50 50 1 1 5 2 10 10 10 10 30 5 15 30 1 1 5 10 20 10 50 50 10 1 2 5 5 5 2 1 5 2 10 5 5 inner [mm] 42 60 60 60 60 60 60 60 70 70 70 70 70 70 70 70 85 85 85 85 85 90 90 90 100 100 100 100 100 100 100 100 100 100 100 100 120 120 120 120 120 120 120 120 120 155 155 155 155 155 180 180 180 180 180 250 250 Dimensions outer [mm] 148 148 186 148 148 148 148 200 148 186 148 148 148 200 148 186 148 148 148 148 148 186 186 186 186 186 200 186 250 250 250 250 250 186 186 235 200 200 200 200 200 200 200 200 250 250 250 250 270 270 270 270 270 270 270 450 340 height [mm] 100 80 120 60 140 120 160 100 80 160 80 60 160 160 100 140 60 160 80 120 80 60 80 60 80 80 160 120 100 100 100 100 140 60 60 80 80 80 180 180 100 80 80 80 100 80 120 200 140 80 120 80 120 80 200 100 160

The Parameters depend on the transfomer type (size); generally, the bigger the current transformer, the higher the technical parameters. If other electrical parameters other than those given in the tables are required please contact our sales department.

Cable current transformers 9

Ordering data The order should contain the following data: Type of current transformer Rated primary current/rated secondary current [A/A] Rated burden and accuracy class for each winding [VA] Short-time thermal current Ith Dimension of the window [mm] Standard Quantity Order example KOKM 1 FC 8; 600/5 A/A; 10 VA; 0.5; Ith = 60xIpn/1s; IEC 60044-1; 9 Pcs. Terminal markings
P1 P2 KOKM 1 NK 10

S1 S2 one secondary winding example: 100/1 [A/A]

P1

P2

S1 S2 S3 multi-tap secondary winding example: 50-100/1 [A/A]

P1

P2

1S 1 2S 1 1S 2 2S2 two secondary windings example: 800/5/5 [A/A/A]

Warranty A two-year warranty period is granted from the date the transformer starts to operate. However, a maximum warranty period of three years is granted from the time of purchase. The warranty only covers manufacturing defects and does not include defects due to: Incorrect transport Incorrect storage A failure to follow instructions correctly during installation and operation Incorrect selection of the transformer for the electric power system

10 Cable current transformers

Table 8. KOKM 1_
Outer diameter [mm] C F H J K L M P T W 148 186 200 235 250 270 280 340 450 590 A 33 60 60 80 80 80 80 80 B 42 60 60 80 80 80 80 80 80 D 60 60 60 80 80 80 80 80 80 E 70 60 60 80 80 80 80 80 80 F 85 60 60 80 80 80 80 80 80 80 60 80 80 80 80 80 80 80 80 60 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 Range of transformer width G Hole diameter [mm] H K N R S U W X Y Z KOKM 1_C_ KOKM 1_F_ KOKM 1_H_ KOKM 1_J_ KOKM 1_K_ KOKM 1_L_ KOKM 1_M_ KOKM 1_P_ KOKM 1_T_ 80 KOKM 1_W_ 90 100 120 155 180 200 250 350 400 450 500 Drawing Casting height [mm] 183 213 235 265 275 297 297 379 465 605 Total height [mm] 249 279 301 331 341 363 363 445 513 653 Hole center height [mm] 112 131 138 158 158 158 158 204 225 300

160 160 160 160 160 160 160 160 160 160 160 160 180 180 180 180 180 180 180 180 300 300 300 300 300 300 300 300 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 240 240 240 240 240 240 240 240 240 240 240 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 Example

KOKM 1 D C 10
Transformers width 10 = 100 mm (possibility 6, 8, 10, 12, 14, 16, 18, 20, 22, 24,... 30)

Outer diameter C = 148 mm Hole diameter D = 60 mm Rate voltage 1 = 1.2 kV Type KOKM indoor use (Type KOKU outdoor use)

Cable current transformers 11

Overall dimensions

KOKM 1_C_
124 52

KOKM 1_F_
20

20

11

B2 (10 0 0...160) B2 (60...80)

B 2 (120...160)

B 2 (60...10 0)

40

40

C
11

M6

113 M5

1
18,5

80

52 140

18,5

M6
23 6

113 M5

1
18,5

80

18,5

P1
40

23

P1
40

236 3

183 2

266 3

Di

+2 0

213 2

Di

+3 0

112 2

186

14

18

M8

131 2

P1

P2

P1

P2

S1

S2

M8

148

18

S1
85 F

S2

14

Di = 33 A

42 B

60 D

70 E

KOKM 1 _ C __
Di = 33 A 6 42 B 8 60 D 10 70 E 12 85 F 14 90 G 16

170 100 H

KOKM 1 _ F __

6 8 10 12 14 16 B = 60 80 100 120 140 160 C= 80 100 120

Note: 1) KOKM 1_C6 without the cover

B= C=

60

80 100 120 140 160 60 80 100 120

Note: 1) KOKM 1_F6 without the cover

KOKM 1_H_

KOKM 1_J_

B2 (10 0...180)

80

B2 (80)

18,5

40

11

52 140 M6 113
18,5
18,5 80

18,5

M5

23

P1

40

288 3

2352

Di

+30

200 M8

138 2

P1

P2

S1

S2

18

14

170

Di =

33 A 8

42 B 10

60 D 12

70 E 14

85 F 16

90 G 18

100 H

120 K

KOKM 1 _ H _

B= C=

80 100 120 140 160 180 60 80 100 120 140

12 Cable current transformers

Overall dimensions

KOKM 1_K_
20

KOKM 1_L_
20

14

B 2

B2

40

150 246 113 M6 M5 18,5 80


M6 M5

150 246 113 80 18,5

18,5

40 23

14

18,5

23

P1
6

40

P1
40

350 3

P1

6
P2

297 2

Di

+3 0

3283

2752

S1

S2

Di

+3 0

270 -2

158 2

250 -2

18

15

M8

15

270

18

P1

P2

KOKM 1 _ L _
Di = 33 42 60 70 85 90 100 120 155 180 200 A B D E F G H K N R S 8 10 12 14 140 100 16 160 120 18 20

M8 270

S1

S2

Di = 33 42 60 70 85 90 100 120 155 A B D E F G H K N 8 10 12 14 16 18 20 B = 80 100 120 140 160 180 200 C = 40 60 80 100 120 140 160

KOKM 1 _ K _

B = 80 C = 40

100 120 60 80

180 200 140 160

KOKM 1_M_

KOKM 1_P_

80 18,5 80 18,5

18,5

158 2

18,5

Cable current transformers 13

Overall dimensions

KOKM 1_T_

KOKM 1_W_

80 18,5

80 18,5

18,5

18,5

23

23

40

40

Note: Without

base. Fix directly to

Note: Without

base. Fix directly to

Table 9. Standard parameters for KOKM 06 J_ (window type) f = 50 Hz


Type Window [mm] KOKM 06 J2 KOKM 06 J2 KOKM 06 J2 KOKM 06 J2 KOKM 06 J2 KOKM 06 J2 KOKM 06 J2 KOKM 06 J2 KOKM 06 J2 KOKM 06 J21 KOKM 06 J21 KOKM 06 J21 KOKM 06 J21 KOKM 06 J22 KOKM 06 J22 KOKM 06 J22 KOKM 06 J22 KOKM 06 J22 KOKM 06 J23 KOKM 06 J23 KOKM 06 J23 KOKM 06 J23 KOKM 06 J24 KOKM 06 J24 KOKM 06 J29 KOKM 06 J29 KOKM 06 J29 KOKM 06 J29 300x500 300x500 300x500 300x500 300x500 300x500 300x500 300x500 300x500 150x500 150x500 150x500 150x500 300x200 300x200 300x200 300x200 300x200 600x200 600x200 600x200 600x200 300x200 300x250 450x650 450x650 450x650 450x650 Primary current [A] 50 50 100 100 150 300 500 600 800 50 100 700 2,000 50 100 300 1,200 2,000 50 50 100 200 50 150 50 50 100 400 Secondary current [A] 1 5 1 5 1 5 1 5 5 1 5 1 1 1 1 1 5 5 1 5 1 1 1 1 1 5 1 1 10P10 10P10 10P10 10P10 10P10 10P10 5P10 10P10 0.5 10P10 10P10 5P10 1 10P10 10P10 5P10 5P10 5P10 10P10 10P10 10P10 10P10 10P10 10P10 10P10 10P10 10P10 5P10 1 0.5 2 1 2 1 10 5 15 1 1 3 5 1 2 3 30 50 1 0.5 3 2 1 2 1 0.5 2 7.5 Accuracy class Burden [VA]

If other electrical parameters other than those given in the tables are required please contact our sales department.

14 Cable current transformers

Overall dimensions

KOKM 06 J2
113

KOKM 06 J21
80 18,5

113

M6
15

M5
18,5

M6

80 18,5

M5
18,5

23

40

40

370

300

4 10

R4

462

R1 4

500 20 573 613

+3 0

80

S1 S2

20

R4

P1

P2

500 +3 0

573

613

R1 4

150 20 220 260

P1 S1 S2

P2

KOKM 06 J22
113
80 18,5

KOKM 06 J23
113
80 18,5

80

M6
15

M5
18,5

M6
23

M5
18,5

665

20

15

23

40

40

300

410

370

R4

0
+3 0

462

20

R1 4

200 20 270 310

P1 S1 S2

P2
R4
80

673

713

600

20

4 R1
20

200 270 310

P1 S1 S2

P2
80

Cable current transformers 15

765

15

23

Overall dimensions

KOKM 06 J24
113 113
80 18,5 18,5
80

KOKM 06 J29
M6 M6
15
15

M5 M5
18,5
18,5

M6 M6

113 113 M5 M5
18,5 18,5

80 80
18,5 18,5

23

23 23

23

1
6
6

5 15

40 40

40 40

370 410 300 370

410

300

462

462

560 520 560 450 520 450

R4

04 R

20 R1 20 4 R1 4

R4

40

20

20

20

20

R1 4

R1 4

20

20

320 360

320 360

P1

P2 S1 S2 S1 S2
80

P1

P2

16 Cable current transformers

80

80 80

250

250

P1

P1

P2 P2 S1 S2 S1 S2

650+3 0 650+3 0 720 720 760 760

612 612

6 6

Indoor cable current transformers type KOKM (for GIS type ZX)

KOKM 1 LH_ is the indoor, cable, low-voltage current transformer in resin insulation. These transformer types are suitable for the measurement of phase currents. A busbar or low-voltage cable serves as the primary conductor. Current transformers from the KOKM series can also be used to measure phase currents at voltages higher than 1.2 kV if the insulation of the high-voltage primary conductor fulfils the requirements of the relevant standards related to the working voltage. Ordering data The order should contain following data: Type of current transformer Rated primary current/rated secondary current [A/A] Rated burden and accuracy class for each winding [VA] Short-time thermal current Ith Standard Quantity Order example KOKM 06 NN; 12 150/1 A/A, Ith = 60 x Ipn, 1 VA 10P10 3 Pcs.

Table 10. Technical data


Type Max. number of windings Level of insulation Highest permissible voltage of the current transformer Ur Rating test voltage of insulation (50 Hz, 1 min U p) Rating frequency Rating thermal current Short-time withstand thermal current Ith, 1 s Rating peak current Idyn Working temperature range Conformity with standards 50 Hz 1.2 x I pn 60 x I pn 2.5 x Ith -5 ... +40C IEC, ANSI, PN-EN, CAN 6 kV KOKM 1 LH_ 1 1/6/1.2 kV

Cable current transformers 17

Table 11. Standard parameters for KOKM 1 LH_


Primary current Ipn [A] FS 0.5 50 60 70 75 100 110 120 140 150 200 240 250 300 350 400 500 600 630 800 1000 1200 1250 4 9 10 17 29 60 60 60 60 90 90 90 90 1 1.5 3 3.5 6 8.5 20 30 32 50 60 90 90 90 90 90 90 90 90 10P10 2 2 2.5 2.5 3.5 4 4 5 5.5 7.5 8.5 9 11 12 12 15 18 19 20 26 31 31 Secondary current I sn = 1 [A] Measurement class Protection class Fa 10P20 1 1 1 1 1.5 1.5 1.5 1.5 2 2 3.5 3.5 4 4.5 3 4 5.5 5.5 5.5 7 8.5 8 5P10 0.5 0.5 1.5 1.5 3.5 4 4 5 5.5 7.5 8.5 9 11 12 12 15 18 19 20 26 31 31 5P20 0.5 0.5 1 1 1.5 1.5 1.5 2 2 3 3.5 3.5 4 4.5 3 4 5.5 5.5 5.5 7 8.5 8 Fs 0.5 2.5 9 10 19 29 39 50 60 60 90 90 90 90 1 1.5 2.5 3.5 7.5 8.5 11 29 33 50 60 60 90 90 90 90 90 90 90 10P10 1.5 2 2.5 2.5 3 3.5 3.5 4.5 5 7 8.5 9 10 12 14 18 21 21 26 27 30 32 Maximum permissible load [VA] Secondary current Isn = 5 [A] Measurement class Protection class Fa 10P20 1 1 1 1.5 1.5 1.5 1.5 2 2 2.5 3 3.5 4.5 5.5 6 8 8.5 8.5 9 5.5 6 6.5 5P10 0.5 1 1.5 2 3 3.5 3.5 4.5 5 7 8.5 9 10 12 14 18 21 21 26 27 30 32 5P20 0.5 0.5 1 1 1.5 1.5 1.5 2 2 2.5 3 3.5 4.5 5.5 6 8 8.5 8.5 9 5.5 6 6.5

By special request current transformers with secondary current values different from those given in the table above (eg. 4.3 A), and current transformers for a frequency of 60 Hz can be supplied.

18 Cable current transformers

Overall dimensions

KOKM 1 LH_ version 01


126 60
14,5 19

KOKM 1 LH_ version 02


126 70

26

37

37

126 60
14,5

70

90
26
1 30

126

0 13
37

235

19

2 37

235

M8

235

37

200 37
90 126 180 200 200 30,5

10

37

11

M8

117,5

90 126 180 200

235

B A

90 126 180 200


11

10

30

30

37

11

M8

117,5

11

117,5

90

M8

200

117,5

B A

10

200 40
12

24,5

M5

M5

M5

M3

58
37

40

40

12

24,5

Type KOKM 1 LH 6 KOKM 1 LH 9 KOKM 1 LH 12

Dimensions [mm] A 60 90 120


M5

30,5

B
M5

M5

M3

30 60 90

KOKM 1 LH_ version 03


245

1
secondary terminals, lenght 6 m, cable 4 mm

30

112,5

secondary terminals, lenght 6 m, cable 4 mm

112,5

fixing base rating plate

screw cap for bushing PG16

170

seal wire pocket PG16

145 170 200

55,5

fixing base rating plate

15

Index of CT 1YMA183183R0013
170

105,5

117,5

145 170 200

55,5

245

30

105,5

117,5

Description CT KOKM 1 LH 12 with cable and P2 from cable side CT KOKM 1 LH 9 with cable and P2 from cable side CT KOKM 1 LH 6 with cable and P2 from cable side CT KOKM 1 LH 12 with cable and P1 from cable side CT KOKM 1 LH 9 with cable and P1 from cable side CT KOKM 1 LH 6 with cable and P1 from cable side

37

90 126 58 180 40 200

B A

B A

10

Code KOKM 1 LH 12-v3-P2 KOKM 1 LH 9-v3-P2 KOKM 1 LH 6-v3-P2 KOKM 1 LH 12-v3-P1 KOKM 1 LH 9-v3-P1 KOKM 1 LH 6-v3-P1

A 120 90 60 120 90 60

B P2 P2 P2 P1 P1 P1

seal wire pocket PG16 screw cap for bushing PG16

330 360

15

1YMA183183R0012
15

1YMA183183R0011
330 360 15

1YMA183183R0003 1YMA183183R0002 1YMA183183R0001

Cable current transformers 19

KOKM 1 NJ_ is the indoor, cable, low-voltage current transformer in resin insulation. These transformer types are suitable for the measurement of phase currents in low-voltage switchgears. A non-insulated busbar or low-voltage cable serves as the primary conductor. Current transformers from the KOKM series can also

be used to measure phase currents at voltages higher than 1.2 kV if the insulation of the high-voltage primary conductor fulfils the requirements of the relevant standards related to the working voltage.

Table 12. Technical data


Type Max. number of windings Highest permissible voltage of the current transformer Ur Rating test voltage of insulation (50 Hz, 1 min U p) Rating frequency Rating thermal current Short-time withstand thermal current Ith, 1 s Rating peak current Idyn Working temperature range KOKM 1 NJ 8 version 01 Conformity with standards 6 kV 50 Hz 1.2 x I pn 60 x I pn 2.5 x Ith -5 ... +40C IEC, ANSI, PN-EN, CAN KOKM 1 NJ_ 1 1.2 kV

Table 13. Standard parameters for KOKM 1 NJ_


Primary current Ipn [A] FS 0.5 50 60 70 75 100 110 120 140 150 200 240 250 300 350 400 500 600 630 800 1000 1200 1250 1.5 4.5 5 9 18 29 35 50 50 60 90 90 90 1 0.5 2 3.5 5 6.5 8 13.5 15 23 35 50 80 90 90 90 90 90 90 10P10 2 2.5 3 3.5 4.5 5 5.5 6.5 7 8 9.5 10 12 14 16 20 24 25 31 38 42 45 Secondary current Isn = 1 [A] Measurement class Protection class Fa 10P20 1 1 1.5 1.5 2 2.5 2.5 3 3 3.5 4.5 4.5 5.5 6.5 7.5 9 11 11 14 16 18 18 5P10 0.5 0.5 1.5 2 4 4.5 5.5 6.5 7 8 9.5 10 12 14 16 20 24 25 31 38 42 45 5P20 0.5 1 1.5 1.5 2 2.5 2.5 3 3 3.5 4.5 4.5 5.5 6.5 7.5 9 11 11 14 16 18 19 1 4.5 5 11 18 20 30 45 50 90 90 60 60 FS 0.5 1 0.5 1.5 3 4.5 5 9 14 15 26 32 40 60 90 90 90 90 90 90 10P10 2 2.5 3 3 4 4.5 5 6 6.5 9 10 11 13 15 18 20 25 26 30 38 40 40 Maximum permissible load [VA] Secondary current Isn = 5 [A] Measurement class Protection class Fa 10P20 0.5 1.5 1.5 1.5 1.5 2 2 2.5 3 4 5 5 6 7 8 10 12 12 13 14 13 12 5P10 0.5 0.5 1 1.5 4 4.5 5 6 6.5 9 10 11 13 15 18 20 25 26 30 38 40 40 5P20 0.5 0.5 1 1 1.5 2 2 2.5 3 4 5 5 6 7 8 10 12 12 13 14 13 12

By special request current transformers with secondary current values different from those given in the table above (eg. 4.3 A), and current transformers for a frequency of 60 Hz can be supplied.

20 Cable current transformers

Overall dimensions

KOKM 1 NJ_ version 01


105 60 14,5 19

KOKM 1 NJ_ version 02


105 70
26

55

240

55

247

55

55

120

11

M8 55

11

M8 55 90 105 215 235 235 10

10

120

90 105 215 235 235

B A

93 40 58 55 31 31 37

40

12

24,5

30,5 M5

M5

M3

M5

Type KOKM 1 NJ 6 KOKM 1 NJ 9 KOKM 1 NJ 12

Dimensions [mm] A 60 90 120 B 30 60 90

KOKM 1 NJ_ version 03


A

secondary terminals, lenght 6 mm cable 4 mm

205 235

73

fixing plate rating plate

seal wire pocket PG16 screw cap for bushing PG16

15 15

330 360

Index of CT 1YMA183182R0013 1YMA183182R0012 1YMA183182R0011 1YMA183182R0003 1YMA183182R0002 1YMA183182R0001

205

Description CT KOKM 1 NJ 12 with cable and P2 from cable side CT KOKM 1 NJ 9 with cable and P2 from cable side CT KOKM 1 NJ 6 with cable and P2 from cable side CT KOKM 1 NJ 12 with cable and P1 from cable side CT KOKM 1 NJ 9 with cable and P1 from cable side CT KOKM 1 NJ 6 with cable and P1 from cable side

105,5 112,5 127,5

245

15

Code KOKM 1 NJ 12-v3-P2 KOKM 1 NJ 9-v3-P2 KOKM 1 NJ 6-v3-P2 KOKM 1 NJ 12-v3-P1 KOKM 1 NJ 9-v3-P1 KOKM 1 NJ 6-v3-P1

A 120 90 60 120 90 60

B P2 P2 P2 P1 P1 P1

Cable current transformers 21

KOKM 1 EB_ and KOKM 1 ED_ are indoor, cable, low-voltage current transformers in resin insulation. These transformer types are suitable for the measurement of phase currents. A busbar or cable serves as the primary conductor. Current transformers from

the KOKM series can also be used to measure phase currents at voltages higher than 1.2 kV if the insulation of the high-voltage primary conductor fulfils the requirements of the relevant standards related to the working voltage.

Table 14. Technical data


Type Max. number of windings Level of insulation Highest permissible voltage of the current transformer Ur Rating test voltage of insulation (50 Hz, 1 min Up) Rating frequency Rating thermal current Short-time withstand thermal current Ith, 1 s KOKM 1 EB version 03 Rating peak current Idyn Working temperature range Conformity with standards 50 Hz, 60 Hz 1.2 x I pn 60 x Ipn 2.5 x Ith -5 ... +40C IEC, ANSI, PN-EN, CAN 6 kV KOKM 1 EB_, KOKM 1 ED_ 3 1/6/1.2 kV

Table 15. Standard parameters for KOKM 1 EB_


Primary current Ipn [A] FS 0.5 50 60 70 75 100 110 120 140 150 200 240 250 300 350 400 500 600 630 800 1000 0.5 1 1 1.5 5.5 5.5 4.5 12 9 22 35 60 60 60 60 1 0.5 1 2.5 4 4.5 4.5 6 8.5 20 25 40 27 40 50 60 60 60 60 10P10 0.5 0.5 1 1 1.5 1.5 1.5 1.5 2 2.5 2.5 3 3 5 4.5 6 6 5 5 6 Secondary current Isn = 1 [A] Measurement class Protection class Fa 5P10 0.5 0.5 1 1 1.5 1.5 1.5 1.5 2 2.5 2.5 3 3 5 4.5 6 6 5 5 6 5P20 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 1 1.5 2 1 0.5 Fs 0.5 0.5 1.5 1.5 2.5 8 11 15 22 30 45 60 60 60 60 1 0.5 1 1.5 2.5 3 7 7 12 25 28 40 45 60 60 60 60 60 60 10P10 0.5 0.5 0.5 1 1 1 1.5 2 2 2.5 3.5 3.5 4.5 5 6 6 5.5 6 7 Maximum permissible load [VA] Secondary current Isn = 5 [A] Measurement class Protection class Fa 5P10 0.5 0.5 1 1 1 1.5 2 2 2.5 3.5 3.5 4.5 5 6 6 5.5 6 7 5P20 0.5 0.5 1 1 1 1.5 1.5 2 1.5

By special request current transformers with secondary current values different from those given in the table above (eg. 4.3 A), and current transformers for a frequency of 60 Hz can be supplied.

22 Cable current transformers

Overall dimensions

KOKM 1 EB_ version 01


74 60

KOKM 1 EB_ version 02


56 77

14,5 32

19

0,5

72
170

205

72

70

~5m
70

70

M6

56 80
100 128 58 40 A B

100 128 M6

2=S2 M6 1=S1

40

12

M5

M3

24,5

Type KOKM 1 E ...8 KOKM 1 E ...10 KOKM 1 E ...12

Dimensions [mm] A 56 76 96 B 80 100 120

KOKM 1 EB_ version 03


8

KOKM 1 ED_
8

ok. 50 0 0

74

74

ok 50 0 0

max 6

32

90

90

32

max 6

0,5

170

170

72

M6

M6

70

70

72

0,5
120 148

A B

100 128

A B

3S 2S
90

130

50

1S

Type KOKM 1 E ...8 KOKM 1 E ...10 KOKM 1 E ...12 KOKM 1 E ...14 KOKM 1 E ...16 KOKM 1 E ...18

Dimensions [mm] A 56 76 96 116 136 156 B 80 100 120 140 160 180

50

90

130

Cable current transformers 23

KOKM 06 NN_ is the indoor, cable, low-voltage current transformer in resin insulation. These transformer types are suitable for the measurement of phase currents. A non-insulated busbar or cable serves as the primary conductor. Current transformers from

the KOKM series can also be used to measure phase currents at voltages higher than 0.72 kV if the insulation of the high-voltage primary conductor fulfils the requirements of the relevant standards related to the working voltage. Table 16. Technical data
Type Max. number of windings Level of insulation Highest permissible voltage of the current transformer Ur Rating test voltage of insulation (50 Hz, 1 min Up) Rating frequency Rating thermal current Short-time withstand thermal current Ith, 1 s Rating peak current Idyn Working temperature range 50 Hz 1.2 x I pn 60 x Ipn 2.5 x Ith -5 ... +40C IEC, ANSI, PN-EN, CAN 3 kV KOKM 06 NN_ 2 0.6/3/0.72 kV

KOKM 06 NN 12

Conformity with standards

Table 17. Standard parameters for KOKM 06 NN_


Primary current Ipn [A] FS 0.5 50 60 70 75 100 110 120 140 150 200 240 250 300 350 400 500 600 630 800 1000 1200 1250 1500 0.5 15 35 60 60 90 90 90 90 90 1 8 15 19 31 50 60 90 90 90 90 90 90 90 90 10P10 3.5 4 5 5.5 7 7.5 8 10 10 14 17 18 21 25 28 34 41 42 52 66 80 82 90 Secondary current I sn = 1 [A] Measurement class Protection class Fa 10P20 1.5 2 2.5 2.5 3.5 4 4 5 5 7 8.5 9 10 12 13 16 17 18 23 28 34 35 40 5P10 7 7.5 8 10 10 14 17 18 21 25 28 34 41 42 52 66 80 82 90 5P20 1 1.5 4 5 5 7 8.5 9 10 12 13 16 17 18 23 28 34 35 40 Fs 0.5 15 35 60 60 90 90 90 90 90 1 9 16 19 31 50 55 60 90 90 90 90 90 90 90 10P10 3 3.5 4.5 5 6 7 7 9 9 13 15 16 20 22 25 31 38 39 49 63 77 79 90 Maximum permissible load [VA] Secondary current Isn = 5 [A] Measurement class Protection class Fa 10P20 1 1.5 1.5 2 2.5 3 2.5 3.5 4 5.5 6.5 7 8 10 11 14 15 16 21 26 32 33 40 5P10 6 7 7 9 9 13 15 16 20 22 25 31 38 39 49 63 77 79 90 5P20 1 1.5 2.5 3.5 4 5.5 6.5 7 8 10 11 14 15 16 21 26 32 33 40

By special request current transformers with secondary current values different from those given in the table above (eg. 4.3 A), and current transformers for a frequency of 60 Hz can be supplied.

24 Cable current transformers

Overall dimensions

KOKM 06 NN_
M5 A 95.5 69 26.5

60

10

22

13

55

65 235

15 2 x brass pipe 12x1,5

30

Type KOKM 06 NN 6 KOKM 06 NN 9 KOKM 06 NN 12 KOKM 06 NN 14 KOKM 06 NN 16 KOKM 06 NN 18

0.5

Dimensions [mm] A 60 90 120 140 160 180

15

420

310

Cable current transformers 25

KOKM 06 LM_ is the indoor, cable, low-voltage current transformer in resin insulation. These transformer types are suitable for the measurement of phase currents. A busbar or cable serve as the primary conductor. Current transformers from the KOKM series

can also be used to measure phase currents at voltages higher than 0.72 kV if the insulation of the high-voltage primary conductor fulfils the requirements of the relevant standards related to the working voltage. Table 18. Technical data
Type Max. number of windings Level of insulation Highest permissible voltage of the current transformer Ur Rating test voltage of insulation (50 Hz, 1 min U p) Rating frequency Rating thermal current Short-time withstand thermal current Ith, 1 s Rating peak current Idyn Working temperature range Conformity with standards 50 Hz 1.2 x I pn 60 x I pn 2.5 x Ith -5 ... +40C IEC, ANSI, PN-EN, CAN 3 kV KOKM 06 LM_ 2 0.6/3/0.72 kV

KOKM 06 NN_ versus KOKM 06 LM_

Table 19. Standards parameters for KOKM 06 LM_


Primary current Ipn [A] FS 0.5 50 60 70 75 100 110 120 140 150 200 240 250 300 350 400 500 600 630 800 1000 1200 1250 1500 12 20 40 60 60 90 90 90 90 90 1 11 20 23 35 55 60 90 90 90 90 90 90 90 90 10P10 3.5 3.5 5 5 7 8 8 10 11 13 16 18 21 25 28 34 41 42 52 66 80 82 90 Secondary current I sn = 1 [A] Measurement class Protection class Fa 10P20 1.5 1.5 2.5 2.5 3.5 4 4 5 5 7 8.5 9 10 12 13 16 17 18 23 28 34 35 40 5P10 5 5 8 8 10 11 13 16 18 21 25 28 34 47 42 52 66 80 82 90 5P20 1.5 3.5 4 5 5 7 8.5 9 10 12 13 16 17 18 23 28 34 35 40 Fs 0.5 12 20 40 60 60 90 90 90 90 90 1 11 20 23 35 55 60 90 90 90 90 90 90 90 90 10P10 3 3.5 4.5 5 6 7 7 9 9 13 15 16 20 22 25 31 38 39 49 63 77 79 90 Maximum permissible load [VA] Secondary current Isn = 5 [A] Measurement class Protection class Fa 10P20 1 1.5 1.5 2 2.5 3 3 3.5 4 5.5 6.5 7 8 10 11 14 15 16 21 23 32 33 40 5P10 6 7 7 9 9 13 15 16 20 22 25 31 38 39 49 63 77 79 90 5P20 1.5 2.5 3 3.5 4 5.5 6.5 7 8 10 11 14 15 16 21 23 32 33 40

By special request current transformers with secondary current values different from those given in the table above (eg. 4.3 A), and current transformers for a frequency of 60 Hz can be supplied.

26 Cable current transformers

Overall dimensions

KOKM 06 LM_

KOKM 06 LM
95.5 M5 69 26.5

22

17

130

65 210

55

15 2 x brass pipe 12x1,5

30

Type KOKM 06 LM 6 KOKM 06 LM 9 KOKM 06 LM 12 KOKM 06 LM 14 KOKM 06 LM 16 KOKM 06 LM 18

20

.5

Dimensions [mm] A 60 90 120 140 160 180

15

400

280

Cable current transformers 27

Indoor cable current transformers type KOKM (for RMU)

KOKM 072 BA 10, CA 10 These indoor ring core current transformer types supply metering and protection devices at a maximum nominal voltage of 0.72 kV and nominal frequency of 50 or 60 Hz. The transformers can be mounted inside the switchgear. The nominal temperature recommended during the Table 20. Electrical parameters
Type Number of windings for measuring Number of windings for the test Rated insulation level Highest voltage for equipment Um Rated power-frequency withstand voltage (r.m.s.) Rated frequency fn Rated primary current Ipn Rated secondary current Isn Test Winding Accuracy class with relay type MPRB / WIC1 Rated burden Rated continuous thermal current Icth Rated short-time thermal current Ith 1 s Rated dynamic current Idyn Insulation class Protection External dimensions DxdxLxH Weight Working temperature range Conformity with standards 2.5 x Ith A E IP 20 100x42x100x124 3.3 -25 ... +70C IEC 60044-1 2.5 x Ith A E IP 20 100x50x100x124 2.8 -25 ... +70C IEC 60044-1 4 x Ipn (ext. 400%) 100 x Ipn A 4 x Ipn (ext. 400%) 100 x Ipn A 50/60 Hz 14.4 41.1 A 0.3 A 0.3 A 5P30 50/60 Hz 117.4 - 335 A 0.3 A 0.3 A 5P30 KOKM 072 BA 10 2 pcs. (terminals S0-S1-S2 137 turns (48+89)) 1 pcs. (terminals C-D 48 turns) 0.72/3/0.72 kV 3 kV KOKM 072 CA 10 2 pcs. (terminals S0-S1-S2) 1116 turns (391+725) 1 pcs. (terminals C-D 391 turns) 0.72/3/0.72 kV 3 kV

transport and storage of these transformers is in the range +5C ... +40C. Secondary circuits should be mounted using copper wires with a cross sectional area of at least 2.5 mm2. Connecting schemes for current and energy measurements are shown on pages 30 and 31.

KOKM 072 CA 10 1 pcs. (terminals S1-S2 187 turns) 1 pcs. (terminals C-D 50 turns 0.72/3/0.72 kV 3 kV 50/60 Hz 14.4 A 0.075 A 0.288 A 10P80 0.1 VA 10 x Ipn (ext. 1000%) 20 kA 62.5 kA E IP 20 100x50x100x124 2.27 -25 ... +70C IEC 60044-1

KOKM 072 CA 10 1 pcs. (terminals S1-S2 381 turns) 1 pcs. (terminals C-D 100 turns) 0.72/3/0.72 kV 3 kV 50/60 Hz 28.8 A 0.075 A 0.288 A 5P80 0.1 VA 10 x Ipn (ext. 1000%) 20 kA 62.5 kA E IP 20 100x50x100x124 1.9 -25 ... +70C IEC 60044-1

KOKM 072 CA 10 1 pcs. (terminals S1-S2 765 turns) 1 pcs. (terminals C-D 200 turns) 0.72/3/0.72 kV 3 kV 50/60 Hz 57.6 A 0.075 A 0.288 A 5P80 0.1 VA 10 x Ipn (ext. 1000%) 20 kA 62.5 kA E IP 20 100x50x100x124 1.4 -25 ... +70C IEC 60044-1

KOKM 072 CA 10 1 pcs. (terminals S1-S2 1535 turns) 1 pcs. (terminals C-D 400 turns) 0.72/3/0.72 kV 3 kV 50/60 Hz 115.2 A 0.075 A 0.288 A 5P80 0.1 VA 10 x Ipn (ext. 1000%) 20 kA 62.5 kA E IP 20 100x50x100x124 1.7 -25 ... +70C IEC 60044-1

28 Cable current transformers

Terminal marking

P1 S0 S1 S2 C D

P2

KOKM 072 BA 10 = MPTA 96-14-90


Terminals S0 S1 S0 S2 CD Ratio 14.4/0.3 A 41.1/0.3 A 0.3 A Class 5P30 5P30 test winding Number of windings 48 137 (48+89) 48 P1 P1 S0 S1 S0 S1 S2 C S2 C D D P2 P2

KOKM 072 CA 10 for REJ 603*


Terminals S1 S2 CD Ratio 14.4/0.075 A 0.288 A Burden 0.1 VA test winding Class Number of windings 10P80 187 50 P1 P1 S1 S2 S0 S1 C S2 D C P2 D P2

KOKM 072 CA 10 for REJ 603*


Terminals S1 S2 CD Ratio 28.8/0.075 A 0.288 A Burden 0.1 VA test winding Class Number of windings 5P80 381 100 P1 P1 P1 S1 S2 S1 S2 S0 S1 P2 P2 D P2

C C S2

D D C

KOKM 072 CA 10 for REJ 603*


Terminals S1 S2 CD Ratio 57.6/0.075 A 0.288 A Burden 0.1 VA test winding Class Number of windings 5P80 765 200 P1 P1 S1 S1 S2 S2 P2 P2

C C

D D

KOKM 072 CA 10 for REJ 603*


Terminals S1 S2 CD Ratio 115.2/0.075 A 0.288 A Burden 0.1 VA test winding Class Number of windings 5P80 1535 400 P1 P1 P1 S1 S2 S1 S2 S1 S2 C C C D D D P2 P2 P2

KOKM 072 CA 10 = MPTA 96-117-737


Terminals S0 S1 S0 S2 CD Ratio P1 117.4/0.3 A Class 5P30 P2 Number of windings 391 1116 (391+725) 391 P1 P1 P1 S1 S2 S1 S2 S0 S1 C C D D P2 P2 D P2

335/0.3 D S0 S1 A S2 C 5P30 0.3 A test winding

S2

*or other non ABB relays e.g. WIC

P1 P1 P1 S1 S2 S1 S2 S1 S2

C C C

D D D

P2 P2 P2

P1 S1 S2 C D

P2

P1 P1

S1 S1

S2 S2

C C

D D

P2 P2

P1 P1 P1 S1 S2 S1 S2 S1 S2

C C C

D D D

P2 P2 P2

P1 S1 S2 C D

P2

P1 S1 S2 C D

P2

P1

P2

Cable current transformers 29

Overall dimensions, connection diagram

CT outside dimensions for ratios of: 14.4/0.075 A, 28.8/0.075 A, 57.6/0.075 A, 115.2/0.075A


6.5

70

60

R50
124 143

50

100 18

L1

L3

L2
1 2 3 gn/ge 1 2 3 gn/ge S1 S2 C D S1 S2 C D S1 S2 C D

FI+ flag indicator low energy FITC+ TC230V 115V N N

extrenal power source

WIC1

30 Cable current transformers

80

133

115

Overall dimensions, connection diagram

CT outside dimensions for ratios of: 14.4 41.1/0.3 A, 117.4 335/0.3 A


6.5

70

60

R50
124 143

42

100 18
remote trip 230 V AC

L1

L2

L3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 MPRB

S2 S1 S0 C D S2 S1 S0 C D S2 S1 S0 C D power supply 230 V AC

Cable current transformers 31

80

133

115

S1 S2 C D S1 S2 C D S1 S2 C D S1 S2

REJ 603
L3

L2

L1

N E

trip coil

TC(+) TC(-) BI BI

external input

Product number 1YMA183190R0001 1YMA183190R0002 1YMA183190R0003 1YMA183190R0004 1YMA183190R0005 1YMA183190R0006

Type of CT KOKM 072 CA 10 KOKM 072 CA 10 KOKM 072 CA 10 KOKM 072 CA 10 KOKM 072 CA 10 KOKM 072 BA 10

Primary current Ipn [A] 14.4 A 28.8 A 57.6 A 115.2 A 117.4 - 335 A 14.4 - 41.1 A

Secondary current Isn [A] 0.075 A 0.075 A 0.075 A 0.075 A 0.3 A 0.3 A for REJ 603 - CT2 for REJ 603 - CT3 for REJ 603 - CT4 for REJ 603 - CT5

Order example KOKM 072 CA 10 (1YMA183190R0003); 57.6/0.075 A/A; 0.1 VA; 5P80; Ith= 20 kA/1s; IEC 60044-1; 21 Pcs.

32 Cable current transformers

Indoor special current transformer type KORI 072 GH 8

KORI 072 GH 8 Low-voltage current instrument transformer, without a primary conductor that can be assembled on the switchgear bushing with its own insulation. Transformers of this type enable protection and are designed for use in indoor installations. KORI072 GH 8 transformers are generally designed with one transformer ratio. However, they can also have more ratios if the possibility to reconnect them to the secondary side exists. The transformer assembly procedure on the bushings of a UniGear 550 switchgear panel is specified exactly. All transformers meet the requirements of the relevant standard i.e. the IEC 60044-1. Table 21. Technical data
Type (low voltage current transformer for medium voltage application) Highest voltage for equipment Power frequency test voltage Rated insulation level Rating frequency Rated primary current Rated secondary current Rated short-time thermal current Rating peak current Accuracy classes Burden Highest voltage of a system Flammability class KORI 072 GH 8 current transformers are designed for ABB switchgear type Unigear 550.
Other parameters have to be agreed with the manufacturer and will be considered on an individual basis. Reconnectable variants are also possible, but need to be examined on an individual basis (according to the customers requirements and the agreement with the manufacturer).

KORI Um Up (1 min) fn Ipn Isn Ith (3 s) Idyn Sn [kV] [kV] [kV] [Hz] [A] [A] [kA] [kA] [VA] [kV] 0.72 3 0.72/3/ 50 1600 up to 2500 1 or 5 50.0 125.0 5P20 10, 15, 20, 25 or 30 12 17.5 kV by using CT ROD B

Cable current transformers 33

Overall dimensions

90 29

4x 8.5

197

173 197

17

197 75 40

173

90

90 29

rating plate

4x 8.5

197

173 197

17
34 Cable current transformers

197 rating plate 75 40

173

90

Current transformers type KOLT (for oil-immersed transformers)

KOLT this transformer type has no housing and primary winding. Under operating conditions, the bushing insulator, which is the main current transformer insulation, also serves as the primary winding. The secondary windings are evenly wound on the circumference of the toroidal core. Secondary winding insulation is made of polyester tape (torlen). Current transformers weighing 100 kg or more consist of several

parts to facilitate both transport and installation. Each individual part contains the following information: a serial number which coincides with the one stated on the rating plate, and markings for primary and secondary winding terminals.

Table 22. Technical data


Type Primary current range Rated secondary current Insulation level Range of rated output Number of windings Conformity with standards Accuracy class acc. to IEC FS ALF Rated frequency Short-time withstand thermal current Peak withstand current Insulation class acc. to IEC Min. inside diameter Max. outside diameter Height Length of leads
Transformers with other dimensions and parameters are available upon request.

KOLT Ipn Isn Sn [A] [A] [kV] [VA] 100 A - 15,000 A 1A 5A 0.72/3/1 VA -90 VA 1-4 IEC, PN-EN, SEV, VDE, ANSI, BS, CAN, CSA, GOST 0.2s; 0.5s; 0.2; 0.5; 1; 3; 5; 5P; 10P; PX 5; 10 5; 10; 15; 20; 25; 30 f I th (1 s) I dyn A B h D [Hz] [A] [A] [mm] [mm] [mm] [mm] 50, 60 100 x Ipn max. 100 kA 2.5 x Ith max. 250 kA B min. 30 mm depending on parameters max. 900 mm depending on parameters max. 900 mm depending on parameters 1 m, other length at the clients request

Cable current transformers 35

Versions available Single phase With one or several windings With one or several tappings Insulation cotton tape + impregnating varnish Without housing Without primary winding Aplication KOLT type current transformers can be mounted inside power transformers. They will operate in oil, and under moderate and tropical climate conditions. These current transformers are designed to supply measurement and protection circuits of power systems operating under a rated frequency of 50 Hz. Marking Each current transformer is fitted with a rating plate in accordance with the IEC 60044-1 Standard. Values of rated voltage and the rated power frequency test voltage of the insulation (stated on the rating plate) refer to the insulation of the secondary windings. Primary and secondary terminals are directly marked on the current transformer. Transport During transportation, current transformers must be protected against humidity and heavy shocks. Current transformers weighing more than 50 kg and which are especially sensitive to shocks are transported on wooden pallets. Installation During installation of current transformers the following instructions should be observed: Secondary winding marked 1S1- 1S2 should be placed on the top Keep the same polarization for all parts of the current transformer (P1 P2 P1 P2 markings) Avoid shocks Compliance with standards Current transformers meet the requirements of the following standards: IEC 60044-1. At the clients request we manufacture current transformers that meet the requirements of SEV, VDE, ANSI, BS, CAN, CSA, GOST standards. Warranty A two-year warranty period is granted from the date the transformer starts to operate. However, a maximum warranty period of three years is granted from the time of purchase. The warranty only covers manufacturing defects and does not include defects due to:

Incorrect transport Incorrect storage A failure to follow instructions correctly during installation and operation Incorrect selection of the transformer for the electric power system Ordering The order must contain the following: Name and type of current transformer Rated primary current / rated secondary current Ipn/Isn [A] Short-time thermal current, 1 s Ith [kA] Rated output power and accuracy class of each winding Sn [VA] Limit transformer dimensions (min. inside diameter, max. outside diameter, max. height) Length of leads Standard Quantity Order example Current transformer type KOLT 1200/5/1/1 A Ith = 72 kA I. 15 VA, class 0.5 FS10 II. 60 VA, class 5P15 III. 60 VA, class 5P20 min. inside diameter A = 150 mm max. outside diameter B = 300 mm max. height h = 200 mm length of leads 1.5 m standard IEC 60044-1 quantity 9 Pcs.

36 Cable current transformers

Overall dimensions

1S...

2S...

...S...
D

1S5 1S4 1S3 1S2 1S1

Rating plate

Rating plate

Rating plate

P1
Cable current transformers 37

38 Cable current transformers

Cable current transformers 39

Contact us

www.abb.com

We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction in whole or in parts is forbidden without ABBs prior written consent. Copyright 2011 ABB All rights reserved

1VLC000519-rev-,en,2011.02.25

ABB PPMV Brno Videnska 117 619 00 Brno, Czech Republic Phone: +420 547 152 602 +420 547 152 614 Fax: +420 547 152 626 e-mail:info.ejf@cz.abb.com

We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.

Anda mungkin juga menyukai