Data Acquisition Unit
Document ID: 40-08557-01

www.qualitrolcorp.com

Legal

Information in this document is subject to change without notice. This document is provided to purchasers of QUALITROL products for use in the installation, operation and servicing of such products. No other use, nor any reproduction, distribution or the making of any derivatives of this document is authorized, without the express prior written permission of Qualitrol. QUALITROL endeavors to ensure the accuracy and quality of its published materials; however, no warranty, expressed or implied, is provided. QUALITROL disclaims any responsibility or liability for any direct or indirect damages resulting from the use of the information in this manual or products described in it. Mention of any product or brand does not constitute an endorsement by QUALITROL of that product or brand. This document was originally composed in English and was subsequently translated into other languages. The fidelity of subsequent translations cannot be guaranteed. In case of conflict between the English version and another language version, the English version takes precedence.
2010 QUALITROL Company LLC, an ISO 9001 system certified company. All rights reserved. Information subject to change without notice. All trademarks are properties of their respective companies, as noted herein. 40-08557-01.

www.qualitrolcorp.com

Certificate

Note

Please contact Qualitrol for detailed test report for Class A certification.

www.qualitrolcorp.com

Contents

Contents
1. About This Manual ................................................................................. 2
1.1. 1.2. 1.3. Symbols Used................................................................................................2 Abbreviations and Acronyms.......................................................................3 Standards and References ...........................................................................4 INFORMA PMD-A License.............................................................................6 Safety Summary ............................................................................................6 Customer Helpline Information ....................................................................7 Environmental Requirements.......................................................................9 Power Supply and Earthing ..........................................................................9
Standard Power Supply..................................................................................... 9 UPS ................................................................................................................ 10 +12 VDC External Power Supply..................................................................... 12

2.

Overview of INFORMA PMD-A .............................................................. 6


2.1. 2.2. 2.3.

3.

Components and Specifications .......................................................... 9


3.1. 3.2.
3.2.1. 3.2.2. 3.2.3.

3.3. 3.4. 3.5. 3.6.

Physical Details ...........................................................................................13 Front Panel Description ..............................................................................14 Rear Panel Description ...............................................................................16
Rear Panel of the INFORMA PMD-A 3U Device ............................................. 16 Rear Panel of the INFORMA PMD-A 6U Device ............................................. 17 MMI CPU Mode............................................................................................... 18 MMI LCD Navigation ....................................................................................... 18 MMI Overview Screen..................................................................................... 20 CPU Overview Screen .................................................................................... 21 CPU Main Menu Screen.................................................................................. 22 LED Functions ................................................................................................ 28 Shutdown Switch............................................................................................. 31 Reset Switch ................................................................................................... 32 PPH/PPM/IRIG-B In/IRIG-B Out...................................................................... 32 Fiber/Differential PPS...................................................................................... 32 Ethernet Connections...................................................................................... 33 Serial Ports ..................................................................................................... 34 USB Functionality............................................................................................ 36 USB Functions with or Without Script and MMI-LCD ....................................... 37 LED Indication................................................................................................. 37

3.5.1. 3.5.2. 3.6.1. 3.6.2. 3.6.3. 3.6.4. 3.6.5. 3.6.6.

Standard MMI ...............................................................................................18

3.7. 3.8.

Shutdown and Reset ...................................................................................31 Communication Ports .................................................................................32

3.7.1. 3.7.2. 3.8.1. 3.8.2. 3.8.3. 3.8.4.

3.9.

USB...............................................................................................................36

3.9.1. 3.9.2. 3.9.3.

3.10.

Clock Synchronization ............................................................................38


INFORMA PMD-A as Master ......................................................................... 38 INFORMA PMD-A as Slave ........................................................................... 40 INFORMA PMD-A Time Accuracy.................................................................. 41 PPS Detection, Stability, and Lock Mechanism .............................................. 41

3.10.1. 3.10.2. 3.10.3. 3.10.4.

Contents i

www.qualitrolcorp.com

Contents

3.11. 3.12. 3.13.

Analog Inputs ...........................................................................................43


TX-AFE.......................................................................................................... 43 HIA-AFE......................................................................................................... 43

3.11.1. 3.11.2.

Digital Inputs ............................................................................................44 Alarm Output ............................................................................................46 Unpacking Procedure .................................................................................52 Accessories .................................................................................................52 INFORMA PMD-A Installation Specifications ............................................53 Device Communication Settings................................................................55 Installation Procedure .................................................................................55
Setting up the Device ...................................................................................... 55 Starting the Device.......................................................................................... 55 Checking for Correct Operation:...................................................................... 56

4.

Installation............................................................................................. 52
4.1. 4.2. 4.3. 4.4. 4.5.

4.5.1. 4.5.2. 4.5.3.

5. 6.

Serial Ports............................................................................................ 58
5.1. Functionality/Service ..................................................................................58
PPPD on Serial ............................................................................................... 58 5.1.1.

Configuration ........................................................................................ 80
6.1. 6.2. Hardware Configuration..............................................................................80
Connection Diagrams...................................................................................... 80 Configuration Overview ................................................................................... 94 Communications ............................................................................................. 95 PQ Overview................................................................................................... 98 PQ Configuration............................................................................................. 99 Continuous Recording..................................................................................... 99 EN 50160 reports (standard threshold and user threshold) ........................... 102 IEC 61000-3-6/7 Report ................................................................................ 103 Histograms.................................................................................................... 104 RMS Envelope .............................................................................................. 106 DSI Dip/Sag, Swell, and Interruption ......................................................... 107 Rapid Voltage Change ................................................................................. 108 FR General .................................................................................................. 110 FR Sensor Channels.................................................................................... 111 Data Storage................................................................................................ 112 6.1.1. 6.2.1. 6.2.2. 6.2.3. 6.2.4. 6.2.5. 6.2.6. 6.2.7. 6.2.8. 6.2.9. 6.2.10. 6.2.11. 6.2.12. 6.2.13. 6.2.14.

Software Configuration...............................................................................90

7.

Maintenance........................................................................................ 114
7.1. 7.2. Calibration..................................................................................................114
Calibration Procedure.................................................................................... 114 Points to Remember ..................................................................................... 121 Storage ......................................................................................................... 122 Transport....................................................................................................... 122 Routine Maintenance .................................................................................... 122 UPS Maintenance ......................................................................................... 123 INFORMA PMD-A Firmware Upgrade Procedure.......................................... 124 During File Upload to INFORMA PMD-A ....................................................... 129 7.1.1. 7.1.2. 7.2.1. 7.2.2. 7.2.3. 7.2.4.

General Maintenance ................................................................................122

7.3.

Firmware Upgrade .....................................................................................124

7.3.1. 7.3.2.

Contents ii

www.qualitrolcorp.com

Contents

7.3.3. 7.3.4.

During CPU File Upload to INFORMA PMD-A............................................... 130 System and Diagnostic Information............................................................... 131 Power Healthy LED on the Front Panel is Off................................................ 136 Communication LED is Off ............................................................................ 137 Clock Sync LED is Off ................................................................................... 138 Test Points to Verify the Supply Voltages...................................................... 138

7.4.

Troubleshooting ........................................................................................134

7.4.1. 7.4.2. 7.4.3. 7.4.4.

Appendix A Technical Specifications .................................................... 141


EMC Standards.....................................................................................................144

Appendix B INFORMA PMD-A Functions .............................................. 150


Power Quality Parameters ...................................................................................150
Power Line Frequency (10-second) ............................................................................ 150 Magnitude of Supply Voltage ...................................................................................... 151 Flicker......................................................................................................................... 152 Voltage Unbalance ..................................................................................................... 153 Harmonics .................................................................................................................. 154 Inter-Harmonics .......................................................................................................... 155 Mains Signaling Voltage ............................................................................................. 156 Dips, Swells, And Interruptions (DSI).......................................................................... 157 Rapid Voltage Change (RVC)..................................................................................... 158

Power Quality Sensors ........................................................................................160


PQ Sensor Functionality ............................................................................................. 160 PQ Sensor Types ....................................................................................................... 161

Handling Time Changes ......................................................................................163


Forward Time Shift ..................................................................................................... 163 Backward Time Shift................................................................................................... 163

PQ Calculated Quantities ....................................................................................166


STAR Topology .......................................................................................................... 166 Delta Topology ........................................................................................................... 176

Types of Fault Recording ....................................................................................180


DFR............................................................................................................................ 180

DFR Sensor Types ...............................................................................................181

Appendix C Recording Data Rates and Memory Consumption Rates 188 Appendix D License Updates .................................................................. 193
Modifying an Existing License............................................................................194

Appendix E Battery Replacement Procedure........................................ 198


Battery Replacement Procedure for an INFORMA PMD-A 3U Device..............198

Appendix F On-Board LED Functionalities ........................................... 200 Appendix F On-Board LED Functionalities ........................................... 201
LED Functions on the Motherboard ...................................................................201 LED Functions on the DSP Board.......................................................................202 CPU MMI Modes ...................................................................................................203

Appendix G On-Board Jumper Settings ................................................ 206 Appendix H Linearity Report of TX-AFE and HIA-AFE ......................... 232
TX-AFE Linearity Report......................................................................................232

Contents iii

www.qualitrolcorp.com

Contents

References.................................................................................................... 240

Contents iv

www.qualitrolcorp.com

About This Manual

Chapter 1
About This Manual

www.qualitrolcorp.com

About This Manual

1.

About This Manual


The manual assumes that the user has minimum operational knowledge of this type of monitoring equipment. This manual provides instructions to help the user to:

Install the device and connect its accessories. Configure the device. Operate the device. Maintain and troubleshoot the device.

1.1. Symbols Used


The following table lists the symbols used on the device and in the manual. Symbol Description A Warning identifies conditions and actions that pose hazard(s) to the user. Risk of electrical shock

Potentially dangerous situation A Caution identifies conditions and actions that may damage the test instrument. Risk of danger

Alternating current Direct Current Protective Earth USB Communication GPS Antenna

www.qualitrolcorp.com

About This Manual

1.2. Abbreviations and Acronyms


The following table lists the various abbreviations and acronyms used in this manual. INFORMA PMD-A AC AWG BCD CF CPU/Motherboard CTS DC DCE DFE DFR DSI DSP DTE EMC FPGA FR GPS HIA-AFE iQ+ LCD LED MMA MMI NA NTP PMD PPPD PPS PQ RH RI RoHS RTC RTS RVC SER SPST THD Data Acquisition Unit Name Alternating Current American Wire Gauge Binary Coded Decimal Control Function Processor Card Clear To Send Direct Current Data Communication Equipment Digital Front End Digital Fault Recorder Dip/Sag, Swell, Interruption Digital Signal Processing Data Terminal Equipment Electro Magnetic Compatibility Field Programmable Gate Array Fault Recording Global Positioning System High Impedance Anti-aliasing- Analog Front End Master Station Software Liquid Crystal Display Light Emitting Diode Minimum, Maximum, and Average (For PQ parameters) Man Machine Interface Not Applicable Network Time Protocol Performance Measuring and Monitoring Device Point-to-Point Protocol Daemon Pulse Per Second Power Quality Relative Humidity Ring Indicator Restriction of Hazardous Substances Real Time Clock Request To Send Rapid Voltage Change Sequence of Events Recorder Single-Pole Single Throw Total Harmonic Distortion

www.qualitrolcorp.com

About This Manual

INFORMA PMD-A TOD TX-AFE UPS Urms (1/2) WEEE

Data Acquisition Unit Name Time Of the Day Transformer - Analog Front End Uninterrupted Power Supply R.M.S. voltage refreshed each half-cycle. Waste Electrical and Electronic Equipment

1.3. Standards and References


The following table lists the different standards followed in this document. Standards EN 50160 References Voltage Characteristics of electricity supplied by public distribution system. This Standard issued by the CENELEC specifies voltage quality requirements for distribution networks Electromagnetic compatibility (EMC) Part 3-6: Limits Assessment of emission limits while connecting distorting installations to MV, HV, and EHV power systems Electromagnetic compatibility (EMC) Part 3-7: Limits Assessment of emission limits while connecting fluctuating installations to MV, HV, and EHV power systems Electromagnetic Compatibility (EMC) Part 4-6: Testing and Measurement Techniques Immunity to conducted disturbances, induced by radio frequency fields Electromagnetic Compatibility (EMC) Part 4-7: Testing and Measurement Techniques General guide on harmonics and inter-harmonics measurements and instrumentation for power supply systems and equipment connected thereto Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 15: Flicker meter - Functional and design specifications Electromagnetic Compatibility (EMC) Part 4-30: Testing and Measurement Techniques Power quality measurement methods

IEC 61000-3-6

IEC 61000-3-7

IEC 61000-4-6

IEC 61000-4-7

IEC 61000-4-15

IEC 61000-4-30

www.qualitrolcorp.com

Overview

Chapter 2
Overview

www.qualitrolcorp.com

Overview

2.

Overview of INFORMA PMD-A


INFORMA PMD-A is an advanced multifunctional data acquisition device designed to perform the following: Monitor Power Quality parameters (for recording and reports) Support Fault Recording functions Provide Fast Transient Recording

This product, when coupled with its complementary master station software iQ+, provides a powerful platform for the monitoring, analyzing, and reporting of data and information about power system networks and substations.

Note

Refer to Appendix B for details about INFORMA PMD-A functions.

2.1. INFORMA PMD-A License


The INFORMA PMD-A device is a licensed product. Consequently, some features of this multifunctional device may not be available as described in this manual. Additional licenses may be purchased to activate the required functionalities.

Note

Refer to Appendix D for details about any INFORMA PMD-A license updates.

2.2. Safety Summary


Warnings and Cautions are presented throughout the manual to alert the user to potentially hazardous situations. Remember the following:

Only qualified personnel must perform installation, operation, and maintenance of the equipment. Read the User Manual before using the equipment. The equipment must be operated within its stated parameters. The performance of the equipment may be adversely affected if used in extreme conditions.

www.qualitrolcorp.com

Overview

Do not use the equipment for any purpose other than the measurement of voltages and currents that are within the measuring ranges and categories. Improper use shall void all warranty. Install the equipment in such a manner that its power cable is accessible at all times and can easily be disconnected. At least 10 cm free space shall be available on either side of the enclosure for air flow/ventilation. Ensure that the power cables and connecting cables are not damaged and are in proper working condition. Use only those accessories that are supplied with the equipment. Refer the equipment to the authorized service personnel if any damage or defect is found.

2.3. Customer Helpline Information


For any customer or technical support, contact: Qualitrol Corporation-Instrumentation Division 15 Wildflower Way, Belfast, BT12 6TA, Northern Ireland Telephone: +44 28 9022 5200 Fax: +44 28 9022 5225 Qualitrol Instruments 8 Av. Newton B-1300 Wavre Belgium Telephone: +32 10 22 67 16 Fax: +32 10 22 69 98 Technical support: +32 10 235 237 Qualitrol Company LLC 1385 Fairport Road, Fairport, NY 14450 USA Telephone: +1 585 586 1515 Web site: www.qualitrolcorp.com Technical Support contact: From Austria: +43 (0)1 79 576 203 From Belgium: +32 (0)10 235 237 From France: 0825 540 050 From Germany: +49(0)69 50 07 13 46 From Switzerland: +41 (0)44 80 09 931 From UK: +44 28 9022 5200 From other countries: +44 28 9022 5200 Technical support E-mail: csc@qualitrolcorp.com

www.qualitrolcorp.com

Components and Specifications

Chapter 3
Components and Specifications

www.qualitrolcorp.com

Components and Specifications

3.

Components and Specifications


This chapter describes the different components of the INFORMA PMD-A device and its specifications.

3.1. Environmental Requirements


The following table lists the environmental requirements for the device. Parameters Operating Temperature Storage Temperature Humidity Note: Conforms to RoHS and WEEE. Cold start is not possible below 0C. Requirements -5C to +50C (irrespective of the UPS module) -30C to +70C 0 to 95% RH non-condensing

3.2. Power Supply and Earthing


This section provides the power requirements for the device. 3.2.1. Standard Power Supply INFORMA PMD-A supports three types of power supply modules. The specifications are as follows: Power Supply Input Range Type 1: 90 264 VAC (88 - 300 VDC), 47 63 Hz Type 2: 36 72 VDC Type 3: 18 36 VDC Maximum Load 40 VA for 3U INFORMA PMD-A device and 80 VA for 6U INFORMA PMD-A device Typical Load 25 VA for 3U INFORMA PMD-A device and 50 VA for 6U INFORMA PMD-A device

Note

Wire gauge to be used at TB1: 1222 AWG.

www.qualitrolcorp.com

Components and Specifications

6U

3U

Figure 3.1 Standard Power Supply Terminal

Connect the power cord to the power socket on the rear panel of the device (through screw terminal blocks). The labels L and N are for line and neutral of the AC supply (+ and indicate the polarity of the DC supply). It is very important to connect an earth to the main earth stud. This earth stud should be connected to the system substation earth. An ON/OFF switch is provided on the rear panel to control the power to the device. 3.2.2. UPS The UPS card provides power supply to the INFORMA PMD-A device for a minimum of 15 minutes. In normal operating conditions, the user can expect battery backup for 30 minutes with a new and fully charged battery. The battery must be charged for 12 hours to provide a minimum backup of 15 minutes. In a 6U configuration, the battery is external and interfaced to the INFORMA PMD-A device through a connector (Reference designator is UPS I/P) on the rear panel.

Note

Refer to Appendix E for details about the battery replacement procedure.

10

www.qualitrolcorp.com

Components and Specifications

The following table describes the details of the two batteries that are used in the INFORMA PMD-A device. Details Manufacturer Part Number/Reference Battery Specifications Rated Capacity (minimum) 3.9 Ah with 0.5 C Charging and 0.5 C Discharging 4.8 Ah 4S2P5SWB-SB Rajamane Telectric Private Limited 4S2P5SWB-SB-002 NH2054 INSPIRED ENERGY, Inc. NH2054HD24

Operating Environment Charging 0C +45C, Maximum 90% RH Discharging -20C ~ +60C, Maximum 90% RH Storage Environment Short Period less than 1 month Long Period more than 3 months Recommended storage -20C ~ +45C, Maximum 90% RH -10C ~ +30C, Maximum 90% RH +15C ~ +35C, Maximum 85% RH Notes If the battery is not used for more than 3 months, then it has to be discharged completely and recharged to 50% power. If the batteries are not used for more than 6 months, there can be a serious effect on the battery life. The shelf life of the battery is 6 months when stored at 25C. If the storage temperature exceeds 25C over a 6-month period, then the shelf life of the battery is reduced. <21C -20C ~ +60C<= 80% RH -10C to 50C, <= 80% RH 0C to 45C, <= 80% RH

11

www.qualitrolcorp.com

Components and Specifications

The Rajamane battery is the default battery. The Qualitrol reference number for this battery is 3601-0087.

Note

Refer to Section 7.2.5 for further information about UPS maintenance.

3.2.3. +12 VDC External Power Supply TB2 provides an auxiliary DC output for external devices. 3U 6U

Figure 3.2 - External Power Supply

The +12 VDC External Power Supply has the following specifications:

Output voltage: +12 V@750 mA Maximum

Note

Wire gauge to be used at TB2: 12-24 AWG.

12

www.qualitrolcorp.com

Components and Specifications

3.3. Physical Details


The following table provides the mechanical dimensions for the INFORMA PMD-A 3U and INFORMA PMD-A 6U devices. Devices Physical Dimensions Net Weight (Approx.) 15 kg without battery 15.5 kg with battery Gross Weight (Approx.) 15 kg without battery. Includes packaging and accessories if any. 15.5 kg with battery. Includes packaging and accessories if any. 25 kg without battery. Includes packaging and accessories if any. 26 kg with two external batteries. Includes packaging and accessories if any.

INFORMA 487 mm wide, 132.5 PMD-A 3U mm high, 362.2 mm Device deep

INFORMA 487 mm wide, 265.8 PMD-A 6U mm high, 362.2 mm Device deep

23 kg without any external battery 24 kg with two external batteries

13

www.qualitrolcorp.com

Components and Specifications

3.4. Front Panel Description


This section provides a description of the different components on the front panel of the INFORMA PMD-A 3U and INFORMA PMD-A 6U devices. The following table lists the labels for the front panel of the INFORMA PMD-A 3U and INFORMA PMD-A 6U devices. Label Name 1 2 3 LED Indicators LCD Display Keypad Description Status is configured to indicate different alarm conditions. Used to display information related to the device. Used to navigate.

A picture of the front panel of INFORMA PMD-A 3U device is shown below.

Figure 3.3 INFORMA PMD-A 3U Front View

14

www.qualitrolcorp.com

Components and Specifications

A picture of the front panel of the INFORMA PMD-A 6U device is shown below.

Figure 3.4 INFORMA PMD-A 6U Front View

15

www.qualitrolcorp.com

Components and Specifications

3.5. Rear Panel Description


This section describes the different components on the rear panel of the INFORMA PMD-A 3U and INFORMA PMD-A 6U devices. 3.5.1. Rear Panel of the INFORMA PMD-A 3U Device A picture of the rear panel of INFORMA PMD-A 3U device is shown below.

Figure 3.5 INFORMA PMD-A 3U Rear View

The following table lists the different components on the rear panel of the INFORMA PMD-A 3U device. Label 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 BNC Connector -Out DB9 Connector RJ45 Connector Fiber Connector BNC Connector Fiber Connector Tx/Rx On/Off Switch Earth Post Name AC Power Socket DC Power Socket Phoenix Connector 2*4 Pin connector 2*10 Pin connector Phoenix Connector 1*5 Pin Connector 4*10 Pin Connector 18 Pin Terminal Block BNC Connector -In Labels on the Rear Panel TB1 TB2 TB3 TB4, TB5 TB6, TB7 TB8 TB9 TB10 TB11 Description 3 pin AC/DC power input connector DC power output connector (+12 V, 750 mA) Alarm output NA NA Differential PPS Out (Master mode)/In (Slave mode) RS485 Communication 32 Digital inputs Connecting 9 analog channels IRIG-B INPUT (TTL/AM)/PPM IN/PPH IN IRIG-B OUTPUT (TTL/AM) RS232 Communication Wired Ethernet Communication Fiber Ethernet Communication GPS antenna PPS Out/In Power ON/OFF the device Earthing connection

16

www.qualitrolcorp.com

Components and Specifications

3.5.2. Rear Panel of the INFORMA PMD-A 6U Device A picture of the rear panel of INFORMA PMD-A 6U device is shown below.

Figure 3.6 INFORMA PMD-A 6U Rear View

The following table lists the different components on the rear panel of the INFORMA PMD-A 6U device. Label 1 2 3 4 5 6 7 8 9 10 Name AC Power Socket DC Power Socket Phoenix Connector 4*4 Pin connector 4*10 Pin connector Phoenix Connector 1*5 Pin Connector 8*10 Pin Connector 4*18 Pin Terminal Block BNC Connector -In BNC Connector -Out DB9 Connector RJ45 Connector Fiber Connector BNC Connector Fiber Connector Tx/Rx Labels on the Rear Panel TB1 TB2 TB3 TB4, TB5 TB6, TB7 T B8 TB9 TB10 TB11 Description 3 pin AC/DC power input connector DC power output connector (+12 V, 750 mA) Alarm output NA NA Differential PPS Out (Master mode)/In (Slave mode) RS485 Communication 128 Digital inputs Connecting 36 analog channels IRIG-B INPUT (TTL/AM)/PPM IN/PPH IN IRIG-B OUTPUT (TTL/AM) RS232 Communication Wired Ethernet Communication Fiber Ethernet Communication GPS antenna PPS Out/In

11 12 13 14 15

17

www.qualitrolcorp.com

Components and Specifications

16 17

On/Off Switch Earth Post

Power ON/OFF the device Earthing connection

3.6. Standard MMI


Standard MMI includes the LCD, keypad, and the LEDs. 3.6.1. MMI CPU Mode MMI operates in the following modes:

2 CPU mode (INFORMA PMD-A 6U device) 1 CPU mode with LCD (INFORMA PMD-A 3U device/INFORMA PMD-A 6U device) 1 CPU mode without LCD (INFORMA PMD-A 3U device)

Refer to Appendix F for MMI CPU modes.

3.6.2. MMI LCD Navigation The LCD display format is 240X80 dots. A keypad is provided to navigate between the screens.

The front panel keypad consists of 7 keys. The left arrow key is used to navigate to CPU 1. The right arrow key is used to navigate to CPU 2. The up arrow key is used to scroll up in the screen. The down arrow key is used to scroll down in the screen. The ENTER key is used to enter into the screen. The ESC key is used to navigate to previous screen. The RESET key is reserved for future use.

Figure 3.7 Standard MMI

18

www.qualitrolcorp.com

Components and Specifications

MMI communicates with CPU to obtain the status and other information. The Overview screen on the LCD reflects the status of the device. Using the left or right arrow key, the user can view detailed information of the device. The following flowchart illustrates the MMI LCD navigation.

MMI Overview

CPU Overview

Main Menu

System Information

Alarms/ Logs

Communic ations

Data Download

Clock Synchroniz ation

Channel Check

Relay Test

Manual Trigger

Display Settings

Firmware Information

System Diagnostic Log

RS232-1

Log

Clock synch Status

Digital Inputs

FR Manual trigger

Memory Information

Reboot History

RS232-2

FR

Analog Inputs

FL Manual trigger

Diagnostic Report

Time Synch Status Log

RS232-3

CSS

FL Lines

TR Manual trigger

Programmi ng Status

Event Status Log

RS485

PQ Continuous

Line Module Status

DTF result

Ethernet 1

PQ Othres

FL Log

Ethernet 2

RMS Env

DFR Log

FL

TR Log

TR

Figure 3.8 MMI LCD Navigation Flowchart

19

www.qualitrolcorp.com

Components and Specifications

3.6.3. MMI Overview Screen The default screen displayed on the LCD interface is the Overview screen of the device. It shows the CPU's overview status. The following screen is displayed if there are two CPUs. To display details about CPU 1, the user must press the left arrow key, and for details about CPU 2, the user must press the right arrow key.

Figure 3.9 MMI Overview Screen

The following screen is displayed if there is only one CPU. For the purpose of this document, the 1 CPU scenario is discussed.

Figure 3.10 MMI Overview Screen for One CPU

The following table lists the icons displayed in the MMI Overview screen and their descriptions. Icons Description Power Health icon. Communication icon.

Clock Synchronization icon.

Indicates that the status is healthy.

20

www.qualitrolcorp.com

Components and Specifications

Icons

Description Indicates that the status is unhealthy. Indicates that the clock is locked. Any number next to this icon represents the number of times the clock has been locked since the device was switched on (refer to Figure 3.11). If there is no number next to this icon, it means that the clock has never been locked. Indicates that the clock is unlocked. Any number next to this icon represents the number of times the clock has been unlocked since the device was switched on. Indicates that the device is running with an internal UPS.

Indicates that the Power Health status is bad. Indicates that an alarm condition has occurred. Refer to Section 3.6.6 for details.

Note

If there are no status icons, it means that the status is unknown.

3.6.4. CPU Overview Screen Pressing the left arrow key displays the information of CPU 1. This screen displays the system (CPU) date and time, time synchronization information, station name, device name, and network information (IP address of the device, and default gateway). It also displays the functionality and menus based on the license purchased.

.
Figure 3.11 CPU Overview Screen

21

www.qualitrolcorp.com

Components and Specifications

3.6.5. CPU Main Menu Screen If the enter key is pressed on the CPU Overview screen, the CPU Main Menu screen is displayed. The Main menu displays the following options. The user can use the up and down arrow keys to scroll through the options. Pressing Enter on each option displays its details.

Figure 3.12 CPU Main Menu Screen

System information: This menu provides information about the following:

Figure 3.13 System Information


Firmware Information Displays the CPU and peripherals firmware information. Memory Information Displays the CPU RAM and file system information. Diagnostic Report Displays the status of Power Health, FPGA, SD RAM, PIC, and ADC. Programming Status Displays the various peripheral programming statuses.

22

www.qualitrolcorp.com

Components and Specifications

Alarms/Logs This menu provides the options for viewing various logs. This menu displays the following:

Figure 3.14 Alarms/Logs


Sys.Diag. Log Displays the system diagnostic log. Reboot History Displays the last five reboot conditions. Time Sync Status Log Displays the status log for time synchronization. Event Status Log Displays information about the FR and PQ trigger events. DTF Results - Displays the DTF result with corresponding configured unit (Miles/kilometer). FL Log Is displayed if this feature/license is available. DFR Log Displays the DFR logs. Transient Log Is displayed if this feature/license is available.

Figure 3.15 Transient Log

23

www.qualitrolcorp.com

Components and Specifications

Communication This menu provides the communication status. It displays the serial communication and Ethernet communication status. This menu displays the following options:

Figure 3.16 Communication


RS232-1 RS232-2 RS232-3 RS485 Ethernet-1 Ethernet-2

24

www.qualitrolcorp.com

Components and Specifications

Data Download This menu provides the option for user to download the data from the device to the USB. This menu will display the submenus to download the log, DFR record, CSS record, PQ Continuous record, PQ reports, RMS record and FL/TR record respectively. USB should be connected to the device in order to download logs and records. The number of days of data required to be downloaded is specified using the up and down arrow keys. MMI LCD will display the downloading status.

Figure 3.17 Data Download

25

www.qualitrolcorp.com

Components and Specifications

Clock Synchronization: This menu provides the CPU clock source information. This menu displays the Time mode of CPU, Source of clock, status of synchronization, and additional information based on source.

Figure 3.18 Clock Synchronization

Manual Trigger: This menu provides options for the user to give a manual trigger. This menu displays the following options:

Figure 3.19 Manual Trigger

FR Manual Trigger Gives a manual trigger to the FR engine.

26

www.qualitrolcorp.com

Components and Specifications

Channel Check: This menu provides the user with the option to test the analog, digital channels and FL channels. This menu displays the following options:

Figure 3.20 Channel Check

Analog Inputs - Navigates the screen to the Analog Inputs Check screen. This screen displays the selected analog channel status. The analog channel is selected using the up and down arrow keys. Digital Inputs - Displays the channel state of all 64 digital channels. FL Lines Displays the FL channel status.

Relay Test: This menu provides the user with the option to test the relay, as shown in the following figure. The relay is selected using the up and down arrow key.

Figure 3.21 Relay Test

Display Settings: This menu provides the user with the option to change the LCD and backlight settings, as shown in the following figure.

Figure 3.22 Display Settings

27

www.qualitrolcorp.com

Components and Specifications

3.6.6. LED Functions Normal Run Time Mode There are nine tri-colored (green, red, and amber) LEDs on the INFORMA PMD-A front panel. When the device is on, all nine LEDs keep flashing (anti-clock wise direction) in green for a maximum of 3 minutes. This indicates that the LCD interface is booting up. If the firmware is upgrading, then the right side LEDs scroll from top to bottom and the left side LEDs scroll from bottom to top in green. Once the firmware is upgraded successfully, only the Health LEDs flash in green and the others are in an OFF state. If a communication failure occurs during the upgrade, all nine LEDs flash in red.

Figure 3.23 LED Indicators

Sl. No. LED 1

Feature Healthy

Purpose To check the health condition of the device

LED Color Green

LED Status ON-INFORMA PMD-A is Healthy. Flashing- INFORMA PMD-A is initializing. Problem in hardware module No Power Ethernet/RS232/RS485 communication is in Progress Communication error (Error in any one of the Ethernet/RS232/RS485 communication) No communication

Red Off LED 2 Comms Communication Green Red

Off

28

www.qualitrolcorp.com

Components and Specifications

Sl. No. LED 3

Feature Clock Sync

Purpose To check the clock synchronization

LED Color Green

Red LED 4 Battery Off To check Green whether the device is running on raw power or battery Red back-up Off

LED Status INFORMA PMD-A is locked (The internal clock is synchronized with the external clock). INFORMA PMD-A is unlocked. Nil INFORMA PMD-A is running on raw power and device is fitted with UPS card (Battery backup is available). INFORMA PMD-A is running on battery backup. INFORMA PMD-A is running on raw power and device is not fitted with UPS card (Battery backup is not available in the device.) DFR/TR/FL trigger in progress Nil No trigger Nil Indicates 90% Memory full or phase error in any of the channels selected by user, or user-configured event. No problem occurred.

LED 5

Trigger

To check DFR/TR triggering status. User Configurable: Default events are 90% Memory full or phase error in any of the channels. Or User can configure for any event. User Configurable: Default event is Channel Saturation event Or User can configure for any event.

Green Red Off Green Red

LED 6

Alarm

Off

LED 7

Status 1

Green

On/Flashing User-configured event occurred. On/Flashing -- Channel Saturation/user-configured event occurred. No Channel Saturation/Userconfigured event

Red

Off

29

www.qualitrolcorp.com

Components and Specifications

Sl. No. LED 8

Feature Status 2

Purpose User Configurable: Default event is Maintenance Mode start Or User can configure for any event. User configurable: Default state is USB communication Or User can configure for any event.

LED Color Green Red

LED Status On/Flashing User-configured event occurred. On/Flashing Maintenance Mode started/user-configured event occurred. INFORMA PMD-A is in Normal Mode/No user-configured event.

Off

LED 9

Status 3

Green

Flashing Firmware updating/ Configuration download/ Configuration updating/Data download is through USB/userconfigured event occurred. On If the USB communication process is completed/Userconfigured event occurred. USB communication error/Userconfigured event occurred. No USB communication/No userconfigured event.

Red Off

Channel Check Mode in 1 CPU Mode Without LCD When the Enter key in the MMI keypad is pressed, or when the shutdown switch (refer to Section 3.7.1 for shutdown information) is pressed for 3 seconds or less (if the shutdown switch is pressed for more than 3 seconds, the device will shut down), the front panel LEDs will display the status of the analog channels. The nine LEDs on the front panel display the status of the first nine analog channels as shown in the following table (9 LEDs and 9 analog channels are mapped one-to-one; LED 1 indicates the status of Channel 1, LED 2 indicates the status of Channel 2, and so on). LED Status Off Green Channel State Channel is not measuring. Channel is measuring. Description Amplitude is less than 10% of the nominal voltage. Amplitude is in between 10% and 120% of the nominal voltage and the phase sequence is proper. Phase sequence is not proper. Amplitude is greater than 120% of the nominal voltage.

Amber Red

Phase error in the Channel Channel is saturated.

30

www.qualitrolcorp.com

Components and Specifications

The Channel Check mode is terminated and moved to the default state when:

The Enter key is pressed, or After 5 minutes (fixed length timeout).

Channel Check Mode in 1 CPU Mode with LCD and 2 CPU Modes The user can select the Channel Check mode menu option by using the LCD and the keypad (refer to Figure 3.20). In this mode, the user can observe the sub menu options as:

Analog Inputs Digital Inputs

The Analog Inputs Check screen is editable for changing the channel numbers using the up and down arrow keys. The screen displays the RMS magnitude and transformer ratio of the selected channel. Alarm LEDs represent the phase error status of the selected channel. For example, suppose Channel 1 is configured as phase A, Channel 2 is configured as phase B, and Channel 3 is configured as phase C. If the user selects Channel 1, and if any phase error occurs, then alarm LED will glow Red. For details, refer to the LED 6 indication provided in the table in Section 3.6.6. For standalone, the Phase error indication is not applicable. The Digital inputs screen displays the state of the 64 digital channels. The user has to scroll using the up and down arrow keys to check the state of all the 64 channels.

3.7. Shutdown and Reset


Pressing the reset or the shutdown switch when the device is running may lead to the loss of data that is under acquisition. However, the data that is already available in the device will not be affected. 3.7.1. Shutdown Switch The INFORMA PMD-A device can be shut down gracefully by pressing the shutdown switch for more than 3 seconds. After the device shuts down, the Healthy LED (on the front panel of the device) stops glowing, indicating a successful shutdown. Now, the user can switch off the power supply to the device. Switching off the device without a graceful shutdown might corrupt the memory device. If the user releases the shutdown switch before 3 seconds, the device enters into the Channel check mode (for details about the Channel check mode, refer to Section 3.6.6). The shutdown switch is available on the motherboard/CPU. Refer to section 7.4.4.

31

www.qualitrolcorp.com

Components and Specifications

3.7.2. Reset Switch When the device is functioning abnormally, the user can reset the device by pressing the reset switch, which is available on the motherboard. When the user presses this switch, the CPU and all other peripherals restart immediately. The reset switch is available on the motherboard/CPU. Refer to section 7.4.4.

3.8. Communication Ports


3.8.1. PPH/PPM/IRIG-B In/IRIG-B Out 6U 3U

Figure 3.23 INFORMA PMD-A PPH/PPM

Note

A default 75 IRIG-B termination is provided by the INFORMA PMD-A device. If a 120 termination is required, then the user must use an external BNC adapter.

A suitable 75 to 120 Ohm terminator similar to L-Com part number ACC 8060 is required. 3.8.2. Fiber/Differential PPS

Figure 3.24 INFORMA PMD-A Fiber/Differential PPS

The master INFORMA PMD-A sends PPS signals to the slave INFORMA PMD-A by using either a differential PPS (TB8) or a fiber PPS.

32

www.qualitrolcorp.com

Components and Specifications

Note

Wire Gauge to be used at TB8 (PPS Out/In): 1426 AWG.

3.8.3. Ethernet Connections INFORMA PMD-A supports two types of Ethernet connections, a 10/100 Base-T that is operated at a speed of 10/100 Mbit/second, and a 100 Base-FX that is operated at a speed of 100 Mbit/second.

The 10/100 Base-T connection is done through the RJ45 socket and is used for shortrange communication over standard twisted pair cables. INFORMA PMD-A has two RJ45 Ethernet ports, one each on the front and the rear panel, referred to as Ethernet port 1 and Ethernet port 2, respectively. The 100 Base-FX connection is done through two ST fiber connectors and is used for longer-range communication over fiber optic cables. The white connector is used to transmit and the grey connector is used to receive. The connectors are suitable for 62.5/125 micron multi-mode fiber cable. The wavelength used is 1300 nm. The user can find the ST-fiber connectors on the rear panel of the device. 6U

3U

Figure 3.25 INFORMA PMD-A PPH/PPM

INFORMA PMD-A can be assigned an IP address statically or dynamically (by setting DHCP status as DHCP Client). The default IP address used by Ethernet port 1 is 192.168.0.11. Ethernet port 2 uses a default IP address until the user changes the default IP address (192.168.1.11) to any other IP address. In addition, INFORMA PMD-A has the capability to act as a DHCP server (by setting DHCP status as DHCP Server), in which the user can assign a range of IP addresses that can be allocated to other devices connected to the network.

33

www.qualitrolcorp.com

Components and Specifications

For network related configuration, IP address, Subnet Mask, Gateway, DNS IP, and DHCP, consult the network administrator. An incorrect network configuration will prevent proper equipment communication and network access. Network Services Provided by INFORMA PMD-A Through Ethernet Telnet: Telnet is a network protocol that allows users to connect to an INFORMA PMD-A device over a TCP/IP network. It provides access to a command-line interface, allowing a trained technician to analyze or debug problems. Secure Shell (SSH): SSH is a network protocol used to create a secure connection between INFORMA PMD-A and a users computer. The SSH connection provides authentication and encryption. File Transfer Protocol (FTP): FTP is used to transfer files between INFORMA PMD-A and the users computer over the network. IP Forwarding: IP Forwarding allows network requests to be redirected to a specified IP address that might be located on another network. IP Forwarding enables one device to act as a gateway, forwarding IP packets to another network device. 3.8.4. Serial Ports INFORMA PMD-A has four serial ports. The RS232-1 port is accessible from the front panel (open the front panel), and the RS232-2, RS232-3, and RS485 are accessible from the rear panel. The pin out details for the RS232-1, RS232-2, RS232-3, and RS485 are provided in the following table. RS232-1 Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8 Pin 9 GND DCE RTS CTS RXD TXD RS232-2 Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8 Pin 9 SD RXD TXD DTE GND DCE RTS CTS RI RS232-3 Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8 Pin 9 GND DCE RTS CTS RXD TXD RS485 Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 +RXD -RXD +TXD -TXD GND

34

www.qualitrolcorp.com

Components and Specifications

The following table provides details of the services that can be run on each port and the corresponding serial cable type to be used. Port Name RS232-1 Functionality/Services Debug port Cable Type Simple null modem without handshaking Null modem with loop back handshaking Standard modem cable (DTE-DCE) Simple null modem without handshaking Simple null modem without handshaking Null modem with loop back handshaking -

RS232-2

PPPD on SERIAL PPPD on MODEM

RS232-3

Protocols * IRIG-J PPPD on SERIAL PIC Programming (on-boot up)

RS485

Protocols (DNP/Mod bus/IEC 60870/IEC 61850)

*: Optional PPPD on SERIAL: This service is enabled or used when the INFORMA PMD-A device needs to be connected directly to a computer without a modem. PPPD on MODEM: This service is enabled or used when the INFORMA PMD-A device needs to be accessed through a modem.

35

www.qualitrolcorp.com

Components and Specifications

Cable Types The following figures show the different cable types.

Figure 3.24 Simple Null Modem Without Handshaking

Figure 3.25 Null Modem With Loop Back Handshaking

Figure 3.26 Standard Modem Cable

3.9. USB
3.9.1. USB Functionality When a user plugs in a USB storage device to INFORMA PMD-A, the device checks for a specific folder and validates the unique serial number and digital signature available in the script file inside the folder. Once the digital signature is verified, the INFORMA PMD-A device parses the script file to perform any of the following operations:

36

www.qualitrolcorp.com

Components and Specifications

Upload and download configuration Firmware upload Data download

In addition, the user can select and download data to the USB through the MMI. 3.9.2. USB Functions with or Without Script and MMI-LCD The following table lists the different scenarios of the USB script file and the LCD interface. Scenarios Script file is available but the LCD interface is not available. Both the script file and the LCD interface are available. Both the script file and the LCD interface are not available. The script file is not available but the LCD interface is available. USB Operation The USB performs operations according to the script. The USB performs operations according to the script because the script has higher priority. The USB does not perform any operation. The USB performs the data download operation through the LCD interface.

Note

The USB script is a future enhancement.

3.9.3. LED Indication The following table lists the LED indications: LED Indicators Flashing Green Description For any operation, such as a firmware update/configuration download/configuration update or a data download that happens through the USB. The USB communication process is completed. An error occurred in the USB communication process. No USB communication.

Solid Green Red OFF

37

www.qualitrolcorp.com

Components and Specifications

Figure 3.27 USB LED Indication

3.10. Clock Synchronization


Each INFORMA PMD-A device has an internal clock for maintaining the time-stamp for recorded data. This clock can be synchronized to an external GPS, internal RTC, IRIG-B, or IRIG-J. When multiple INFORMA PMD-A devices are installed at any one site, any one device (the time master) can be used to synchronize the other devices (time slaves) by using a PPS signal (Refer to Figure 4.2). Therefore, using clock synchronization, all INFORMA PMD-A devices can be synchronized to the same time and synchronously sampled to the GPS, internal RTC, IRIG-B, or IRIG-J. 3.10.1. INFORMA PMD-A as Master Using an External GPS PPS An external GPS antenna shall be connected to the BNC connector on the rear panel of the INFORMA PMD-A device. The antenna cable type is RG6 with BNC terminations connected to a Trimble Bullet antenna (maximum length is 45 m without an amplifier). Using Internal RTC INFORMA PMD-A can be configured to use its internal RTC as the time reference. When INFORMA PMD-A uses internal RTC as a time reference for its operation, the external substation pulses of PPM or PPH correct any drift in the RTC time. Alternatively,

38

www.qualitrolcorp.com

Components and Specifications

INFORMA PMD-A can be configured to generate an internal PPH signal by counting the 50/60 Hz line frequency signal from a configured FR Frequency reference voltage channel. Internal PPH signal should only be used when the line frequency has a tolerance of 0.06%. This would typically be used to eliminate a long-term drift in the internal RTC time when an external time reference is not available. If the frequency in the selected voltage channel is beyond 0.06% tolerance, the device will experience frequent Abrupt Time Shifts. If the amplitude in the selected voltage channel is below 10% of nominal voltage, the device will experience frequent Abrupt Time Shifts. External PPH signal is validated only if it is within 5 minutes of an hour boundary as determined by RTC time. If the PPH signal is received beyond this 5-minute time window, it is rejected and no actions are performed. Therefore, a user must initially set the time on the INFORMA PMD-A device to an accuracy of 5 minutes while using the external PPH. External PPM signal is validated only if it is within 10 seconds of a minute boundary as determined by RTC time. If the PPM signal is received beyond this 10-second time window, it is rejected and no actions are performed. Therefore, a user must initially set the time on the INFORMA PMD-A device to an accuracy of 10 seconds while using the external PPM. INFORMA PMD-A can be configured as the time master using iQ+, as shown in the following figure. Refer to iQ+ help for additional information.

Figure 3.28 - Time Management

39

www.qualitrolcorp.com

Components and Specifications

Using IRIG-B INFORMA PMD-A can be configured to use an external IRIG-B time source as the time reference. Connect the IRIG-B cable from the IRIG-B time source to the BNC connector. INFORMA PMD-A IRIG-B supports the following: 1. IRIG-B 001 Modulation Type Coded expression 2. IRIG-B 121 Modulation Type: Coded expression: Amplitude Modulated Sine Wave BCD (does not include year information), CF (includes year information). Frequency/Resolution: 1000 Hz carrier : Unmodulated, also called DC level shift. : BCD (does not include year information), CF (includes year information). Frequency/Resolution: No carrier

The INFORMA PMD-A device to which the IRIG-B time source is connected will be the time master. This time master INFORMA PMD-A device may now be used to provide time synchronization to other slave INFORMA PMD-A devices, using the differential or Fiber connection for PPS synchronization. Using IRIG-J INFORMA PMD-A can be configured to use an external IRIG-J time source as the time reference. Connect the serial cable from the IRIG-J time source to the RS232-2 port. INFORMA PMD-A IRIG-J supports IRIG-J-14. IRIG-J-14 The IRIG-J-14 is a Time-of-Year format with a 1-second resolution and frame length. The IRIG-J-14 baud rate is 1200. The INFORMA PMD-A device to which the IRIG-J time source is connected will be the time master. This time master INFORMA PMD-A device may now be used to provide time synchronization to other slave INFORMA PMD-A devices, using the differential or Fiber connection for PPS synchronization. 3.10.2. INFORMA PMD-A as Slave When INFORMA PMD-A is configured as a time slave, it receives PPS input from the time master and derives the time of the day by using NTP over the network. INFORMA PMD-A can be configured as a time slave using iQ+, as shown in the following figure. Refer to iQ+ help for additional information. For INFORMA PMD-A to be fully time-synchronized as a time slave, both PPS and NTP are required from the time master.

40

www.qualitrolcorp.com

Components and Specifications

Figure 3.29 INFORMA PMD-A Time Master/Slave Configuration

Note

In the absence of PPS input for the slave mode of operation, INFORMA PMDA will use NTP time as the time reference from the configured NTP server. Because INFORMA PMD-A is not synchronized with the PPS time marker, the accuracy of time synchronization is impacted.

3.10.3. INFORMA PMD-A Time Accuracy

Figure 3.30 - INFORMA PMD-A Time Accuracy

3.10.4. PPS Detection, Stability, and Lock Mechanism INFORMA PMD-A can be configured with any one of the external PPS sources for time reference. Once the edge of the external PPS is detected, the ON duration of the PPS pulse is checked, and it must exceed a minimum of 100 ms for the PPS to be validated.

41

www.qualitrolcorp.com

Components and Specifications

The next level of validation is the PPS stability check. The external PPS pulse is said to be stable, as long as the PPS to PPS duration remains constant within the acceptable jitter limit as mentioned in below table. Sl. No. 1 2 3 4 External Time Source (PPS) GPS INT RTC IRIG-B IRIG-J Jitter Limit (+/- ) 10 s 1 ms 1 ms 1 ms

This check is performed continuously and the status of the PPS stability is updated every 16 seconds. If the external PPS is stable for 16 seconds, then the PPS is declared as stable; else, it is rejected. When multiple INFORMA PMD-A devices are in the locked state, ADC sampling is synchronized. INFORMA PMD-A is said to be locked to External time source when the internal time is synchronized with the external time source within an acceptable band of time accuracy. INFORMA PMD-A is said to be in Not-Locked State if any of the following conditions occurs: The external PPS does not pass the stability check. The time difference is not within the acceptable jitter limit.

When there is a transition of INFORMA-PMD-A internal PPS from not-locked to a locked state, time correction occurs. The time correction can happen in any of the following ways: Gradual time correction Abrupt time shift

Gradual Time Correction The INFORMA-PMD-A internal time is corrected gradually if the difference is less than 0.5 seconds with respect to the external time. The maximum error correction allowed per cycle is approximately half of the intersample delay. Approximately, the time required to perform the correction for a 0.5-second error is 8.5 minutes. As a result, after the device is switched on, the clock synchronization LED might take a maximum of 8.5 minutes to turn on indicating the system is locked. Abrupt Time Shift If the difference in time is greater than 0.5 seconds, then the INFORMA-PMD-A internal time will be abruptly shifted to the external time. The abrupt shift in time is always indicated to the user.

42

www.qualitrolcorp.com

Components and Specifications

3.11. Analog Inputs


The INFORMA PMD-A 3U device supports 9 analog channels and the INFORMA PMD-A 6U device supports 9/18/27/36 analog channels. INFORMA PMD-A has the following types of analog inputs:

TX-AFE HIA-AFE

3.11.1. TX-AFE TX-AFE analog channels have the following characteristics:


16-bit resolution for voltage and 20-bit resolution for current Phase angle between channels: Accuracy 0.1 Channel Input Impedance of > 2.5 M (at 63 V), > 2 M (at 110 V), 1 M (at 230 V), and > 0.1 M (at 440 V)

3.11.2. HIA-AFE HIA-AFE analog channels have the following characteristics:


24-bit resolution for voltage/current Phase angle between channels: Accuracy 0.1 Channel input impedance of 4 M

Refer to Appendix A for details on the technical specifications. For TX-AFE and HIA-AFE, the range of input of the analog channels is listed in the following table: Channel Type AC Voltage Nominal Values 63.5 V 120 V 240 V 440 V 1A 2A 5A 10 A 12 V 120 V 240 V 480 V (4-20) mA current loop External current clamp Full Scale Deflection (FSD) 140 V 270 V 480 V 800 V 10 A 20 A 50 A 100 A

AC Current

DC input Voltages

Current inputs

43

www.qualitrolcorp.com

Components and Specifications

Selection of the nominal value is through jumper settings that are available internally to the TX-AFE and HIA-AFE boards. The appropriate FSD of any channel is configured at the factory as per the customer order. TX-AFE and HIA-AFE support a maximum overload of 1000 V continuous; 3.6 times of nominal voltage (maximum input voltage) for 10 seconds.

Note

Wire gauge to be used for TX-AFE and HIA-AFE analog inputs: 12-22 AWG.

All analog channels are calibrated at the factory and there is no need for site calibration. When there is a combination of current and voltage channels, the user must always ensure that the selected input channel is a current channel before connecting a CT circuit. Fast Transient Recording (optional) The fast transient recording card is optional and need to fit in the factory.

The signals taken from the HIA-AFE channel are processed in order to detect a trigger condition (when the transients occur), and to allow the digital recording of the waveforms before and after the trigger. The transient voltage (up to 6 kV) is detected by the TR module with a bandwidth of 2.5 kHz to 5 MHz. Sampling rates (user configurable): 20 MHz 10 MHz 5 MHz 2.5 MHz 1.25 MHz

TR analog channels have a 12-bit resolution.

3.12. Digital Inputs


The INFORMA PMD-A 3U device supports 32 digital inputs and the INFORMA PMD-A 6U device supports 32/64/96/128 digital inputs. All the input channels are bi-directional. INFORMA PMD-A supports two voltage levels configured at the factory as per the customer order as shown below.

For nominal voltage 24 V to a maximum input of 250 V: Less than 12 V No activation

44

www.qualitrolcorp.com

Components and Specifications

o o

(12-17) V Undefined Above 18 V Activation For nominal voltage 48 V, 110 V, and 220 V, to a maximum input of 250 V: Less than 30 V No activation (30-35) V Undefined Above 35 V Activation

o o o

The scanning rate of digital inputs is 2 kHz. The minimum pulse width of the digital inputs that can be detected and recorded is greater than 0.5 ms. The debounce time of digital inputs ranges from 0 to 1000 ms in 1 ms steps. The purpose of digital inputs is to monitor the state of external contacts normally associated with protection relays and circuit breakers. 3U

< Figure 3.31 INFORMA PMD-A Digital Inputs

45

www.qualitrolcorp.com

Components and Specifications

6U

Digital inputs are in groups of 8 and each group is galvonically isolated from the other group. The digital input connections are done through terminal blocks that plug into TB10 for an INFORMA PMD-A 3U device, and TB10 and TB12 for an INFORMA PMD-A 6U device.

Terminals 1-8 are digital inputs. Terminal 9 is common for digital inputs (1-8). Terminal 10 is earth and must be connected to the system earth.

Note

Wire gauge to be used for Digital inputs: 14-26 AWG.

3.13. Alarm Output

46

www.qualitrolcorp.com

Components and Specifications

INFORMA PMD-A supports alarm outputs 1 to 4 on the TB3 terminal block.

Note

Relay 1 is not configurable. However, relays 2, 3, and 4 are configurable. iQ+ does not support.

6U

3U

Figure 3.32 INFORMA PMD-A Alarm Outputs

Relay Specifications Contact Form Coli Voltage Service Life Mechanical Electrical : 50,000,000 operations minimum (at 18,000 operations/hour) : 100,000 operations minimum (at 1,800 operations/hour under rated load) : SPST NO/SPST NC : 5 VDC

Contact Rating : 5 A at 250 VDC/30 VAC, 8 A at 250 VAC/30 VDC

47

www.qualitrolcorp.com

Components and Specifications

The following pin out table lists the different alarm configurations. Pin No.
Pin 1 Pin 2 Pin 3 Pin 4

Alarm Configuration Relay1 Out + Relay1 Out Relay2 Out + Relay2 Out -

Indication

Pulse Width (ms)

Default State Normally Closed (NC)

System Healthy

DHCP configuration changed Memory threshold crossed for linear mode of recordings RMS envelope recording PQP 10 Min record threshold crossed Free Interval record threshold crossed Histogram - 10 Min threshold crossed Histogram - Free Interval threshold crossed Busbar1 EN 50160 Standard threshold Report memory threshold crossed Busbar1 EN 50160 User threshold Report memory threshold crossed Busbar1 - IEC 61000 3-6/7 report memory threshold crossed Busbar2 EN 50160 Standard threshold Report memory threshold crossed Busbar2 EN 50160 User threshold Report memory threshold crossed Busbar2 - IEC 61000 3-6/7 report memory threshold crossed Any PQ sensor triggered Any FR sensor triggered DFR manual trigger activated by user. Refer to Figure 6.24 in Section 6.3 for details.

100 500

Normally Open (NO)

350 350 500

48

www.qualitrolcorp.com

Components and Specifications

Pin No.
Pin 5

Alarm Configuration Relay3 Out +

Indication

Pin 6

Relay3 Out -

Device shutdown Manual Time set by user Memory full for linear mode of recordings RMS envelope recording PQP 10 Min record threshold recording Free Interval record threshold recording Histogram - 10 Min threshold recording Histogram - Free Interval threshold recording Busbar1 EN 50160 Standard threshold Report memory threshold recording Busbar1 EN 50160 User threshold Report memory threshold recording Busbar1 - IEC 61000 3-6/7 report memory threshold recording Busbar2 EN 50160 Standard threshold Report memory threshold recording Busbar2 EN 50160 User threshold Report memory threshold recording Busbar2 - IEC 61000 3-6/7 report memory threshold recording TR recordings DFR recording Refer to Figure 6.24 in Section 6.3 for details.

Pulse Width (ms) 500 500 500

Default State Normally Open (NO)

500 500

Pin 7 Pin 8 Pin 9 Pin 10

Relay4 Out + Relay4 Out Internally connected to GND

Temperature Over/Under Threshold crossed

65535

Normally Open (NO)

49

www.qualitrolcorp.com

Components and Specifications

The relay default settings are done at the factory as per the customer order.

Note

Wire gauge to be used for Alarm outputs: 14-26 AWG.

50

www.qualitrolcorp.com

Installation

Chapter 4
Installation

51

www.qualitrolcorp.com

Installation

4.

Installation
This chapter describes the installation procedure of the INFORMA PMD-A device.

4.1. Unpacking Procedure


Verify the package is not damaged if so contact courier. Remove and verify contents from package.

4.2. Accessories
Following accessories are provided:

Serial port cable RJ45 cable 2 m (straight) RJ45 cable 2 m (crossover) Operating manual Configuration CD (containing the standalone configuration tool) Four loose empty labels that the customer can place over existing labels if any settings are changed at a later stage. Test reports (including the serial port communication default settings of the device)

52

www.qualitrolcorp.com

Installation

4.3. INFORMA PMD-A Installation Specifications


The following figure shows a single INFORMA PMD-A communication to a computer through Ethernet or Modem.

1.
Figure 4.1 Standalone INFORMA PMD-A

53

www.qualitrolcorp.com

Installation

If multiple INFORMA PMD-A devices are installed at a given location or across different locations, they communicate with each other using twisted pair or fiber-optic Ethernet as shown in the following figure.

Figure 4.2 Networked INFORMA PMD-A

In Figure 4.2, INFORMA PMD-A #1 is configured as the time master and INFORMA PMD-A #2, #3, and #4 are configured as time slaves.

Note

The twisted pair Ethernet communications are also known as 10/100 Base-T, and have a maximum range of 100 m (300 ft) under normal conditions for error free communication. It is not recommended that the user extend twisted pair Ethernet cables beyond an adjacent cubicle in a substation environment. This is done to avoid induced transients from other conductors. Fiber-optic Ethernet network, also known as 100Base-FX, is recommended for long distance communication that can be extended over 1 km, when being used in multi-mode fiber.

54

www.qualitrolcorp.com

Installation

4.4. Device Communication Settings


1. Connect the device using default communication settings of the device. 2. User can change the device communication settings in the iQ+. Refer section 5.2.6. 3. Open the configuration window and make the respective changes in the communication port settings of Ethernet, modem and serial ports 4. Once the changes are done, user can send the configuration to the device by clicking on the button Send To Device in the configuration window of iQ+.

4.5. Installation Procedure


Remember the following:

In order to ensure safe operation, first connect the device to protective earth and then connect it to the power supply. Before connecting the circuits, ensure that the maximum measuring voltage and maximum voltage to earth are not exceeded. Do not use leads and accessories that do not fulfill the relevant safety standards. This could lead to serious injury or death from electric shock. Make sure that the device is installed in an area where heat dissipation is not restricted. Ensure that the device is in the operating temperature range and humidity conditions as specified in Appendix A before switching it ON.

4.5.1. Setting up the Device 1. Mount the device on the rack. 2. Connect the power cord to the 3-pin terminal block located on the rear panel of the device. 3. The 3-pin power terminal block is labeled with L, N, and an Earth symbol. The power cord must be connected accordingly. 4. Connect analog and digital inputs, and alarm outputs as per the specified configuration instructions (refer to Section 3.5). 5. If a UPS card is present, ensure that the UPS is switched ON. 6. Switch on the power supply using the button located on the rear panel of the device. 4.5.2. Starting the Device To ensure that the device has been installed correctly, the following needs to be checked. When the INFORMA PMD-A device is powered ON, all the LEDs on the front panel must flash in green (in anti-clock wise direction). This indicates that the device is booting up. INFORMA PMD-A takes about 6-7 minutes for boot-up process.

55

www.qualitrolcorp.com

Installation

Note

If the user has upgraded the firmware for standard MMI, then during the next boot up of INFORMA PMD-A, the LEDs on the right flash from top to bottom, and the LEDs on the left flash from bottom to top in green. This is in addition to the normal boot up mode.

4.5.3. Checking for Correct Operation: The front panel Healthy LED must be green. This indicates that the device is installed correctly and is ready to use.

56

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Chapter 5
Serial Connection to INFORMA PMD-A

57

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

5.

Serial Ports
This chapter provides instructions to configure serial connections to the INFORMA PMD-A device.

5.1. Functionality/Service
5.1.1. PPPD on Serial User has to enable/ use this service, when the INFORMA PMD-A device is connected directly to a PC without a modem. The type of cable need to be used for this service is Null Modem with loop back handshaking. Steps to establish a PPPD connection over Serial 1. In Windows-XP, go to Start->Control Panel->Network and Internet Connections >Network Connections. 2. In the Network Tasks, click on Create a new connection. The following wizard should appear for creating the new connection.

Figure 5.1 New Connection Wizard

3. Click on Next > button.

58

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Figure 5.2 Network Connection Type

4. Select the radio button Set up an advanced connection and click on Next> button.

Figure 5.3 Advanced Connection Options

5. Select the radio button Connect directly to another computer and click on Next> button.

59

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Figure 5.4 Host or Guest Page

6. Select the radio button Guest and then click on Next>button.

Figure 5.5 Connection Name

7. Mention any name say LnT and click on Next> button.

60

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Figure 5.6 Select a Device

8. Select Communications Port (COM x) and then click on Next> button.

Figure 5.7 Connection Availability

9. Select the radio button Anyones use and then click on Next> button.

61

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Figure 5.8 Completing the New Connection

10. Check on Add a shortcut to this connection to my desktop and then click on Finish button. A shortcut icon for serial connectivity is created on the desktop of the PC. 11. Now double click on the created shortcut icon, below wizard appears

Figure 5.9 Connect to LnT

62

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

12. Click on Properties then the below wizard appears

Figure 5.10 LnT Properties

13. Click on Configure, then the below wizard appears

Figure 5.11 Modem Configuration

63

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

14. From the Maximum speed (bps) drop down list provided user has to select the speed as 38400. (The default baud rate of serial port on INFORMA PMD-A device is set to 38400). 15. User has to de-select the Enable hardware flow control. 16. Click on OK, then the below wizard appears.

Figure 5.11 Modem Configuration

17. PC name appears in the User name by default. User has to enter any password. 18. Click on connect, then the below screens will appear.

64

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Figure 5.12 Verifying and Completing Registration

19. This implies the connection is formed. To check the status of connection: 1. Go to Start->Control Panel-> Network and Internet Connections -> Network Connections

Figure 5.13 Status-General

2. 3. 4. 5.

Double Click on Direct ->LnT to know the status of connection. A popup screen LnT Status will be displayed In the General tab user has to observe the status as connected. Click on Details tab, the screen appears as shown below

65

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Figure 5.14 Status-Details

Note

Server IP address: It is the new / temporary IP address assigned to INFORMA PMD-A device and meant only for the PPPD on serial link. Client IP address: It is the new / temporary IP address assigned to PC and meant only for the PPPD on serial link. The Server IP address & Client IP address is user configurable.

User has to use Server IP address (10.38.0.2 in the above mentioned example screen) to access the INFORMA PMD-A device via PPPD serial link.
PPPD ON MODEM:

User can enable/ use this service, when the INFORMA PMD-A device need to be accessed via modem. User has to use Standard Modem cable type for this service. Pre Requisites: User has to make sure that appropriate modem drivers are installed and the modem is detected by the PC. Please refer to the CD/Manual provided by the Modem manufacturer for driver installation instructions. Once the drivers are installed and modem is connected to the PC, user has to follow the below procedure to verify whether modem is detected or not.

Note

66

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

In the PC, go to Start->Control Panel-> Printers and Other Hardware->Phone and Modem Options.

Figure 5.15 Phone and Modem Options

Under the tab Modems user can observe the installed modems as shown below.

67

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Figure 5.16 Modems

Ex: In the above screen the modem detected is Conexant ACF External PnP ..Modem.

Steps to establish a PPPD connection over Modem


Once the Pre-requisites are met, user has to follow the below steps for establishing the PPPD connection over Modem. 1. In Windows-XP, Go to Start->Control Panel-> Network and Internet Connections -> Network Connections 2. Click on Create New Connection

68

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

The following wizard will appear for creating the new connection.

Figure 5.17 New Connection Wizard

3. Click on Next button.

Figure 5.18 Network Connection Type

69

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

4. Select the radio button Connect to the network at my workplace and click on Next> button

Figure 5.19 Network Connection

5. Select the radio button Dial-up connection and click on Next> button

Figure 5.20 Connection Name

70

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

6. Enter the name on your choice under the Company Name (In this case it is LnT ) and click on Next> button. The below wizard appears.

Figure 5.21 Phone Number to Dial

7. User has to enter the phone number (which user wishes to dial) under Phone Number and click on Next> button. 8. Please refer to the instructions present in the wizard for entering correct number with appropriate area code ,0 prefixing etc.,

71

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Figure 5.22 Connection Availability

9. User can select either Anyones use / My use and then click Next> button

Figure 5.23 Completing the New Connection Wizard

10. Click on Finish by selecting the option Add a Shortcut to this connection to my desktop for creating a shortcut to the dial up connection on the desktop.

72

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Now, user will be able to see a connection formed with LnT (in this example) short cut in the desktop as well as in the Network connections (in control panel)

Figure 5.24 Network Connections

11. Now double click on LnT shortcut present on the desktop for the following wizard

Figure 5.25 Connect LnT

73

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

12. For setting the Baud rate user has to click on Properties .A window appears as shown below

Figure 5.26 Lnt Properties

13. Click on Configure

Figure 5.27 Modem Configuration

74

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

14. Change the Maximum Speed to 38400 15. Ensure that all Hardware Features are enabled. 16. Click on OK. The below mentioned wizard appears.

Figure 5.28 Connect LnT

Note

If user wishes to change the number, then edit in the click on Dial column provided.

17. Enter any password. 18. Click on Dial button, the below screens will appear.

75

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Figure 5.29 Verifying and Completing Registration

19. This implies the connection is formed. To check the status of connection: 1. Go to Start->Control Panel-> Network and Internet Connections -> Network Connections

76

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Figure 5.30 LnT Status

2. 3. 4. 5.

Double Click on Direct ->LnT to know the status of connection. A popup screen LnT Status will be displayed In the General tab the status should be connected. Click on Details tab, the below screen will appear.

Figure 5.31 Status Details

77

www.qualitrolcorp.com

Serial Connection to Informa PMD-A

Note

Server IP address: It is the new / temporary IP address assigned to INFORMA PMD-A device and meant only for the PPPD on modem link. Client IP address: It is the new / temporary IP address assigned to PC and meant only for the PPPD on modem link. The Server IP address & Client IP address is user configurable.

User has to use Server IP address (10.38.0.2 in the above mentioned example screen) to access the INFORMA PMD-A device via PPPD modem link

78

www.qualitrolcorp.com

Configuration

Chapter 6
Configuration

79

www.qualitrolcorp.com

Configuration

6.

Configuration
This chapter provides instructions to configure the INFORMA PMD-A device and the iQ+ software.

6.1. Hardware Configuration


INFORMA PMD-A supports the following cabling configuration: 6.1.1. Connection Diagrams Single Phase Network Single-phase, 2-conductor network connections are shown in Figure 5.1. The connections to the channels must be made as per the labels on the analog channel port shown in Section 3.5.

Figure 6.1 Single Phase Network

Note

For more information about configuration, refer to iQ+ Help.

80

www.qualitrolcorp.com

Configuration

3-Wire Network 2 Current Sensors L1, L3 (Aron Method/Two Wattmeter Method) The connections to the channels must be made as per the labels on the analog channel port as shown in Section 3.5.

Note

Observe the polarity of voltage connection V1 (V1+ and V1-) and current sensor I1 (I1+ and I1-). The device does not correct the systemic phase shift of 30 between phase-to-phase voltage and associated current; the individual phase power values are calculated values and might deviate considerably from the actual values. The actual threephase total power can be determined accurately using this method. This method is applicable only if IL1 + IL2 + IL3 =0, that is, if there is no N conductor.

The following figure shows 3-wire network (Aron measuring circuit) connections.

Figure 6.2 Aron Method/Two Wattmeter Method

Note

For more information about configuration, refer to iQ+ Help.

81

www.qualitrolcorp.com

Configuration

3-Wire Network (3U3I) 3-wire network (3U3IThree Wattmeter method) connections are shown below. The connections to the channels must be made as per the labels on the analog channel port shown in Section 3.5.

Figure 6.3 3-Wire Network (3U3I)

Note

Refer to iQ+ Help for associated software settings.

82

www.qualitrolcorp.com

Configuration

4-Wire Network (4U4I) 4-wire network (4U4I) connections are shown below. The connections to the channels must be made as per the labels on the analog channel port shown in Section 3.5.

Figure 6.4 4-Wire Network (4U4I)

Note

Refer to iQ+ Help for associated software settings.

83

www.qualitrolcorp.com

Configuration

Two 4-Wire Networks (2M4U) in Star Configuration With this method, 3 phase voltages and the respective N conductor voltages can be determined in two star connected three-phase systems. Two 4-wire network (2M4U) connections are shown below. The connections to the channels must be made as per the labels on the analog channel port shown in Section 3.5.

Figure 6.5 - 2M4U in Star Configuration

Note

Refer to iQ+ Help for associated software settings.

84

www.qualitrolcorp.com

Configuration

Two 3-Wire Networks (2M3U) in Delta Configuration This method is used to measure 3 phase-to-phase voltages in two delta configured threephase systems. Two 3-wire network (2M3U) connections are shown below. The connections to the channels must be made as per the labels on the analog channel port shown in Section 3.5.

Figure 6.6 - 2M3U in Delta Configuration

Note

Refer to iQ+ Help for associated software settings.

85

www.qualitrolcorp.com

Configuration

3U 3U (Star configuration) connections are shown below. The connections to the channels must be made as per the labels on the analog channel port shown in Section 3.5.

Figure 6.7 3U Configuration

Note

Refer to iQ+ Help for associated software settings.

86

www.qualitrolcorp.com

Configuration

4U 4U (Star configuration) connections are shown below. The connections to the channels must be made as per the labels on the analog channel port shown in Section 3.5.

Figure 6.8 4U Configuration

Note

Refer to iQ+ Help for associated software settings.

87

www.qualitrolcorp.com

Configuration

3U6I 3U6I (Star configuration) connections are shown below. The connections to the channels must be made as per the labels on the analog channel port shown in Section 3.5.

Figure 6.9 3U6I Configuration

Note

Refer to iQ+ Help for associated software settings.

88

www.qualitrolcorp.com

Configuration

6U3I 6U3I (Star configuration) connections are shown below. The connections to the channels must be made as per the labels on the analog channel port shown in Section 3.5.

Figure 6.10 6U3I Configuration

Note

Refer to iQ+ Help for associated software settings.

89

www.qualitrolcorp.com

Configuration

6.2. Software Configuration


To establish the communication using iQ+, the following steps must be performed: 1. Start iQ+.

Figure 6.11 Starting iQ+

90

www.qualitrolcorp.com

Configuration

2. To create a new device, right click All Devices as shown below:

Figure 6.12 Creating a New Device

91

www.qualitrolcorp.com

Configuration

3. Select INFORMA PMD-A from the device list.

Figure 6.13 Selecting INFORMA PMD-A Device

92

www.qualitrolcorp.com

Configuration

4. Enter the device details and save this information.

Figure 6.14 Creating a Device

5. A new device is created. 6. Right click the INFORMA PMD-A device and select Retrieve Configuration. The previously configured settings are loaded. (Factory default settings are loaded when the INFORMA PMD-A device is initialized for the first time.)

93

www.qualitrolcorp.com

Configuration

6.2.1. Configuration Overview

Figure 6.15 - Configuration Overview

1. The user needs to refer to iQ+ Help for detailed procedures to configure INFORMA PMD-A for different Power Quality and Fault Recording measurements.

INFORMA PMD-A must be configured for all required parameters including the device name and substation name through navigation across all subfields of the overview tree structure as described in the following sections.

2. After modifying the configuration, the user can save it in the database or save and send the configuration to the device by clicking the following buttons:

Save to Database: To convert the configuration to XML file and send it to the server; the file is saved in the database. Send To Device: To convert the configuration to XML and send it to the server. The file is saved in the database and also sent to the INFORMA PMD-A device for measurements.

94

www.qualitrolcorp.com

Configuration

6.2.2. Communications Through Ethernet Ports:

Figure 6.16 Ethernet Ports configuration with default values

Through Modem: To communicate using modem, port RS232-2 must be configured for the internal or external modem (the user needs to select the Modem Type). RS232-2 is the configuration editor for INFORMA PMD-A device in iQ+. If the user selects the Modem Type as None, then the modem service will not run in INFORMA PMD-A. Through Serial Ports: To communicate using serial ports, the user must configure the hardware settings for the respective port.

95

www.qualitrolcorp.com

Configuration

Figure 6.17 RS232-2


Note

Internal modem is optional. For more information about configuration, refer to iQ+ Help.

96

www.qualitrolcorp.com

Configuration

Figure 6.18 RS232-3

Note

For more information about configuration, refer to iQ+ Help.

97

www.qualitrolcorp.com

Configuration

6.2.3. PQ Overview

Figure 6.19 PQ Overview Flow Chart

Note

Each record and report can be enabled or disabled.

98

www.qualitrolcorp.com

Configuration

6.2.4. PQ Configuration

Figure 6.20 PQ Configuration

The user can enable or disable any of the PQ records and report generating functions. Figure 6.30 shows the options for disabling and enabling PQ records and report generating functions. The user can also configure the power and energy window and reference channel for system frequency. Power and energy will be logged according to the configured window. 6.2.5. Continuous Recording Ten Minute Recordings (Standard PQ measurement, according to IEC 61000-4-30 Class A)

Minimum, Maximum, and Average values are calculated using 200 ms data. A maximum of 1188 out of 3634 parameters (total number of parameters depend on the cabling configuration) can be configured including 10-second frequency. Configurable data types: - 10-minute MMA data, 10-minute frequency, 10-minute flicker, and 10-second frequency. Output: MMA values for each of the selected parameters except for 10-minute frequency flicker and 10-second frequency.

99

www.qualitrolcorp.com

Configuration

Figure 6.21 PQ 10-Minute Continuous Recording

Free Interval Recordings

Minimum, Maximum, and Average values are calculated using data as per the aggregation interval configured. The user can configure the aggregation interval as 200 ms, 1 second, 2 seconds, 3 seconds, 6 seconds, 15 seconds, 30 seconds, and 1 minute to 1440 minutes. For aggregation interval as 200 ms, 200 ms data is considered and the record will contain only the average value. 200 ms data is aggregated for aggregation intervals of 1 second and 2 seconds. 3 seconds data is aggregated for aggregation intervals of 3 seconds, 6 seconds, 15 seconds, 30 seconds, and 1 minute to 30 minutes. For an aggregation interval greater than 30 minutes, 10-minute data is aggregated. The user can configure the PQ parameters to be recorded (limited to 256 parameters). Output available will be Minimum, Maximum, and Average values for each of the selected parameters for the entire duration.

100

www.qualitrolcorp.com

Configuration

Figure 6.22 PQ Free Interval Continuous Recording

101

www.qualitrolcorp.com

Configuration

6.2.6. EN 50160 reports (standard threshold and user threshold) EN 50160 Report with Standard Limits (For Busbar 1) The EN 50160 report is based on 10-minute average values (except for frequencies that use 10-second values). Each parameter value is checked against its limits and is used to increment the total tally count or a bad tally count accordingly. The report provides a tabular summary of these tally counts across a reporting period of one week. Parameter limits are defined in the standard.

Figure 6.23 EN 50160 Standard Report Standard Limits (Busbar 1)

EN 50160 Report with User-Defined Limits (For Busbar 1) The EN 50160 is based on 10-minute average values (except for frequencies that use 10second values). Each parameter value is checked against its limits and is used to increment the total or bad tally count accordingly. The report provides a tabular summary of these tally counts across a reporting period of one week. The user can configure the parameter limits; therefore, this report is not restricted to the limits specified by the standard.

102

www.qualitrolcorp.com

Configuration

Figure 6.24 EN 50160 User Report User-defined Limits (Busbar 1)

6.2.7. IEC 61000-3-6/7 Report

Figure 6.25 - IEC 61000-3-6/7 Report

103

www.qualitrolcorp.com

Configuration

This creates a compliance report according to the IEC 61000 3-6/7 standards. This report contains the histogram of the selected parameter and also the minimum and maximum values of the selected parameter for the report duration. 6.2.8. Histograms Ten Minute Histogram Report This is a histogram report of the selected parameters derived from 10-minute data. The duration of histograms can be defined by the user from 10 minutes to a maximum of 24 hours. The user can select the minimum, maximum, or average values of the parameter for the histogram plot. The number of bins for each histogram is common for all the parameters selected.

Configurable data types: 10-minute MMA data, 10-minute flicker, and 10-minute frequency. Output: Histogram data of all parameters for the entire duration.

Figure 6.26 10-Minute Histogram Report

Free Interval Histogram Report This creates a histogram from 3-second values. There is a configuration item called aggregation interval, which indicates to what duration the 3-second values of the selected parameter should be aggregated before considering it for a histogram plot. For example, if the report duration is of 60 minutes and the aggregation interval is 1 minute, the 3-second values will be aggregated for each minute before considering it for the histogram plot. As a result, the histogram will display 60 points.

104

www.qualitrolcorp.com

Configuration

Free interval histogram can be configured from 1 minute to 24 hours. Aggregation interval should be less than the report duration. However, it should be a proper fraction of the report duration for proper data points. The user can configure the number of bins and their sizes. The user can also select the minimum, maximum, or average values of the parameter for the histogram plot.

Configurable parameters: 3 second MMA data and 10 second frequency. Output: Histogram data of all the parameters for the entire duration.

Figure 6.27 Free Interval Histogram Report

105

www.qualitrolcorp.com

Configuration

6.2.9. RMS Envelope

Figure 6.28 - RMS Envelope

The user can set the values of Pre-trigger time, Voltage Dead band, and Current Dead band as required. Dead band is a non-sensitive band that is used to avoid the recording of multiple half-cycle data with minor variations, and to save the storage memory.

Note

For more information about configuration, refer to iQ+ Help.

106

www.qualitrolcorp.com

Configuration

6.2.10. DSI Dip/Sag, Swell, and Interruption The user must select the Apply default values option to set the default values of Dip, Swell, and Interruptions as per the IEC 61000-4-30 standard. Alarm1 and Alarm2 configurations are applicable for UA- Under, UA-Over, and UA-Both sensor types.

Figure 6.29 - DSI and User Alarm


Note

Refer to Appendix B for more information. For more information about configuration, refer to iQ+ Help.

107

www.qualitrolcorp.com

Configuration

6.2.11. Rapid Voltage Change An RVC-PQ sensor operation is detected when the magnitude and the rate of change of voltage between two steady state averages exceeds the user settings. The user must select the Apply default values option to set the default values. When the user selects this option, all user entries are disabled.

Figure 6.30 Rapid Voltage Change

Voltage change: Defines the amplitude of change between the two steady state averages, and is used for voltage magnitude change and voltage gradient checking. Time window: Defines the time at which the rate of change of voltage is calculated. Steady Voltage Noise: During a steady state time window, the steady voltage noise defines the maximum amplitude of noise to maintain the steady state. Steady Hold Time: Defines the steady state time window based on which the steady state averages are calculated. Steady Time Out: Defines the timeout period after which the no steady state detected warning is issued.

Note

For more information about configuration, refer to iQ+ Help.

108

www.qualitrolcorp.com

Configuration

Power Quality (PQ) Sensor Channels

Figure 6.31 - PQ Sensor Channels

Note

For details about PQ Sensor Channels, refer to PQ Sensor Types in Appendix B. For more information about configuration, refer to iQ+ Help.

109

www.qualitrolcorp.com

Configuration

6.2.12. FR General The user must select the reference channel for FR frequency. In addition, the user can specify the following settings:

Pre-fault time between 10 ms and 10000 ms Sample rate as 32, 64, 128, 256, or 512 samples per cycle Post-fault time between 10 ms and 10000 ms Operational limit between 100 ms and 30000 ms Priority between 1 and 100

Figure 6.32 - FR General

Note

For more information about configuration, refer to iQ+ Help.

110

www.qualitrolcorp.com

Configuration

6.2.13. FR Sensor Channels The user can select the FR parameter, sensor type, threshold limits, nominal value, and other specifications for each sensor channel, as required.

Figure 6.33 - FR Sensor Channels

Note

For details about FR Sensor, refer to DFR Sensor Types in Appendix B. For more information about configuration, refer to iQ+ Help.

111

www.qualitrolcorp.com

Configuration

6.2.14. Data Storage

Figure 6.34 Data Storage

The memory configuration for various records and reports are configured here. Recorded data is stored into the memory allocated to each recording. The user has an option of configuring in linear or circular mode. Recording is stopped if configured in the linear mode and the memory limit has been reached. If configured in the circular mode, the oldest file is automatically overwritten. If the user configures memory that is less than the already allocated memory, then there is a potential chance of loss of data. The user must make a backup of the existing data before configuring memory.

112

www.qualitrolcorp.com

Maintenance

Chapter 7
Maintenance

113

www.qualitrolcorp.com

Maintenance

7.

Maintenance
INFORMA PMD-A is shipped after calibration. However, if the user has changed the FSD jumper setting or the nominal frequency, then the device shall be re-calibrated as per the following procedure.

7.1. Calibration

7.1.1. Calibration Procedure Calibration source details are as follows: Voltage source error < 0.02% of full scale Current source error < 0.02% of full scale

The following steps must be performed for calibration: 1. Open a Web browser and enter the following URL:

<http://Board_ip_address/mfgindex>
Board IP is the IP address configured for the device and it must be mentioned in the URL. For example:

<http://192.168.36.226/mfgindex>
Default user and password (mfgindex/tabindex): Username: qualitrol Password: qualcorp_techSupport10 For changing password go to: http://<ip address of device>/tabindex_password 2. Click the Calibration tab.

Figure 7.1 PMD-A Manufacturing Utility Homepage

114

www.qualitrolcorp.com

Maintenance

3. Identify the analog channel types (voltage/current) that physically exist on the acquisition board. Select the channel types based on the jumper/tap settings of analog channels and group similar channel types. Once the grouping is done, click Calibrate System. Consider the following example: The acquisition unit has 3 current and 3 voltage channels in the following manner:

Channels 1, 4, and 7 are current channels with tap settings 10 A and Channels 2, 3, and 5 are voltage channels with tap settings 140 V For channels 1, 4, and 7, select Type as Current 10 AC and Group as 1. This indicates that Group 1 corresponds to a set of channels of type Current 10 AC. For channels 2, 3, and 5, select Type as Voltage 140 AC and Group as 2. This indicates that Group 2 corresponds to a set of channels of type Voltage 140 AC.

In this situation, perform the following during calibration:

Figure 7.2 Calibrating the System

115

www.qualitrolcorp.com

Maintenance

4. Select the group that needs to be calibrated, and then click Continue. The device performs offset calibration.

Figure 7.3 Offset Calibration

116

www.qualitrolcorp.com

Maintenance

5. The following Web page allows the user to short the input channels under calibration. After shorting all the channels displayed, click Continue to proceed further. When calibrating with Relay Test Set, apply Zero current/voltage to channels under calibration.

Figure 7.4 Shorting the Channels

117

www.qualitrolcorp.com

Maintenance

6. The calibration command is sent to the device after a delay of 10 seconds. The delay is introduced by the GUI to allow the device to settle with the specified input. During offset calibration, the device enters the Calibration mode in which all sensors are disabled, and the data recording is paused.

Figure 7.5 Calibration in Progress

7. After the offset calibration is done, the system prompts the user for confirmation to perform a low gain calibration.

Figure 7.6 System Prompt

TX-AFE:

For Voltage/mA loop/DC calibration, the device proceeds for only low gain calibration For Current/External Clamp CT, the device proceeds for low gain as well as high gain calibration. In HIA-AFE, all channels have only one gain calibration.

HIA-AFE:

118

www.qualitrolcorp.com

Maintenance

Figure 7.7 - Voltage Calibration

119

www.qualitrolcorp.com

Maintenance

Figure 7.8 Current Low Calibration

8. Click Continue to allow the device to perform low gain calibration. The utility sends the command to the device after a 10 second delay. For normal TX-AFE current calibration, the device performs a high gain calibration. The same process is followed as mentioned earlier for the high gain factor of the channels under calibration.

120

www.qualitrolcorp.com

Maintenance

Figure 7.9 High Gain Calibration

7.1.2. Points to Remember


The voltage/current source channels must be connected properly. To ensure if the calibration is done properly, the user has to form a DFR and check whether the values are proper with respect to the applied values to the device. If the user changes the frequency of the device in the calibration window, then the device needs to be calibrated. In case of an inaccurate calibration, the user has to load the default calibration values.

Figure 7.10 Load Defaults

121

www.qualitrolcorp.com

Maintenance

For every group change or type change, the earlier calibration values are lost. Consider the following example: Suppose the user has calibrated a few channels leaving all the others to Undefined Channels. As a result, the next time the user configures and calibrates these channels, the earlier calibrated values will be lost. In this condition, the user has to save the earlier calibrated values and then proceed.

The default frequency setting of the INFORMA PMD-A device is 50 Hz. If the user wants to operate the device at 60 Hz, the device must be re-calibrated with a 60 Hz frequency setting. The operating frequency can be changed by using the System frequency drop-down menu as shown in Figure 6.2. When a frequency change occurs, the device is restarted; the user must wait for the device to restart and then proceed for calibration.

7.2. General Maintenance


7.2.1. Storage

Keep the original packaging intact. It might be required at a later stage for transport. Store the device in a dry room; maintain a temperature range of -30C to +70 C and a maximum humidity of 95 %. Keep the User Manual supplied with the device for future reference. Protect the device against direct sunlight, heat, moisture, and mechanical impacts. If the unit has a battery, switch off the battery by using the switch that is available on the UPS board during storage. Refer to Appendix E for more information.

7.2.2. Transport

Only the original packaging guarantees proper protection against mechanical impacts. Transport the device only in its original packaging. Protect the device during transport against heat and moisture; maintain the temperature range of -30C to +70C and maximum humidity of 95%. Protect the device against impacts and loads.

7.2.3. Routine Maintenance This instrument is a solid-state electronic device and there are no adjustable or renewable parts inside that require routine maintenance. However, after the first commissioning, it is recommended that a calibration check be performed every 5 years.

122

www.qualitrolcorp.com

Maintenance

7.2.4. UPS Maintenance Precautions for Handling and Use of Battery:


Avoid shorting the battery. Do not immerse in water. Do not disassemble or deform the battery. Do not expose to, or dispose the battery in fire. Store the battery in a cool, dry, and well-ventilated area. Never use a battery that has suffered abuse.

Acute Health Effects and First Aid Measures: In the unlikely event of an accidental exposure to the battery fluids, direct contact with skin and eyes are to be considered serious and must be treated immediately. In the event of a contact with the battery fluids, rinse with large volumes of water for at least 15 minutes, and consult a doctor. Storage of Battery for a Long Time: If the batteries are stored for more than 3 months without use, then they have to be discharged completely and recharged until 50% of the "end of charge" voltage. If these batteries are stored for more than 6 months, there can be a serious effect on the battery life. For further information about batteries, refer to data provided by the manufacturer.

123

www.qualitrolcorp.com

Maintenance

7.3. Firmware Upgrade


7.3.1. INFORMA PMD-A Firmware Upgrade Procedure Perform the following tasks to upgrade the firmware: 1. Contact Qualitrol for the latest versions of firmware. 2. Create a new folder on the computer to store the firmware files. 3. Save the initrd_CMxx.yy_Azz_with_crc.bin file in this folder. 4. Save the dsp_bank1.bin file in this folder. 5. Save either fpga_bank1.bin (for TX-AFE) or fpgaHiAfe_bank1.bin (for HIA-AFE) in this folder. 6. Save the pic_bank1.bin file in this folder. If the kernel has to be changed, then save the ulmage_x.y_with_crc file in this folder. 7. Communication between the computer and the device can be made in one of the following ways :

Local TCP-IP through a hub/switch/crossover cable connection to the RJ45 connector on the rear panel of the device. Remote PPP through a modem (external/internal) direct dial-in connection to the device. The external modem uses a rear panel RS232-2 connector and no VPN access is required.

Note

The user must set up a phone book entry/dial-up connection on the computer with the appropriate phone number settings (refer to Appendix A).

124

www.qualitrolcorp.com

Maintenance

8. When TCP-IP communications are properly established between the computer and the device, open a URL (the default IP is directed to either <http://192.168.1.11/tabindex.html> when the communication is through RJ45, or to <http://10.38.0.2/tabindex.html> when the communication is through a modem). Default user and password (mfgindex/tabindex): Username: qualitrol Password: qualcorp_techSupport10 For changing password go to: http://<ip address of device>/tabindex_password The following Web page is displayed.

Figure 7.11 System Information

125

www.qualitrolcorp.com

Maintenance

9. Delete data from the PMD-A Remark: make sure required data is downloaded before using iQ+ software Delete data with: <http://192.168.1.11/cgi-bin/delrecs.cgi> (RJ45) Or <http://10.38.0.2/cgi-bin/delrecs.cgi> (modem) Caution: Deleting data could take up to 15 minutes. The status of used memory can be seen on the Diagnostic Information page on "http://device_ip/mfgindex.html". Once it becomes "1%", we shall proceed with next step. 10. Open a Web browser and enter the following URL: <http://192.168.1.11/upgrade.html> (RJ45) Or <http://10.38.0.2/upgrade.html> (modem) Default user and password for upgrade: Username: qualitrol Password: qualcorp_Upgrade10 For changing password go to: http://<ip address of device>/upgrade_password The following Web page is displayed.

Figure 7.12 PMD-A Upgrade Page (Top)

126

www.qualitrolcorp.com

Maintenance

Figure 7.13 PMD-A Upgrade Page (Bottom)

The PMD-A Upgrade page allows the user to upgrade the following:

CPU_Application DSP FPGA FPGA_HI_A PICFirmWare MMIFirmware All of the above

The PMD-A Upgrade page also allows the user to upgrade the CPU-Kernel.

Note

The CPU-Kernel should only be sent along with the latest CPU_Application.

11. For upgrading the firmware, perform the following steps: a. Browse through the folder to locate the appropriate file.

127

www.qualitrolcorp.com

Maintenance

The following table lists the files which can be upgraded for INFORMA PMD-A. Application CPU_Application DSP FPGA FPGA_HI_A PIC MMI File to be Selected initrd_CMxx.yy_Azz_with_crc.bin dsp_bank1.bin fpga_bank1.bin fpgaHiAfe_bank1.bin pic_bank1.bin mmi_bank1.bin Check Box CPU_APP DSP FPGA FPGA_HI_A PIC MMI

b. After browsing the appropriate file, click on Send button. When the file is sent successfully, a success message error_string=SUCCESS is displayed. c. Repeat above procedure for all files to be upgraded in device. d. Scroll down webpage and go to TOGGLE_ALLsection, click the respective check box for which you have browsed and send files to device and then click on ToggleAll button. This process will upgrade to all newly sent firmware version executables/applications to the INFORMA PMD-A device. After clicking ToggleAll button device will be automatically restarted . e. Wait until the Healthy LED glows on the front panel of the device. 12. Only if necessary, for upgrading CPU-Kernel, click on CPU-Kernel browse button to locate the ulmage_x.y_with_crc file, and then click on Send button. On receiving the confirmation that the file is sent successfully, click the Toggle button for the CPUkernel,. After clicking Toggle button device will be automatically restarted .Wait until the Healthy LED glows on the front panel of INFORMA PMD-A device.

Note

The user can toggle multiple applications by selecting the respective check boxes provided in the TOGGLEALL section.

The subsequent pages show the updating processes involved after the device is successfully upgraded. The user can then check for new versions through the System and Diagnostic Information pages that are displayed. If the user is using a modem, then the file transfer rate may be very slow. For example, the CPU_Application may take up to 1 hour 45 minutes to upload the initrd_wthcrcPx.yz file, which is at least 17MB. After the application file is sent, it needs to be toggled for the new file to take effect. If the person upgrading the device has left the computer unattended for a long time, then the modem connection might be dropped because of no activity on the line. The default modem inactive time is 66 seconds.

128

www.qualitrolcorp.com

Maintenance

In this situation, the modem connection must be re-established and the Toggle/ToggleAll button must be invoked in order for the new version to take effect 7.3.2. During File Upload to INFORMA PMD-A During the upload process, a progress bar is displayed that signifies that communications and re-programming are in progress.

Note

For the purpose of this manual, the URL shown here has a device with the IP address 192.168.35.242.

When the file has been uploaded and stored into the INFORMA PMD-A device, a success message error_string=SUCCESS is displayed.

Figure 7.14 String Success

129

www.qualitrolcorp.com

Maintenance

7.3.3. During CPU File Upload to INFORMA PMD-A During the upload process, a progress bar is displayed that signifies that communications and re-programming are in progress, similar to other file uploads.

Figure 7.15 Uploading the File

130

www.qualitrolcorp.com

Maintenance

When re-programming is completed, a success message error_string=SUCCESS is displayed.

Figure 7.16 File upgrade status

7.3.4. System and Diagnostic Information After the INFORMA PMD-A device has restarted and the Healthy LED is on, open a Web page and enter the URL as: <http://board_ip address/mfgindex.html> For example, <http://192.168.33.114/mfgindex.html>

131

www.qualitrolcorp.com

Maintenance

The following page is displayed.

Figure 7.17 - System Information

Ensure that the newly installed firmware versions displayed in the page are correct. Consult Qualitrol for the latest versions.

Note

The Firmware versions shown in the Figure 6.19 may have been updated after this manual is written.

132

www.qualitrolcorp.com

Maintenance

Click the Diagnostic Information tab and the following page is displayed. Ensure that the DSP, FPGA, and PIC are programmed successfully, and Power Health, PIC, and CPU are working.

Figure 7.18 - Diagnostic Information Page (Top)

133

www.qualitrolcorp.com

Maintenance

Figure 7.19 - Diagnostic Information Page (Bottom)

7.4. Troubleshooting
No part of the equipment is serviceable by the user. Always follow the safety instructions and safety precautions mentioned in SAFETY SUMMARY. Before attempting to troubleshoot a defective INFORMA PMD-A device, contact Qualitrol for help at csc@qualitrolcorp.com .

134

www.qualitrolcorp.com

Maintenance

If any one or all three LEDs (Power healthy, Communication, and Clock Sync) on the front panel of the INFORMA PMD-A device are not working, perform the steps mentioned in the following table for finding the fault in the device and rectification.
Problem Symptom and Indication Potential Causes Corrective Action

Not all the LEDs are glowing. Or

Power Supply not Refer to Section 6.4.1 for initial inspection and working rectification. Motherboard not working

Only Power Healthy LED is OFF and all other are working. No Communication Only COMMS LED is OFF and all other LEDs on the front panel are working.

Communication modules not working Motherboard not working

1. Ensure that the serial port and connection cable pin-out are compatible. 2. Check the PC baud rate. Refer to Section 6.4.2 for further probing information.

Clock sync LED is OFF and all other LEDs on the front panel are working.

Not synchronized with GPS/RTC PPS (in master mode) Not synchronized with external master (in slave mode) Motherboard not working

Refer to Section 6.4.3 for initial inspection.

135

www.qualitrolcorp.com

Maintenance

7.4.1. Power Healthy LED on the Front Panel is Off To find the possible causes for power supply failure, follow the steps mentioned below:
Power healthy LED (HEALTHY) is OFF

Check whether input power is correctly available on the rear panel?

Is Power Available?

NO

Resolve Power Connection Issue

YES

Open the front panel of the equipment

Check the voltages at the respective test points on the motherboard. Refer Section 6.4.4 for details.

Are Voltages correct?

YES

Reboot the system by pressing the RESET switch that is present on the Mother Board. Refer section 6.4.4

NO NO

Contact Qualitrol Support for further help with Model and Serial Number.

Is Healthy LED ON?

Figure 7.20 Power Failure Causes

136

www.qualitrolcorp.com

Maintenance

7.4.2. Communication LED is Off To find the cause for the communication failure, follow the steps mentioned below:

Figure 7.21 - Communication Failure

137

www.qualitrolcorp.com

Maintenance

7.4.3. Clock Sync LED is Off To find the cause for the clock synchronization failure, follow the steps mentioned below:

Figure 7.22 - Clock Synchronization Failure

7.4.4. Test Points to Verify the Supply Voltages Supply voltage test points are available on the motherboard. Test points are located between the connector CN19 and the connector CN8 on the motherboard.

138

www.qualitrolcorp.com

Maintenance

Shutdown switch

Reset switch

DGND

+5V

-12V

Figure 7.23 Location of Reset and Shutdown Switches and Supply Voltage Test Points on the Motherboard

139

+12V

www.qualitrolcorp.com

Appendix A Technical Specifications

Appendix A
Technical Specifications

140

www.qualitrolcorp.com

Appendix A Technical Specifications

Appendix A Technical Specifications


The following table lists the technical specifications for the INFORMA PMD-A device. Category General Parameters Processor Specifications 32 bit, 400 MHz processor 9 configurable analog channels for INFORMA PMD-A 3U device , 9/18/27/36 configurable analog channels for INFORMA PMD-A 6U device. Sampling rate 25.6 kHz at 50 Hz, 30.72 kHz at 60 Hz Bandwidth 25 to 4600 Hz 0.5 dB Operating System Status Indicators Quality System Calibration Monta Vista Linux with real time extensions 9 LEDs (Healthy, Communication, clock sync, battery, trigger, alarm and sensors( status)) Developed, designed, and manufactured according to DN ISO 9001:2000. Solid state design, no user adjustments. Calibration check to be performed once in 5 years. Data Storage Compact Flash for record storage 4 GB standard (8 GB/16 GB optional) On-board Flash for firmware 64 MB A RAM based temporary file system is used to avoid excessive Flash use avoiding Flash wear. The INFORMA firmware is designed to optimize the write operations for every memory block. Power Supply Input Range Type 1: 90 264 VAC (88-300 VDC), 47 63 Hz Type 2: 36 72 VDC Type 3: 18 36 VDC Maximum Load 40 VA for 3U INFORMA PMD-A device and 80 VA for 6U INFORMA PMD-A device

141

www.qualitrolcorp.com

Appendix A Technical Specifications

Category

Parameters Typical Load

Specifications 25 VA for 3U INFORMA PMD-A device and 50 VA for 6U INFORMA PMD-A device

Auxiliary Output Analog Inputs Voltage AC Input Range

DC output 12 VDC at 750 mA Nominal (full scale) in VAC: 63.5 (140) 120 (270) 240 (480) 440 (800)

Safety Rating Maximum Overload Input Option 1: TX_AFE

300 V CAT III, 150 V CAT IV 1000 VAC continuous Impedance: > 2.5 M (at 63.5 V) ,> 2 M (at 120 V) , > 1 M (at 240 V), > 0.1 M (at 440 V) 16-bit resolution for voltage

Input Option 2: HIA-AFE

Impedance: > 4M 24-bit resolution for voltage/current channels: Accuracy 0.1

Optional for HIA-AFE: Fast Transient Recording

The transient voltage (up to 6 kV) is detected by the TR module with a bandwidth of 2.5 kHz to 5 MHz. Sampling rates (user configurable): 20 MHz, 10 MHz, 5 MHz, 2.5 MHz, 1.25 MHz 12-bit resolution

Analog Inputs Voltage DC (optional instead of AC)

Input Range Safety Rating Maximum Overload Input Impedance

Full scale in VDC: 12, 120, 240, 480 300 V CAT III, 150 V CAT IV 500 VDC continuous >= 420 K - (TX-AFE and HIA-AFE) Nominal (full scale) in AAC: 1 (10), 2 (20), 5 (50), 10 (100)

Analog Inputs Current

Input Range

142

www.qualitrolcorp.com

Appendix A Technical Specifications

Category

Parameters Maximum Overload Input Impedance

Specifications 200 A for 1 second, 40 A continuous < 0.02 20-bit resolution for current
(To achieve a 20-bit resolution on a current channel two 16-bit A/D converters are used with different gain factors to provide an effective 20-bit resolution.)

Digital Inputs

32 (isolated into groups of 8) Voltage range independent from 24/48 to 250 VDC

Alarm Notification

4 form A/B relay outputs (configurable normally closed or normally open at factory) Relay 1 indicates system Healthy. Relay 2, 3 are user configurable for PQ parameters . Relay 4 is user configurable for either temperature under/over temperature threshold. Resistive load: 250 VAC 5 A, 110 VDC 0.5 A, 48 VDC 1.0 A

Options

Time Synchronization

GPS (accuracy 300 ns between time masters) IRIG-B modulated and level shift (accuracy 2 ms between time masters) Time slave (synchronized through 1 PPS)

Mechanical

Dimensions

H x W x D: 132.5 mm 487 mm x 362.2 mm for INFORMA PMD-A 3U device H x W x D: 265.8 mm 487 mm x 362.2 mm for INFORMA PMD-A 6U device

Weight

15 kg without battery and 15.5 kg with battery for INFORMA PMD-A 3U device 23 kg without any external battery and 4 kg with two external batteries for INFORMA PMDA 6U device

Housing/Mounting

Metal 19 rack mounted cabinet

143

www.qualitrolcorp.com

Appendix A Technical Specifications

Category Communication

Parameters Ports

Specifications Four Serial (of these, three are RS232 ports with male DB-9 connectors, and one is RS485 with 1*5 pin connector.) Internal PSTN (V.90) modem (optional on RS232-2) Two 100 Mb Ethernet ports with RJ45 connectors Optional Fiber optic Ethernet (on rear port) Differential (RS485 levels) for 1 PPS for time synchronization Fiber optic 1 PPS output (master)/input (slave) TCP/IP, Modbus, IEC 60870-5, IEC 61850, GSM, GPRS IEC 61000-4-30 Class A IEC 61000-4-7 harmonics and inter-harmonics IEC 61000-4-15 flicker CBEMA, ITIC IEEE 1159, IEEE 519

Protocols Standard Compliance

Environmental

Temperature

Operating: -5C to 50C (23F to 122F) Cold start is not possible below 0C (32F) Storage: -30C to +70C (-22F to +158F)

Humidity Enclosure Others

0 to 95% non-condensing IP 40 according to IEC 60529 RoHS compliant

EMC Standards
Standards IEC 60255-22-6 / IEC 61000-4-6 Conducted Susceptibility (CS) References/Test criteria Tested to IEC 61000-4-6, Tested for 10 V, 150 kHz 80 MHz Tested on Power-line, RS232 -1, Ethernet port 1, Analog inputs (V & I), Digital Inputs, and Relay Outputs. Passed with : Criteria A

144

www.qualitrolcorp.com

Appendix A Technical Specifications

Standards IEC 60255-22-4 / IEC 61000-4-4 & ANSI C37.90.1.2002 Electrical fast transient burst test

References/Test criteria Tested to IEC 61000-4-4, Tested for : 4 kV, 5KHz/100KHz/2.5KHz Tested on Power-line, RS232-1, Ethernet port 1, Analog inputs (V & I), Digital Inputs, Relay outputs. Passed with : Criteria A

IEC 60255-22-3 / IEC 61000-4-3 Radiated Susceptibility (RS)

Tested to IEC 61000-4-3, Tested for 10 V/m, 80 MHz 1000 MHz Tested on Complete Device Passed with : Criteria A

EN 55011 Conducted Emission (CE)

Tested to CISPR-11 Tested for 79 dB (V) quasi-peak and 66 dB (V) average at 0.15 MHz to 0.5 MHz 73 dB (V) quasi-peak and 60 dB (V) average at 0.50 MHz to 5 MHz 73 dB (V) quasi-peak and 60 dB (V) average at 0.50 MHz to 5 MHz Tested on : Complete Device Passed & the Emission levels are within the Specified limits of CISPR 11

EN 55011 Radiated Emission (CE)

Tested to CISPR-11 Tested for 40 dB (V/m) quasi-peak from 30 MHz to 230 MHz at 10 m (32.8 ft) 47 dB (V/m) quasi-peak from 230 MHz to 1000 MHz at 10 m (32.8 ft) Tested on : Complete Device Passed & the Emission levels are within the Specified limits of CISPR 11

IEC 61000-4-8 Power frequency magnetic field test

Tested to IEC 61000-4-8 ,Tested for 30 A/m, x, y, z axis Tested on : Complete Device Passed with : Criteria A

IEC 60255-22-1 / IEC 61000-4-12 & ANSI C37.90.1.2002 Damped oscillatory wave disturbance tests

Tested to IEC 61000-4-12 ,Tested for 2.5 kV Common Mode, 1 kV Differential Mode, 1MHz Tested on : Power-line, Digital, Analog

145

www.qualitrolcorp.com

Appendix A Technical Specifications

Standards

References/Test criteria inputs( V ), Relay Passed with : Criteria A

IEC 61000-4-12 Ring wave test

Tested to IEC 61000-4-12, Tested for Level 3,+/- 2 kV Common Mode, 1 kV Differential Mode, 100KHz Tested on Power-line, Digital, Analog inputs( V ), Relay Passed with : Criteria A

IEC 61000-4-5 Surge test

Tested to IEC 61000-4-5 ,Tested for Class 4, I/O 4 KV Common Mode, 2KV Differential Mode Tested on Power-line, Digital, Analog inputs( V ), Relay Passed with : Criteria A

ENV 50204 Immunity to EMI from digital radio telephones

Tested to ENV 50204, Tested for level 3, 10 V/m, @900 MHz +/- 5 MHz, @1890 MHz +/10 MHz keyed at frequency 200 Hz +/- 1%, 50% duty cycle [2.5 ms ON 2.5 ms OFF]. Tested on Complete Device Passed with : Criteria A

IEC 60255-5 Clause 6 Dielectric test ANSI IEEE C37.90 1989 SWC dielectric tests

Tested to 2.5kV for 1 minute, Tested for 2.5 kV for Power-port, Analog inputs (V & I),Digital inputs, Relay, and 1 kV for isolated communication ports (RS232 & RS485) . No flashover or breakdown occurred.

IEC 60255-5 Clause 7 Insulation test

Tested to applied 500 VDC with respect to Earth. Tested on Power port, Analog inputs (V & I), Digital inputs & Relay. The impedance was greater than 100Mohms.

IEC 60255-5 Clause 8 Impulse voltage test

Tested to +/-5 kV, 0.5 J. Tested on: Power-line, digital, Analog inputs (V & I) & Relay. No flashover or breakdown occurred.

IEC 61000-4-11 Supply Voltage Dips

Tested to Dips-Class-3,Interruptions-Class-3

146

www.qualitrolcorp.com

Appendix A Technical Specifications

Standards and Interruptions

References/Test criteria Tested on Power-port. Passed with : Dips - Criteria A Interruptions - Criteria B

IEC 60255-22-2 / IEC 61000-4-2 Electro static discharge tests

Tested to IEC 61000-4-2,Tested for : 8 kV contact, 15 kV air Tested on Enclosure, all accessible I/O lines and ports. Passed with : Criteria A

IEC 60255-6/EN60255-6 Supply voltage limit test

Tested for PSU Tested for DC range 80VDC to 132VDC

IEC 60068-2-1/EN60068-2-1 Cold tests

Tested for Cold Storage -45 C (49 F) for 96 hours Cold Operating: -5 C (23 F) for 16 hours Tested on Complete Device

IEC 60068-2-6 Vibration tests

Tested for 2g Acceleration, Frequency is 10- 150 HZ, 20 sweep cycles in each of three mutually perpendicular planes (x, y, and z). Tested on Complete Device

IEC 60068-2 Cyclic Temperature Test

Tested for Cyclic Temperature test for a 5 cycles. Each cycle has 3 hours for 70 degrees & 3 hours for -5 degree in Power off Condition Tested on Complete Device

147

www.qualitrolcorp.com

Appendix A Technical Specifications

IEC 61000-4-30 Class A


The following table summarizes the INFORMA PMD-A accuracy and range specification of IEC 61000-4-30 Class A parameters. The INFORMA PMD-A is specified for Udin = 230V, 50/60 Hz. Accuracy Specified over Range 42.5 Hz ~ 57.5 Hz, 51 Hz ~ 69 Hz 10%~150% of Udin. 0.2~10.0 Pst N/A N/A Measuring Range 42.5 Hz ~ 57.5 Hz, 51 Hz ~ 69 Hz 10%~200% Udin 0~20 Pst N/A N/A

Parameter

Accuracy

Frequency Voltage RMS Flicker short term (10 min)-Pst Supply Voltage Dips and Swells Voltage interruptions Voltage Unbalance

+/- 0.01 Hz of injected +/- 0.1% of Udin 5% of Measured Value / applied input 0.2% of Udin. 0.2% of Udin. If unbalance is in the range 1 to 5% = +/-0.15% Um >= 1% Unom 5% of Um Um < 1% Unom .05% Unom ( Max allowed THD = 20% ) Um >= 1% Unom 5% of Um Um < 1% Unom 0.05% Unom ( Max allowed THD = 20% ) 1% and 3% of Udin 0.15% of Udin 3% and 15% of Udin 5 % of the measured value +/- 0.1% of Udin

1 5%

0 100%

Harmonics (up to 50th order)

10% to 200% of Class 3 IEC 61000-2-4 10% to 200% of Class 3 IEC 61000-2-4

200% of Class 3 of IEC 610002-4 200% of Class 3 of IEC 610002-4

Interharmonics (up to 50th order)

Signaling Voltages

0% to 15% of Udin [below 3 kHz]

0% ~ 15% Udin

Supply Voltage Under and Over deviation Note: Udin = Nominal voltage Um = Measured Voltage Unom = Nominal voltage

10% ~ 150% of Udin.

N/A

148

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Appendix B
INFORMA PMD-A Functions

149

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Appendix B INFORMA PMD-A Functions


Power Quality Parameters
Power quality parameters can be distinguished between steady state phenomena and nonsteady state phenomena.
Steady State Phenomena

In these phenomena, INFORMA PMD-A records PQ parameters continuously at 10-minute intervals and/or a user-defined time interval. Steady state phenomena = continuous recording (10-minute recording and or user-defined time interval)

Power frequency (10-second) Magnitude of supply voltage Flicker Voltage unbalance Harmonics Inter-harmonics Mains signaling (3-second) Over deviation and under deviation

Non-Steady State Phenomena

In these phenomena, INFORMA PMD-A records PQ events/Triggered recordings (DSI, RVC). Non-steady state phenomena = triggered recordings/PQ Events

Voltage dips/sags, swells, and interruptions (DSI) Rapid voltage changes (RVC)

Power Line Frequency (10-second) The power frequency is recorded by measuring the time between two positive zero crossings of the signal. 10-second frequency is a single value derived from configured reference channel, with time tag, and flagging information. The frequency calculation complies with IEC 61000-4-30.

150

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Figure B.1 10-Second Frequency Record


Note

Applied Frequency = 50 Hz Measured Frequency = 50 Hz

Magnitude of Supply Voltage The RMS value of the voltage at a given time at the supply terminals, measured over a given interval. The supply voltage recording is at 10-minute intervals and/or user-defined time intervals.

151

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Figure B.2 - Magnitude of Supply Voltage Record

Note

The device is connected to the main supply. The voltage fluctuates between 235 V to 250 V.

Flicker Flicker is a slow cyclical variation of the amplitude of the RMS voltage envelope. It is the impression of unsteadiness of visual sensation induced by a light stimulus whose luminance or spectral distribution fluctuates with time. Flicker recording complies with the IEC 61000-4-15 standard. Flicker is calculated on all three phases. Flicker data is stored in the recorder memory where it can be retrieved using the iQ+ Master Station software.

152

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Figure B.3 Flicker Record

Note

Flicker applied to the device is 10 Pst (nominal voltage 230 VAC). The green line indicates the voltage RMS value and the other 3 lines indicate the flicker Pst values on all the three phases.

Voltage Unbalance Voltage unbalance is a condition in which the RMS values of the phase voltages or the phase angles between consecutive phases are not equal. The level of unbalance is typically monitored from 10-minute average intervals and is expressed in %. Unbalance recording complies with the IEC 61000-4-30 standard. The INFORMA PMD-A device records the unbalance at 10-minute intervals and/or user-defined time intervals. Unbalance data can be stored in the recorder memory where it can be retrieved using the iQ+ Master Station software.

153

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Figure B.4 Unbalance Record

Voltage unbalance is displayed as 100% because all phases are In-phase.

Note

The maximum voltage unbalance displayed is 100%.

Harmonics Harmonics are systematic distortions of the waveform resulting from the super imposition of secondary signals having frequencies of a multiple of the fundamental frequency. The power quality recording function in the INFORMA PMD-A provides a comprehensive harmonic recording function comply with IEC 61000-4-7. The user can select up to the 50th harmonic quantity for each three-phase group of analog channels to be recorded at 10minute intervals and/or user-defined time intervals. The conditions in which the harmonics, inter-harmonics, and THD parameters are forced to zero are:

When applied voltage (fundamental) is zero. When applied voltage (fundamental) is less than 10% of nominal voltage.

154

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Figure B.5 Harmonics Record

Note

Harmonics applied to the device is 6% of nominal voltage 230 VAC. The green line indicates the voltage RMS value and the other 3 lines indicate the voltage harmonic (% of fundamental) values on all the three phases.

Inter-Harmonics Harmonics that have frequencies equal to non-integer multiples of the fundamental are interharmonics. The inter-harmonic recording function complies with IEC 61000-4-7. The user can select up to the 49th inter-harmonic quantity for each three-phase group of analog channels to be recorded at 10-minute intervals and/or user-defined time intervals.

155

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Figure B.6 - Inter-Harmonics Record

Note

Voltage inter-harmonics applied to the device is 10% and then 5% of nominal voltage 230V AC. The green line indicates the voltage RMS value and the blue line indicates the voltage inter-harmonic (% of fundamental) value on a single phase. The user can observe a slight variation in the voltage RMS because of the delay in the transition of voltage inter-harmonics from 10% to 5% of nominal voltage.

Mains Signaling Voltage


Voltage signals whose frequencies are different from the fundamental frequency are injected into the network. These injected voltage signals have to remain within acceptable limits (maximum RMS value) to avoid disturbing the connected equipments. Signaling voltage records are of fixed length (no re-triggering during a recording) and composed of 10-second pre fault and up to a maximum of 120-second post fault, specified by the user in 10-second steps.

156

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Figure B.7 - Signaling Voltage Record

Note

Mains signaling voltage applied to the device is 5% of nominal voltage 230 VAC. The green line indicates the voltage RMS value and the other 3 lines indicate the signaling voltage values on all the three phases.

Dips, Swells, And Interruptions (DSI) The power quality recording is equipped with a software power quality sensor that automatically detects voltage dips, swells, and interruptions. The duration and magnitude of each incident is characterized in compliance with IEC 61000-4-30. Incidents are retained in memory and can be retrieved for display and analysis by the iQ+ Master Station software.

157

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Figure B.8 RMS Envelope Swell

Rapid Voltage Change (RVC) A rapid voltage change is a quick transition in the RMS voltage between two steady-state conditions. To measure rapid voltage changes, thresholds are defined for each of the following:

The minimum rate of change The minimum duration of the steady-state conditions The minimum difference in voltage between the two steady-state conditions The steadiness of the steady-state conditions

The voltage during a rapid voltage change must not exceed the DSI threshold; else, it is considered as a DSI.

158

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Figure B.9 - RMS Envelope PQRVC

159

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Power Quality Sensors


PQ Sensor Functionality Resulting Record DFR RMS Envelope Record DSI RVC

Interval of PQ Calculation Urms (1/2) 200 ms (10/12 Cycle)

PQ Calculated Quantity RMS Voltage RMS Current RMS voltage / Current Harmonic (up to 50 individually) and interharmonic (up to 49 individually) (voltage/current) THD/TDD Power: 1-Ph Active, 3-Ph Active 1-Ph Reactive, 3Ph Reactive 1-Ph Apparent, 3Ph Apparent 1-Ph Distorted, 3Ph Distorted Harmonic Power(up to 50 harmonics individually) 1-Ph Power factor, 3-Ph Power factor Cos Phi Crest factor (voltage/current) k-factor Zero/negative sequence

Over

Under

Both

UAUnder X -

UAOver X -

X X

X X

X X

UABot h X -

X -

X -

X X

X X

X X

X X X X

X X X X

X X X X

160

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Resulting Record

DFR RMS Envelope Record

(voltage/current) Positive sequence (voltage/current) Unbalance (voltage/current) Signalling voltage 10 seconds 10 minutes Frequency Flicker

X X X X

X X X

X X X

Sensors are programmed to look for various types of PQ thresholds on calculated quantities and digital input changes, if they are configured as PQ sensors. INFORMA PMD-A sensors are completely adjustable either on site, or remotely, to meet user requirements. Prefault, postfault, and Oplimit (operational limit time) logic are fully adjustable. The user can also inhibit the sensors using software and digital input configuration. Oplimit is the maximum time for which DFR is performed after a fault occurs, if the fault persists for more than the postfault time. This comes into picture if the event trigger (causing a record to start) lasts beyond the user-specified operational limit. The device may be configured in order to perform one or more functions. Sensor Inhibit Using Software Configuration: Each PQ sensor can be individually enabled/disabled by user configurations. Sensor Inhibit Using Digital Input Configuration: Each PQ sensor can be inhibited by the state of single specified digital input. A total of 80 PQ sensors are available in INFORMA PMD-A. INFORMA PMD-A provides the following PQ sensor types on which different types of sensors can be configured. PQ Sensor Types Over: Applied on 200 ms data, 10-second frequency, and 10-minute flicker. If the computed value of the configured parameters exceeds the Over_Start -threshold calculated value, then the event is triggered. If the computed value of the configured parameter reduces below the Over_Stop -threshold calculated value later, then the event is de-triggered. Corresponding logs and records are generated. Under: Applied on 200 ms data, 10-second frequency, and 10-minute flicker. If the computed value of the configured parameters reduces below the Under_Start -threshold calculated value, then the event is triggered. If the computed value of the configured

161

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

parameter exceeds the Under_Stop -threshold calculated value later, then the event is detriggered. Corresponding logs and records are generated. Both: Applied on 200 ms data, 10-second frequency, and 10-minute flicker. If the computed value of the configured parameters reduces below the Under_Start -threshold calculated value OR exceeds the Over_Start -threshold calculated value, then the event is triggered. If the computed value of the configured parameter exceeds the Under_Stop -threshold calculated value OR reduces below the Over_Stop -threshold calculated value later, then the event is de-triggered. Retriggering happens if the parameter value swings between Under to Over and vice-versa. Corresponding logs and records are generated. UA-Under: Applied on Urms (1/2) data. If the Urms (1/2) value reduces below the UA_Under Start threshold calculated value, then the event is triggered. If the RMS value exceeds the UA_Under Stop -threshold calculated value later, then the event is de-triggered. Corresponding logs and records are generated. UA-Over: Applied on Urms (1/2) data. If the Urms (1/2) value exceeds the UA_Over Start threshold calculated value, then the event is triggered. If the RMS value reduces below the UA_Over Stop -threshold calculated value later, then the event is de-triggered. Corresponding logs and records are generated. UA-Both: Applied on Urms (1/2) data. If the Urms (1/2) value exceeds the UA_Over Start threshold calculated value OR reduces below the UA_Under Start threshold calculated value, then the event is triggered. If the RMS value reduces below the UA_Over Stop threshold calculated value OR exceeds the UA_Under Stop -threshold calculated value later, then the event is de-triggered. Retriggering happens if the parameter value swings between Under to Over and vice-versa. Corresponding logs and records are generated. DSI: Applied on Urms (1/2) data. If the Urms (1/2) value exceeds the Start limits of either Dip or Swell or Interruption, then the event is triggered. It is retriggered if the RMS value swings between any of the three limits. De-triggering happens if the RMS value is in normal limits. Corresponding logs and records are generated. RVC: Applied on Urms (1/2) data. If the rate of change of the Urms (1/2) value exceeds the limit decided by threshold, a sensor is triggered. It remains de-triggered in normal conditions. Corresponding logs and records are generated. Only sensors of the DSI or RVC types can initiate an RMS Envelope Recording. These are special function sensors and may be applied to voltage channels only.

For each busbar, any of the following are allowed:


A maximum of 3 sensors of the DSI type A maximum of 3 sensors of the RVC type If the "Connection/Cable-type" is set to Aron, only two voltage channels are available; consequently 2 sensors each, of the DSI and RVC types, are available for each of the busbar.

162

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Note that the sensors of the UA-Under, UA-Over, and UA-Both types will not trigger an RMS Envelope, although these sensors use an algorithm identical to that of DSI.

Handling Time Changes


When the user is setting the device time, it can be shifted forward or backward from the current set time using the iQ+ software. Forward Time Shift If the user has set the device time ahead of the current device time, then the situation is referred to as a Forward time shift.

Forward time shift of less than 10 minutes: The 10-second frequency counts will decrease in the EN 50160 reports (standard threshold and user threshold) equivalent to the amount of drift. In a 10-minute permanent recording, the timestamps and frequency values in the drift duration are set to zero. In free interval recording, if the aggregation duration is configured for less than or equal to 10 minutes, then the new segment is formed. If the aggregation duration is configured for more than 10 minutes, the data corresponding to the duration of drift will not be available. In the IEC 61000 report, data will not be available for the duration of the drift. In free interval histogram, if there is no impact for all other reports when the aggregation duration is configured for less than or equal to 10 minutes, then the new report is formed from the newly set time. If the aggregation duration is configured for more than 10 minutes, then the data is not available for the duration of the drift. There is no impact on a 10-minute Histogram. Forward time shift of more than 10 minutes: A new segment is formed in both 10-minute permanent recording and free interval recording. All other reports (EN 50160 standard threshold, EN 50160 user threshold, IEC 61000, 10-minute histogram, and free interval histogram) will be restarted from the newly set time.

o o o

o o

o o

Backward Time Shift

Backward time shift of less than 1 minute: In free interval recording, if the aggregation duration is configured for less than or equal to 1 minute, then a new segment is formed. If the aggregation duration is configured for more than 1 minute, then there is no impact.

163

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

No impact on 10-minute permanent recording and all other reports. Backward time shift of more than 1 minute and less than 10 minutes: No impact on 10-minute permanent recording and all other reports except for free interval histogram. In free interval recording, if the aggregation duration is configured for less than 10 minutes, the recording will be restarted with a new segment once the device time reaches the current recording time. If the aggregation duration is more than 10 minutes, then free interval recording will discard the data until the device time reaches the current recording time and will not break segments. Free interval histogram report will be restarted at the next 10-minute boundary; till then, all recorded data will be discarded. Backward time shift of more than 10 minutes: The device will not record data until the device time reaches the current recording time. PQ recording will restart with the new segment once the device time reaches the current recording time. For example, suppose the current device time is 11:30 and the user has changed the time back to 9:30. The device will not record data until the device time is 11:30; this helps the user not to lose recorded data from the device accidentally because of the changed time. However, if the user wishes to start recording the data with the backward shifted time (9:30 in this case), then the following steps need to be performed: 1. Save all available data from the device to the iQ+ server. 2. Access the Causeway Web server software by entering the following URL: <http://192.168.35.242/cgi-bin/delrecs.cgi>

o o

Note

192.168.35.242 is the device IP address.

The following Web page is displayed.

164

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Figure B.10 Deleting Records

Note

The user may be prompted for a password to access this Web page.

3. Select all records by clicking on the individual check boxes and then click the Delete selected data from system button. Now the device will start recording the data with immediate effect.

165

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

PQ Calculated Quantities
Following are the possible calculations recorded for PQ parameters.

Note

Star and delta are types of topology. 3U, 3U3I, etc. are types of cabling.

STAR Topology The following calculations are possible for 3U-star cabling (Ph-N type). 10 seconds Parameters Frequency RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Inter-harmonics (up to 50th order) THD( THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 minutes)-Pst Frequency (10 minutes) Signaling Voltages (3) Crest Factor Under and Over Deviation RMS Total Nos. 1 3 1 1 1 2 150 147 9 32 3 1 3 3 6 3 366

Voltage

10/12 Cycle Calculation

Urms (1/2) Calculation

166

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

The following calculations are possible for 3U-star cabling (Ph-Ph type). 10 seconds Parameters Frequency RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Inter-harmonics (up to 50th order) THD( THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 minutes)-Pst Frequency (10 minutes) Signaling Voltages (3) Crest Factor Under and Over Deviation RMS Total Nos. 1 3 1 1 1 2 150 147 9 32 3 1 3 3 6 3 366

Voltage

10/12 Cycle Calculation

Urms (1/2) Calculation

The following calculations are possible for 4U-star cabling (Ph-N type). Voltage 10 seconds 10/12 cycle calculation Parameters Frequency RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Inter-harmonics (up to 50th order) THD( THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 minutes)-Pst Total Nos. 1 4 1 1 1 2 200 196 12 32 3

167

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Urms (1/2) Calculation

Parameters Frequency (10 minutes) Signaling Voltages (3) Crest Factor Under and Over Deviation RMS

Total Nos. 1 3 4 6 4 471

The following calculations are possible for 4U-star cabling (Ph-Ph type). 10 seconds Parameters Frequency RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Inter-harmonics (up to 50th order) THD( THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 minutes)-Pst Frequency (10 minutes) Signaling Voltages (3) Crest Factor Under and Over Deviation RMS Total Nos. 1 3 1 1 1 2 150 147 9 32 3 1 3 3 6 3 366

Voltage

10/12 cycle calculation

Urms (1/2) Calculation

168

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

The following calculations are possible for 3U+3I-star cabling (Ph-N type). 10 seconds Parameters Frequency RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Inter-harmonics (up to 50th order) THD (THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 minutes)-Pst Frequency (10 minutes) Signaling Voltages (3) Under and Over Deviation RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance RMS Harmonic (up to 50th order) Inter-harmonics TDD k-Factor RMS Single Phase Active Power Three Phase Active Power Single Phase Reactive Power Three Phase Reactive Power Single Phase Apparent Power Three Phase Apparent Power Single Phase Distorted Power Total Nos. 1 3 1 1 1 2 150 147 9 32 3 1 3 6 3 1 1 1 2 3 150 147 3 3 3 3 1 3 1 3 1 3

Voltage

10/12 cycle calculation

Urms (1/2) Calculation

Current

10/12 cycle calculation

Urms (1/2) Calculation Power

169

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Parameters Three Phase Distorted Power Single phase power factor Three phase power factor cos phi Harmonic Power Crest Factor Energy

Total Nos. 1 3 1 3 150 6 8 864

The following calculations are possible for 3U+3I-star cabling (Ph-Ph type). 10 seconds Parameters Frequency RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Inter-harmonics (up to 50th order) THD( THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 minutes)-Pst Frequency (10 minutes) Signaling Voltages (3) Under and Over Deviation RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance RMS Harmonic (up to 50th order) Inter-harmonics TDD k-Factor Total Nos. 1 3 1 1 1 2 150 147 9 32 3 1 3 6 3 1 1 1 2 3 150 147 3 3

Voltage

10/12 cycle calculation

Urms (1/2) Calculation Current

10/12 cycle calculation

170

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Urms (1/2) Calculation

Power

Parameters RMS Single Phase Active Power Three Phase Active Power Single Phase Reactive Power Three Phase Reactive Power Single Phase Apparent Power Three Phase Apparent Power Single Phase Distorted Power Three Phase Distorted Power Single phase power factor Three phase power factor cos phi Harmonic Power Crest Factor

Total Nos. 3 0 1 0 1 0 1 0 0 0 1 0 0 6 8 695

Energy

The following calculations are possible for 4U+4I-star cabling (Ph-N type). 10 seconds Parameters Frequency RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Inter-harmonics (up to 50th order) THD(THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 minutes)-Pst Frequency (10 minutes) Signaling Voltages Under and Over Deviation RMS Total Nos. 1 4 1 1 1 2 200 196 12 32 3 1 3 6 4

Voltage

10/12 cycle calculation

Urms (1/2) Calculation 171

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Current

10/12 cycle calculation

Urms (1/2) Calculation

Power

Parameters Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance RMS Harmonic (up to 50th order) Inter-harmonics TDD k-Factor RMS Single Phase Active Power Three Phase Active Power Single Phase Reactive Power Three Phase Reactive Power Single Phase Apparent Power Three Phase Apparent Power Single Phase Distorted Power Three Phase Distorted Power Single phase power factor Three phase power factor Cos phi Harmonic Power Crest Factor

Total Nos. 1 1 1 2 4 200 196 4 3 4 3 1 3 1 3 1 3 1 3 1 3 150 8 8 1072

Energy

The following calculations are possible for 4U+4I-star cabling (Ph-Ph type). Voltage 10 seconds 10/12 cycle calculation Parameters Frequency RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Total Nos. 1 3 1 1 1 2 150

172

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Urms (1/2) Calculation

Current

10/12 cycle calculation

Urms (1/2) Calculation

Power

Parameters Inter-harmonics (up to 50th order) THD(THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 minutes)-Pst Frequency (10 minutes) Signaling Voltages (3) Under and Over Deviation RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance RMS Harmonic (up to 50th order) Inter-harmonics TDD k-Factor RMS Single Phase Active Power Three Phase Active Power Single Phase Reactive Power Three Phase Reactive Power Single Phase Apparent Power Three Phase Apparent Power Single Phase Distorted Power Three Phase Distorted Power Single phase power factor Three phase power factor Cos phi Harmonic Power Crest Factor

Total Nos. 147 9 32 3 1 3 6 3 1 1 1 2 3 150 147 3 3 3 0 1 0 1 0 1 0 0 0 1 0 0 6 8 695

Energy

173

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

The following calculations are possible for 4U+3I-star cabling (Ph-N type). Voltage 10 seconds 10/12 cycle calculation Parameters Frequency RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Inter-harmonics (up to 50th order) THD(THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 minutes)-Pst Frequency (10 minutes) Signaling Voltages Under and Over Deviation RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance RMS Harmonic (up to 50th order) Inter-harmonics TDD k-Factor RMS Single Phase Active Power Three Phase Active Power Single Phase Reactive Power Three Phase Reactive Power Single Phase Apparent Power Three Phase Apparent Power Single Phase Distorted Total Nos. 1 4 1 1 1 2 200 196 12 32 3 1 3 6 4 1 1 1 2 3 150 147 3 3 3 3 1 3 1 3 1 3

Current

Urms (1/2) Calculation 10/12 cycle calculation

Urms (1/2) Calculation Power

174

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Parameters Power Three Phase Distorted Power Single phase power factor Three phase power factor cos phi Harmonic Power Crest Factor Energy

Total Nos. 1 3 1 3 150 7 8 969

The following calculations are possible for 4U+3I-star cabling (Ph-Ph type). Voltage 10 seconds 10/12 cycle calculation Parameters Frequency RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Inter-harmonics (up to 50th order) THD( THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 minutes)-Pst Frequency (10 minutes) Signaling Voltages (3) Under and Over Deviation RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance RMS Harmonic (up to 50th order) Inter-harmonics Total Nos. 1 3 1 1 1 2 150 147 9 32 3 1 3 6 3 1 1 1 2 3 150 147

Current

Urms (1/2) Calculation 10/12 cycle calculation

175

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Urms (1/2) Calculation Power

Parameters TDD k-Factor RMS Single Phase Active Power Three Phase Active Power Single Phase Reactive Power Three Phase Reactive Power Single Phase Apparent Power Three Phase Apparent Power Single Phase Distorted Power Three Phase Distorted Power Single phase power factor Three phase power factor cos phi Harmonic Power Crest Factor

Total Nos. 3 3 3 3 1 3 1 3 1 3 1 3 1 3 150 6 8 829

Energy

Delta Topology The following calculations are possible for 3U-delta cabling. Voltage 10 seconds 10/12 Cycle Calculation Parameters Frequency RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Inter-harmonics (up to 50th order) THD( THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 Total Nos. 1 3 1 1 1 2 150 147 9 32 3 176 www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Parameters minutes)-Pst Frequency (10 minutes) Signaling Voltages (3) Crest Factor Under and Over Deviation RMS

Total Nos. 1 3 3 6 3 366

Urms (1/2) Calculation

The following calculations are possible for 3U+3I-delta cabling. 10 seconds Parameters Frequency RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Inter-harmonics (up to 50th order) THD(THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 minutes)Pst Frequency (10 minutes) Signaling Voltages (3) Under and Over Deviation Total Nos. 1 3 1 1 1 2 150 147 9 32 3 1 3 6 3 1 1 1 2 3 150 147 3 3 3

Voltage

10/12 cycle calculation

Urms (1/2) Calculation

Current

RMS Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance 10/12 cycle RMS calculation Harmonic (up to 50th order) Inter-harmonics TDD k-Factor Urms (1/2) Calculation RMS

177

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Power

Single Phase Active Power Three Phase Active Power Single Phase Reactive Power Three Phase Reactive Power Single Phase Apparent Power Three Phase Apparent Power Single Phase Distorted Power Three Phase Distorted Power Single phase power factor Three phase power factor cos phi Harmonic Power Crest Factor

0 1 0 1 0 1 0 0 0 1 0 0 6 8 695

Energy

178

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

The following calculations are possible for 2U+2I-delta cabling (Aron). Parameters 10 seconds Frequency Voltage 10/12 cycle RMS calculation Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance Harmonics (up to 50th order) Inter-harmonics (up to 50th order) THD(THD, THD Odd, THD Even) Flicker instantaneous(Pinst) Flicker short term (10 minutes)-Pst Frequency (10 minutes) Signaling Voltages (3) Under and Over Deviation Urms (1/2) Calculation RMS Current 10/12 cycle calculation Zero Sequence Positive Sequence Negative Sequence Unbalance and Zero Unbalance RMS Harmonic (up to 50th order) Inter-harmonics TDD k-factor RMS Single Phase Active Power Three Phase Active Power Single Phase Reactive Power Three Phase Reactive Power Single Phase Apparent Power Three Phase Apparent Power Single Phase Distorted Power Three Phase Distorted Power Single phase power factor Three phase power factor cos phi

Total Nos. 1 3 1 1 1 2 150 147 9 32 3 1 3 6 3 1 1 1 2 3 150 147 3 3 3 0 1 0 1 0 1 0 0 0 1 0

Urms (1/2) Calculation Power

179

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Parameters Harmonic Power Crest Factor Energy

Total Nos. 0 6 8 695

Types of Fault Recording


DFR DFR provides high speed monitoring and recording of the power system and equipment. The recording is carried out when a system fault occurs, which is user configurable. The following types of sources can initiate a DFR recording:

FR sensors PQ Sensors External Triggers Digital Inputs

Figure B.11 Digital Fault Record 1

Note

For more information about capturing DFR records, refer to iQ+ Help.

180

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

Figure B.12 - Digital Fault Record 1

DFR Sensor Types


Sensor Inhibit Using Software Configuration: Each FR sensor can be individually enabled/disabled by user configuration. Sensor Inhibit Using Digital Input Configuration: Each FR sensor can be inhibited by the state of a single specified digital input. A total of 32 FR sensors are available in INFORMA PMD-A.

181

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

INFORMA PMD-A provides the following FR data types on which different types of sensors can be configured.
FR Calculated Quantity Over Under BOTH Power Swing ROC (dx/dt)

Frequency RMS Fundamental/Full Power Sequence components amplitude AC RMS /DC Magnitude for standalone channels

x x x x

x x x x

x x x x

x x -

x x x -

Over: Applied on all FR parameters. If the computed value of the configured parameters exceeds the Over_Start -threshold calculated value, then the event is triggered. If the computed value of that configured parameter reduces below the Over_Stop -threshold calculated value later, then the event is de-triggered. Corresponding logs and records are generated. Under: Applied on all FR parameters. If the computed value of the configured parameters reduces below the Under_Start -threshold calculated value, then the event is triggered. If the computed value of that configured parameter exceeds the Under_Stop -threshold calculated value later, then the event is de-triggered. Corresponding logs and records are generated. Both: Applied on all FR parameters. If the computed value of the configured parameters reduces below the Under_Start -threshold calculated values, OR exceeds the Over_Start threshold calculated value, then the event is triggered. If the computed value of that configured parameter exceeds the Under_Stop -threshold calculated value, OR reduces below the Over_Stop -threshold calculated value later, then the event is de-triggered. Retriggering happens if the parameter value swings between Under to Over and vice-versa. Corresponding logs and records are generated. Power Swing: Applied on frequency and power values. The event is triggered when it detects poorly dampened oscillations. It is de-triggered if normal condition resumes. Dx/dt: Applied on RMS values of voltage and current, frequency, and power values. The event is triggered when it detects magnitude variations. It is de-triggered if normal condition resumes.

182

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

The following tables list the possible calculations recorded for DFR parameters. The following calculations are possible for 3U+3I cabling. Parameters Frequency RMS Magnitude, fundamental Phase Angle, fundamental RMS Magnitude, full Positive Sequence, amplitude Positive Sequence, angle Negative Sequence, amplitude Negative Sequence, angle Zero Sequence, amplitude Zero Sequence, angle RMS Magnitude, fundamental Phase Angle, fundamental RMS Magnitude, full Positive Sequence, amplitude Positive Sequence, angle Negative Sequence, amplitude Negative Sequence, angle Zero Sequence, amplitude Zero Sequence, angle Active power, fundamental Reactive Power, fundamental Apparent Power, fundamental Active power, full Reactive Power, full Apparent Power, full Total Nos. 1 3 3 3 1 1 1 1 1 1 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 37

Voltage

Current

Power

183

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

The following calculations are possible for 3U+3I+3I cabling. Parameters Frequency RMS Magnitude, fundamental Phase Angle, fundamental RMS Magnitude, full Positive Sequence, amplitude Positive Sequence, angle Negative Sequence, amplitude Negative Sequence, angle Zero Sequence, amplitude Zero Sequence, angle RMS Magnitude, fundamental Phase Angle, fundamental RMS Magnitude, full Positive Sequence, amplitude Positive Sequence, angle Negative Sequence, amplitude Negative Sequence, angle Zero Sequence, amplitude Zero Sequence, angle Active power, fundamental Reactive Power, fundamental Apparent Power, fundamental Active power, full Reactive Power, full Apparent Power, full Total Nos. 1 3 3 3 1 1 1 1 1 1 6 6 6 2 2 2 2 2 2 2 2 2 2 2 2 58

Voltage

Current

Power

184

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

The following calculations are possible for 3U+3I+3I+3I cabling. Parameters Frequency RMS Magnitude, fundamental Phase Angle, fundamental RMS Magnitude, full Positive Sequence, amplitude Positive Sequence, angle Negative Sequence, amplitude Negative Sequence, angle Zero Sequence, amplitude Zero Sequence, angle RMS Magnitude, fundamental Phase Angle, fundamental RMS Magnitude, full Positive Sequence, amplitude Positive Sequence, angle Negative Sequence, amplitude Negative Sequence, angle Zero Sequence, amplitude Zero Sequence, angle Active power, fundamental Reactive Power, fundamental Apparent Power, fundamental Active power, full Reactive Power, full Apparent Power, full Total Nos. 1 3 3 3 1 1 1 1 1 1 9 9 9 3 3 3 3 3 3 3 3 3 3 3 3 79

Voltage

Current

Power

185

www.qualitrolcorp.com

Appendix B INFORMA PMD-A Functions

The following calculations are possible for NO circuit cabling. Parameters Stand alone channel 1 (AC/DC) Stand alone Channel1 angle(if channel is A/C) Stand alone channel 2 (AC/DC) Stand alone Channel2 angle(if channel is A/C) Stand alone channel 3 (AC/DC) Stand alone Channel3 angle(if channel is A/C) Stand alone channel 4 (AC/DC) Stand alone Channel4 angle(if channel is A/C) Stand alone channel 5 (AC/DC) Stand alone Channel5 angle(if channel is A/C) Stand alone channel 6 (AC/DC) Stand alone Channel6 angle(if channel is A/C) Stand alone channel 7 (AC/DC) Stand alone Channel7 angle(if channel is A/C) Stand alone channel 8 (AC/DC) Stand alone Channel8 angle(if channel is A/C) Stand alone channel 9 (AC/DC) Stand alone Channel9 angle(if channel is A/C) Stand alone channel 10 (AC/DC) Stand alone Channel10 angle(if channel is A/C) Stand alone channel 11 (AC/DC) Stand alone Channel11 angle(if channel is A/C) Stand alone channel 12 (AC/DC) Stand alone Channel12 angle(if channel is A/C) Total Nos. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 24

186

www.qualitrolcorp.com

Appendix C Recording Data Rates and Memory Consumtion Rates

Appendix C
Recording Data Rates and Memory Consumption Rates

187

www.qualitrolcorp.com

Appendix C Recording Data Rates and Memory Consumtion Rates

Appendix C Recording Data Rates and Memory Consumption Rates


The following table lists the data rates and memory consumption rates. Functionality Default Memory Assigned (in MB) Number of Parame ters Record Duration (in minutes) Total Time Duration Taken to Fill Assigned Memory (in minutes) Mode of Operation Alarm Level

PQ Permanent recording -10 min Permanent recording Free interval Embedded recordings / Histograms EN 50160 for Busbar 1 Embedded recordings / Histograms EN 50160 (Free thresholds) for Busbar 1

40

1188 (Max) 256 (Max)

10

147880

Linear/ Circular Linear/ Circular

%x alarm threshold %x alarm threshold

40

12334

40

C110 (Max)

10

128600

Linear/ Circular

%x alarm threshold

40

110 (Max)

10

128600

Linear/ Circular

%x alarm threshold

188

www.qualitrolcorp.com

Appendix C Recording Data Rates and Memory Consumtion Rates

Functionality

Default Memory Assigned (in MB)

Number of Parame ters

Record Duration (in minutes)

Total Time Duration Taken to Fill Assigned Memory (in minutes)

Mode of Operation

Alarm Level

Embedded recordings / Histograms 10min Histogram Embedded recordings / Histograms 61000 3 6/7 Embedded recordings / Histograms Free interval Histogram Embedded recordings / Histograms EN 50160 for Busbar2 Embedded recordings / Histograms EN 50160 (Free thresholds) for Busbar 2 Embedded recordings / Histograms 61000 3 6/7 for Busbar 2 RMS Partition

40

512 (Max)

10

2000

Linear/ Circular

%x alarm threshold

40

55 (Max)

10

17270

Linear/ Circular

%x alarm threshold

40

512 (Max)

200

Linear/ Circular

%x alarm threshold

40

110 (Max)

10

128600

Linear/ Circular

%x alarm threshold

40

110 (Max)

10

128600

Linear/ Circular

%x alarm threshold

40

55 (Max)

10

17270

Linear/ Circular

%x alarm threshold

189

www.qualitrolcorp.com

Appendix C Recording Data Rates and Memory Consumtion Rates

Functionality

Default Memory Assigned (in MB)

Number of Parame ters

Record Duration (in minutes)

Total Time Duration Taken to Fill Assigned Memory (in minutes)

Mode of Operation

Alarm Level

Memory Assigned (in MB)

Record Duration (in seconds)

Total Time Duration Taken to Fill Assigne d Memory (in seconds ) 1 Record Duration (in minutes) 128 Total Time Duration Taken to Fill Assigned Memory (in hours) 17.26 Total Number of Records 500 Linear/ Circular %x alarm threshold Linear/ Circular %x alarm threshold Linear/ Circular %x alarm threshold

DFR

300 Memory Assigned (in MB)

CSS

1024 Memory Assigned (in MB)

32 Record Size

1 Record Duration (in minutes) 10

TR Configuration Log Firmware Total Memory Occupied in MB Total Memory Occupied in

1024 0.009 300 128 3180.009

1.52 MB

3.105478

190

www.qualitrolcorp.com

Appendix C Recording Data Rates and Memory Consumtion Rates

Functionality

Default Memory Assigned (in MB)

Number of Parame ters

Record Duration (in minutes)

Total Time Duration Taken to Fill Assigned Memory (in minutes)

Mode of Operation

Alarm Level

GB Compact Flash Size in GB Free Space Available in GB

0.894522

191

www.qualitrolcorp.com

Appendix D License Information

Appendix D
License Information

192

www.qualitrolcorp.com

Appendix D License Information

Appendix D License Updates


If the user wants to request for a license update, Qualitrol must be provided with access to the device. Else, Qualitrol must be provided with the <serial_number.req> file generated by the device. As a result, Qualitrol is able to update the existing license details as requested. For instructions to generate the <serial_number.req> file, refer to Section D.1. When the TCP-IP communication is established between the device and the computer, open a Web browser and enter the URL in the following format: <http://IP_Address/mfgindex.html>

Note

For the purpose of this manual, the URL shown here has a device with the IP address 192.168.1.11. Therefore, the URL should be similar to the following sample URL: <http://192.168.1.11/mfgindex.html>

On the Web page by default, it displays System Information. The software will prompt the user to modify the existing license. The instructions in the next section describe how to modify an INFORMA PMD-A license.

193

www.qualitrolcorp.com

Appendix D License Information

Modifying an Existing License


If a license already exists, then the System Information Web page is displayed. The Web page shows the existing license information, such as the device serial number, customer ID, order number, features included in the current license, and so on. To modify an existing license: 1. Click Modify License.

Figure D.1 System Information

194

www.qualitrolcorp.com

Appendix D License Information

2. On the page that is displayed, enter the customer ID and order number. This information is provided by the sales representative.

Figure D.2 Modifying the License Request

3. Click Modify Request. 4. A new <serial_number.req> file is generated on the devices file system. Save the <serial_number.req> file on the computer and send it to the appropriate sales representative or the Qualitrol licensing authority.

Figure D.3 Saving the Serial Number

195

www.qualitrolcorp.com

Appendix D License Information

5. The licensing authority sends back a <serial_number.xml> file. Save this file on the computer. 6. Using the Browse button, locate the file, and click Install license.

Figure D.4 Installing the License

7. The license is transferred to the INFORMA PMD-A devices file system and the device restarts. To return to the main System Information page, refresh the Web page.

Figure D.5 Completing the License Installation

196

www.qualitrolcorp.com

Appendix E Battery Replacement Procedure

Appendix E
Battery Replacement Procedure

197

www.qualitrolcorp.com

Appendix E Battery Replacement Procedure

Appendix E Battery Replacement Procedure


Battery Replacement Procedure for an INFORMA PMD-A 3U Device
To replace a battery, the following steps must be performed: 1. Switch off the main power supply to the INFORMA PMD-A 3U device and disconnect the input power cord. 2. Switch off the battery by using the switch provided on the UPS board. 3. Separate the UPS module from the device by removing the screws on the rear panel.

3U

6U
Figure E.1 Screws to be Removed

198

www.qualitrolcorp.com

Appendix E Battery Replacement Procedure

4. Isolate the old battery by disconnecting the CN5 connector.

Figure E.2 CN5 Connector

5. Uninstall the old battery by removing the screws as shown below. 6. Install the new battery. 7. Connect the new battery to the CN5 connector.

Figure E.3 Rajamane Battery

8. Reconnect the UPS/power supply module to the INFORMA PMD-A 3U device. 9. Connect the power cord and switch on the INFORMA PMD-A 3U device.

199

www.qualitrolcorp.com

Appendix F On-Board LED Functionalities and CPU MMI Modes

Appendix F
On-Board LED Functionalities and CPU MMI Modes

200

www.qualitrolcorp.com

Appendix F On-Board LED Functionalities and CPU MMI Modes

Appendix F On-Board LED Functionalities


LED Functions on the Motherboard
All LEDs are red in color.

D38 (under Internal Modem PCB)

D704 (under Relay PCB)

D701, D703, D36, D34, D1 D35, D37, D21, D22

Figure F.1 LEDs on the Motherboard

201

www.qualitrolcorp.com

Appendix F On-Board LED Functionalities and CPU MMI Modes

The following table describes the LEDs on the motherboard. LED D14 D21 D22 D704 D35 D37 D36 D34 D1 D701 D38 D703 Description Reset status for the INFORMA PMD-A device. ON indicates that Power On RESET has occurred and is still in reset condition. Debug LED (Reserved for future use) CPU_DONE indicates that FPGA is programmed. Debug LED for PIC Voltage indicator for -12 V Voltage indicator for +12 V Voltage indicator for +5 V Voltage indicator for +3.3 V Voltage indicator for +2.5 V Voltage indicator for +ISO+3.3 V Voltage indicator for +1.8 V

LED Functions on the DSP Board

Figure F.2 LEDs on the DSP Board

202

www.qualitrolcorp.com

Appendix F On-Board LED Functionalities and CPU MMI Modes

The following table describes the LEDs on the DSP board. LED LED2 LED1 Description Voltage indicator for +3.3 V which is used for DSP I/O Voltage indicator for +1.2 V which is used for DSP core

CPU MMI Modes


Based on the Dip switch position, the MMI mode is decided. There are two Dip switch positions, one indicates the CPU mode (1 CPU mode or 2 CPU mode), and the other indicates if the LCD is available. The 2 CPU mode always has the LCD. Purpose Dip Switch Designation S1-1 Identify the LCD mode Identify the CPU mode S1-2 Position W/ LCD W/o LCD 1 CPU 2 CPU Selection MMI with LCD MMI without LCD 1 CPU with LCD 2 CPU with LCD Description Default Selection W/o LCD Selection for LCD present/ absent. Selection of 1 CPU CPU mode

203

www.qualitrolcorp.com

Appendix F On-Board LED Functionalities and CPU MMI Modes

In the 1 CPU mode, the CPU must be connected to the first UART port (refer to legend J1 on MMI card).

Figure F.3 MMI Card Dip Switch (S1) and First UART Port (J1)

If the CPU is connected to the second UART port (J2 on MMI card), then the connection will not be detected because the second UART port is not initialized in the 1 CPU mode.

204

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

Appendix G
On-Board Jumper Settings

205

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

Appendix G On-Board Jumper Settings


The following table lists the TX-AFE jumper settings. TX-AFE Jumper Table Sl No. Channel No /Purpose Channel Jumper Position Selection Type Legend 2-3 Description Default

Mode Selection

J60 1-2

Channel Configuration for CH1

1-2 J13 2-3

CH1 J1

2-3

1-2 Voltage 2-3 J8 1-2

Current J22

1-2

2-3 J14

When the Standalone TX-AFE/HIAMode AFE board is tested without Motherboard 1-2 (Standalone). Normal With Mode motherboard (Normal Mode) Channel Configured as Voltage For Channel Configuration Channel Configured as Current Mounted for Input 140V FSD Mounted for Input Voltage 270V FSD Range Mounted Selection for Input 480V FSD Mounted for Input 800V FSD Current Mounted Range for Input Selection 10A FSD Mounted for Input 20A FSD Mounted for Input www.qualitrolcorp.com

1-2

206

Appendix G On-Board Jumper Settings

TX-AFE Jumper Table Sl No. Channel No /Purpose Channel Jumper Position Selection Type Legend 50A FSD Mounted for Input 100A FSD Channel Configured as Voltage Channel Configured as Current Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Channel Configured as Voltage Channel Configured as Current Mounted for Input 140V FSD Description Default

2-3

Channel Configuration for CH2

1-2 J40 2-3

For Channel Configuration

2-3 J25 1-2 Voltage 2-3 3 J31 1-2 CH2 1-2 J48 2-3 Current 1-2 J39 2-3

Voltage Range Selection

Current Range Selection

Channel Configuration for CH3

1-2 J49 2-3

For Channel Configuration

CH3

Voltage

J52

2-3

Voltage Range Selection

207

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

TX-AFE Jumper Table Sl No. Channel No /Purpose Channel Jumper Position Selection Type Legend 1-2 Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Channel Configured as Voltage Channel Configured as Current Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input www.qualitrolcorp.com Description Default

2-3 J59 1-2

1-2 J73 2-3 Current 1-2 J67 2-3

Current Range Selection

Channel Configuration for CH4

1-2 J18 2-3

For Channel Configuration

CH4 J3

2-3

1-2 Voltage 2-3 J9 1-2

Voltage Range Selection

Current J24

1-2

Current Range Selection

2-3

208

Appendix G On-Board Jumper Settings

TX-AFE Jumper Table Sl No. Channel No /Purpose Channel Jumper Position Selection Type Legend 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Channel Configured as Voltage Channel Configured as Current Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Channel Configured as Voltage Channel Configured as Current Description Default

1-2 J16 2-3

Channel Configuration for CH5

1-2 J42 2-3

For Channel Configuration

2-3 J26 1-2 Voltage 2-3 6 J32 1-2 CH5 1-2 J47 2-3 Current 1-2 J38 2-3

Voltage Range Selection

Current Range Selection

Channel Configuration for CH6

1-2 J63 2-3

For Channel Configuration

209

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

TX-AFE Jumper Table Sl No. Channel No /Purpose Channel Jumper Position Selection Type Legend 2-3 J51 1-2 Voltage 2-3 J57 1-2 CH6 1-2 J69 2-3 Current 1-2 J65 2-3 Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Channel Configured as Voltage Channel Configured as Current Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input Description Default

Voltage Range Selection

Current Range Selection

Channel Configuration for CH7

1-2 J17 2-3

For Channel Configuration

CH7 J2

2-3

1-2 Voltage 2-3 J7 1-2 Current J15

Voltage Range Selection

1-2

Current Range

210

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

TX-AFE Jumper Table Sl No. Channel No /Purpose Channel Jumper Position Selection Type Legend 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Channel Configured as Voltage Channel Configured as Current Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Channel Configured as Voltage Description Default

2-3

1-2 J23 2-3

Selection

Channel Configuration for CH8

1-2 J41 2-3

For Channel Configuration

2-3 J27 1-2 Voltage 2-3 9 J33 1-2 CH8 1-2 J46 2-3 Current 1-2 J37 2-3 Channel Configuration for CH9

Voltage Range Selection

Current Range Selection

10

J66

1-2

For Channel Configuration

211

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

TX-AFE Jumper Table Sl No. Channel No /Purpose Channel Jumper Position Selection Type Legend 2-3 Channel Configured as Current Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Board configured as TXAFE/HIAAFE 1 Board configured as TXAFE/HIAAFE 2 External CT Internal CT Description Default

2-3 J50 1-2 Voltage 2-3 J53 1-2 CH9 1-2 J68 2-3 Current 1-2 J64 2-3

Voltage Range Selection

Current Range Selection

TX-AFE/ HIA-AFE J76-J89 1 11 AFE BOARD SELECTION TX-AFE/ HIA-AFE J76-J89 2

2-3

1-2

12

External/ Internal CT Selection

For CT

J90J107

1-2 2-3

212

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

The following table lists HIA-AFE jumper settings. HIA-AFE Jumper Table Sl No. 1 Channel No./Purpose Channel Jumper Type Legend J16 J25 J162 J40 J41 J40 J41 J152 J16 J25 J162 J15 J40 J41 J16 J25 J15 J162 J40 J41 J152 J40 J41 CH1 Full Scale Selection Position 1-2 2-3 1-2 2-3 2-3 1-2 1-2 2-3 2-3 1-2 2-3 1-2 2-3 2-3 2-3 1-2 2-3 2-3 1-2 1-2 1-2 1-2 1-2 2-3 J1 1-2 Voltage 2-3 J2 1-2 Selection Description

Channel Configured as Voltage

Channel Configured as Current

CH1 Channel Configuration

Channel Configured as DC Voltage

For Channel Configuration

Channel Configured as mA loop

Channel Configured as Current Clamp Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD

Voltage Range Selection

213

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

HIA-AFE Jumper Table Sl No. Channel No./Purpose Channel Jumper Type Legend Position 1-2 J22 2-3 Current J14 2-3 1-2 Selection Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Mounted for Input 12VDC FSD Mounted for Input 120VDC FSD Mounted for Input 240VDC FSD Mounted for Input 480VDC FSD Channel Configured as Voltage Channel Configured as Current Description

Current Range Selection

1-2 J12 2-3 DC Voltage 1-2 J13 2-3 2 CH2 Channel Configuration J37 J42 J59 J163 J60 J59 J60 J153 J37 J42 J163 J28 J59 J60 J37 J42 J28 J163 J59 1-2 2-3 2-3 1-2 1-2 1-2 2-3 2-3 2-3 1-2 2-3 1-2 2-3 1-2 2-3 1-2 2-3 2-3 1-2

DC Voltage Range Selection

For Channel Configuration

Channel Configured as DC Voltage

Channel Configured as mA loop

214

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

HIA-AFE Jumper Table Sl No. Channel No./Purpose Channel Jumper Type Legend J60 J59 J60 J153 Position 2-3 1-2 2-3 1-2 2-3 J8 1-2 Voltage 2-3 J9 1-2 1-2 J6 CH2 Full Scale Selection 2-3 Current J7 2-3 1-2 Channel Configured as CC Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Mounted for Input 12VDC FSD Mounted for Input 120VDC FSD Mounted for Input 240VDC FSD Mounted for Input 480VDC FSD Channel Configured as Voltage Selection Description

Voltage Range Selection

Current Range Selection

1-2 J26 2-3 DC Voltage 1-2 J27 2-3 3 Channel Configuration for CH3 J46 J47 J164 J72 1-2 2-3 1-2 2-3

DC Voltage Range Selection

For Channel Configuration

215

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

HIA-AFE Jumper Table Sl No. Channel No./Purpose Channel Jumper Type Legend J73 J72 J73 J154 J46 J164 J47 J44 J72 J73 J46 J47 J44 J164 J72 J73 J72 J73 J154 CH3 J19 1-2 Voltage 2-3 J20 1-2 1-2 J17 2-3 Current 1-2 J18 2-3 Position 1-2 1-2 2-3 2-3 2-3 2-3 1-2 1-2 2-3 1-2 2-3 1-2 2-3 2-3 1-2 2-3 1-2 2-3 1-2 2-3 Selection Description

Channel Configured as Current

Channel Configured as DC Voltage

Channel Configured as mA loop

Channel Configured as CC Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A www.qualitrolcorp.com

Voltage Range Selection

Current Range Selection

216

Appendix G On-Board Jumper Settings

HIA-AFE Jumper Table Sl No. Channel No./Purpose Channel Jumper Type Legend Position Selection FSD Mounted for Input 12VDC FSD Mounted for Input 120VDC FSD Mounted for Input 240VDC FSD Mounted for Input 480VDC FSD Channel Configured as Voltage Channel Configured as Current Description

1-2 J10 2-3 DC Voltage 1-2 J43 2-3 4 J52 J53 J24 J90 J91 J90 J91 J155 J52 J53 J24 J50 J90 J91 J52 J53 J50 J24 J90 J91 J90 J91 J155 CH4Full Scale Voltage J31 1-2 2-3 1-2 2-3 1-2 1-2 2-3 2-3 2-3 1-2 2-3 1-2 2-3 1-2 2-3 1-2 2-3 2-3 1-2 2-3 1-2 2-3 1-2 2-3

DC Voltage Range Selection

CH4 Channel Configuration

Channel Configured as DC Voltage

For Channel Configuration

Channel Configured as mA loop

Channel Configured as CC Mounted for Input 140V Voltage Range

217

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

HIA-AFE Jumper Table Sl No. Channel No./Purpose Channel Jumper Type Legend Position Selection FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Mounted for Input 12VDC FSD Mounted for Input 120 VDC FSD Mounted for Input 240VDC FSD Mounted for Input 480VDC FSD Channel Configured as Voltage Channel Configured as Current Channel Configured as DC Voltage Description

1-2

2-3 J32 1-2 1-2 J4 2-3 Current Selection J21 2-3 1-2

Selection

Current Range Selection

1-2 J48 2-3 DC Voltage 1-2 J49 2-3 5 CH5 Channel Configuration J65 J66 J36 J103 J104 J103 J104 J156 J65 J66 J36 1-2 2-3 1-2 2-3 2-3 1-2 1-2 2-3 2-3 1-2 2-3

DC Voltage Range Selection

For Channel Configuration

218

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

HIA-AFE Jumper Table Sl No. Channel No./Purpose Channel Jumper Type Legend J63 J103 J104 J65 J66 J63 J36 J103 J104 J156 J103 J104 CH5 Full Scale Selection Position 1-2 2-3 2-3 2-3 1-2 2-3 2-3 1-2 1-2 1-2 1-2 1-2 2-3 J56 1-2 Voltage 2-3 J57 1-2 1-2 J54 2-3 Current J55 2-3 DC Voltage J61 2-3 J62 1-2 1-2 Selection Description

Channel Configured as mA loop

Channel Configured as CC Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Mounted for Input 12VDC FSD Mounted for Input 120VDC FSD Mounted for

Voltage Range Selection

Current Range Selection

1-2

DC Voltage Range Selection

219

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

HIA-AFE Jumper Table Sl No. Channel No./Purpose Channel Jumper Type Legend Position Selection Input 240VDC FSD Mounted for Input 480VDC FSD Channel Configured as Voltage Channel Configured as Current Description

2-3 6 J78 J79 J45 J116 J117 J116 J117 J157 J78 J45 J79 J76 J116 J117 J78 J79 J76 J45 J116 J117 J116 J117 J157 CH6 J69 Voltage 1-2 1-2 2-3 1-2 2-3 1-2 1-2 2-3 2-3 2-3 2-3 1-2 1-2 2-3 1-2 2-3 1-2 2-3 2-3 1-2 2-3 1-2 2-3 1-2 2-3

Channel Configuration for CH6

Channel Configured as DC Voltage

For Channel Configuration

Channel Configured as mA loop

Channel Configured as CC Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for www.qualitrolcorp.com

Voltage Range Selection

J70

2-3 1-2 220

Appendix G On-Board Jumper Settings

HIA-AFE Jumper Table Sl No. Channel No./Purpose Channel Jumper Type Legend Position Selection Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Mounted for Input 12VDC FSD Mounted for Input 120VDC FSD Mounted for Input 240VDC FSD Mounted for Input 480VDC FSD Channel Configured as Voltage Channel Configured as Current Description

1-2 J67 2-3 Current J68 2-3 1-2

Current Range Selection

1-2 J74 2-3 DC Voltage 1-2 J75 2-3 7 Channel Configuration for CH7 J96 J97 J161 J136 J137 J136 J137 J158 J96 J161 J97 J94 J136 J137 J96 J97 J94 1-2 2-3 2-3 2-3 1-2 1-2 2-3 2-3 2-3 1-2 1-2 1-2 2-3 1-2 2-3 1-2 2-3

DC Voltage Range Selection

For Channel Configuration

Channel Configured as DC Voltage

Channel Configured as mA loop

221

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

HIA-AFE Jumper Table Sl No. Channel No./Purpose Channel Jumper Type Legend J161 J136 J137 J136 J137 J158 Position 1-2 1-2 2-3 1-2 2-3 1-2 2-3 J82 1-2 Voltage 2-3 J88 1-2 1-2 J80 2-3 CH7 Current J81 2-3 1-2 Channel Configured as CC Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Mounted for Input 12VDC FSD Mounted for Input 120VDC FSD Mounted for Input 240VDC FSD Mounted for Input 480VDC FSD Channel Configured as Selection Description

Voltage Range Selection

Current Range Selection

1-2 J92 2-3 DC Voltage 1-2 J93 2-3 8 Channel Configuration J109 J110 1-2 2-3

DC Voltage Range Selection

For Channel Configuration

222

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

HIA-AFE Jumper Table Sl No. Channel No./Purpose for CH8 Channel Jumper Type Legend J51 J138 J139 J138 J139 J159 J109 J51 J110 J107 J138 J139 J109 J110 J107 J51 J138 J139 J138 J139 J159 CH8 J100 1-2 Voltage 2-3 J101 1-2 Current J98 2-3 J99 1-2 1-2 Position 1-2 2-3 1-2 1-2 2-3 2-3 2-3 2-3 1-2 1-2 2-3 1-2 2-3 1-2 2-3 2-3 1-2 2-3 1-2 2-3 1-2 2-3 Selection Voltage Description

Channel Configured as Current

Channel Configured as DC Voltage

Channel Configured as mA loop

Channel Configured as CC Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD

Voltage Range Selection

Current Range Selection

223

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

HIA-AFE Jumper Table Sl No. Channel No./Purpose Channel Jumper Type Legend Position Selection Mounted for Input 100A FSD Mounted for Input 12VDC FSD Mounted for Input 120VDC FSD Mounted for Input 240VDC FSD Mounted for Input 480VDC FSD Channel Configured as Voltage Description

2-3

1-2 J105 2-3 DC Voltage 1-2 J106 2-3 9 Channel Configuration for CH9 J122 J123 J64 J140 J141 J140 J141 J160 J122 J64 J123 J120 J140 J141 J118 J123 J120 J64 J140 J141 J140 J141 1-2 2-3 1-2 2-3 1-2 1-2 2-3 2-3 2-3 2-3 1-2 1-2 2-3 1-2 2-3 1-2 2-3 2-3 1-2 2-3 1-2 2-3

DC Voltage Range Selection

For Channel Configuration

Channel Configured as Current

Channel Configured as DC Voltage

Channel Configured as mA loop

Channel Configured as CC

224

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

HIA-AFE Jumper Table Sl No. Channel No./Purpose Channel Jumper Type Legend J160 Position 1-2 2-3 J113 1-2 Voltage 2-3 J114 1-2 1-2 J111 2-3 CH9 Current J112 2-3 1-2 Mounted for Input 140V FSD Mounted for Input 270V FSD Mounted for Input 480V FSD Mounted for Input 800V FSD Mounted for Input 10A FSD Mounted for Input 20A FSD Mounted for Input 50A FSD Mounted for Input 100A FSD Mounted for Input 12VDC FSD Mounted for Input 120VDC FSD Mounted for Input 240VDC FSD Mounted for Input 480VDC FSD Selection Description

Voltage Range Selection

Current Range Selection

1-2 J118 2-3 DC Voltage 1-2 J119 2-3

DC Voltage Range Selection

Note

User can configure the TX-AFE/ HIA-AFE board as TX-AFE/ HIA-AFE 1 or TXAFE/ HIA-AFE 2 for INFORMA PMD-A 6U device, which means TX-AFE/ HIAAFE 1 relates to analog channels 1-9 and TX-AFE/ HIA-AFE 2 relates to analog channels 10-18.

The following table lists the jumper settings while configuring TX-AFE/HIA-AFE as TXAFE/HIA-AFE1 orTX-AFE/HIA-AFE 2.

225

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

Jumper Legend J87 J86 J132 J85 J83 J29 J130 J133 J135 J134 J129 J84 J128 J147 J131 J149 J127 J148 J143 J144 J145 J146 J142

TX-AFE1 /HIA-AFE 1 2-3 2-3 1-2 1-2 1-2 2-3 1-2 2-3 2-3 2-3 1-2 2-3 2-3 2-3 2-3 1-2 1-2 1-2 2-3 2-3 2-3 2-3 2-3

TX-AFE2 /HIA-AFE 2 1-2 1-2 2-3 2-3 2-3 1-2 2-3 1-2 1-2 1-2 2-3 1-2 1-2 1-2 1-2 2-3 2-3 2-3 1-2 1-2 1-2 1-2 1-2

Changes in the jumper on TX-AFE/ HIA-AFE board affects the calibration, hence device needs to be re-calibrated.

226

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

The following table lists the AFE child card jumper settings. AFE Child Card Jumper selection Table JUMPER SELECTION J2 J3 J9 1-2 Unmount 1-2 1-2 1-2 1-2 3-2 Unmount Unmount Unmount Mounted 3-2 Unmount Unmount Unmount

DC Inputs/mA Current Loop 12 V 120V 240V 480V mA

J10 Unmount Unmount 1-2 3-2 Unmount

The following table lists the CPU/mother board jumper settings. CPU/Mother Board Jumper Table Sl No. 1 Purpose Jumper Legend CN712 Position Selection Description Default jumper setting 2-3

IRIG-OUT Voltage Selection

1-2

2-3

+12V IRIGOUT Signal For Modulated IRIG output +5V IRIG-OUT Signal For TTL IRIG output IRIGB AM-IN 100 V PPS IN IRIGB TTL IN IRIGB AM-OUT IRIGB TTL OUT ISO-GND(IRIGIN)

AM Modulator operates on +12V logic level and TTL on +5V

IRIGIN/IRIGOUT Format Selection IRIG Reference Selection

JPR1

1-2 2-3 4-5 6-7 7-8 1-2

JPR2

Selection of IRIG-IN/OUT Format. Either AM or TTL/PPM/PPH for IRIG-IN format Selection of reference for IRIG-IN/OUT. For IRIGB AM-IN, 100 V PPS IN, IRIGB TTL IN, selected ISOGND ( JPR2 :1-2 --> ISOGND ) & for IRIGB AMOUT & IRIGB TTL OUT select DGND ( JPR2 :2-

2-3

1-2

2-3

DGND(IRIGBOUT)

227

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

CPU/Mother Board Jumper Table Sl No. Purpose Jumper Legend Position Selection Description Default jumper setting

3--> DGND )

IRIG-TTL or PPM/PPH Selection GPS PPS Debug Selection WDI Enable Jumper IRIG-J or User-Port Selection

JPR701

1-2

PPM/PPH/TTL

J704

GPS PPS TEST Unmount Normal operation 1-2 2-3 1-2 WDI Enabled WDI Disabled COM 3 Port is configured as CPU COM Port COM 3 Port is configured as PIC COM PORT for IRIGJ IN TX is selected FX is selected

Mount

Selection of IRIGTTL/PPM/PPH Source. Used for GPSPPS debugging

1-2

Unmount

J6

WDI Control Jumper PIC or CPU as COM3 Port

1-2

CN18

1-2

2-3

Ethernet FX or TX Selection

CN3

1-2 2-3

JP1

Mount FX is selected Unmount TX is selected Console enabled Unmount Console disabled Mount Enable the differential termination Mount

Fiber or Copper Ethernet Port selection Disable Auto Negotiation in FX mode To select the COM port as console port For enabling or disabling differential

1-2

Unmount

Console Output Selection

Main

Mount

10

Differential J2 PPS

Unmount

228

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

CPU/Mother Board Jumper Table Sl No. Purpose Jumper Legend Position Selection Description Default jumper setting

11

Isolated RS485

J3

12

GPS Antenna Voltage Select

JPR3

Unmount Disable the differential Termination Mount Enable the differential termination Unmount Disable the differential Termination 1-2 5V 2-3 3.3V

termination for RS485 signals For enabling or disabling differential termination for RS485 signals For antenna voltage input Unmount

1-2

The following table lists the DFE jumper settings.

DFE Jumper Table


Sl No.
1

Purpose
Chip Select

Jumper Legend
CN4

Position
1-2 2-3

Selection
CS1 CS2 SD01 SD02

Description
For DFE board 1-CS1 is selected & for board 2-CS2 is selected For DFE board 1-SD01 is selected & for board 2-SD02 is selected

Serial Data Out

CN6

1-2 2-3

The following table lists the relay jumper settings.

Relay Jumper Table


Sl No.
1

Purpose
Relay Contact 1

Jumper Position Legend


J1 J2 J1 J2 Mount Unmount Unmount Mount

Description
Output contacts open Output contacts closed

Default Selection

Unmount Mount

229

www.qualitrolcorp.com

Appendix G On-Board Jumper Settings

Relay Jumper Table


Sl No.
2

Purpose
Relay Contact 2

Jumper Position Legend


J3 J4 J3 J4 Mount Unmount Unmount Mount Mount Unmount Unmount Mount Mount Unmount Unmount Mount

Description
Output contacts open Output contacts closed Output contacts open Output contacts closed Output contacts open Output contacts closed

Default Selection

Unmount Mount

Relay Contact 3

J5 J6 J5 J6

Unmount Mount

Relay Contact 4

J7 J8 J7 J8

Unmount Mount

230

www.qualitrolcorp.com

Appendix H Linearity Report of TX-AFE and HIA-AFE

Appendix H
Linearity Report of TX-AFE and HIA-AFE

231

www.qualitrolcorp.com

Appendix H Linearity Report of TX-AFE and HIA-AFE

Appendix H Linearity Report of TX-AFE and HIA-AFE


TX-AFE Linearity Report
For Voltage Channel: Potential Transformer, tap setting 270 V FSD Frequency Nominal Voltage : 50 Hz : 120 V

Input voltage Voltage measured Error in terms of % Error in terms of % applied in by the device in Input applied FSD volts volts 12 11.9999 -0.000833333 -3.7037E-05 60 59.975 -0.041666667 0.009259259 120 120.0076 0.006333333 0.002814815 144 143.9326 -0.046805556 0.024962963 180 179.92 -0.044444444 -0.02962963

Figure H.1 % Error in Terms of FSD for Voltage Channel

232

www.qualitrolcorp.com

Appendix H Linearity Report of TX-AFE and HIA-AFE

Figure H.2 % Error in Terms of Fed Input for Voltage Channel

For Current Channel: Current Transformer, tap setting 100 A FSD Frequency Nominal Voltage : 50 Hz : 10 A

Input current Current measured Error in terms of % Error in terms of % applied in by the device in Input applied FSD Amps Amps 0.5 0.496845 -0.631 -0.003155 1 1.004535 0.4535 0.004535 2 2.000091 0.00455 9.1E-05 3 2.999727 -0.0091 -0.000273 5 5.001462 0.02924 0.001462 6 5.998593 -0.02345 -0.001407 8 8.001606 0.020075 0.001606

233

www.qualitrolcorp.com

Appendix H Linearity Report of TX-AFE and HIA-AFE

Figure H.3 % Error in Terms of FSD for Current Channel

Figure H.4 -- % Error in Terms of Fed Input for Current Channel

234

www.qualitrolcorp.com

Appendix H Linearity Report of TX-AFE and HIA-AFE

HIA-AFE Linearity Report: For Voltage Channel: Potential Transformer, tap setting 270 V FSD Frequency Nominal Voltage Input voltage applied in volts 12 24 60 120 144 180 Voltage measured by the device in volts 12.002 24.0037 60.0076 120.0076 144.0049 180.004 : 50 Hz : 120 V Error in terms of % Input applied 0.016666667 0.015416667 0.012666667 0.006333333 0.003402778 0.002222222 Error in terms of % FSD Error in terms of % of Nominal voltage 0.001666667 0.003083333 0.006333333 0.006333333 0.004083333 0.003333333

0.000740741 0.00137037 0.002814815 0.002814815 0.001814815 0.001481481

Figure H.5 -- % Error in Terms of FSD (120 VAC nominal)

235

www.qualitrolcorp.com

Appendix H Linearity Report of TX-AFE and HIA-AFE

Figure H.6 -- % Error in Terms of FED Input (120 VAC nominal)

Figure H.6 -- % Error in Terms of % Udin (120 VAC)

236

www.qualitrolcorp.com

Appendix H Linearity Report of TX-AFE and HIA-AFE

For Current Channel:

Current Transformer, tap setting 100 A FSD Frequency Nominal Voltage : 50 Hz : 10 A

Input current Current observed in Error in terms of % Error in terms of % applied in Amps Input FSD Amps 0.5 0.5000132 0.00264 1.32E-05 1 1.000136 0.0136 0.000136 2 1.999933 -0.00335 -6.7E-05 3 2.999757 -0.0081 -0.000243 5.5 5.498199 -0.032745455 -0.001801 8.5 8.501754 0.020635294 0.001754

Figure H.7 -- % Error in Terms of FSD for Current Channel (10 AAC nominal)

237

www.qualitrolcorp.com

Appendix H Linearity Report of TX-AFE and HIA-AFE

Figure H.8 -- % Error in Terms of FED Input for Current Channel (10 AAC nominal)

238

www.qualitrolcorp.com

References

References

239

www.qualitrolcorp.com

References

References
For Configuration forms, refer to the document 36-8218-xx. For details of error log messages/codes and their meanings, refer to the document 40-08576-01.

240

www.qualitrolcorp.com

About QUALITROL

QUALITROL Field Services QUALITROL provides on-site commissioning/ start-up and comprehensive maintenance contracts to all customers worldwide. To further improve reliability, an extended warranty is available on selected products commissioned by QUALITROL . QUALITROL Educational Services QUALITROL professional training (designed to achieve hands-on performance based objectives) prepares operations, maintenance, and engineering personnel to install, test, configure, operate and maintain QUALITROL products. QUALITROL Accelerated Delivery QUALITROL provides accelerated delivery on many products and services including replacements, spare parts and repairs.

About QUALITROL QUALITROL manufactures substation and transformer monitoring and protection devices used by electric utilities and manufacturing companies. It is the global leader in sales and installations of transformer asset protection equipment, fault recorders and fault locators. Established in 1945, QUALITROL produces thousands of different types of products on demand, each customized to customers' unique requirements.